This document provides an overview of commonly used protective relay functions and their ANSI device numbers. It discusses instantaneous overcurrent (50), time overcurrent (51), directional overcurrent (67), reclosing relay (79), and under/over frequency (81O/U) functions. It explains how these functions work, their settings, and considerations for coordination between devices to ensure selective tripping during faults. Microprocessor relays allow for customized curves and grouping of protective functions.
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
Part 1. Generator Protection
Protection of generators against stator faults
Rotor faults and abnormal conditions
Restricted earth fault and inter-turn fault protection
Numerical examples
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
Part 1. Generator Protection
Protection of generators against stator faults
Rotor faults and abnormal conditions
Restricted earth fault and inter-turn fault protection
Numerical examples
Bus Bar protection Schemes,Simple Current differential scheme,Need for bus bar protection,requirement of bus bar protection,recommendations for providing bus bar protection,basics of busbar protection,Types of bus-bar protections,High speed differential protection
Since the loads having the trends towards growing density. This requires the better appearance, rugged construction, greater service reliability and increased safety. An underground cable essentially consists of one or more conductors covered with suitable insulation and surrounded by a protecting cover. The interference from external disturbances like storms, lightening, ice, trees etc. should be reduced to achieve trouble free service. The cables may be buried directly in the ground, or may be installed in ducts buried in the ground.
This directional over current relay employs the principle of actuation of the relay....It has a metallic disc free to rotate between the poles of two...
Electrical fault is the deviation of voltages and currents from nominal values or states. Under normal operating conditions, power system equipment or lines carry normal voltages and currents which results in a safer operation of the system.
Bus Bar protection Schemes,Simple Current differential scheme,Need for bus bar protection,requirement of bus bar protection,recommendations for providing bus bar protection,basics of busbar protection,Types of bus-bar protections,High speed differential protection
Since the loads having the trends towards growing density. This requires the better appearance, rugged construction, greater service reliability and increased safety. An underground cable essentially consists of one or more conductors covered with suitable insulation and surrounded by a protecting cover. The interference from external disturbances like storms, lightening, ice, trees etc. should be reduced to achieve trouble free service. The cables may be buried directly in the ground, or may be installed in ducts buried in the ground.
This directional over current relay employs the principle of actuation of the relay....It has a metallic disc free to rotate between the poles of two...
Electrical fault is the deviation of voltages and currents from nominal values or states. Under normal operating conditions, power system equipment or lines carry normal voltages and currents which results in a safer operation of the system.
International Journal of Engineering Research and DevelopmentIJERD Editor
Electrical, Electronics and Computer Engineering,
Information Engineering and Technology,
Mechanical, Industrial and Manufacturing Engineering,
Automation and Mechatronics Engineering,
Material and Chemical Engineering,
Civil and Architecture Engineering,
Biotechnology and Bio Engineering,
Environmental Engineering,
Petroleum and Mining Engineering,
Marine and Agriculture engineering,
Aerospace Engineering.
Abstract
This report focuses on controlling the speed of a DC motor using PWM technique.
Direct current (DC) motors have been widely used in many industrial applications such as electric vehicles, steel rolling mills, electric cranes, and robotic manipulators due to precise, wide, simple, and continuous control characteristics
The dc motor speed in general is directly proportional to the supply voltage, so if reduce the voltage from 12 volts to 6 volts then our speed become half of what it originally had. But in practice, for changing the speed of a dc motor we cannot go on changing the supply voltage all the time. Rather than simply adjusting the voltage sent to the motor, we can switch the motor supply on and off where switching is done so much fast that the motor only notices the average voltage effect and not the switching operation.
This study guide is intended to provide those pursuing the CCNA certification with a framework of what concepts need to be studied. This is not a comprehensive document containing all the secrets of the CCNA, nor is it a “braindump” of questions and answers.
I sincerely hope that this document provides some assistance and clarity in your studies.
In this project we will be controlling the speed of Dc motor using Arduino controller. Dc motor is drive by using PWM technique and then using encoder to sense the rpm of DC motor. Encoder produces pulses in the output, which is feed into Arduino and Arduino controls the speed of DC motor. So we have implemented the feedback system which controls the speed of DC motor.
Protection of lines
Overcurrent Protection schemes
PSM, TMS
Numerical examples
Carrier current and three-zone distance relay using impedance relays
Protection of bus bars by using Differential protection
Power system analysis ETAP. The power system analysis is the field of electrical engineering that focuses on multiple aspects of system studies. It encompasses studies such as load flow, arc flash, short circuit, relay coordination, motor starting study, transient analysis etc.
This presentation will discuss how the use and need for voltage transformers has changed over the last twenty years. With the introduction of auto-ranging electric meters, meter technicians need to be prepared, use the appropriate tools and PPE for high capacity circuits (without VT's), as this method has become increasingly popular.
Student information management system project report ii.pdfKamal Acharya
Our project explains about the student management. This project mainly explains the various actions related to student details. This project shows some ease in adding, editing and deleting the student details. It also provides a less time consuming process for viewing, adding, editing and deleting the marks of the students.
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
Welcome to WIPAC Monthly the magazine brought to you by the LinkedIn Group Water Industry Process Automation & Control.
In this month's edition, along with this month's industry news to celebrate the 13 years since the group was created we have articles including
A case study of the used of Advanced Process Control at the Wastewater Treatment works at Lleida in Spain
A look back on an article on smart wastewater networks in order to see how the industry has measured up in the interim around the adoption of Digital Transformation in the Water Industry.
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...Amil Baba Dawood bangali
Contact with Dawood Bhai Just call on +92322-6382012 and we'll help you. We'll solve all your problems within 12 to 24 hours and with 101% guarantee and with astrology systematic. If you want to take any personal or professional advice then also you can call us on +92322-6382012 , ONLINE LOVE PROBLEM & Other all types of Daily Life Problem's.Then CALL or WHATSAPP us on +92322-6382012 and Get all these problems solutions here by Amil Baba DAWOOD BANGALI
#vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore#blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #blackmagicforlove #blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #Amilbabainuk #amilbabainspain #amilbabaindubai #Amilbabainnorway #amilbabainkrachi #amilbabainlahore #amilbabaingujranwalan #amilbabainislamabad
About
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Technical Specifications
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
Key Features
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface
• Compatible with MAFI CCR system
• Copatiable with IDM8000 CCR
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
Application
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Water scarcity is the lack of fresh water resources to meet the standard water demand. There are two type of water scarcity. One is physical. The other is economic water scarcity.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
6. Interrupting Methods
• Fuse
Fusible element melts to disconnect faulty
zone/equipment
I2T law
• Recloser
Single or three-phase, 15 to 38kV
Line or substation
• Circuit Breaker
• Indoor switchgear
• Outdoor breaker or switchgear
• Air, Oil, SF6, Vacuum, Magnetic blast
8. 50 – Instantaneous OC
Instantaneous Overcurrent (function 50)
• The instantaneous overcurrent protective element operates with no intentional time delay
when the current has exceeded the relay setting
• There is a pickup setting.
• 50P – phase inst. overcurrent. Pickup usually set at 25% higher than the maximum current
seen by the relay for a three-phase fault at the end of the circuit.
• 50N – neutral inst. overcurrent
(The phasor summation of phase currents Ia, Ib, Ic equals In)
• 50G – ground inst. overcurrent – low pickup setting
(Uses separate or zero sequence CT)
12. 51 – Time Overcurrent
• Where it is desired to have more time delay before the element operates for the purpose of
coordinating with other protective relays or devices, the time overcurrent protective element is
used. The trip time varies inversely with current magnitude.
• Characteristic curves most commonly used are called “inverse,””very inverse,” and “extremely
inverse.” The user must select the curve type. They are said to be a family of curves and selected
by the time dial.
• Curve type and time dial are separate settings. Time dial adjusts the time delay of the characteristic
to achieve coordination between downstream and upstream overcurrent devices.
• There is a minimum pickup setting. The pickup setting should be chosen such that the protective
device will be operating on the most inverse part of its time curve over the range of current for
which must operate.
• 51P – phase time overcurrent
• 51N – neutral time overcurrent
(The phasor summation of phase currents Ia, Ib, Ic equals In)
• 51G – ground time overcurrent ‐ low pickup setting (uses separate or zero sequence CT)
17. 51 ‐ Fuses
• The time verses current characteristics of a fuse
has two curves.
• The first curve is called the minimum melt curve
• The minimum melt curve is the time between
the initiation of a current large enough to
cause the fusible element(s) to melt and the
instant when arcing occurs.
• The second curve is called the total clearing time.
• The total clearing time is the total time
elapsing from the beginning of an
overcurrent to the final circuit interruption.
• The time current characteristic curve of a fuse
follows a I2T characteristic - that is to say as the
current goes up, the time drops by the square of
the current increase.
Total clearing
time curve
Minimum
melt
Current
Time
18. 51 – Coordinating Fuses
Load
Primary
Secondary
LoadSecondary
2I
1I 1I
Time
Current
• The operating time of a fuse is a function of the pre-arcing (melting) and arcing time
• For proper coordination, total I2T of secondary fuse shouldn’t exceed the pre-arcing
(melting) of primary fuse. This is established if current ratio of primary vs.
secondary fuse current rating is 2 or greater for fuses of the same type.
19. 51 – Coordinating Fuses & Relays
Current
Time
Minimum TCI time of
0.4s
Time Over Current Curve
Fuse curve
• The time overcurrent relay should back
up the fuse over full current range.
The time overcurrent relay
characteristic curve best suited for
coordination with fuses is the
Extremely Inverse, which is similar to
the I2t fuse curves. For Extremely
Inverse relay curves, primary pickup
current setting should be 3-times fuse
rating. For other relay curves, up to 4-
times fuse rating should be considered.
Ensure no cross over of fuse or time
overcurrent relay curves.
• To account for CT saturation and
errors, electro-mechanical relay
overshoot, timing errors and fuse
errors a minimum TCI of 0.4s should
be used.
20. 51 – Coordinating Relays
• The following is recommended TCI to ensure proper coordination.
0 1000 2000 3000 4000
0
0.5
1
1.5
2
2.5
3
Fault current at 11 kV
Timetooperate(s)
0.4 s between relay and fuse
0.3 s between digital relays
21. 51 – Reset Curves
• Reset of Time Overcurrent Element
• There are (2) different types of resets within Time Overcurrent Protection:
• EM or Timed Delay Reset – this mimics the disc travel of an
electromechanical relay moving back to the reset position.
• If the disc has not yet completely traveled back to the reset position and the
time overcurrent element picks up again, the trip time will be shorter.
• If the current picks up and then dropouts many times, the disc will “ratchet”
itself to the operate position.
• Be careful when coordinating with upstream or downstream devices.
• Instantaneous Reset – once the time overcurrent element operates,
it will reset immediately
24. 67 – How it Works
(a) To determine the direction of
current we need a reference
voltage or current that will not
change direction during the
fault. To determine the
direction of current in phase A
we will use Vbc. Digital relays
allow an offset from the
reference voltage or current to
provide better protection.
(b) The protection engineer must
look back into the system from
the fault and determine the
current fault angle (in this case
a 600 lagging in current from
phase Van is determined the
typical fault angle).
31. 79 – Reclosing Relay
• Not all Faults Are Permanent
– Most Industrial Facilities Use Insulated Cable,
Which Results in Permanent Faults
– Utilities Often Use Non‐Insulated Overhead
Conductors, Resulting in Many Temporary Faults:
• Wind Causing Conductors to Touch
• Fires Temporarily Breaking Down Air
32. 79 – Reclosing Relay
• Automatically reclose a circuit breaker or recloser which has been tripped by protective
relaying or recloser control
• Multi‐shot reclosing for distribution circuits
• Instantaneous shot (~0.25s)
• Delayed reclosures (typically two delayed , for example 3s & 15s, or 15s & 30s)
• Coordinate with branch fuses
• After initial reclose block instantaneous overcurrent functions to allow fuse to blow
• After successful reclose, the reclosing function will reset after some adjustable time delay
(typically 60s).
• If the fault is permanent, the protective device will trip and reclose several times. If
unsuccessful, the protective device will go to LOCKOUT and keep the breaker open.
Some devices have a separate reset time from lockout (for example 10s after the breaker
is manually closed).
33. 79 – Reclosing & Fuses
52
R
• Two methods:
• Fuse blowing
• Fuse blows for any fault, including temporary fault
• Fuse saving
• Use automatic reclosing to try and save fuses for temporary faults
39. • Phase instantaneous and
time-delayed overcurrent
is used.
• Ground instantaneous
overcurrent is used.
• Optionally, ground time-
delayed overcurrent is
used
Typical Industrial Feeder CB
40. Typical Utility Feeder CB
• Phase and ground
overcurrent protection
with multi-shot
reclosing relay is used.
• Both instantaneous
and time-delayed
overcurrent are used.
• Reclosing is Often
Included for Overhead
Lines
79
44. 50 – Short Circuit Protection
• The short circuit element provides
protection for excessively high overcurrent
faults
• Phase-to-phase and phase-to-ground
faults are common types of short circuits
• To avoid nuisance tripping during starting,
set the the short circuit protection pick up
to a value at least 1.7 times the maximum
expected symmetrical starting current of
motor.
• The breaker or contactor must have an
interrupting capacity equal to or greater
then the maximum available fault current
or let an upstream protective device
interrupt fault current.
50. A motor can run overloaded without a fault in motor or supply
A primary motor protective element of the motor protection relay is the
thermal overload element and this is accomplished through motor
thermal image modeling. This model must account for thermal process in
the motor while motor is starting, running at normal load, running
overloaded and stopped. Algorithm of the thermal model integrates both
stator and rotor heating into a single model.
• Main Factors and Elements Comprising
the Thermal Model are:
• Overload Pickup Level
• Overload Curve
• Running & Stopped Cooling Time Constants
• Hot/Cold Stall Time Ratio
• RTD & Unbalance Biasing
• Motor State Machine
49 – Overload Protection
51. 49 - Motor Thermal Limit Curves
Thermal Limit Curves:
B. Hot Running Overload
B
A. Cold Running Overload
A
D. Hot Locked Rotor CurveD
C
C. Cold Locked Rotor Curve
F. Acceleration curve @100%
voltage
F
E. Acceleration curve @ 80% rated
voltageE
• Thermal Limit of the model is dictated by overload curve constructed in
the motor protection device in the reference to thermal damage curves
normally supplied by motor manufacturer.
• Motor protection device is equipped with set of standard curves and
capable to construct customized curves for any motor application.
52. 49 - Thermal Overload Pickup
• Set to the maximum allowed by
the service factor of the motor.
• Set slightly above the motor
service factor by 8-10% to
account for measuring errors
• If RTD Biasing of Thermal Model
is used, thermal overload setting
can be set higher
• Note: motor feeder cables are
normally sized at 1.25 times
motor’s full load current rating,
which would limit the motor
overload pickup setting to a
maximum of 125%.
SF Thermal Overload Pickup
1.0 1.1
1.15 1.25
53. • Thermal Capacity Used (TCU) is a criterion selected in thermal model
to evaluate thermal condition of the motor.
• TCU is defined as percentage of motor thermal limit utilized during
motor operation.
• A running motor will have some level of thermal capacity used due
to Motor Losses.
• Thermal Trip when Thermal Capacity Used equals 100%
49 – Thermal Capacity Used
54. Overload Curve
Set the overload curve below cold thermal limit and above hot thermal limit
If only hot curve is provided by mfgr, then must set below hot thermal limit
49 - Overload Curve Selection
55. If the motor starting
current begins to
infringe on the thermal
damage curves or if the
motor is called upon to
drive a high inertia load
such that the
acceleration time
exceeds the safe stall
time, custom or voltage
dependent overload
curve may be required.
49 - Overload Curve Selection
56. 49 - Overload Curve Selection
A custom overload curve
will allow the user to
tailor the relay’s thermal
damage curve to the
motor such that a
successful start can occur
without compromising
protection while at the
same time utilizing the
motor to its full potential
during the running
condition.
57. 49 - Current Unbalance Bias
Negative sequence currents (or unbalanced phase currents) will cause
additional rotor heating that will be accounted for in Thermal Model.
Positive Sequence
Negative Sequence
• Main causes of current unbalance
• Blown fuses
• Loose connections
• Stator turn-to-turn faults
• System voltage distortion and unbalance
• Faults
58. 49 - Current Unbalance Bias
• Equivalent heating motor current is employed to bias thermal model in
response to current unbalance.
• Im - real motor current; K - unbalance bias factor; I1 & I2 -
positive and negative sequence components of motor current.
• K factor reflects the degree of extra heating caused by the negative
sequence component of the motor current.
• IEEE guidelines for typical and conservative estimates of K.
59. Thermal Model - Motor Cooling
• Motor cooling is characterized by separate cooling time constants
(CTC) for running and stopped motor states. Typical ratio of the
stopped to running CTC is 2/1
• It takes the motor typically 5 time constants to cool.
Thermal Model Cooling100% load -
Running
Thermal Model Cooling Motor
Tripped
60. 46 - Unbalance Protection
• Indication of unbalance negative sequence current / voltage
• Unbalance causes motor stress and temperature rise
• Current unbalance in a motor is result of unequal line voltages
• Unbalanced supply, blown fuse, single-phasing
• Current unbalance can also be present due to:
• Loose or bad connections
• Incorrect phase rotation connection
• Stator turn-to-turn faults
• For a typical three-phase induction motor:
• 1% voltage unbalance (V2) relates to 6% current unbalance (I2)
• For small and medium sized motors, only current transformers (CTs) are available and
no voltage transformers (VTs). Measure current unbalance and protect motor.
• The heating effect caused by current unbalance will be protected by enabling the
unbalance input to the thermal model
• For example, a setting of 10% x FLA for the current unbalance alarm with a delay of
10 seconds and a trip level setting of 25% x FLA for the current unbalance trip with a
delay of 5 seconds would be appropriate.
Motor Relay
61. 27 – Undervoltage Protection
• The overall result of an undervoltage condition is an increase
in current and motor heating and a reduction in overall motor
performance.
• The undervoltage protection element can be thought of as
backup protection for the thermal overload element. In some
cases, if an undervoltage condition exists it may be desirable
to trip the motor faster than thermal overload element.
• The undervoltage trip should be set to 90% of nameplate
unless otherwise stated on the motor data sheets.
• Motors that are connected to the same source/bus may
experience a temporary undervoltage, when one of motors
starts. To override this temporary voltage sags, a time delay
setpoint should be set greater than the motor starting time.
62. 59 – Overvoltage Protection
• The overall result of an overvoltage condition is a
decrease in load current and poor power factor.
• Although old motors had robust design, new motors are
designed close to saturation point for better utilization of
core materials and increasing the V/Hz ratio cause
saturation of air gap flux leading to motor heating.
• The overvoltage element should be set to 110% of the
motors nameplate unless otherwise started in the data
sheets.
68. Size Matters
• Small 500 to 10,000 kVA
• Medium 10,000 kVA to 100 MVA
• Large 100 MVA and above
• Less than 500kVA not considered a power transformer
• Our Discussion is mainly applicable to Medium and Large
Power Transformers
73. Transformer Phase Shifts
• H1 (A) leads X1 (a) by 30
• Currents on “H” bushings are
line-to-line quantities
• Subtract from reference
phase vector the connected
non-polarity vector
HV LV
H1
H2
H3
X1
X3
X2
A
B
C
a
b
c
a
b
c A
B
C
Assume 1:1 transformer
81. 87T ‐ Inrush Detection
• Inrush Detection and Restraint
– 2nd harmonic restraint has been employed
for years
– “Gap” detection has also been employed
– As transformers are designed to closer
tolerances, the incidence of both 2nd
harmonic and low current gaps in waveform
have decreased
– If 2nd harmonic restraint level is set too low,
differential element may be blocked for
internal fault due to generated harmonics
83. Traditional 2nd Harmonic
> Responds to the RATIO of magnitudes of 2nd Harmonic and
Fundamental Frequency Components
> Typical setting is 15-20% (dependent on transformer
construction)
Adaptive 2nd Harmonic
> Responds to both Magnitudes and Phase Angles of 2nd Harmonic
and Fundamental Frequency Component
> Use on transformers experiencing lower than normal 2nd
harmonic levels during magnetizing inrush conditions (say 5-
10%)
87T – Harmonic Restraint
86. Igd, pu
I= max( IR1, IR2,IR0 ), pu
Min. PKP
S lope
Fast detection of winding ground faults
Very secure performance on external ground
faults
Configurable pickup, slope, and time delay
87TG - Restricted Ground Fault Protection
88. 63 – Pressure Devices
• Two Main Types:
– Sudden Pressure Relay – Applied to transformers
without a Conservator Tank, uses pressure Rate of
Rise
– Bucholtz Relays – Applied to Transformers with a
Conservator Tank, uses accumulated gas pressure
• When an Arc occurs in oil, a release of various
gasses occurs.
• Sudden Pressure Increase is Detected by Relay
91. SUDDEN PRESSURE
RELAY
CHANGE PRESSURE RELIEF
DEVICE
63 - Sudden Pressure Relay (SPR)
•The SPR detects excessive rates of pressure rise within the
tank as result of internal arcing causing oil breakdown and
subsequent gas evolution
•They can operate on a change in oil or gas pressure
•Using a bellows and orifice to respond to rapid differential
pressure changes, they are an inverse-time characteristic
•The SPR should be an input on the digital transformer relay
for targeting, SOE and waveform capture
92. 63 - Buchholtz Relay
•Used on conservator type oil preservation systems
as a protective device that senses gas accumulation
•If a low level fault results in arcing, the small
amount of gas that is produced will accumulate in
this relay resulting in an alarm
•The SPR should be an input on the digital
transformer relay for targeting, SOE and waveform
capture
94. 59/81 – Overexcitation Causes
• Transmission Systems that Supply Distribution Substations
– High voltage from Generating Plants
– Voltage and Reactive Support Control Failures
• Runaway LTCs
• Capacitor banks in when they should be out
• Shunt reactors out when they should be in
• Near‐end breaker failures resulting in voltage rise on
line (Ferranti effect)