PROTECTION SCHEMES
PROTECTIVE RELAYING
ZONE OF PROTECTION
• Power system is protected in zones, each
containing an alternator, a transformer, a
bus bar section or a transmission line.
Each zone has one or more protective
schemes, which are coordinated with
the overall protection with the following
characteristics
ATTRIBUTES OF RELAYING
• RELIABILITY: security (avoid false operation) &
Dependability ( correct operation)
• SELECTIVITY: minimum disconnection & Maximum
continuity of service
• SPEED :
– Improved power system stability
– Decreased amount of damage incurred
– Less annoyance to electric power consumers
– Decreased likelihood of development of one type of fault into
other more severe type
– Rapid re-closure of circuit breakers to restore service to
customer.
Maximum load
Permissible over load
Minimum Fault current
Maximum Fault current
over load
Fault Clearing Time
• Relay operating Time
– High speed or instantaneous Relay: 1.0 to
2.0 cycles i.e., 0.02 to 0.04 sec.
• Circuit Breaker clearing Time:
– High speed C.Bs: 2.5 to 3.0 cycles i.e. 0.05
to 0.06 sec.
• Total clearing time = relay operating time+
circuit breaker clearing time
– Total clearing time may be between 0.07 to
0.1 sec.
PROTECTION OF VARIOUS
COMPONENTS OF POIWER SYSTEM
• Feeder protection
– Radial system
– Mesh Network
• HV TXN Line protection
• Transformer Protection
• Alternator Protection
• Motor Protection
Feeder protection
Protection of Distribution Network
And Feeders
• Time graded
Discrimination
• Current graded
Discrimination
CURRENT GRADED
DISCRIMINATION
Criteria for over current
protection of radial feeder
• The relay at the far end is operated in the shortest time as it does
not have to give back up to any other relay. Upstream relays
(moving back to source side) are time graded with about 0.3 second
delays. Definite time relays can be used where source impedance is
large as compared to the line impedance i.e., small variation of
current for near and far end faults.
• Inverse time (IDMT) relays can be used if lines are long and fault
level is much smaller at the far end fault than it is for source end
fault.
• Very or extremely inverse time can be selected where the line
impedance is high as compared to source impedance or in case
where coordination with fusses or re-closure is necessary.
Feeder Protection by IDMT relay
• Both current graded & time graded
discrimination can be implemented
• Requires adjustment of PS and TMS
• Coordination delay time (C.D.T)= 0.3 or
0.5 seconds
Example
• Use 2.2 IDMT relay to design a well coordinated over current
protection scheme for a radial distribution system with the help
of following information available:
substatio
n
C.T ratio Fault
current
A 400:5 6000
B 200:5 5000
C 200:5 4000
Bus A Bus B Bus C
Load current
IDMT
relay
IDMT
relay
Fault
current
Fault Location
A B
If,A
If,B
If,C
Bus A Bus B Bus C
Load current
IDMT
relay
IDMT
relay
Fault
current
Fault Location
A B
If,A
If,B
If,C
• Start relay settings for the substation C farthest from the source
• set Relay B for back up protection for Rc
• Use CDT=0.5 seconds
• Check operating time of RB for the plug setting done in the preceding
step for a fault at substation B.
• Set PS and TMS of RA for backup of RB; using the CDT=0.5 seconds
• Check RA operating time for a fault at sub station A
Fault location RA
PS=125%
TMs=37.9%
RB
PS=125%
TMs=29%%
RC
PS=100%
TMs=10%
C - 0.72s 0.22s
B 1.138s 0.638s -
A 0.985s - -
Use of Directional over current relay
page 366
Directional relay
For DC current
For ac : induction cup
relay
EARTH FAULT PROTECTION
• Restricted Earth
fault scheme
• Unrestricted Earth
fault scheme
Use of residual current & core
balance C.T
TXN LINE PROTECTION
Problems with transmission
lines protection
• System configuration changes continuously
• More load added time to time
• Outages of T.L and/or generating units are
frequent.
• Due to complex meshed network and
interconnections, various loops exist in the
system. Hence selectivity can not be achieved
through simple over current relays
Reach of over current relay
• Reach of over current
relay depends on:
– type of fault
– Generation level or source
impedance value
23
Distance relaying
Distance relying scheme is
independent of source impedance
variations
24
Impedance relay
Balanced beam relay
25
26
27
schematic
28
Relay characteristics-RX
diagram
29
30
Effect of Power swings and arc resistance on the
performance of simple impedance relay
Effect of Arc resistance on
Relay operation
32
Effect of Load swing on Relay
operation
33
Reactance Relay
• Current operated directional restraint relay
34
35
Performance during Normal Load and
effect of arc resistance
36
Directional Property
37
Use of directional features with
simple impedance relay
38
Mho Relay
• It is directional relay with voltage Restraint
39
40
Effect of Arc resistance and
performance under Normal Load
41
42
distance protection
43
44
45
46
47
48
Power line carrier communication(PLCC)
• For 80% first zone protection setting, only 60% of the line covers
fast tripping zone of both relay located at each end of a double fed
Tx. Line
• Opening of circuit breakers located on both ends is necessary to
maintain system stability
• Therefore, a communication link is to be established between these
two relays to ensure opening of both Circuit breakers
“simultaneously”
Possible communication
Channels
• The information to be transmitted is only about
state of the Circuit breaker i.e., either closed or
Tripped. Therefore, no requirement of large
bandwidth sets the carrier frequency just above
audible frequency range ( 50kHz to 200kHz)
• Possible channels are
– Telephone lines
– Microwave
– Satellite communication
– Power line conductor itself
Unit Protection
• Graded over current schemes drawbacks
– Satisfactory grading can not always be
arranged for complex network
– Setting may cause greater tripping times at
point in the system making protection
insufficient for excessive disturbance
• Concept of unit protection
– Where sections of the power system are
protected as a complete unit without
reference to other parts
Example : Differential protection
• Works on difference between incoming and
outgoing currents
Pilot wires
Healthy condition
Faulty condition
Requirements for differential scheme
• Current magnitude seen by the relay on both sides should be equal
and in phase
• Relay must not trip for external or through faults
– Because of CT mismatch of characteristics, relay can mal-operate for external
fault as well.
– Therefore a restraint coil is used in addition to operating coil.
– Relay characteristics are changed to percent differential characteristics.
Use of Percent differential relay
Difficulties with transformer protection
• No load transformer
Switching transients
(inrush current) may be
differentiated from fault current by
measuring harmonics contents,(2nd
harmonic). Relay false operation is
blocked by harmonic restraint
• C.T ratio error is prominent for
through faults because of CTs
saturation at different level. Percent
bias coil is to be used
• Phase shift in YD
transformers is addressed by
proper connections of CTs on both
sides
Protection of YD
Transformer
Requirements:
• C.Ts secondary line currents ( or current in
pilot wires) as seen by the relay should be
in phase
• C.Ts ratio must be adjusted so that current
seen by the relay should be equal in
magnitude under normal condition
CT connections-30° phase shift offset
Ex 14.7
• A 3-phase transformer rated
for 33kV/6.6kV is connected
star-delta and the protecting
current transformer on the LV
side have a ratio of 400:5.
determine the ratio of the CT
on HV side
• A 3 phase , 200 kVA 110.4 kV,
DY transformer has CTs on
0.4 kV side a turns ratio of
500:5. what should be the CT
ratio on HV side of the
transformer? Also determine
the out of balance current
when a fault of 750A of the
following type occurs on LV
side: a) Earth fault within
protection zone and b) earth
fault outside the zone

Electrical Protection Schemes in detail

  • 1.
  • 2.
    ZONE OF PROTECTION •Power system is protected in zones, each containing an alternator, a transformer, a bus bar section or a transmission line. Each zone has one or more protective schemes, which are coordinated with the overall protection with the following characteristics
  • 3.
    ATTRIBUTES OF RELAYING •RELIABILITY: security (avoid false operation) & Dependability ( correct operation) • SELECTIVITY: minimum disconnection & Maximum continuity of service • SPEED : – Improved power system stability – Decreased amount of damage incurred – Less annoyance to electric power consumers – Decreased likelihood of development of one type of fault into other more severe type – Rapid re-closure of circuit breakers to restore service to customer.
  • 4.
    Maximum load Permissible overload Minimum Fault current Maximum Fault current over load
  • 5.
    Fault Clearing Time •Relay operating Time – High speed or instantaneous Relay: 1.0 to 2.0 cycles i.e., 0.02 to 0.04 sec. • Circuit Breaker clearing Time: – High speed C.Bs: 2.5 to 3.0 cycles i.e. 0.05 to 0.06 sec. • Total clearing time = relay operating time+ circuit breaker clearing time – Total clearing time may be between 0.07 to 0.1 sec.
  • 6.
    PROTECTION OF VARIOUS COMPONENTSOF POIWER SYSTEM • Feeder protection – Radial system – Mesh Network • HV TXN Line protection • Transformer Protection • Alternator Protection • Motor Protection
  • 7.
  • 8.
    Protection of DistributionNetwork And Feeders • Time graded Discrimination • Current graded Discrimination
  • 9.
  • 10.
    Criteria for overcurrent protection of radial feeder • The relay at the far end is operated in the shortest time as it does not have to give back up to any other relay. Upstream relays (moving back to source side) are time graded with about 0.3 second delays. Definite time relays can be used where source impedance is large as compared to the line impedance i.e., small variation of current for near and far end faults. • Inverse time (IDMT) relays can be used if lines are long and fault level is much smaller at the far end fault than it is for source end fault. • Very or extremely inverse time can be selected where the line impedance is high as compared to source impedance or in case where coordination with fusses or re-closure is necessary.
  • 11.
    Feeder Protection byIDMT relay • Both current graded & time graded discrimination can be implemented • Requires adjustment of PS and TMS • Coordination delay time (C.D.T)= 0.3 or 0.5 seconds
  • 12.
    Example • Use 2.2IDMT relay to design a well coordinated over current protection scheme for a radial distribution system with the help of following information available: substatio n C.T ratio Fault current A 400:5 6000 B 200:5 5000 C 200:5 4000 Bus A Bus B Bus C Load current IDMT relay IDMT relay Fault current Fault Location A B If,A If,B If,C
  • 13.
    Bus A BusB Bus C Load current IDMT relay IDMT relay Fault current Fault Location A B If,A If,B If,C
  • 14.
    • Start relaysettings for the substation C farthest from the source • set Relay B for back up protection for Rc • Use CDT=0.5 seconds • Check operating time of RB for the plug setting done in the preceding step for a fault at substation B. • Set PS and TMS of RA for backup of RB; using the CDT=0.5 seconds • Check RA operating time for a fault at sub station A Fault location RA PS=125% TMs=37.9% RB PS=125% TMs=29%% RC PS=100% TMs=10% C - 0.72s 0.22s B 1.138s 0.638s - A 0.985s - -
  • 15.
    Use of Directionalover current relay page 366
  • 16.
    Directional relay For DCcurrent For ac : induction cup relay
  • 18.
    EARTH FAULT PROTECTION •Restricted Earth fault scheme • Unrestricted Earth fault scheme
  • 19.
    Use of residualcurrent & core balance C.T
  • 21.
  • 22.
    Problems with transmission linesprotection • System configuration changes continuously • More load added time to time • Outages of T.L and/or generating units are frequent. • Due to complex meshed network and interconnections, various loops exist in the system. Hence selectivity can not be achieved through simple over current relays
  • 23.
    Reach of overcurrent relay • Reach of over current relay depends on: – type of fault – Generation level or source impedance value 23
  • 24.
    Distance relaying Distance relyingscheme is independent of source impedance variations 24
  • 25.
  • 26.
  • 27.
  • 28.
  • 29.
  • 30.
  • 31.
    Effect of Powerswings and arc resistance on the performance of simple impedance relay
  • 32.
    Effect of Arcresistance on Relay operation 32
  • 33.
    Effect of Loadswing on Relay operation 33
  • 34.
    Reactance Relay • Currentoperated directional restraint relay 34
  • 35.
  • 36.
    Performance during NormalLoad and effect of arc resistance 36
  • 37.
  • 38.
    Use of directionalfeatures with simple impedance relay 38
  • 39.
    Mho Relay • Itis directional relay with voltage Restraint 39
  • 40.
  • 41.
    Effect of Arcresistance and performance under Normal Load 41
  • 42.
  • 43.
  • 44.
  • 45.
  • 46.
  • 47.
  • 48.
  • 49.
    Power line carriercommunication(PLCC) • For 80% first zone protection setting, only 60% of the line covers fast tripping zone of both relay located at each end of a double fed Tx. Line • Opening of circuit breakers located on both ends is necessary to maintain system stability • Therefore, a communication link is to be established between these two relays to ensure opening of both Circuit breakers “simultaneously”
  • 50.
    Possible communication Channels • Theinformation to be transmitted is only about state of the Circuit breaker i.e., either closed or Tripped. Therefore, no requirement of large bandwidth sets the carrier frequency just above audible frequency range ( 50kHz to 200kHz) • Possible channels are – Telephone lines – Microwave – Satellite communication – Power line conductor itself
  • 51.
    Unit Protection • Gradedover current schemes drawbacks – Satisfactory grading can not always be arranged for complex network – Setting may cause greater tripping times at point in the system making protection insufficient for excessive disturbance • Concept of unit protection – Where sections of the power system are protected as a complete unit without reference to other parts
  • 52.
    Example : Differentialprotection • Works on difference between incoming and outgoing currents Pilot wires
  • 53.
  • 55.
    Requirements for differentialscheme • Current magnitude seen by the relay on both sides should be equal and in phase • Relay must not trip for external or through faults – Because of CT mismatch of characteristics, relay can mal-operate for external fault as well. – Therefore a restraint coil is used in addition to operating coil. – Relay characteristics are changed to percent differential characteristics.
  • 57.
    Use of Percentdifferential relay
  • 60.
    Difficulties with transformerprotection • No load transformer Switching transients (inrush current) may be differentiated from fault current by measuring harmonics contents,(2nd harmonic). Relay false operation is blocked by harmonic restraint • C.T ratio error is prominent for through faults because of CTs saturation at different level. Percent bias coil is to be used • Phase shift in YD transformers is addressed by proper connections of CTs on both sides
  • 61.
  • 62.
    Requirements: • C.Ts secondaryline currents ( or current in pilot wires) as seen by the relay should be in phase • C.Ts ratio must be adjusted so that current seen by the relay should be equal in magnitude under normal condition
  • 63.
  • 65.
    Ex 14.7 • A3-phase transformer rated for 33kV/6.6kV is connected star-delta and the protecting current transformer on the LV side have a ratio of 400:5. determine the ratio of the CT on HV side • A 3 phase , 200 kVA 110.4 kV, DY transformer has CTs on 0.4 kV side a turns ratio of 500:5. what should be the CT ratio on HV side of the transformer? Also determine the out of balance current when a fault of 750A of the following type occurs on LV side: a) Earth fault within protection zone and b) earth fault outside the zone