The document summarizes instrument transformers, which are used to isolate protection, control, and measurement equipment from high voltages in power systems. It discusses current transformers (CTs) and potential transformers (PTs). CTs reduce system current to a lower value for measurement. They function by inducing a current in a secondary winding from the magnetic field of a primary winding connected to the power circuit. PTs provide isolation from high voltages and measure voltage. They have errors in voltage ratio and phase angle between primary and secondary voltages.
Current Transformer and Potential TransformerRidwanul Hoque
One of the major difference between them is that the current transformer converts the high value of current into low value whereas the potential or voltage transformer converts the high value of voltages into low voltage.
It is based on current transformer description
It's working and applications are present in it ,it also includes videos of it's windings and it's inrush ability of transformer, and also about instrument transformer and it's working with applications.Current transformers are used-in measuring high currents and connected with it in parallel to it
Nowadays, it is very important to maintain voltage level. Controlling of that voltage is also important. This Presentation contains methods of voltage control.
Current Transformer and Potential TransformerRidwanul Hoque
One of the major difference between them is that the current transformer converts the high value of current into low value whereas the potential or voltage transformer converts the high value of voltages into low voltage.
It is based on current transformer description
It's working and applications are present in it ,it also includes videos of it's windings and it's inrush ability of transformer, and also about instrument transformer and it's working with applications.Current transformers are used-in measuring high currents and connected with it in parallel to it
Nowadays, it is very important to maintain voltage level. Controlling of that voltage is also important. This Presentation contains methods of voltage control.
This ppt provides a brief overview on thyristors commonly known as SCRs. V- I characteristics curve, triggering methods, protection methods, series and parallel operations of SCRs, applications are discussed in this slide.
CT, PT And CVT
It help in measurement of high voltage And current.
* It provide low voltage and current to the electrical device.
* It’s measure application is in the protection system where relay is work on low amount of voltage and current.
These slides provide an elementary description of Power Electronics and its application domains. It also shows the different power devices and converters.
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]Md Irshad Ahmad
Instrument Transformers: CT and PT; their errors, Applications of CT and PT in the extension of instrument range, Introduction to measurement of speed, frequency and power factor.(
This ppt provides a brief overview on thyristors commonly known as SCRs. V- I characteristics curve, triggering methods, protection methods, series and parallel operations of SCRs, applications are discussed in this slide.
CT, PT And CVT
It help in measurement of high voltage And current.
* It provide low voltage and current to the electrical device.
* It’s measure application is in the protection system where relay is work on low amount of voltage and current.
These slides provide an elementary description of Power Electronics and its application domains. It also shows the different power devices and converters.
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]Md Irshad Ahmad
Instrument Transformers: CT and PT; their errors, Applications of CT and PT in the extension of instrument range, Introduction to measurement of speed, frequency and power factor.(
100 watt inverter using IC CD4047 and MOSFET IRF540
CD 4047 is a low power CMOS astable/monostable multivibrator IC. Here it is wired as an astable multivibrator producing two pulse trains of 0.01s which are 180 degrees out of phase at the pins 10 and 11 of the IC. Pin 10 is connected to the gate of Q1 and pin 11 is connected to the gate of Q2. Resistors R3 and R4 prevents the loading of the IC by the respective MOSFETs. When pin 10 is high Q1 conducts and current flows through the upper half of the transformer primary which accounts for the positive half of the output AC voltage. When pin 11 is high Q2 conducts and current flows through the lower half of the transformer primary in opposite direction and it accounts for the negative half of the output AC voltage.
A Bipolar Junction Transistor is a three-terminal semiconductor device consisting of two p-n junctions which are able to amplify or magnify a signal. It is a current controlled device. The three terminals of the BJT are the base, the collector and the emitter. A BJT is a type of transistor that uses both electrons and holes as charge carriers
Coupling of Amplifiers- Direct coupled amplifiertanishashukla147
The topic is part of electronics and deals with the coupling of two-stage or multi-stage amplifiers without the use of any resistors, capacitors or transformers.
EEE 453( Semiconductor Switch and Triggering Device) UthsoNandy
Here is the information about electronics devices( Semiconductor Switch and Triggering Device) and amplifiers and application that will help to upgrade yourself and your knowledge
Acorn Recovery: Restore IT infra within minutesIP ServerOne
Introducing Acorn Recovery as a Service, a simple, fast, and secure managed disaster recovery (DRaaS) by IP ServerOne. A DR solution that helps restore your IT infra within minutes.
This presentation by Morris Kleiner (University of Minnesota), was made during the discussion “Competition and Regulation in Professions and Occupations” held at the Working Party No. 2 on Competition and Regulation on 10 June 2024. More papers and presentations on the topic can be found out at oe.cd/crps.
This presentation was uploaded with the author’s consent.
0x01 - Newton's Third Law: Static vs. Dynamic AbusersOWASP Beja
f you offer a service on the web, odds are that someone will abuse it. Be it an API, a SaaS, a PaaS, or even a static website, someone somewhere will try to figure out a way to use it to their own needs. In this talk we'll compare measures that are effective against static attackers and how to battle a dynamic attacker who adapts to your counter-measures.
About the Speaker
===============
Diogo Sousa, Engineering Manager @ Canonical
An opinionated individual with an interest in cryptography and its intersection with secure software development.
Have you ever wondered how search works while visiting an e-commerce site, internal website, or searching through other types of online resources? Look no further than this informative session on the ways that taxonomies help end-users navigate the internet! Hear from taxonomists and other information professionals who have first-hand experience creating and working with taxonomies that aid in navigation, search, and discovery across a range of disciplines.
This presentation, created by Syed Faiz ul Hassan, explores the profound influence of media on public perception and behavior. It delves into the evolution of media from oral traditions to modern digital and social media platforms. Key topics include the role of media in information propagation, socialization, crisis awareness, globalization, and education. The presentation also examines media influence through agenda setting, propaganda, and manipulative techniques used by advertisers and marketers. Furthermore, it highlights the impact of surveillance enabled by media technologies on personal behavior and preferences. Through this comprehensive overview, the presentation aims to shed light on how media shapes collective consciousness and public opinion.
Sharpen existing tools or get a new toolbox? Contemporary cluster initiatives...Orkestra
UIIN Conference, Madrid, 27-29 May 2024
James Wilson, Orkestra and Deusto Business School
Emily Wise, Lund University
Madeline Smith, The Glasgow School of Art
Sharpen existing tools or get a new toolbox? Contemporary cluster initiatives...
Instrument Transformer Presentation
1.
2. Instrument Transformer
Guided By :
Sr. Er. S. K. Roy
Instrument Transformer
Manufacturing Department
BHEL Jhansi
Presented By :
Rishi Kumar
1604320042
B.Tech (EE)
A
Summer Vocational Training Presentation
On
2
Head of Department :
Dr. D. K. Srivastava
Electrical Engineering Department
BIET Jhansi
3. Overview
1. Introduction to Instrument Transformer
2. Its Classification
3. Design & Function of CT
4. Construction, Accuracy Limit & Equivalent CKT
5. Safety Precaution & Usage of CT
6. Design & Function of PT
7. Construction & Error of PT
8. Cause of Error in PT
9. Conclusion
10. Reference
4. Introduction
Instrument transformers are necessary for
Isolating the protection, control &
measurement equipment from the
high voltages of apower system
Supplying the equipment with the
appropriate values of current and
voltage
5. Types of Instrument Transformers
Two Types of Instrument Transformers :
Current Transformer (CT)
Potential Transformer (PT)
Current transformer & Potential transformer
7. Like any other transformer, a current transformer has a
primary winding, a magnetic core and asecondary winding
The primary winding of a current transformer is
connected in series with the powercircuit
The impedance is negligible compared with that of the
power circuit
Thealternating current flowing inthe primary produces a
magnetic field in the core & induces acurrent in the
secondary winding
TheCT'sprimary circuit consists of a single 'turn' of
conductor, with a secondary of many tens or hundreds of
turns
Theprimary winding maybe a permanent part of the
current transformer, with aheavycopperbar to carry
current through the magnetic core
Design
8. Reduce power system current to
lower value for measurement
Insulate secondary circuits
from the primary
Permit the use of standard
current ratings for secondary
equipment
Function
10. RELAY
1A1000A
1000 turnssec
Insulation covered wire,
giving inter-turn insulation
& secondary to core
insulation
Generator, orsystem
voltagesource
‘Feeder’ or ‘Bus-bar’forming
1 turn of primary circuit
Insulation to stop flash-over
from HVprimary to core&
secondary circuit
Bar-Primary Type CT
Laminated‘strip’woundsteel toroidal core
11. Accuracy
The accuracy of a CT is directly related to a number of
factors :
Burden : The secondary load of a current transformer is usually called the
"burden" to distinguish it from the load of the circuit whose current is being
measured
Rating factor : Rating factor is a factor by whichthe nominal full load current of
a CT can be multiplied to determine its absolute maximum measurable
Load
External electromagnetic fields
Temperature
Physical configuration.
The selected tap, for multi-ratio CTs
12. C.T. Equivalent Circuit
ZbN
P1
ZCT
S1
VtZe
Is
Ip
Ip/N
Ie
Es
Ip = Primaryrating of C.T. Ie = Secondaryexcitation current
N = C.T.ratio Is = Secondarycurrent
Zb = Burdenof relays in ohms Es = Secondaryexcitation voltage
(r+jx) Vt = Secondaryterminal voltage
ZCT= C.T.secondary winding
impedancein ohms (r+jx)
acrossthe C.T. terminals
Ze = Secondaryexcitation
13. Safety Precaution
The secondary of a current transformer is not disconnected
from its load while current is flowing in the primary
The transformer secondary will attempt to continue driving current
across the effectively infinite impedance.
This will produce a high voltage across the open secondary
This high peaks of voltage may not be measured by conventional
voltmeter. But these high peaks of induced voltage may breakdown
the CT insulation, and may case accident to personnel
14. Usage
Current transformers are used:
A CT for operation on a 110 kV grid
Monitoring the operation of
the power grid
Measuring current
16. Design
A Potential Transformer theory is just like
theory of general purpose step down
transformer
Primary of this transformer is connected across
the phases or and ground depending upon the
requirement
PThaslowers turns winding at itssecondary
In an ideal Potential Transformer when rated
burden connected across the secondary the
ratio of primary and secondary voltages of
transformer is equal to theturns ratio
But in actual transformer there must be an error
in the voltage ratio as well as in the phase angle
between primary and secondaryvoltages
17. Types of Potential Transformer
Two main basic types are available :
Electromechanical PTs
Similar to a power transformer
May not be economical above 132kV
Capacitor PTs (CPT)
Used at high voltages
Main difference is that CPT has a capacitor divider on the
front end
18. Construction of PT
The construction of a voltage transformer takes into
account the following factors
a. Output – Seldom more than 200-300VA. Cooling is
rarely a problem
b. Insulation – Designed for the system impulse
voltage level. Insulation volume is often larger
than the winding volume
c. Mechanical Design – Not usually necessary to
withstand short-circuit currents. Must be small to
fit the space available within switchgear
19. Provides isolation from high
voltages
Must operate in the linear
region to prevent accuracy
problems - Do not over specify
VT
Must be capable of driving the
burden, specified by relay
manufacturer
Protection class VT will suffice
Function
20. Errors in PT
Is - Secondary Current
Es - Secondary induced emf
Vs - Secondary terminal voltage Ip -
Primary current
Ep - Primary induced emf
Vp - Primary terminal voltage
KT - numbers of primary turns/number of
secondary turns
Io - Excitation Current
β - phase angle error
The difference between the ideal value
Vp/KT and actual value Vs is the voltage
error or ratio error in a potential
transformer
% voltage error = Vp − KT.Vs /Vp X 100 %
The angle ′β′ between the primary
system voltage Vp and the reversed
secondary voltage vectors KT.Vs is the
phase error
21. The voltage applied to the primary
of the potential transformer first
drops due to internal impedance of
primary
Cause of Error in PT
Transformed voltage across
secondary winding will again
drops due to internal impedance
of secondary before appearing
across burden terminals
22. Conclusion
Current Transformer
Measuring current
Monitoring the operation of
the power grid
• CT secondary should not be kept open
Potential Transformer
Measuring Voltage
Provides isolation from high voltages
23. References
1. "Measurement Canada Standard Dwg. No.3400 D3 Delta Connected CTs" (PDF).
Measurement Canada. Retrieved 12 December 2012.
2. "Limits of the 0.3 and 0.6 accuracy classes for measuring current transformers".
Measurement Canada. Retrieved 18 April 2013.
3. "PS-E-15 — Provisional Specifications for Approval of Electronic Voltage
Transformers". Measurement Canada. Retrieved 18 April 2013.
4. Monsef, H.; Ghomian, T. (2006). "Modified quadrature method for accurate voltage
measurement in optical voltage transducer". IEE Proceedings - Generation,
Transmission and Distribution. 153 (5): 524. doi:10.1049/ip-
gtd:20050189. ISSN 1350-2360.
5. Network Protection & Automation anshu, AREVA 2002