Basic training water based fire protectionSabrul Jamil
This presentation contains training materials of my training of Introduction to WATER BASED FIRE PROTECTION SYSTEM, Which includes, Standpipe (Hydrant) System, Wet pipe Sprinkler System, Dry pipe Sprinkler System,
Deluge Sprinkler System, Single interlock Pre-Action Sprinkler System, Double Interlock Pre-Action Sprinkler System and
Water Mist Fire Protection
1. Sprinkler system Type
WET PIPE SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
PRE-ACTION SYSTEM
DELUGE SYSTEM
WET PIPE ANTI FREEZE SYSTEM
FOAM WATER SPRINKLER SYSTEM
2. Sprinkler Selection
For COMPLETE PREMIUM BOOK PLZZ
Check out my product on Instamojo:https://www.instamojo.com/ezazsidd1993/fire-fighting-a-complete-handbook/
Fire fighting, types of fires, types of fire extinguishers, building management systems, sprinkler systems, heat and smoke sensors.
http://www.greenarchworld.com/
Basic training water based fire protectionSabrul Jamil
This presentation contains training materials of my training of Introduction to WATER BASED FIRE PROTECTION SYSTEM, Which includes, Standpipe (Hydrant) System, Wet pipe Sprinkler System, Dry pipe Sprinkler System,
Deluge Sprinkler System, Single interlock Pre-Action Sprinkler System, Double Interlock Pre-Action Sprinkler System and
Water Mist Fire Protection
1. Sprinkler system Type
WET PIPE SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
PRE-ACTION SYSTEM
DELUGE SYSTEM
WET PIPE ANTI FREEZE SYSTEM
FOAM WATER SPRINKLER SYSTEM
2. Sprinkler Selection
For COMPLETE PREMIUM BOOK PLZZ
Check out my product on Instamojo:https://www.instamojo.com/ezazsidd1993/fire-fighting-a-complete-handbook/
Fire fighting, types of fires, types of fire extinguishers, building management systems, sprinkler systems, heat and smoke sensors.
http://www.greenarchworld.com/
Some fire fighting systems in a building that should always be there during the time of hazards. Fire accidents require the most efficient and proper solutions or it would worsen the situation . These are some of the fire fighting systems that can be implemented.
FOR DOWNLOAD THIS GO THROUGH THIS BELOW LINK
https://ezazsidd1993.stores.instamojo.com/?ref=profile_bar
AUTOMATIC FIRE FIGHTING SYSTEM -WATER SPRINKLER SYSTEM
WATER MIST SYSTEM
FOAM SYSTEM
GAS SUPPRESSION SYSTEM
Fire hydrant installation consists of a system of pipe work connected directly to the water supply main to provide water to each and every hydrant outlet and is intended to provide water for the firemen to fight a fire. The water is discharged into the fire engine form which it is then pumped and sprayed over fire. Where the water supply is not reliable or inadequate, hydrant pumps should be provided to pressurize the fire mains.
described definition ..all types of fire protection devices...fire alarm systems..fire detector systems..standards for designing building in case of afire,emergency exit,safety factors...
PREMIUM BOOK WITH HIGH DEFINITION QUALITY.
**A complete Guide of Fire fighting System.**
This HANDBOOK has been made from references of many books from all over the world. Which has been collected in one book.
1. Sprinkler system Type
WET PIPE SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
PRE-ACTION SYSTEM
DELUGE SYSTEM
WET PIPE ANTI FREEZE SYSTEM
FOAM WATER SPRINKLER SYSTEM
2. Sprinkler Selection
3 . Piping
4. Hydraulic Calculation
5. Standpipe System
6. Pump Selection & Types
Novec Fire Suppression System
Novec 1230 Fire Protection Fluid
The search for halon 1301 replacements has been on-going for over 10 years and each alternative brings with it a unique set of properties. We have brought to the market products that match the requirements of industry and our latest research allows us to introduce fire protection systems using Novec 1230 fluid , a new development with some advantages over current technologies. Novec 1230 fluid allows us to complement our existing range of agents as the phase out of halons accelerates in many countries around the world.
1 . Piping
2. Tank Design
3. Standpipe System
4. Pump Selection & Types
For Complete FIREFIGHTING Presentation
Check out my product on Instamojo:https://www.instamojo.com/ezazsidd1993/fire-fighting-a-complete-handbook/
Some fire fighting systems in a building that should always be there during the time of hazards. Fire accidents require the most efficient and proper solutions or it would worsen the situation . These are some of the fire fighting systems that can be implemented.
FOR DOWNLOAD THIS GO THROUGH THIS BELOW LINK
https://ezazsidd1993.stores.instamojo.com/?ref=profile_bar
AUTOMATIC FIRE FIGHTING SYSTEM -WATER SPRINKLER SYSTEM
WATER MIST SYSTEM
FOAM SYSTEM
GAS SUPPRESSION SYSTEM
Fire hydrant installation consists of a system of pipe work connected directly to the water supply main to provide water to each and every hydrant outlet and is intended to provide water for the firemen to fight a fire. The water is discharged into the fire engine form which it is then pumped and sprayed over fire. Where the water supply is not reliable or inadequate, hydrant pumps should be provided to pressurize the fire mains.
described definition ..all types of fire protection devices...fire alarm systems..fire detector systems..standards for designing building in case of afire,emergency exit,safety factors...
PREMIUM BOOK WITH HIGH DEFINITION QUALITY.
**A complete Guide of Fire fighting System.**
This HANDBOOK has been made from references of many books from all over the world. Which has been collected in one book.
1. Sprinkler system Type
WET PIPE SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
PRE-ACTION SYSTEM
DELUGE SYSTEM
WET PIPE ANTI FREEZE SYSTEM
FOAM WATER SPRINKLER SYSTEM
2. Sprinkler Selection
3 . Piping
4. Hydraulic Calculation
5. Standpipe System
6. Pump Selection & Types
Novec Fire Suppression System
Novec 1230 Fire Protection Fluid
The search for halon 1301 replacements has been on-going for over 10 years and each alternative brings with it a unique set of properties. We have brought to the market products that match the requirements of industry and our latest research allows us to introduce fire protection systems using Novec 1230 fluid , a new development with some advantages over current technologies. Novec 1230 fluid allows us to complement our existing range of agents as the phase out of halons accelerates in many countries around the world.
1 . Piping
2. Tank Design
3. Standpipe System
4. Pump Selection & Types
For Complete FIREFIGHTING Presentation
Check out my product on Instamojo:https://www.instamojo.com/ezazsidd1993/fire-fighting-a-complete-handbook/
Presentation of our Inert Fire Suppression Systems available at 200 bar and 300 bar.
All 4 types of gases offered:
Argon (IG-01), Nitrogen (IG-100), IG-55 and IG-541
Presentation on Alternative Refrigerants related to mechanical engineering for application in mechanical systems (air conditoning and refrigerators etc) and chemical engineering
Mr Sanjay Goyal, Director & Sr. VP, VRV, Light Commercial Business & Technical Support, Daikin India gave presentation on The Ecological Power of Green Refrigerant at CII-IGBC 15th Green Building Congress 2017 event at Jaipur.
Changing Best Practices in Flue Gas AnalysisYokogawa1
Zirconium Oxide and Catalytic Bead sensor based analyzers have been the primary means of flue gas analysis for control and safety. The recently published API-556 has highlighted several considerations when using these technologies that were not commonly known throughout the industry. This webinar will explain the theory of operation of tunable diode laser spectrometers and the application thereof to gas fired reformers, boilers, & heaters as a layer of protection during startup and efficiency diagnostic during operation.
During this webinar recording, you will learn:
-What is the purpose of flue gas?
-The evolution of flue gas Analyzers
-Industry standards and recommended practices on the application of different types of instruments
Congres F-gassen 2015. Workshop 8: Scroll CO2, bied veel meer dan alleen een ...RCCKL
Gábor Böszörményi en Jack Quadflieg van Emerson gaan in op Scroll CO2, een ideale keuze voor lage temperatuur Cascade en Boostersysteem.
Met de combinatie digitale scroll ZBD en ZB range voor medium temperatuur en ZO scroll compressoren voor CO2 subkritische lage temperatuur heeft Copeland een betrouwbaar en volledig productportfolio te bieden dat al zeer succesvol is toegepast. Met een case study laten we zien hoe en waar Scolls CO2 zijn ingezet en welke voor- en nadelen het biedt in vergelijk met de traditionele CO2 oplossingen.
Het gebruik van (digitale)scroll in cascade systemen helpt klanten en eindgebruikers de extra investeringskosten met R134a en R744 vergeleken met Standard HFK's te neutraliseren. Significante kostenbesparingen kunnen gerealiseerd worden in vergelijking met Cascade systemen op basis van semihermetische oplossingen met inverters. Het compacte ontwerp van de scroll minimaliseert de vloeroppervlakte van de machinekamer. Daarom is dit een ideale keuze voor kleine retail toepassingen. Bovendien, samen met de Stream compressoren voor transkritische CO2 toepassingen, biedt de ZO(D) scroll vele mogelijkheden om de grootte van de booster systemen te verminderen en de investeringskosten te beperken. Digitale scroll technologie (10-100% modulatie) kan worden ingezet om de hoge kosten van inverter technologie te reduceren, resulterend in een aanzienlijke kostenbesparingterwijl de efficiency van het apparatuur gewaarborgd wordt.
Lees alles over F-gassen op http://www.koudeenluchtbehandeling.nl/f-gassen-dossier
The currently used refrigerant properties were recommended as unsuitable for the future use due to their high ozone-depleting rate. To abide with the Montrcal Protocol norms have been taken into account and suitable alternative, which is innocuous to ozone layer.
Performance of HFC-152a is researched to develop the HFC-152a as alternative mixture. The HFC-152a has been tested under various systems. Its properties, comparison with HFC-134a, cost, risk assessment, efficiency and technological issues have been discussed.
energy conservative and efficient technologies in industriesKamran Hassan
Variable Frequency Drive
Energy Efficient Motor
Thermo Compressor
Biogas Plant
Diffuser
Cogeneration
Use Of Boiler’s Flue Gases/Exhaust In Economizer
HP Boiler
Fire detectors - Aspiratory smoke detectorKamran Hassan
Aspirated smoke detection (ASD) is a method of smoke detection where the air from the protected area is actively drawn through a network of air sampling pipes, passed through a central detection unit and sampled for the presence of smoke.
Basic requirement for fire suppression piping - ECARO-25Kamran Hassan
Design requirements of fire suppression system like tee factor, concentration at different temperature, min pressure, nozzle design and min flow rate for fire extinguishing agent
Fire alarm , detection and suppression systemKamran Hassan
fire detection and suppression system. Types of fire and different fire extinguishing material and agents like FM200, NOVEC and ECARO, water, foam and dry agents
COMMON PROBLEMS AND CHALLENGES IN DATA CENTRESKamran Hassan
in this paper common problems and challenges of data center have been identified and methods have been explained to improve the efficiency and reliability of data center
it explains
Temperature Classes
Causes of High Temperature
Cooling Symbol
ONAN (oil natural air natural).
ONWF (oil natural water forced).
ONAF (oil natural air forced).
OFAN (oil forced air natural).
OFWF (oil forced water forced).
• Directed cooling or zig-zag cooling
• Non directed cooling or axial cooling
• Fully directed cooling or pumped cooling
We have compiled the most important slides from each speaker's presentation. This year’s compilation, available for free, captures the key insights and contributions shared during the DfMAy 2024 conference.
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTjpsjournal1
The rivalry between prominent international actors for dominance over Central Asia's hydrocarbon
reserves and the ancient silk trade route, along with China's diplomatic endeavours in the area, has been
referred to as the "New Great Game." This research centres on the power struggle, considering
geopolitical, geostrategic, and geoeconomic variables. Topics including trade, political hegemony, oil
politics, and conventional and nontraditional security are all explored and explained by the researcher.
Using Mackinder's Heartland, Spykman Rimland, and Hegemonic Stability theories, examines China's role
in Central Asia. This study adheres to the empirical epistemological method and has taken care of
objectivity. This study analyze primary and secondary research documents critically to elaborate role of
china’s geo economic outreach in central Asian countries and its future prospect. China is thriving in trade,
pipeline politics, and winning states, according to this study, thanks to important instruments like the
Shanghai Cooperation Organisation and the Belt and Road Economic Initiative. According to this study,
China is seeing significant success in commerce, pipeline politics, and gaining influence on other
governments. This success may be attributed to the effective utilisation of key tools such as the Shanghai
Cooperation Organisation and the Belt and Road Economic Initiative.
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressionsVictor Morales
K8sGPT is a tool that analyzes and diagnoses Kubernetes clusters. This presentation was used to share the requirements and dependencies to deploy K8sGPT in a local environment.
Low power architecture of logic gates using adiabatic techniquesnooriasukmaningtyas
The growing significance of portable systems to limit power consumption in ultra-large-scale-integration chips of very high density, has recently led to rapid and inventive progresses in low-power design. The most effective technique is adiabatic logic circuit design in energy-efficient hardware. This paper presents two adiabatic approaches for the design of low power circuits, modified positive feedback adiabatic logic (modified PFAL) and the other is direct current diode based positive feedback adiabatic logic (DC-DB PFAL). Logic gates are the preliminary components in any digital circuit design. By improving the performance of basic gates, one can improvise the whole system performance. In this paper proposed circuit design of the low power architecture of OR/NOR, AND/NAND, and XOR/XNOR gates are presented using the said approaches and their results are analyzed for powerdissipation, delay, power-delay-product and rise time and compared with the other adiabatic techniques along with the conventional complementary metal oxide semiconductor (CMOS) designs reported in the literature. It has been found that the designs with DC-DB PFAL technique outperform with the percentage improvement of 65% for NOR gate and 7% for NAND gate and 34% for XNOR gate over the modified PFAL techniques at 10 MHz respectively.
ACEP Magazine edition 4th launched on 05.06.2024Rahul
This document provides information about the third edition of the magazine "Sthapatya" published by the Association of Civil Engineers (Practicing) Aurangabad. It includes messages from current and past presidents of ACEP, memories and photos from past ACEP events, information on life time achievement awards given by ACEP, and a technical article on concrete maintenance, repairs and strengthening. The document highlights activities of ACEP and provides a technical educational article for members.
A review on techniques and modelling methodologies used for checking electrom...nooriasukmaningtyas
The proper function of the integrated circuit (IC) in an inhibiting electromagnetic environment has always been a serious concern throughout the decades of revolution in the world of electronics, from disjunct devices to today’s integrated circuit technology, where billions of transistors are combined on a single chip. The automotive industry and smart vehicles in particular, are confronting design issues such as being prone to electromagnetic interference (EMI). Electronic control devices calculate incorrect outputs because of EMI and sensors give misleading values which can prove fatal in case of automotives. In this paper, the authors have non exhaustively tried to review research work concerned with the investigation of EMI in ICs and prediction of this EMI using various modelling methodologies and measurement setups.
6. NFPA 2001
Standard for Clean Agent Fire Extinguishing Systems
Standard contains MINIMUM requirements for total flooding
clean agent systems, NOT local application.
Halocarbon Agents:
-HFC-125 (DuPont FE-25 / Fike ECARO-25)
-HFC-227ea ( FM-200 DuPont )
-HFC-23 (DuPont / Kidde FE-13)
-FK-5-12 (3M / Ansul Novec 1230) new agent in NFPA 2001
Inert Gas Agents:
-IG-55 (Chemetron Argonite & Fike ProInert)
-IG-541 (Ansul Inergen & Fike Proinert)
DOES NOT cover Carbon Dioxide or Water agents
11. Inert Gas Fire Extinguishing Method
• Are designed to reduce the ambient oxygen
concentration in a protected space to
between 10 - 14% by utilizing a
concentration of 38.5 - 42% by volume, a
level that is breathable but will not support
flaming combustion.
• Argon / Nitrogen / CO2 or a blend.
12. P/N: 06-384-INTRO
• Typical system design will result in a residual Oxygen
level between 10 and 15% after agent discharge
(based on system designed at 38.5%)
• Design Concentrations up to 43% will result in
Oxygen level of 12% (requires 5 minute egress)
• Design Concentrations between 43 and 52% will
result in Oxygen levels between 12 and 10% (requires
3 minute egress)
• Reference NFPA 2001
Approved for use in Occupied Spaces
We are often asked whether the chemical agent alternatives extinguish via the same methods as Halon 1301. This chart illustrates that the clean agents of today do extinguish via the same mechanisms as Halon 1301 but the extinguishing affects have different impacts. One of the key attributes of Halon 1301 was that it extinguished “primarily” via reaction interruption. This drove the extinguishing concentration for Halon 1301 well below the predicted levels if heat absorption was the sole method for extinguishment.
In the case of FE-25™, the primary method of extinguishment is via Heat Absorption vs. Reaction Interruption. This explains why the extinguishing concentration of FE-25™ and the other chemical agent alternatives is so much higher that Halon 1301. This is part of the reason why the systems cost more and require more agent consuming more space.