The document discusses electrical grounding, including its importance for safety and protection from electrical hazards. It outlines several benefits of proper grounding, such as personal protection from electric shocks, protection of devices from voltage fluctuations, and reducing damage from lightning strikes. The document also covers general concepts regarding grounding, relevant standards and regulations, and the factors that influence grounding resistance.
Basics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protection
Basics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protectionBasics of busbar protection
This presentation is from my talk Delivered to Young Engineers to have a brief overview of :
1. Substation And Its Types
2. Substation Equipment
3. Substation Grounding
4. Design Consideration
5. Bus Switching Scheme
6. Basic Insulation Level and Its importance
7. Fault level and its importance
8. Other Equipment
9. Substation IEC 61850 Protocol Basic
It will be helpful for Engineering students to have an overview from a Practical point of view. Widely publicize it for benefit of others.
MV Switchgear provides centralized control and protection of medium-voltage power equipment and circuits in industrial, commercial, and utility installations involving generators, motors, feeder circuits, and transmission and distribution lines.
Design of a generating substation with the description of designing a transformer. Here we show some basic components of a substation. and we also show the parameters and calculation to design a transformer of a specific ratings.
Presentation on Over-/under-voltage protection of electrical applianceNishant Kumar
Sudden fluctuation in supply is a very big problem in industries and domestic applications. It causes a major loss for industries, offices and homes.
This project gives a low cost and powerful solution for this problem. This Circuit protects refrigerators ,ACs, Microwave ovens as well as other appliances from over and under voltage fluctuations.
Unit I: Introduction to Protection System:
Introduction to protection system and its elements, functions of protective relaying, protective zones, primary and backup protection, desirable qualities of protective relaying, basic terminology.
Relays:
Electromagnetic, attracted and induction type relays, thermal relay, gas actuated relay, design considerations of electromagnetic relay.
Unit-II: Relay Application and Characteristics:
Amplitude and phase comparators, over current relays, directional relays, distance relays, differential relay.
Static Relays: Comparison with electromagnetic relay, classification and their description, over current relays, directional relay, distance relays, differential relay.
Unit-III Protection of Transmission Line:
Over current protection, distance protection, pilot wire protection, carrier current protection, protection of bus, auto re-closing,
Unit-IV: Circuit Breaking:
Properties of arc, arc extinction theories, re-striking voltage transient, current chopping, resistance switching, capacitive current interruption, short line interruption, circuit breaker ratings.
Testing Of Circuit Breaker: Classification, testing station and equipments, testing procedure, direct and indirect testing.
Unit-V Apparatus Protection:
Protection of Transformer, generator and motor.
Circuit Breaker: Operating modes, selection of circuit breakers, constructional features and operation of Bulk Oil, Minimum Oil, Air Blast, SF6, Vacuum and d. c. circuit breakers.
Troubleshooting of Electrical Switchyard & Substation EquipmentsMarcep Inc.
AGENDA FOR
TRAINING PROGRAMME ON TROUBLESHOOTING,
OPERATION & MAINTENANCE OF SWITCHYARDS AND SUB-
STATION EQUIPMENT WITH A CURSORY GLANCE ON
TRANSMISSION LINES.
Engineering review on AC Power.
Presentation lecture for energy engineering class.
Course: MS in Renewable Energy Engineering, Oregon institute of technology
This presentation is from my talk Delivered to Young Engineers to have a brief overview of :
1. Substation And Its Types
2. Substation Equipment
3. Substation Grounding
4. Design Consideration
5. Bus Switching Scheme
6. Basic Insulation Level and Its importance
7. Fault level and its importance
8. Other Equipment
9. Substation IEC 61850 Protocol Basic
It will be helpful for Engineering students to have an overview from a Practical point of view. Widely publicize it for benefit of others.
MV Switchgear provides centralized control and protection of medium-voltage power equipment and circuits in industrial, commercial, and utility installations involving generators, motors, feeder circuits, and transmission and distribution lines.
Design of a generating substation with the description of designing a transformer. Here we show some basic components of a substation. and we also show the parameters and calculation to design a transformer of a specific ratings.
Presentation on Over-/under-voltage protection of electrical applianceNishant Kumar
Sudden fluctuation in supply is a very big problem in industries and domestic applications. It causes a major loss for industries, offices and homes.
This project gives a low cost and powerful solution for this problem. This Circuit protects refrigerators ,ACs, Microwave ovens as well as other appliances from over and under voltage fluctuations.
Unit I: Introduction to Protection System:
Introduction to protection system and its elements, functions of protective relaying, protective zones, primary and backup protection, desirable qualities of protective relaying, basic terminology.
Relays:
Electromagnetic, attracted and induction type relays, thermal relay, gas actuated relay, design considerations of electromagnetic relay.
Unit-II: Relay Application and Characteristics:
Amplitude and phase comparators, over current relays, directional relays, distance relays, differential relay.
Static Relays: Comparison with electromagnetic relay, classification and their description, over current relays, directional relay, distance relays, differential relay.
Unit-III Protection of Transmission Line:
Over current protection, distance protection, pilot wire protection, carrier current protection, protection of bus, auto re-closing,
Unit-IV: Circuit Breaking:
Properties of arc, arc extinction theories, re-striking voltage transient, current chopping, resistance switching, capacitive current interruption, short line interruption, circuit breaker ratings.
Testing Of Circuit Breaker: Classification, testing station and equipments, testing procedure, direct and indirect testing.
Unit-V Apparatus Protection:
Protection of Transformer, generator and motor.
Circuit Breaker: Operating modes, selection of circuit breakers, constructional features and operation of Bulk Oil, Minimum Oil, Air Blast, SF6, Vacuum and d. c. circuit breakers.
Troubleshooting of Electrical Switchyard & Substation EquipmentsMarcep Inc.
AGENDA FOR
TRAINING PROGRAMME ON TROUBLESHOOTING,
OPERATION & MAINTENANCE OF SWITCHYARDS AND SUB-
STATION EQUIPMENT WITH A CURSORY GLANCE ON
TRANSMISSION LINES.
Engineering review on AC Power.
Presentation lecture for energy engineering class.
Course: MS in Renewable Energy Engineering, Oregon institute of technology
Ohm's Law V = I x R (Volts = Current x Resistance). The Ohm (Ω) is a unit of electrical resistance equal to that of a conductor in which a current of one ampere is produced by a potential of one volt across its terminals. 1)Measurement of Low resistance: 1) Ammeter Voltmeter method: This is very popular method for measurement of medium resistances since ...
Electrochemical Machining (ECM) has established itself as one of the major alternatives to conventional methods of machining difficult - to - cut materials of and generating complex contours, without inducing residual stress and tool wear.
This seminar is devoted to the study of influences of variable ECM parameters like applied voltage and feed rate keeping other parameters constant on the surface roughness (Ra) using Response Surface Methodology (RSM).
Conductor materials - Copper and its alternativesLeonardo ENERGY
The only known electrical conductor materials with a commercial applicability are copper and aluminium. Between these two there is only limited competition because their other characteristics beyond electrical conductivity are so different. Which are these differences, and are there any other materials that may serve as electrical conductors? How about competing technologies such as wireless energy transfer?
SmalTec International is the world’s leading manufacturer of micromachining equipment for aerospace, communications, medical, automotive, optics, nanotechnology and other innovative industries.
Lawrence Livermore National Laboratory
المحرك الصاروخي المعدل بقي حقيقه وقفزة علمية
بدأ اعتمادا علي المحاكاة فقط وصلا للنجاح وطبعا تحت مظلة وزاره الدفاع الامريكيه لتأمين الدعم اللازم و...
اضافة مؤثرة فعلا في تلك الصناعة
وأهم حاجه فيه ان الثرست زاد مع زياده الكفاءه ايضا ده غير ان الثرست نفسه بيعتمد علي الارتفاع
ده هيطور رحلات الذهاب >> والعوده!! كمان بشكل كبير
https://str.llnl.gov/november-2015/burton
multi mission radar (MMR) - EL/M-2084 FOR IRON DOMEHossam Zein
multi mission radar (MMR) - EL/M-2084 FOR IRON DOME
from IAI MELTA
for more detailed info. visit -::-
http://hossamozein.blogspot.com/2011/10/iron-dome.html
Safalta Digital marketing institute in Noida, provide complete applications that encompass a huge range of virtual advertising and marketing additives, which includes search engine optimization, virtual communication advertising, pay-per-click on marketing, content material advertising, internet analytics, and greater. These university courses are designed for students who possess a comprehensive understanding of virtual marketing strategies and attributes.Safalta Digital Marketing Institute in Noida is a first choice for young individuals or students who are looking to start their careers in the field of digital advertising. The institute gives specialized courses designed and certification.
for beginners, providing thorough training in areas such as SEO, digital communication marketing, and PPC training in Noida. After finishing the program, students receive the certifications recognised by top different universitie, setting a strong foundation for a successful career in digital marketing.
Unit 8 - Information and Communication Technology (Paper I).pdfThiyagu K
This slides describes the basic concepts of ICT, basics of Email, Emerging Technology and Digital Initiatives in Education. This presentations aligns with the UGC Paper I syllabus.
Acetabularia Information For Class 9 .docxvaibhavrinwa19
Acetabularia acetabulum is a single-celled green alga that in its vegetative state is morphologically differentiated into a basal rhizoid and an axially elongated stalk, which bears whorls of branching hairs. The single diploid nucleus resides in the rhizoid.
Synthetic Fiber Construction in lab .pptxPavel ( NSTU)
Synthetic fiber production is a fascinating and complex field that blends chemistry, engineering, and environmental science. By understanding these aspects, students can gain a comprehensive view of synthetic fiber production, its impact on society and the environment, and the potential for future innovations. Synthetic fibers play a crucial role in modern society, impacting various aspects of daily life, industry, and the environment. ynthetic fibers are integral to modern life, offering a range of benefits from cost-effectiveness and versatility to innovative applications and performance characteristics. While they pose environmental challenges, ongoing research and development aim to create more sustainable and eco-friendly alternatives. Understanding the importance of synthetic fibers helps in appreciating their role in the economy, industry, and daily life, while also emphasizing the need for sustainable practices and innovation.
Model Attribute Check Company Auto PropertyCeline George
In Odoo, the multi-company feature allows you to manage multiple companies within a single Odoo database instance. Each company can have its own configurations while still sharing common resources such as products, customers, and suppliers.
Read| The latest issue of The Challenger is here! We are thrilled to announce that our school paper has qualified for the NATIONAL SCHOOLS PRESS CONFERENCE (NSPC) 2024. Thank you for your unwavering support and trust. Dive into the stories that made us stand out!
Introduction to AI for Nonprofits with Tapp NetworkTechSoup
Dive into the world of AI! Experts Jon Hill and Tareq Monaur will guide you through AI's role in enhancing nonprofit websites and basic marketing strategies, making it easy to understand and apply.
Biological screening of herbal drugs: Introduction and Need for
Phyto-Pharmacological Screening, New Strategies for evaluating
Natural Products, In vitro evaluation techniques for Antioxidants, Antimicrobial and Anticancer drugs. In vivo evaluation techniques
for Anti-inflammatory, Antiulcer, Anticancer, Wound healing, Antidiabetic, Hepatoprotective, Cardio protective, Diuretics and
Antifertility, Toxicity studies as per OECD guidelines
1. 2011
Electrical Earthling
Construction, Faults & Protection
Given the importance of electric power as one of the basic elements of
economic and social development has provided a lot of countries support the
electricity sector, by producing power electricity projects resulting in a
significant expansion in using devices & equipments run on electricity.
[ÉáátÅ T{Åxw mx|Ç
Modern Academy for Engineering & Technology
1/1/2011
2. ELECTRICAL EARTHLING
Introduction
Given the importance of electric power as one of the basic elements of economic and social development
has provided a lot of countries support the electricity sector, by producing power electricity projects
resulting in a significant expansion in using devices & equipments run on electricity.
In other way exist the electrical dangerous like fires, electric shocks and other so we must use … (Earth
Leakage Circuit Breakers) for electrical leakage protection. (Will be mentioned in details…)
Likely to feel the normal person that often do not impact the ground on the electrical systems or devices
through its normal operating, Which give the false impression that it is possible to separate the ground
without notice any effects as a result it appears (seemingly only) that the b ground good contact with the
ground poor is not a do not know the importance of the effectiveness of the ground unless it conducted
periodic surveys from time to time.
The grounding is required to provide for the safety of the electrical system and the staff a
t the facility and this is known in general among some of people, but is not clear the most of them how to
achieve that.
B enefits:
Firstly: personal protection of electric shocks caused by Isolation failure.
Secondly: protection from Electrical Discharging.
Thirdly: Protect devices from sudden changes in Voltage source.
Fourthly: Reduce the likelihood of damage as a result of lightning or fault currents, Lightning Strikes,
Static Discharges, EMI and RFI signals and Interference.
Fifthly: Functional earthling in electrical power system.
T he agencies and organizations all have recommendations and / or standards for grounding, to
ensure that personnel safety is being protected. The organizations that provide guide lines/rules for
grounding are: The International Electrotechnical Commission (IEC), European Committee for
Electrotechnical Standardization (CENELEC), Underwriters Laboratories (UL), National Fire Protection
Association (NFPA), American National Standards Institute (ANSI), Mine Safety Health Administration
(MSHA), Occupational Safety Health Administration (OSHA), Telecommunications Industry Standard (TIA)
and others.
I nstrument And Devices Must be Earthed:
To make Good ground Network, it is necessary to ground the following elements: - All metal objects
vertically and more than 240 cm in length or extended horizontally and more than 150 cm in length and
are exposed to contact. - All electrical appliances. - All Albriz exits رج ا اand lighting units.
2
Page
Hossam Ahmed Zein
3. ELECTRICAL EARTHLING
General Concepts
Step Voltage :
The difference in surface Potential experienced by a person bridging a distance of 1 meter with his feet
without contacting any grounded object.
Touch Voltage ;
Potential difference between rise and surface potential at the point where the person standing while in
the same time having his hand contact with grounded structure.
Mesh Voltage :
The max. touch voltage within a mesh of groun grid.
Transferred Voltage :
A special case of touch voltage where a voltage is transferred into or out a substation from or to a remote
point external to the substation site.
3
Page
Hossam Ahmed Zein
4. ELECTRICAL EARTHLING
Standards
Ideal Ground Resistance should be Zero ohm But practically, it must be lower than 25 ohm for power
systems & 5 ohm For Telecommunication System achieved by increasing no. of ground electrodes.
It is at least 2,4 m in length and in contact with the soil. There are 3 variables that affect the
resistance of a ground electrode:
a) The ground material Itself.
b) The length/depth of the ground electrode.
• Very effective way of lowering resistance is to drive ground electrodes deeper. Because the
earth is in layers resistivity changes and varies considerably on the layer and the depth within
that layer.
c) Diameter of the ground electrode.
• Increasing the diameter of the ground electrode has very little effect in lowering the
resistance. For example you could double the diameter of a ground electrode and your
resistance would only decrease by as much as 10 %.
d) Chemical Treatment OF the soil:
• Making a hole Beside the grounding electrode with max. distance 10 cm and filled of salts
Mg3SO4 آ ت ال Or Cu2SO4 آ ا سOr ي till 30 cm from surface level .
• By making circular tenth around the electrode with (45 cm-Diameter) & (30 cm-Depth) and
filled with pre-mentioned chemicals ,with no direct contact to the electrode other else
corrosion Occur.
The chemicals recommended to be Cu2SO4 with around (18-40 Kg) as it’s cheap , Good
electrical conductivity and the long run effect (2 years)
• Flood the grounding hole with water for good absorption of salts (chemicals) periodically
that what rain water do.
copper conductor diameter to the Ground Largest copper conductor Diameter
(2mm) Electrode (2mm)
1 1
1.5 1.5
2.5 2.5
4 4
6 6
10 10
16 16
16 25
16 35
25 50
35 70
50 95
70 120
70 150
95 185
120 240
150 300
185 400
4
Page
The allowed Current passing through the Grounding conductor
Hossam Ahmed Zein
5. ELECTRICAL EARTHLING
Instantaneous Current Allowed Current for long Conductor
(A/sec.) time (A) Diameter
(2 mm)
Al Cu AL Cu
- 2500 - 150 16
2700 4000 160 200 25
3700 5500 200 280 35
5300 8000 250 480 50
7400 11500 320 590 70
10500 11600 430 780 95
21000 32500 760 1380 185
Relation between Leakage Current Intensity & Its passing through time in human body
Biological effect on Human
passing through time Current (mA)
body
سو ا ر 0.5 – 0
رو س أا
ك رإ أ ا نا 5 – 0.5
نا را
ً
ء را ل ا
ةد 30 – 5
ا مو ار ع و
ا م – ا م ما
ا 50 – 30
إ ء
ر ا ةا أ
ت ة – 50
ا ر ر ء إ ةا ل أ
ا ر ر ء إ ةا أ
ت ة أآ
ت أو –ء إ ةا ل أ
5
Page
Hossam Ahmed Zein
7. ELECTRICAL EARTHLING
E) Number of ground electrodes
• In this design, more than one electrode is driven into the
ground and connected in parallel to lower the resistance. For
additional electrodes to be effective, the spacing of additional
rods needs to be at least equal to the depth of the driven rod.
F) Ground system design
• Mentioned After ….
7
Page
Hossam Ahmed Zein
8. ELECTRICAL EARTHLING
Ground electrode:
You can use one of the following means of grounding pole, namely:
1 - Extensions of metal pipes for water.
2 - Reinforcing rods أ خ اof the building.
3 - A metal conductor is extended around the building and not less than 75 cm from the surface of the
earth.
4-Specialised Industrial Electrodes:
i. Made Electrode: It is a metal rod or pipe not less than 240 cm in
length buried vertically in contact with the soil unless the ground is
rocky and can be placed diagonally 45 degrees to the vertical level, or
buried in a trench قat a depth of 75 cm from the surface of the
earth at least.
ii. Plate Electrode: It is a sheet metal may be copper (1.5 mm-thick) OR
Iron (6.35mm-min. thickness) , with min. expose area 186 m2
a.
Free Of grease or Oils because they undermine the viability of the properties of the
grounding of the conductivity.
The Electrode consists of three basic components :
1. Ground conductor
2. The connection/bonding of the conductor to the ground electrode
3. The ground electrode itself.
The resistance of a ground electrode has 3 basic components:
A) The resistance of the ground electrode itself and the connections to the electrode.
• it's connection is generally very low, ground rods are generally made of highly
conductive/low resistance material such as copper of copper clad.
B) The contact resistance of the surrounding earth to the electrode.
• The Bureau of Standards has shown this resistance to be almost negligible providing that the
ground electrode is free from paint, grease etc. and that the ground electrode is in firm
contact with the earth
B) The resistance of the surrounding body of earth around the ground electrode. The resistance of a
ground
8
Page
• The ground electrode is surrounded by earth which is made up of concentric shells all having the
same thickness. Those shells closest to the ground electrode have the smallest amount of area
Hossam Ahmed Zein
9. ELECTRICAL EARTHLING
resulting in the greatest degree of resistance. Each subsequent shell incorporates a greater
area resulting in lower resistance. This finally reaches a point where the additional shells offer
little resistance to the ground surrounding the ground electrode.
Types Of grounding
According to the Protective Device
Earth grounding is to ensure that operating equipment within a
structure is properly grounded.
is an intentional connection from a circuit
conductor usually the neutral to a ground
electrode placed in the earth.
Equipment grounding
Complex networks increase the
These two grounding systems are required to prevent amount of contact with the
differences in potential from a possible flashover from a surrounding earth and lower
lightning strike. ground resistances.
According to the Design Simplicity
• Simple grounding systems consist of single 1. Complex grounding systems consist of
ground electrode driven into the ground. The multiple ground rods, connected, mesh or
use of a single ground electrode is the most grid networks, ground plates, and ground
common form of grounding. loops.
• Where: outside your home or place of o Where: at power generating substations,
business. central offices, and cell tower sites.
According to its Design techniques
a. Single ground electrode.
b. Multiple ground electrodes connected.
c. Mesh network.
d. Ground plate. 9
Page
Hossam Ahmed Zein
10. ELECTRICAL EARTHLING
According to its fuctionality :-
1. Functional grounding: this kind of grounding is related to the proper work of the system like (neutral
point grounding, reactors grounding ..etc.)
2. Protective grounding: This kind related to personal protection due electric shocks and its about
connecting all conducting of non-current carrier with earth
3. Lighting Protection: Protect the system from lighting discharging any traveling waves or equip the
substation with equipments to discharge the lighting as it happen
Ground Fault Protection
Circuit Breakers
Electrical circuits Protected by Normal cit. breakers (15-20) -- 60 mA Cause human Death – and it’s so
sensitive for the lowest current .
Types Of Circuit breakers:
1st Type: it shutdown the cit. when the passing current about 6 mA .
2ndType: it shutdown the cit. when the passing current about 20 mA .
Where Cit. Breakers Connected (Elcb):
i. Elcb circuit breaker Connected on the main power line for General protection for all circuits,
(Main Protection)
But it cause total current break down for any current leak in any following circuits (lighting)
ii. Using two cit. breakers , one (normal) for the main lighting board and the other (Elcb) for the
main power board .
10
Page
Hossam Ahmed Zein
11. ELECTRICAL EARTHLING
iii. Could be used for distinct device ( air conditioner ) condition that this device must be earthed. Or
for apart of home or some place (Individual Protection)
11
Page
Hossam Ahmed Zein
13. ELECTRICAL EARTHLING
Structural lightning protection &
Design considerations
esign
Structural lightning protection design considerations
BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the
provision of a conventional Lightning Protection System (LPS) - to the total exclusion of any
other device or system for which claims of enhanced protection are made.
The principle components of a conventional structural lightning protection system, in
accordance with BS 6651 are:
Air Termination Network
13
Down Conductors
Page
Hossam Ahmed Zein
14. ELECTRICAL EARTHLING
Earth Termination Network
Bonding (to prevent side flashing)
Other areas that need to be looked at:
Corrosion
Inspection, testing, records and maintenance
Air termination network
On high risk structures such as explosive factories, no part of the roof should be more than
2.5m from an air termination conductor. This is generally achieved by applying a 5m x 10m
n
mesh to the roof.
However, for most structures, a mesh of 10m x 20m is considered sufficient, giving a
maximum distance from any part of the roof to the nearest conductor of 5m.
Air terminations for tall
conducting structures
The zone of protection does not seem to be applied because of the
need to interconnect the down conductors of the tall block to the
air termination of the lower block.
In such cases it is necessary to connect t
the lower air termination
up to the lower down conductors to facilitate this inter connection,
even though this extension is within the zone of protection of the
tower.
The 'Zone of Protection' offered by an air termination network is considered to be 45º for
heights up to 20m. Above this height, the zone of protection is determined by the 'Rolling
Sphere Method'.
This involves rolling an imaginary sphere of 60m radius over a structure. The areas touched
by the sphere are deemed to require protection. On tall structures, this can obviously include
the sides of the building.
Zones of protection
14
Page
Hossam Ahmed Zein
15. ELECTRICAL EARTHLING
Down conductors
Down conductor siting and distancing is often dictated by architectural circumstances. There
should be one down conductor for every 20m or part thereof of the building perimeter at roof
or ground level (whichever is greater). These should be evenly spaced and distances apart of
more than 20m avoided if possible.
If the building is above 20m in height or of an abnormal risk this distance should be reduced
to 10m.
They should be routed as directly as possible from the air termination network to the earth
termination network to avoid risks of side flashing. Re entrant loops are also to be avoided.
Re-entrant
BS 6651 recommends that the length of conductor forming the loop should not exceed eight
conductor
times the width of its open side.
BS 6651 allows the use of 'natural conductors' such as rebars and structural steelwork,
provided that they are electrically continuous and adequately earthed.
Lightning Protection Scheme to BS 6651 using the reinforced concrete within the
ction
structure for down conductors
Inner area requires no conductors as it is within the zone of protection
determined by the rolling sphere
Earth termination network
Each down conductor must have a separate earth termination. Moreover provision should be
made in each down conductor, for disconnection from the earth for testing purposes. This is
achieved with a test clamp (see below).
BS 6651 stipulates that
the resistance to earth of the
lightning protection system
measured at any point,
should not exceed 10 ohms.
With
the test clamp
15
disconnected, the
Page
resistance of each
individual earth should be no
Hossam Ahmed Zein
16. ELECTRICAL EARTHLING
more than ten times the number of down conductors in the complete system. eg fo a
for
system with 15 down conductors, the individual earth readings should be no more than 10 x
15 = 150 ohms.
Several types of earth electrode are permissible, but by far the most commonly used are
deep driven earth rods. BS 6651 states that the combined earth rod length of a system
earth
should be no less than 9m whilst each individual earth rod should be no less than 1.5m in
length.
Deep driven Oblong test or
earth electrode junction clamp
Parallel earth rod electrodes
Where ground conditions make deep driving of earth rods impossible, a matrix arrangement
of rods coupled to one another by conductors can be used. If possible, the earth rods must
be spaced at a distance at least equal to their driven depth.
If earth rods cannot be driven in a parallel line a "Crows Foot" configuration can be used,
parallel
ensuring that the spacing/depth ratio is still maintained.
High resistivity soil conditions can be overcome by backfilling earth rods with a suitable
medium such as Marconite conductive concrete which effectively increases the diameter of
effectively
the earth rod and hence its surface area, thus lowering resistance to earth.
Spacing of parallel earth rod electrode
16
Page
Hossam Ahmed Zein
17. ELECTRICAL EARTHLING
Bonding
All metal work, including water pipes, gas pipes, handrails, air conditioning units, metal
cladding, metal roofs etc, in the vicinity of the LPS must be bonded to it, to avoid the danger
of side flashing.
For the same reason, the LPS earth should be bonded to the main electrical earth, as well as
any other earthing system present i the structure.
in
Example of side flashing
If the lightning protection system on a structure is hit by lightning, then the
current flowing through the system and the resistance/impedance offered by the
conductor path will determine themagnitude of the potential difference seen by the
otential
lightning conductors with respect to true earth.
The lightning conductors can, instantaneously, have a potential magnitude of
megavolts (1,000,000V) with respect to true earth.
Typically, at instant of discharge:
Potential difference at A = 1,500,000V
Potential difference at B = 0V
Bonding to prevent side
flashing
1 Air termination
2 Down conductor
3 Bond to aerial
4 Bond to vent
5 Bond to re-
-bar
6 Bond to metal staircase
7 Bond to metal window frame
8 Bond to vent pipe
9 Bond to steel door/frame
10 Test clamp
11 Indicating plate
12 Main earthing terminal of
electrical installation
17
13 Earth termination point
Page
Hossam Ahmed Zein
18. ELECTRICAL EARTHLING
Corrosion
BS 6651 contains tables of materials suitable for use in lightning protection system
components. Adherence to these requirements is vital to avoid corrosion problems.
The correct choice of material and installation design should ensure a life span of 30 years
for the earth electrode system.
Measurement
There are three methods of Earth ground testing methods :
1) Soil Resistivity (using stakes)
18
Why: Soil Resistivity is most necessary when deter-mining the design of the grounding system for new
Page
installations (green field applications) to meet your ground resistance requirements.
Hossam Ahmed Zein
19. ELECTRICAL EARTHLING
Lowest Resistance is petter ,if it was high enough could be overcomed with more elaborate ground
systems
Requirements: replacing the electrode as deeper as possible
• where, soil and water exist ( أو ) water
table.
• where there is a stable temperature, i.e. below
the frost line.
Depend on:
Soil Content of Moisture : The Soil Resistivity decreases significantly due increasing of its content of
moisture
19
Page
Hossam Ahmed Zein
20. ELECTRICAL EARTHLING
Temperature: If temp. of Soil was too high the Soil Resistivity increase & if temp. was too low (subzero)
then the moisture will freeze and the Resistivity will increase .
Electric Current : If the current was too high then it will produce a heat all over the carrying conductors
,this heat will dry the moisture and increase the resistivity .
Depth of Soil : that the content of moisture increases as we get deeper within the ground unless re a rock
base.
2) Fall-of-Potential (using stakes) : The Fall-of-Potential test method is used to measure the ability of an
earth ground system or an individual electrode to dissipate energy from a site.
Procedure: >
Disconnect the earth electrode iii. Using Ohm’s Law (V = IR), a known current
i. Two stakes (inner & outer) are placed in is generated by the test device between
the soil in a direct line, away from the the outer stake (auxiliary earth stake) and
earth electrode with indicated table the earth electrode, while the drop in
ii. Connect earth tester to the electrode voltage potential is measured between the
inner earth stake and the earth electrode.
3) Selective (using 1 clamp and Auxiliary stakes)
The earth electrode of interest does not need to be
disconnected from its connection to the site.
Much safer and easier way
Procedure: >
i. a special clamp is placed around the earth electrode, which
eliminates the effects of parallel resistances in a grounded
system
ii. is very similar to the Fall-of-Potential testing, providing all
the same measurements.
4) Stake-less [UNILAP GEO X](using 2 clamps only)
Comparative advantage:
o measure earth ground loop resistances for parallel / multi-
grounded systems using only current clamps.
o Used inside buildings, on power pylons or anywhere you
20
don’t have access to soil.
Page
Produce operating safety and Less Dangerous.
Hossam Ahmed Zein
21. ELECTRICAL EARTHLING
If there is only one path to ground, the Stakeless method will not provide an acceptable value and
the Fall-of-Potential test method must be used.
Procedure :>
i. Two clamps are placed around the earth ground rod or the connecting cable and each are
connected to the tester.
ii. A known voltage is induced by one clamp, and the current is measured using the second clamp.
iii. The tester automatically determines the ground loop resistance at this ground rod.
Some Practical Examples:
21
Page
Hossam Ahmed Zein
22. ELECTRICAL EARTHLING
Cellular sites/microwave and radio towers
At most locations there is a -legged tower with
each leg individually grounded. These grounds
are then connected with a copper cable. Next
to the tower is the Cell site building, housing
all the transmission equipment. Inside the
building there is a halo ground and a MGB,
with the halo ground connected to the MGB.
The cell site building is grounded at all corners
connected to the MGB via a copper cable and
the corners are also interconnected via copper
wire. There is also a connection between the
building ground ring and the tower ground
ring.
Electrical Substations
A substation is a subsidiary station on a transmission and distribution system where voltage is normally
transformed from a high value to low value. A typical substation will contain line termination structures,
high-voltage switchgear, one or more power transformers, low-voltage switchgear, surge protection,
controls, and metering.
22
Page
Hossam Ahmed Zein
23. ELECTRICAL EARTHLING
Measuring of High Voltage Trans. Towers 1
Lightning protection at commercial/industrial sites
Most lightning fault current protection systems follow the design of having all four corners of the building
grounded and these are usually connected via a copper cable. Depending on the size of the building and
the resistance value that it was designed to achieve, the number of ground rods will vary.
Stakeless measurement • The ground stakes of the Selective measurement
building (lightning protection)
First, perform a Stakeless The resistances should be
measurement on: 3-pole Fall-of-Potential measured on:
measurement
• The individual legs of the • Each leg of the tower and
all four corners of the
tower and the four corners of This measurement should be
building (cell sites/towers)
the building (cell recorded and measurements
sites/towers) should take place at least • Individual ground rods and
twice per year. their connections (electrical
• All grounding connections substations)
(electrical substations) This measurement is the
• Both ends of the remote
resistance value for the entire
• The lines running to the site (remote switching)
site.
remote site (remote • All four corners of the
switching) building (lightning protection)
23
Page
Hossam Ahmed Zein
24. ELECTRICAL EARTHLING
Remote switching sites (known as slick sites)
Where digital line concentrators and other telecommunications equipment is operating.
The remote site is typically grounded at either end of the cabinet and then will have a series of ground
stakes around the cabinet connected by copper wire.
Stackless method Fall of potential 1
2
24
Page
Hossam Ahmed Zein