 ROTOR ELECTRICAL FAULTS
 LOSS OF EXCITATION
 LOSS OF SYNCHRONISM
 FAILURE OF PRIME MOVER
 LUBRICATION OIL FAILURE
 OVER SPEEDING
 CORE LAMINATION FAILURE
 STATOR ELECTRICAL FAULTS
 OVER LOADS
 OVER VOLTAGE
 UN BALANCED LOADING
 OVER FLUXING
6
BASIC SYNCHRONOUS GENERATOR
GENERATOR PROTECTION
7
1.ARMATURE WINDING- STATOR
2.FIELD WINDING-ROTOR.
RELATIVE MOTION BETWEEN THESE TWO
WHICH IS ACHIEVED BY THE
3.Prime Mover-TURBINE.
 Capacity – 247MVA
 Stator Voltage – 15KV/15.75KV)
 Stator current – 9060 Amps
 Rotor Voltage – 310V
 Rotor Current – 2600Amps.
 Frequency – 50 Hz. Speed –3000RPM
 Capacity – 222MVA
 Stator Voltage – 13.8
 Stator current – 9297 Amps
 Rotor Voltage – 336V
 Rotor Current – 2180Amps.
 Frequency – 50 Hz. Speed –136RPM
N = 120F/P
N – Rotational Speed RPM
F - Frequency Hz
P – Number of Poles
11
SYNCHRONOUS GENERATOR TYPES
GENERATOR PROTECTION
12
TYPICAL UNIT GENERATOR – TRANSFORMER
CONFIGURATION
13
Device Function
21
Distance Relay. Backup for system
and generator zone phase faults.
24
Volts/Hz protection for generator
over excitation.
32
Reverse power relay. Anti-
motoring protection.
40 Loss-of-field protection.
46
Negative sequence unbalance
current protection for the
generator.
ANSI DEVICE NUMBERS
14
Device Function
49 Stator Thermal Protection.
51GN Time over current ground relay.
51TN Backup for ground faults.
51V
Voltage-controlled or voltage-
restrained time over current
relay. Backup for system and
generator phase faults.
59 Overvoltage protection.
59GN
Overvoltage relay. Stator ground
fault protection for a generator.
ANSI DEVICE NUMBERS
15
Device Function
78 Loss-of-synchronism protection.
81
Frequency relay. Both
underfrequency protection.
86 Hand-reset lockout auxiliary relay.
87G
Differential relay. Primary phase-
fault protection for the generator.
87N Stator ground fault differential .
87T
Differential relay. Primary
protection for the transformer.
87U
Differential relay for overall
generator and transformer
protection.
ANSI DEVICE NUMBERS
16
LOW IMPEDANCE GROUNDING
GENERATOR PROTECTION
17
HIGH IMPEDANCE GROUNDING
GENERATOR PROTECTION
19
NEGATIVE SUENCE RELAYS – BASIC DESIGN
20
GENERATOR CAPABILITY CURVE
LOSS OF FIELD PROTECTION
Generator protection

Generator protection

  • 4.
     ROTOR ELECTRICALFAULTS  LOSS OF EXCITATION  LOSS OF SYNCHRONISM  FAILURE OF PRIME MOVER  LUBRICATION OIL FAILURE  OVER SPEEDING  CORE LAMINATION FAILURE
  • 5.
     STATOR ELECTRICALFAULTS  OVER LOADS  OVER VOLTAGE  UN BALANCED LOADING  OVER FLUXING
  • 6.
  • 7.
    7 1.ARMATURE WINDING- STATOR 2.FIELDWINDING-ROTOR. RELATIVE MOTION BETWEEN THESE TWO WHICH IS ACHIEVED BY THE 3.Prime Mover-TURBINE.
  • 8.
     Capacity –247MVA  Stator Voltage – 15KV/15.75KV)  Stator current – 9060 Amps  Rotor Voltage – 310V  Rotor Current – 2600Amps.  Frequency – 50 Hz. Speed –3000RPM
  • 9.
     Capacity –222MVA  Stator Voltage – 13.8  Stator current – 9297 Amps  Rotor Voltage – 336V  Rotor Current – 2180Amps.  Frequency – 50 Hz. Speed –136RPM
  • 10.
    N = 120F/P N– Rotational Speed RPM F - Frequency Hz P – Number of Poles
  • 11.
  • 12.
    12 TYPICAL UNIT GENERATOR– TRANSFORMER CONFIGURATION
  • 13.
    13 Device Function 21 Distance Relay.Backup for system and generator zone phase faults. 24 Volts/Hz protection for generator over excitation. 32 Reverse power relay. Anti- motoring protection. 40 Loss-of-field protection. 46 Negative sequence unbalance current protection for the generator. ANSI DEVICE NUMBERS
  • 14.
    14 Device Function 49 StatorThermal Protection. 51GN Time over current ground relay. 51TN Backup for ground faults. 51V Voltage-controlled or voltage- restrained time over current relay. Backup for system and generator phase faults. 59 Overvoltage protection. 59GN Overvoltage relay. Stator ground fault protection for a generator. ANSI DEVICE NUMBERS
  • 15.
    15 Device Function 78 Loss-of-synchronismprotection. 81 Frequency relay. Both underfrequency protection. 86 Hand-reset lockout auxiliary relay. 87G Differential relay. Primary phase- fault protection for the generator. 87N Stator ground fault differential . 87T Differential relay. Primary protection for the transformer. 87U Differential relay for overall generator and transformer protection. ANSI DEVICE NUMBERS
  • 16.
  • 17.
  • 19.
    19 NEGATIVE SUENCE RELAYS– BASIC DESIGN
  • 20.

Editor's Notes

  • #7 GENERATOR PROTECTION
  • #12 GENERATOR PROTECTION
  • #13 GENERATOR PROTECTION
  • #14 GENERATOR PROTECTION
  • #15 GENERATOR PROTECTION
  • #16 GENERATOR PROTECTION
  • #17 GENERATOR PROTECTION
  • #18 GENERATOR PROTECTION
  • #20 GENERATOR PROTECTION
  • #21 GENERATOR PROTECTION