This document discusses generator protection methods. It describes how large generators are connected directly to bus bars or via transformers. It also explains different fault conditions generators may experience like overloading, unbalanced loading, and stator winding faults. Various protection systems are discussed like using thermo-couples for temperature monitoring, negative sequence relays for unbalanced loads, and tripping exciters and dissipating stored energy for stator faults.
Transformer Protection May be include protection fro inrush current, overheating, overcurrent and earthing. We can use Buchhloz Relay and Differential Relays for protection.
Transformer Protection May be include protection fro inrush current, overheating, overcurrent and earthing. We can use Buchhloz Relay and Differential Relays for protection.
To sense/detect the fault occurrence and other abnormal conditions at the protected equipment/area/section.
To operate the correct circuit breakers so as to disconnect only the faulty equipment/area/section as quickly as possible, thus minimizing the damage caused by the faults.
To operate the correct circuit breakers to isolate the faulty equipment/area/section from the healthy system in the case of abnormalities like overloads, unbalance, undervoltage, etc.
To clear the fault before the system becomes unstable.
To identify distinctly where the fault has occurred.
The following topics are covered: components of power distribution systems, fuses, padmounted transformers, pole mounted transformers, vault installed transformers, transformer stations protection, transformer connections, thermometers, pressure relief devices, restricted ground faults, differential protection current transformers connections, overexcitation, inrush current, percentage differential relays, gas relays, characteristics of CTs.
How is power transformer protected??? This provides a basic understanding of power transformer. Furthermore, the protective relay application on power transformer is included.
Circuit Breaking:
Properties of arc
Arc extinction theories
Re-striking voltage transient
Current chopping
Resistance switching
Capacitive current interruption
Short line interruption
Circuit breaker ratings.
Testing Of Circuit Breaker: Classification
Testing station and equipment's
Testing procedure
Direct and indirect testing
SWICTH GEAR AND PROTECTION (2170906)
DISTANCE RELAY
• There are mainly Three types of distance relay
1) Impedance Relay
2) Reactance Relay
3) Mho Relay
In a generating station the generator and transformer are the most expensive equipments and hence it is desirable to employ protective system to isolate the faulty equipment as quickly as possible to keep the healthy section in normal operation and to ensure uninterruptable power supply.
Rotor earth fault protection of electric generatormytechinfo
As the field is operated ungrounded, a single fault does not cause any flow of current or affect the operation of the electric generator. However, a single rotor earth fault increases the stress to the ground in the field
To sense/detect the fault occurrence and other abnormal conditions at the protected equipment/area/section.
To operate the correct circuit breakers so as to disconnect only the faulty equipment/area/section as quickly as possible, thus minimizing the damage caused by the faults.
To operate the correct circuit breakers to isolate the faulty equipment/area/section from the healthy system in the case of abnormalities like overloads, unbalance, undervoltage, etc.
To clear the fault before the system becomes unstable.
To identify distinctly where the fault has occurred.
The following topics are covered: components of power distribution systems, fuses, padmounted transformers, pole mounted transformers, vault installed transformers, transformer stations protection, transformer connections, thermometers, pressure relief devices, restricted ground faults, differential protection current transformers connections, overexcitation, inrush current, percentage differential relays, gas relays, characteristics of CTs.
How is power transformer protected??? This provides a basic understanding of power transformer. Furthermore, the protective relay application on power transformer is included.
Circuit Breaking:
Properties of arc
Arc extinction theories
Re-striking voltage transient
Current chopping
Resistance switching
Capacitive current interruption
Short line interruption
Circuit breaker ratings.
Testing Of Circuit Breaker: Classification
Testing station and equipment's
Testing procedure
Direct and indirect testing
SWICTH GEAR AND PROTECTION (2170906)
DISTANCE RELAY
• There are mainly Three types of distance relay
1) Impedance Relay
2) Reactance Relay
3) Mho Relay
In a generating station the generator and transformer are the most expensive equipments and hence it is desirable to employ protective system to isolate the faulty equipment as quickly as possible to keep the healthy section in normal operation and to ensure uninterruptable power supply.
Rotor earth fault protection of electric generatormytechinfo
As the field is operated ungrounded, a single fault does not cause any flow of current or affect the operation of the electric generator. However, a single rotor earth fault increases the stress to the ground in the field
Rotor earth fault protection of electric generatorCS V
As the field is operated ungrounded, a single fault does not cause any flow of current or affect the operation of the electric generator. However, a single rotor earth fault increases the stress to the ground in the field
POWER SYSTEM PROTECTION
Protection Devices and the Lightning,. protection,
Lightning protection, Introduction
Air Break Switches
Disconnect switches
Grounding switches
Current limiting reactors
Grounding transformers
Co-ordination of protective devices
Grounding of electrical installations
Electric shock
Lightning protection
Lightning Arrestor
Explore the innovative world of trenchless pipe repair with our comprehensive guide, "The Benefits and Techniques of Trenchless Pipe Repair." This document delves into the modern methods of repairing underground pipes without the need for extensive excavation, highlighting the numerous advantages and the latest techniques used in the industry.
Learn about the cost savings, reduced environmental impact, and minimal disruption associated with trenchless technology. Discover detailed explanations of popular techniques such as pipe bursting, cured-in-place pipe (CIPP) lining, and directional drilling. Understand how these methods can be applied to various types of infrastructure, from residential plumbing to large-scale municipal systems.
Ideal for homeowners, contractors, engineers, and anyone interested in modern plumbing solutions, this guide provides valuable insights into why trenchless pipe repair is becoming the preferred choice for pipe rehabilitation. Stay informed about the latest advancements and best practices in the field.
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...Amil Baba Dawood bangali
Contact with Dawood Bhai Just call on +92322-6382012 and we'll help you. We'll solve all your problems within 12 to 24 hours and with 101% guarantee and with astrology systematic. If you want to take any personal or professional advice then also you can call us on +92322-6382012 , ONLINE LOVE PROBLEM & Other all types of Daily Life Problem's.Then CALL or WHATSAPP us on +92322-6382012 and Get all these problems solutions here by Amil Baba DAWOOD BANGALI
#vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore#blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #blackmagicforlove #blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #Amilbabainuk #amilbabainspain #amilbabaindubai #Amilbabainnorway #amilbabainkrachi #amilbabainlahore #amilbabaingujranwalan #amilbabainislamabad
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Generation protection - complete
1.
2. Protection of turbo-generators is the most
complex and elaborate.
A Generator is a large machine and is
connected to bus-bars. It is accompanied by
unit transformers, auxiliary transformer and
bus system.
There are two methods by which generators are
connected to Bus:
Generators connected directly to bus
Generators connected via delta-star unit transformer
to HV bus i.e., to transmission line.
A turbo generator is the combination of a turbine directly connected to
an electric generator for the generation of electric power
4. Continued over loading may increase the
winding temperature to such an extent that
the insulation will be damaged and its useful
life reduced.
Temperature rise can also be caused by
failure of cooling system. In large machines
thermal elements (thermo-couples or
resistance thermometers) are embedded in
the stator slots and cooling system.
Electrical overcurrent protection can not
sense the failure of cooling system
5. Un-balanced loading on generator can be due to:
1. Unsymmetrical faults in the system near the
generating station.
2. Mal-operation of a circuit-breaker near generating
station, the three phases not being cleared.
Negative sequence protection senses unbalanced
loading of generators.
Continued unbalanced loads, equal to or more than 10%
of the rated current cause dangerous heating of the
cylindrical rotor in turbo-generators. Salient pole
rotors in hydro-generators often include damper
windings and are, therefore, much less affected by
unbalance loading (negative phase sequence
currents).
6. Stator winding faults involve armature
winding and must therefore be cleared
quickly by complete shutdown of the
generator. Only opening the stator circuit
does not help since the e. m.f. is induced in
the stator winding itself. The field is,
therefore, opened and de-energized by "Field
Suppression".
7. The stator faults include:
1. Phase-to-earth faults
2. Phase-to-phase faults.
3. Stator inter-turn faults.
Phase to phase faults and phase inter-turn
faults are less common.
Inter turn faults are more difficult to detect.
8. These faults normally occur in the armature
slots. The damage at the point of fault is
directly related to the selected neutral
earthing resistor. With fault currents less
than 20 A, negligible burning of the iron core
will result if the machine is tripped within
few seconds. The repair work then amounts
to changing the damaged coil without re-
stacking the core laminations.
9. If, however, the earthing resistor is selected to
pass a much larger earth-fault current (> 200 A)
severe burning of the stator core, will take
place, necessitating re-stacking of laminations.
Even when a high speed earth-fault differential
protection is used, severe damage may be
caused owing to the large time constant of the
field-circuit and the relatively long time
required to completely suppress the field flux. In
the case of high earth-fault currents it is
therefore normal practice to install a circuit
breaker in the neutral of the generator in order
to break the path of earth fault current.
10. As the source of fault current is itself the
stator winding in which voltage is induced
due to field flux, the exciter must be
disconnected and stored field energy of both
alternator and exciter be dissipated in the
resistance . For this purpose,
one trip coil opens the connection of generator
field winding from exciter and simultaneously
shunts it to a resistance,
second trip coil opens the neutral circuit
breaker to break the earth fault current path
And third trip coil opens the exciter armature
circuit and shunts the exciter field winding
across a resistance for flux collapse
14. Resistor earthing is used when generator is
directly connected to station bus. In this
case the IDMT relay used in neutral is
coordinated with other over current relays in
the system
When generator is connected via delta-Y
transformer, no coordination is required with
other relays since earth loop is restricted to
generator and transformer primary(delta)
For combined generator-transformer
protection system, neutral is grounded
through a voltage transformer.
15. With Resistance earthing it is impossible to
provide protection to the whole winding, the
percentage of stator winding protected being
dependent on the value of earthing
resistance.
Another problem with resistance earthing-
resonance may occur between generator
stator winding distribution capacitance and
Earth resistance. The limiting value is given
by
fC
Rn
6
106