SlideShare a Scribd company logo
Equipment Protection
Protection of Transformer, Generator
and Motor
Types of Faults
• Faults in auxiliary equipment which is a part of transformer
such as bushings, tap changer etc
– Transformer oil; low level exposes live parts such as the leads to
bushing. Oil level indicator with alarm give indication to this condition
– Oil temperature; rise in oil temperature may be an indication of
overload or failure of cooling system. A thermometer with alarms will
indicate rise of oil temperature.
• Faults in transformer winding and connections
– Winding Insulation failure; high impulse voltage , mechanical forces,
overload
– Core insulation failure;
• Overloads and external short circuits
Buchholz
relay
Transformer : Earth fault
protection
Magnitude of fault current
depends on
•Source impedance
•Neutral earthing impedance
•Transformer leakage reactance
•Fault voltage
•Winding connection
Fault current-DY
transformer- neutral
solidly grounded
Fault on secondary Y side.
Current magnitude depends on
leakage reactance of transformer
winding which is minimum near
neutral end and maximum at the
middle of winding
Primary fault current varies because of
change in transformation ratio
GENERATOR PROTECTION
• Protection of turbo-generators is the most
complex and elaborate.
– A Generator is a large machine and is connected
to bus-bars. It is accompanied by unit
transformers, auxiliary transformer and bus
system.
Generator connection
Typical small generators connection to
system
Large Generator connection to system
There are two methods by which generators are connected to Bus:
Generators connected directly to bus Generators connected via
delta-star unit transformer to HV bus i.e., to transmission Line
Possible Generator Faults
Usual practices of Generator
Protection
overloading
• Continued over loading may increase the winding
temperature to such an extent that the insulation
will be damaged and its useful life reduced.
• Temperature rise can also be caused by failure of
cooling system. In large machines thermal
elements (thermo-couples or resistance
thermometers) are embedded in the stator slots
and cooling system.
• Electrical overcurrent protection can not sense
the failure of cooling system
Unbalanced loading
Un-balanced loading on generator can be due to:
 1. Unsymmetrical faults in the system near the generating
station.
 2. Mal-operation of a circuit-breaker near generating station, the
three phases not being cleared.
Negative sequence protection senses unbalanced loading of
generators.
Continued unbalanced loads, equal to or more than 10% of the rated
current cause dangerous heating of the cylindrical rotor in turbo-
generators. Salient pole rotors in hydro-generators often include
damper windings and are, therefore, much less affected by
unbalance loading (negative phase sequence currents).
Stator faults
The stator faults include:
1. Phase-to-earth faults
2. Phase-to-phase faults.
3. Stator inter-turn faults.
Phase to phase faults and phase inter-turn faults
are less common.
Inter turn faults are more difficult to detect.
stator winding faults
• Stator winding faults involve armature winding and must therefore be
cleared quickly by complete shutdown of the generator. Only opening the
stator circuit does not help since the e.m.f. is induced in the stator winding
itself. The field is, therefore, opened and de-energized by "Field
Suppression".
• With resistance earthing, protection to full (100%) winding is not
possible.
• Leakage reactance depends on square of the number of turns of stator
winding.
• Fault at some x% of the winding, will therefore reduce leakage reactance
by square of x% turns, making leakage reactance negligible . Current in
fault loop then solely depends on earthing resistor
Phase to earth fault
• These faults normally occur in the armature
slots. The damage at the point of fault is
directly related to the selected neutral
earthing resistor. With fault currents less than
20 A, negligible burning of the iron core
will result if the machine is tripped within few
seconds. The repair work then amounts to
changing the damaged coil without re-
stacking the core laminations.
Methods of connecting alternator
neutral to ground
• Resistor earthing is used when generator is
directly connected to station bus. In this
case the IDMT relay used in neutral is
coordinated with other over current relays
in the system
• When generator is connected via delta-Y
transformer, no coordination is required
with other relays since earth loop is
restricted to generator and transformer
primary(delta)
• For combined generator-transformer
protection system, neutral is grounded
through a voltage transformer.
• With Resistance earthing it is impossible to
provide protection to the whole winding, the
percentage of stator winding protected being
dependent on the value of earthing
resistance.
• Another problem with resistance earthing-
resonance may occur between generator
stator winding distribution capacitance and
Earth resistance. The limiting value is given by
fC
Rn


6
106
If, however, the earthing resistor is selected to pass a
much larger earth-fault current (> 200 A) severe
burning of the stator core, will take place, necessitating
re-stacking of laminations. Even when a high speed
earth-fault differential protection is used, severe
damage may be caused owing to the large time
constant of the field-circuit and the relatively long time
required to completely suppress the field flux. In the
case of high earth-fault currents it is therefore normal
practice to install a circuit breaker in the neutral of the
generator in order to break the path of earth fault
current.
Field suppression
• As the source of fault current is itself the stator
winding in which voltage is induced due to field
flux, the exciter must be disconnected and stored
field energy of both alternator and exciter be
dissipated in the resistance . For this purpose,
– one trip coil opens the connection of generator field
winding from exciter and simultaneously shunts it to a
resistance,
– second trip coil opens the neutral circuit breaker to
break the earth fault current path
– And third trip coil opens the exciter armature circuit
and shunts the exciter field winding across a resistance
for flux collapse
Differential
Protection
Star winding
Delta winding
Rotor
fault
MOTOR PROTECTION
Possible Faults and abnormal
conditions-Induction motor
• Supply side problems
– Faults at motor’s Terminal
– Unbalanced supply
– Single phasing
– Reduced voltage
– Phase reversal
• Motor’s inside faults
– Phase fault
– Ground fault
– Inter turn fault
• Load side Faults
– Bearing Failure
– Prolonged over loads
– Jam Rotor
Coordination of Over current relay
with motor starting current
• Induction motor
– Istart.= 6 to 8 IFL
• To coordinate, OC relay characteristics must lie above
starting characteristics and below thermal capability
curve of the motor
Phase Faults
At motor terminals, fault current is
much greater than Full load current.
Hence, an instantaneous OC relay with
high pick up can be used
Faults inside motor:
Small size motor- protected by HRC
fuse
Big size motor- OC relay is used. Relay
characteristics must lie below motor’s
thermal characteristics
High impedance ground fault:
Fault current less than IFL
Use of current balance type
protection( core balance CT) is used
Unbalance supply
Negative sequence current flow at
almost double frequency
Rotor offers very high resistance due
to skin effect and becomes excessively
heat up and so is the stator
Motors have certain I2t thermal
capability ;usually around a value of 40
Overload Protection
Overload device thermal
characteristics must lie below motor
thermal curve (I2t)
Thermal overload relays provide good
protection against short, medium and
long duration overloads but
insufficient for heavy overloads
Induction type overcurrent relay
provides good protection against
heavy overloads.

More Related Content

What's hot

Generator protection system by nicholas naing
Generator protection system by nicholas naingGenerator protection system by nicholas naing
Generator protection system by nicholas naing
Nicholas Naing
 
3 phase transformer protection
3 phase transformer protection3 phase transformer protection
3 phase transformer protection
Himanshu Paghdal
 
transformer protection
transformer protection transformer protection
transformer protection
jason adidela
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
Rahaf Waheep
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
Dr. Selvarasu Ranganathan
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
Rahul Ruddra
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
Agrey Kato
 
Distribution Transformer Protection for Differential and Overcurrent Faults
Distribution Transformer Protection for Differential and Overcurrent FaultsDistribution Transformer Protection for Differential and Overcurrent Faults
Distribution Transformer Protection for Differential and Overcurrent Faults
ToshaliMohapatra
 
Induction Motor Protection System
Induction Motor Protection SystemInduction Motor Protection System
Induction Motor Protection System
Edgefxkits & Solutions
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generator
Mohammad Abdullah
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
Md. Shoheluzzaman
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
Rishi Tandon
 
Generator Protection
Generator ProtectionGenerator Protection
Generator ProtectionPriten Vasa
 
Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault Protections
Arjay Automation
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Generator protection
Generator protectionGenerator protection
Generator protectionKeshar Rawal
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
jawaharramaya
 

What's hot (20)

Generator protection system by nicholas naing
Generator protection system by nicholas naingGenerator protection system by nicholas naing
Generator protection system by nicholas naing
 
3 phase transformer protection
3 phase transformer protection3 phase transformer protection
3 phase transformer protection
 
transformer protection
transformer protection transformer protection
transformer protection
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Distribution Transformer Protection for Differential and Overcurrent Faults
Distribution Transformer Protection for Differential and Overcurrent FaultsDistribution Transformer Protection for Differential and Overcurrent Faults
Distribution Transformer Protection for Differential and Overcurrent Faults
 
Induction Motor Protection System
Induction Motor Protection SystemInduction Motor Protection System
Induction Motor Protection System
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generator
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Thermoelectricity
ThermoelectricityThermoelectricity
Thermoelectricity
 
Trf ptc
Trf ptcTrf ptc
Trf ptc
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
97
9797
97
 
Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault Protections
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 

Similar to Equipment protection

Generation protection - complete
Generation protection - completeGeneration protection - complete
Generation protection - complete
Slides Hub
 
4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx
Noname812799
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt
sanipriadi1
 
Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)
Abhishek Choksi
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
javid iqbal sodagar
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
javid iqbal sodagar
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
Dr. Rohit Babu
 
TOPIC 6- Transformer Protection.pptx
TOPIC 6- Transformer Protection.pptxTOPIC 6- Transformer Protection.pptx
TOPIC 6- Transformer Protection.pptx
MartMantilla1
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
SHIVANICHAUUHAN1
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
Bhushan Kumbhalkar
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
Rahuldey1991
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
johny renoald
 
protection of transformer
protection of transformerprotection of transformer
protection of transformer
gujjarsb
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipment
sateesh kumar
 
Generator protection
Generator protectionGenerator protection
Generator protection
SSVASAVA
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
Thien Phan Bản
 
Internship presentation
Internship presentationInternship presentation
Internship presentation
Muhammad Zaighum Farooq
 
Motor.ppt
Motor.pptMotor.ppt
Motor.ppt
Kapil Singh
 

Similar to Equipment protection (20)

Generation protection - complete
Generation protection - completeGeneration protection - complete
Generation protection - complete
 
4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt
 
Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
TOPIC 6- Transformer Protection.pptx
TOPIC 6- Transformer Protection.pptxTOPIC 6- Transformer Protection.pptx
TOPIC 6- Transformer Protection.pptx
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
protection of transformer
protection of transformerprotection of transformer
protection of transformer
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipment
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
Internship presentation
Internship presentationInternship presentation
Internship presentation
 
Motor.ppt
Motor.pptMotor.ppt
Motor.ppt
 

More from Slides Hub

Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
Slides Hub
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
Slides Hub
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
Slides Hub
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
Slides Hub
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
Slides Hub
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
Slides Hub
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its types
Slides Hub
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
Slides Hub
 

More from Slides Hub (8)

Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its types
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 

Recently uploaded

CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
Kamal Acharya
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
ongomchris
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
zwunae
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
ViniHema
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
Osamah Alsalih
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
Robbie Edward Sayers
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Recently uploaded (20)

CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 

Equipment protection

  • 1. Equipment Protection Protection of Transformer, Generator and Motor
  • 2. Types of Faults • Faults in auxiliary equipment which is a part of transformer such as bushings, tap changer etc – Transformer oil; low level exposes live parts such as the leads to bushing. Oil level indicator with alarm give indication to this condition – Oil temperature; rise in oil temperature may be an indication of overload or failure of cooling system. A thermometer with alarms will indicate rise of oil temperature. • Faults in transformer winding and connections – Winding Insulation failure; high impulse voltage , mechanical forces, overload – Core insulation failure; • Overloads and external short circuits
  • 4. Transformer : Earth fault protection Magnitude of fault current depends on •Source impedance •Neutral earthing impedance •Transformer leakage reactance •Fault voltage •Winding connection
  • 5. Fault current-DY transformer- neutral solidly grounded Fault on secondary Y side. Current magnitude depends on leakage reactance of transformer winding which is minimum near neutral end and maximum at the middle of winding Primary fault current varies because of change in transformation ratio
  • 7. • Protection of turbo-generators is the most complex and elaborate. – A Generator is a large machine and is connected to bus-bars. It is accompanied by unit transformers, auxiliary transformer and bus system.
  • 8. Generator connection Typical small generators connection to system Large Generator connection to system There are two methods by which generators are connected to Bus: Generators connected directly to bus Generators connected via delta-star unit transformer to HV bus i.e., to transmission Line
  • 9.
  • 11. Usual practices of Generator Protection
  • 12. overloading • Continued over loading may increase the winding temperature to such an extent that the insulation will be damaged and its useful life reduced. • Temperature rise can also be caused by failure of cooling system. In large machines thermal elements (thermo-couples or resistance thermometers) are embedded in the stator slots and cooling system. • Electrical overcurrent protection can not sense the failure of cooling system
  • 13. Unbalanced loading Un-balanced loading on generator can be due to:  1. Unsymmetrical faults in the system near the generating station.  2. Mal-operation of a circuit-breaker near generating station, the three phases not being cleared. Negative sequence protection senses unbalanced loading of generators. Continued unbalanced loads, equal to or more than 10% of the rated current cause dangerous heating of the cylindrical rotor in turbo- generators. Salient pole rotors in hydro-generators often include damper windings and are, therefore, much less affected by unbalance loading (negative phase sequence currents).
  • 14. Stator faults The stator faults include: 1. Phase-to-earth faults 2. Phase-to-phase faults. 3. Stator inter-turn faults. Phase to phase faults and phase inter-turn faults are less common. Inter turn faults are more difficult to detect.
  • 15. stator winding faults • Stator winding faults involve armature winding and must therefore be cleared quickly by complete shutdown of the generator. Only opening the stator circuit does not help since the e.m.f. is induced in the stator winding itself. The field is, therefore, opened and de-energized by "Field Suppression". • With resistance earthing, protection to full (100%) winding is not possible. • Leakage reactance depends on square of the number of turns of stator winding. • Fault at some x% of the winding, will therefore reduce leakage reactance by square of x% turns, making leakage reactance negligible . Current in fault loop then solely depends on earthing resistor
  • 16. Phase to earth fault • These faults normally occur in the armature slots. The damage at the point of fault is directly related to the selected neutral earthing resistor. With fault currents less than 20 A, negligible burning of the iron core will result if the machine is tripped within few seconds. The repair work then amounts to changing the damaged coil without re- stacking the core laminations.
  • 17. Methods of connecting alternator neutral to ground
  • 18. • Resistor earthing is used when generator is directly connected to station bus. In this case the IDMT relay used in neutral is coordinated with other over current relays in the system • When generator is connected via delta-Y transformer, no coordination is required with other relays since earth loop is restricted to generator and transformer primary(delta) • For combined generator-transformer protection system, neutral is grounded through a voltage transformer.
  • 19. • With Resistance earthing it is impossible to provide protection to the whole winding, the percentage of stator winding protected being dependent on the value of earthing resistance. • Another problem with resistance earthing- resonance may occur between generator stator winding distribution capacitance and Earth resistance. The limiting value is given by fC Rn   6 106
  • 20. If, however, the earthing resistor is selected to pass a much larger earth-fault current (> 200 A) severe burning of the stator core, will take place, necessitating re-stacking of laminations. Even when a high speed earth-fault differential protection is used, severe damage may be caused owing to the large time constant of the field-circuit and the relatively long time required to completely suppress the field flux. In the case of high earth-fault currents it is therefore normal practice to install a circuit breaker in the neutral of the generator in order to break the path of earth fault current.
  • 21. Field suppression • As the source of fault current is itself the stator winding in which voltage is induced due to field flux, the exciter must be disconnected and stored field energy of both alternator and exciter be dissipated in the resistance . For this purpose, – one trip coil opens the connection of generator field winding from exciter and simultaneously shunts it to a resistance, – second trip coil opens the neutral circuit breaker to break the earth fault current path – And third trip coil opens the exciter armature circuit and shunts the exciter field winding across a resistance for flux collapse
  • 25. Possible Faults and abnormal conditions-Induction motor • Supply side problems – Faults at motor’s Terminal – Unbalanced supply – Single phasing – Reduced voltage – Phase reversal • Motor’s inside faults – Phase fault – Ground fault – Inter turn fault • Load side Faults – Bearing Failure – Prolonged over loads – Jam Rotor
  • 26. Coordination of Over current relay with motor starting current • Induction motor – Istart.= 6 to 8 IFL • To coordinate, OC relay characteristics must lie above starting characteristics and below thermal capability curve of the motor
  • 27. Phase Faults At motor terminals, fault current is much greater than Full load current. Hence, an instantaneous OC relay with high pick up can be used Faults inside motor: Small size motor- protected by HRC fuse Big size motor- OC relay is used. Relay characteristics must lie below motor’s thermal characteristics High impedance ground fault: Fault current less than IFL Use of current balance type protection( core balance CT) is used
  • 28. Unbalance supply Negative sequence current flow at almost double frequency Rotor offers very high resistance due to skin effect and becomes excessively heat up and so is the stator Motors have certain I2t thermal capability ;usually around a value of 40
  • 29. Overload Protection Overload device thermal characteristics must lie below motor thermal curve (I2t) Thermal overload relays provide good protection against short, medium and long duration overloads but insufficient for heavy overloads Induction type overcurrent relay provides good protection against heavy overloads.