This document provides an overview and discussion of automatic transfer switches, grounding issues, and installation considerations for standby power systems. It discusses NFPA 110 requirements, grounding terminology and rules, applications of 4-pole switches, fuel system considerations and sizing, generator control functions, transfer switch types, and indoor versus outdoor generator installation options. The key topics covered are the two main grounding rules, uses of 4-pole automatic transfer switches, fuel system design best practices, and NFPA 110 compliance guidelines for emergency power systems.
The document discusses busbar protection, including the need for busbar protection, types of busbar protections like high impedance, medium impedance and low impedance protections. It describes the requirements of busbar protection like short tripping time and stable operation during external faults. The document discusses different busbar arrangements and applications of numerical busbar protection systems like RADSS. It provides examples of busbar protection schemes for different bus configurations. The document also includes excerpts from technical manuals providing recommendations on busbar protection in substations.
This document discusses furnace pressure control for a circulating fluidized bed boiler. It describes how furnace pressure is measured by three pressure transmitters, with the average used as the process value for a proportional-integral controller. The controller output controls the inlet vanes of induced draft fans to keep furnace pressure stable. Furnace draft is controlled through the induced draft fan and inlet guide vanes or variable frequency drive. A two out of three selection block is used to select the two most accurate pressure transmitters and generate the process value for the PID controller, which compares the set point to the process value to control the final control elements of the induced draft fan.
This document provides an overview of turbo generators. It describes their history, working principle, design process, manufacturing of rotor windings, applications, advantages, and disadvantages. Turbo generators are large machines that directly connect turbines to electrical generators in order to generate power. They can be powered by steam, gas, or water turbines. The document outlines the 12 step design process and discusses the construction and components of rotor windings. Turbo generators provide reliable, economic, and renewable energy but require high maintenance costs. Future research focuses on improving insulation testing techniques.
Bus Bar protection Schemes,Simple Current differential scheme,Need for bus bar protection,requirement of bus bar protection,recommendations for providing bus bar protection,basics of busbar protection,Types of bus-bar protections,High speed differential protection
180degree conduction mode of 3 phase inverterdineshanand810
This document discusses the 180 degree conduction mode of a 3 phase inverter. It operates by having three transistors conducting at a time over three modes as the phase shifts 60 degrees each time. Tables and equations are provided showing the transistors conducting, equivalent resistances, phase voltages and currents for each of the three operating modes.
This document discusses generator protection techniques. It begins by explaining why protective systems are needed to protect expensive power system elements like generators. It then describes different types of generator faults and various protection schemes. These include stator protection using differential protection and its modifications. Rotor faults and their protections like rotor earth fault protection are also explained. The document provides details on other protections like overcurrent, overvoltage, vibration and overheating protections. It concludes by stating that protective devices help detect faults, notify maintenance, and disconnect faulty elements to ensure continuous and safe operation of power systems.
This document presents information about Buchholz relays. It discusses that Buchholz relays were first developed in 1921 and are installed in large power transformers to protect against internal faults. The relay contains an upper element that closes an alarm circuit during slow developing faults and a lower element that trips the circuit breaker during severe faults. It operates by detecting hydrogen gas generated from transformer oil decomposition during faults, with the gas causing floats that activate mercury switches to signal alarms or trip the transformer. Buchholz relays provide simple and effective protection for oil-immersed transformers while also detecting slow developing faults earlier than other methods.
An alternator is an electrical generator that converts mechanical energy to electrical energy. It uses a rotating magnetic field with a stationary armature. The working principle relies on Faraday's law of electromagnetic induction. As the armature rotates within the magnetic field, an alternating current is produced. The main components are the stator with stationary armature windings and the rotor with a rotating magnetic field supplied by a DC current. Armature reaction causes the magnetic field to be distorted by the armature current. Alternators have various applications including in automobiles, power plants, and for providing regenerative braking in induction motors. Induction generators can also be used to convert the rotational energy of windmills into electrical energy.
The document discusses busbar protection, including the need for busbar protection, types of busbar protections like high impedance, medium impedance and low impedance protections. It describes the requirements of busbar protection like short tripping time and stable operation during external faults. The document discusses different busbar arrangements and applications of numerical busbar protection systems like RADSS. It provides examples of busbar protection schemes for different bus configurations. The document also includes excerpts from technical manuals providing recommendations on busbar protection in substations.
This document discusses furnace pressure control for a circulating fluidized bed boiler. It describes how furnace pressure is measured by three pressure transmitters, with the average used as the process value for a proportional-integral controller. The controller output controls the inlet vanes of induced draft fans to keep furnace pressure stable. Furnace draft is controlled through the induced draft fan and inlet guide vanes or variable frequency drive. A two out of three selection block is used to select the two most accurate pressure transmitters and generate the process value for the PID controller, which compares the set point to the process value to control the final control elements of the induced draft fan.
This document provides an overview of turbo generators. It describes their history, working principle, design process, manufacturing of rotor windings, applications, advantages, and disadvantages. Turbo generators are large machines that directly connect turbines to electrical generators in order to generate power. They can be powered by steam, gas, or water turbines. The document outlines the 12 step design process and discusses the construction and components of rotor windings. Turbo generators provide reliable, economic, and renewable energy but require high maintenance costs. Future research focuses on improving insulation testing techniques.
Bus Bar protection Schemes,Simple Current differential scheme,Need for bus bar protection,requirement of bus bar protection,recommendations for providing bus bar protection,basics of busbar protection,Types of bus-bar protections,High speed differential protection
180degree conduction mode of 3 phase inverterdineshanand810
This document discusses the 180 degree conduction mode of a 3 phase inverter. It operates by having three transistors conducting at a time over three modes as the phase shifts 60 degrees each time. Tables and equations are provided showing the transistors conducting, equivalent resistances, phase voltages and currents for each of the three operating modes.
This document discusses generator protection techniques. It begins by explaining why protective systems are needed to protect expensive power system elements like generators. It then describes different types of generator faults and various protection schemes. These include stator protection using differential protection and its modifications. Rotor faults and their protections like rotor earth fault protection are also explained. The document provides details on other protections like overcurrent, overvoltage, vibration and overheating protections. It concludes by stating that protective devices help detect faults, notify maintenance, and disconnect faulty elements to ensure continuous and safe operation of power systems.
This document presents information about Buchholz relays. It discusses that Buchholz relays were first developed in 1921 and are installed in large power transformers to protect against internal faults. The relay contains an upper element that closes an alarm circuit during slow developing faults and a lower element that trips the circuit breaker during severe faults. It operates by detecting hydrogen gas generated from transformer oil decomposition during faults, with the gas causing floats that activate mercury switches to signal alarms or trip the transformer. Buchholz relays provide simple and effective protection for oil-immersed transformers while also detecting slow developing faults earlier than other methods.
An alternator is an electrical generator that converts mechanical energy to electrical energy. It uses a rotating magnetic field with a stationary armature. The working principle relies on Faraday's law of electromagnetic induction. As the armature rotates within the magnetic field, an alternating current is produced. The main components are the stator with stationary armature windings and the rotor with a rotating magnetic field supplied by a DC current. Armature reaction causes the magnetic field to be distorted by the armature current. Alternators have various applications including in automobiles, power plants, and for providing regenerative braking in induction motors. Induction generators can also be used to convert the rotational energy of windmills into electrical energy.
The document provides details about the cooling and sealing system of a 247MVA turbo generator. It describes the generator specifications including rating, connection type, phases, rated speed, and insulation class. It then summarizes the need for generator cooling using hydrogen gas and water to minimize heat and ensure uniform temperature distribution. The rotor and stator cooling systems are explained along with specifications. Finally, the generator sealing system is outlined, which uses seal oil to prevent hydrogen leakage and maintain differential pressure between the oil and hydrogen.
This document discusses electric drives and AC motor drives. It defines electric drives as systems that use 50% of electrical energy produced and can operate equipment at constant or variable speeds. The main components of electric drives are motors, including DC and AC types, and power sources like batteries or utilities. It also summarizes different types of single-phase and three-phase DC drives classified by their converter configurations. For AC drives, it explains that speed and torque can be controlled through stator voltage, rotor voltage or frequency control. It concludes that variable speed AC drives can increase system efficiency from 15-27% compared to constant speed operation.
The document discusses transformer protection. It describes various failures that can occur in transformers such as winding failures, bushing failures, and tap changer failures. It provides statistics on historical transformer failures. It also discusses different types of protection for transformers including electrical protection methods like differential protection, overcurrent protection, overexcitation protection and thermal protection. Internal short circuits, system short circuits, and abnormal conditions are some of the issues addressed by transformer protection schemes.
This document summarizes different types of excitation systems for alternators. It discusses the function of excitation systems to supply direct current to the field winding and control the voltage and reactive power of alternators. The three main types covered are DC excitation systems, AC excitation systems, and static excitation systems. DC excitation systems use two small DC generators as exciters but are not commonly used for large alternators now. AC excitation systems include brushless and rotating thyristor types and have advantages like eliminating brushes. Static excitation systems have no rotating parts, are suitable for medium and high capacity alternators, and have benefits like smaller size and no windage losses. The document concludes that the selection of an excitation system depends on factors like the altern
Unit-2 Three Phase controlled converter johny renoald
This document discusses three phase controlled rectifiers. It provides equations and diagrams for a three phase half-wave converter with an RL load operating under continuous and constant load current. The average output voltage is derived as one-third the peak phase voltage multiplied by 2/π. Waveforms at different trigger angles are shown. Methods for calculating the maximum, RMS, and normalized average output voltages are also presented.
The buck-boost converter is a DC-to-DC converter that can produce an output voltage either greater than or less than the input voltage. It works by switching the input voltage across an inductor and output capacitor using a transistor. When the transistor is on, current builds in the inductor; when off, current flows from the inductor through a diode to charge the output capacitor. The output voltage depends on the duty cycle of the transistor switching. Applications include battery-powered vehicles, battery charging, and motor control where variable and reversible voltage conversion is needed.
The document lists the main parts of a transformer as: metallic core, holding frame, winding, on load tap changer, bushings and terminals, radiator wings/cooling tubs, breather, Buchholz relay, explosion valve, control panel, and tank. It provides the names of the core components that make up a transformer.
The document discusses basic pneumatic circuitry and components for control and automation. It covers pneumatic symbols, circuit layout principles, and examples of actuator control using 2/2, 3/2, and 5/2 valves. The 2/2 valve uses two valves to admit air to move the actuator in one direction and exhaust air to move it in the other. The 3/2 valve provides inlet and exhaust with one valve. The 5/2 valve simultaneously switches the supply and exhaust paths to control a double-acting actuator.
This document summarizes the key aspects of three phase synchronous motors. It discusses the working principle, construction, features, principle of operation, methods of starting, excitation, phasor diagram, applications, and disadvantages. Synchronous motors operate at a constant synchronous speed determined by supply frequency. They require an external starting mechanism and DC excitation of the rotor. The motor can operate at lagging, unity, or leading power factors depending on the level of excitation. Main applications are in machine tools and industrial machinery due to their constant speed characteristic. Disadvantages include higher cost and need for auxiliary starting components compared to induction motors.
Automatic voltaer regulator and it's modellingrajani51
in power supply system we have to keep the voltage constant.but when load is connected to the generator voltage difference will occur. to tackle this closed loop control of generator voltage is required. this can be achieved by AUTOMATIC VOLTAGE REGULATOR
Variable frequency drives (VFDs) are used to control the speed of AC induction motors by varying the frequency of the power supplied to the motor. A VFD system consists of an AC motor, controller, and operator interface. VFDs allow for control of motor speed, torque, and power to match application needs. They provide benefits like energy savings, protection from overloads, and flexibility in motor control for various industrial applications like pumps, fans, conveyors, and compressors.
The document discusses condition monitoring techniques used in thermal power plants. The objective of condition monitoring is to identify potential failures in machines to avoid damages and downtime. Key techniques discussed include vibration monitoring, lubricant analysis, noise analysis, wear debris analysis, and thermography. Specific machine components that can be monitored include turbines, generators, pumps, motors and more. The document also provides schedules for regularly monitoring critical equipment using different techniques like vibration analysis, oil analysis, thermography and dissolved gas analysis. Standards for condition monitoring are also mentioned.
Current Source Inverter and Voltage Source Inverter Sadanand Purohit
The document discusses two types of inverters - current source inverters (CSI) and voltage source inverters (VSI). It describes the construction and working of CSI, which uses predetermined source current and load impedance to determine output voltage. VSI uses a constant DC input voltage and feedback diodes. The document also covers applications of CSI and VSI, such as use of CSI for AC motor drives due to regenerative capability, and use of VSI in UPS and AC drives. FACTS devices based on VSI are also summarized, including STATCOM, SSSC and UPFC for controlling transmission line parameters.
star delta auto starter with forward reverse and motor protectionBHUPATI PRADHAN
It is a project on pure electrical engineering. Here three phase motor is starting from star to delta automatically by using some components.In other hand it also provide protection to the motor.
Motor bus transfer (MBT) schemes are used to transfer large motor loads between power sources to maintain process continuity. Larger motors may require comprehensive transfer strategies to avoid mechanical damage during improper transfers. An MBT system's mission is to maintain continuity while avoiding damage. Transfers can occur for various reasons like faults, interruptions, or maintenance. MBT can be open or closed transition, with open transition using methods like fast, in-phase, or residual voltage transfer. Motor, load, and system characteristics affect the transfer. Standards provide guidelines for acceptable voltage and frequency parameters.
The document discusses instrumentation and control systems used in thermal power plants. It describes the objectives of instrumentation and control which include safe and efficient plant operation. It provides an overview of the Distributed Digital Control and Management Information System (DDCMIS) and its components, including the burner management system, turbine control system, and generator instruments. It explains the various functions, measurements, controls, and benefits provided by the DDCMIS.
This presentation provides an overview of power transformers. It discusses that power transformers are static machines that transform power from one circuit to another without changing frequency, and are used between generators and distribution circuits. It then describes the typical power ratings of small, medium, and large power transformers. The main components of power transformers are then outlined, including bushings, the core and winding, conservator tank, breather and silica gel, cooling tubes, tap changer, transformer oil, and Buchholz relay. The functions of these key components are explained at a high level.
�The sample calculations shown here illustrate steps involved in calculating the relay settings for generator protection.
�Other methodologies and techniques may be applied to calculate relay settings based on specific applications.
The protections of generator are the most complex and elaborate due to the following reasons: Generator is a large machine, connected to bus-bars. It is accompanied by unit transformers, auxiliary transformers and a bus system. ... The protection of generator should be co-ordinate with associated equipment's.
This document describes various protection schemes for transformers, including differential, restricted earth fault, overcurrent, and thermal protection.
1) Differential protection compares currents entering and leaving the transformer zone to detect internal faults. It provides the best protection for internal faults.
2) Restricted earth fault protection is used to detect high-resistance winding-to-core faults not detectable by differential relays. It uses a neutral current transformer and is sensitive to internal earth faults.
3) Overcurrent protection uses relays with current coils to detect overloads and faults above a pickup threshold. It also includes ground-fault protection.
This document provides an overview of generator basics, including:
1) Descriptions of synchronous generator types and connections to power systems such as direct connected and unit connected configurations.
2) Explanations of generator excitation and automatic voltage regulator (AVR) control systems.
3) Discussions of generator grounding methods like low impedance, high impedance, and dual grounding; and considerations for multiple generator installations.
4) Details on generator protection devices and multifunction digital relays, appropriate levels of redundancy, and potential VT connection issues.
The control panel specifications require a cubical panel made of 16 gauge sheet metal with hinged covers to house the control components above a base frame. Rubber pads will isolate the base frame from the panel supports. A manual bypass switch and earth stud shall be provided. The panel must achieve automatic control of an engine-alternator set through a microprocessor-based controller in auto mode, including starting the engine on mains failure and stopping it on restoration based on voltage and timing settings. Alarms and operational parameters shall be transmitted to a remote monitoring station via GSM modem using GPRS or SMS.
The document provides details about the cooling and sealing system of a 247MVA turbo generator. It describes the generator specifications including rating, connection type, phases, rated speed, and insulation class. It then summarizes the need for generator cooling using hydrogen gas and water to minimize heat and ensure uniform temperature distribution. The rotor and stator cooling systems are explained along with specifications. Finally, the generator sealing system is outlined, which uses seal oil to prevent hydrogen leakage and maintain differential pressure between the oil and hydrogen.
This document discusses electric drives and AC motor drives. It defines electric drives as systems that use 50% of electrical energy produced and can operate equipment at constant or variable speeds. The main components of electric drives are motors, including DC and AC types, and power sources like batteries or utilities. It also summarizes different types of single-phase and three-phase DC drives classified by their converter configurations. For AC drives, it explains that speed and torque can be controlled through stator voltage, rotor voltage or frequency control. It concludes that variable speed AC drives can increase system efficiency from 15-27% compared to constant speed operation.
The document discusses transformer protection. It describes various failures that can occur in transformers such as winding failures, bushing failures, and tap changer failures. It provides statistics on historical transformer failures. It also discusses different types of protection for transformers including electrical protection methods like differential protection, overcurrent protection, overexcitation protection and thermal protection. Internal short circuits, system short circuits, and abnormal conditions are some of the issues addressed by transformer protection schemes.
This document summarizes different types of excitation systems for alternators. It discusses the function of excitation systems to supply direct current to the field winding and control the voltage and reactive power of alternators. The three main types covered are DC excitation systems, AC excitation systems, and static excitation systems. DC excitation systems use two small DC generators as exciters but are not commonly used for large alternators now. AC excitation systems include brushless and rotating thyristor types and have advantages like eliminating brushes. Static excitation systems have no rotating parts, are suitable for medium and high capacity alternators, and have benefits like smaller size and no windage losses. The document concludes that the selection of an excitation system depends on factors like the altern
Unit-2 Three Phase controlled converter johny renoald
This document discusses three phase controlled rectifiers. It provides equations and diagrams for a three phase half-wave converter with an RL load operating under continuous and constant load current. The average output voltage is derived as one-third the peak phase voltage multiplied by 2/π. Waveforms at different trigger angles are shown. Methods for calculating the maximum, RMS, and normalized average output voltages are also presented.
The buck-boost converter is a DC-to-DC converter that can produce an output voltage either greater than or less than the input voltage. It works by switching the input voltage across an inductor and output capacitor using a transistor. When the transistor is on, current builds in the inductor; when off, current flows from the inductor through a diode to charge the output capacitor. The output voltage depends on the duty cycle of the transistor switching. Applications include battery-powered vehicles, battery charging, and motor control where variable and reversible voltage conversion is needed.
The document lists the main parts of a transformer as: metallic core, holding frame, winding, on load tap changer, bushings and terminals, radiator wings/cooling tubs, breather, Buchholz relay, explosion valve, control panel, and tank. It provides the names of the core components that make up a transformer.
The document discusses basic pneumatic circuitry and components for control and automation. It covers pneumatic symbols, circuit layout principles, and examples of actuator control using 2/2, 3/2, and 5/2 valves. The 2/2 valve uses two valves to admit air to move the actuator in one direction and exhaust air to move it in the other. The 3/2 valve provides inlet and exhaust with one valve. The 5/2 valve simultaneously switches the supply and exhaust paths to control a double-acting actuator.
This document summarizes the key aspects of three phase synchronous motors. It discusses the working principle, construction, features, principle of operation, methods of starting, excitation, phasor diagram, applications, and disadvantages. Synchronous motors operate at a constant synchronous speed determined by supply frequency. They require an external starting mechanism and DC excitation of the rotor. The motor can operate at lagging, unity, or leading power factors depending on the level of excitation. Main applications are in machine tools and industrial machinery due to their constant speed characteristic. Disadvantages include higher cost and need for auxiliary starting components compared to induction motors.
Automatic voltaer regulator and it's modellingrajani51
in power supply system we have to keep the voltage constant.but when load is connected to the generator voltage difference will occur. to tackle this closed loop control of generator voltage is required. this can be achieved by AUTOMATIC VOLTAGE REGULATOR
Variable frequency drives (VFDs) are used to control the speed of AC induction motors by varying the frequency of the power supplied to the motor. A VFD system consists of an AC motor, controller, and operator interface. VFDs allow for control of motor speed, torque, and power to match application needs. They provide benefits like energy savings, protection from overloads, and flexibility in motor control for various industrial applications like pumps, fans, conveyors, and compressors.
The document discusses condition monitoring techniques used in thermal power plants. The objective of condition monitoring is to identify potential failures in machines to avoid damages and downtime. Key techniques discussed include vibration monitoring, lubricant analysis, noise analysis, wear debris analysis, and thermography. Specific machine components that can be monitored include turbines, generators, pumps, motors and more. The document also provides schedules for regularly monitoring critical equipment using different techniques like vibration analysis, oil analysis, thermography and dissolved gas analysis. Standards for condition monitoring are also mentioned.
Current Source Inverter and Voltage Source Inverter Sadanand Purohit
The document discusses two types of inverters - current source inverters (CSI) and voltage source inverters (VSI). It describes the construction and working of CSI, which uses predetermined source current and load impedance to determine output voltage. VSI uses a constant DC input voltage and feedback diodes. The document also covers applications of CSI and VSI, such as use of CSI for AC motor drives due to regenerative capability, and use of VSI in UPS and AC drives. FACTS devices based on VSI are also summarized, including STATCOM, SSSC and UPFC for controlling transmission line parameters.
star delta auto starter with forward reverse and motor protectionBHUPATI PRADHAN
It is a project on pure electrical engineering. Here three phase motor is starting from star to delta automatically by using some components.In other hand it also provide protection to the motor.
Motor bus transfer (MBT) schemes are used to transfer large motor loads between power sources to maintain process continuity. Larger motors may require comprehensive transfer strategies to avoid mechanical damage during improper transfers. An MBT system's mission is to maintain continuity while avoiding damage. Transfers can occur for various reasons like faults, interruptions, or maintenance. MBT can be open or closed transition, with open transition using methods like fast, in-phase, or residual voltage transfer. Motor, load, and system characteristics affect the transfer. Standards provide guidelines for acceptable voltage and frequency parameters.
The document discusses instrumentation and control systems used in thermal power plants. It describes the objectives of instrumentation and control which include safe and efficient plant operation. It provides an overview of the Distributed Digital Control and Management Information System (DDCMIS) and its components, including the burner management system, turbine control system, and generator instruments. It explains the various functions, measurements, controls, and benefits provided by the DDCMIS.
This presentation provides an overview of power transformers. It discusses that power transformers are static machines that transform power from one circuit to another without changing frequency, and are used between generators and distribution circuits. It then describes the typical power ratings of small, medium, and large power transformers. The main components of power transformers are then outlined, including bushings, the core and winding, conservator tank, breather and silica gel, cooling tubes, tap changer, transformer oil, and Buchholz relay. The functions of these key components are explained at a high level.
�The sample calculations shown here illustrate steps involved in calculating the relay settings for generator protection.
�Other methodologies and techniques may be applied to calculate relay settings based on specific applications.
The protections of generator are the most complex and elaborate due to the following reasons: Generator is a large machine, connected to bus-bars. It is accompanied by unit transformers, auxiliary transformers and a bus system. ... The protection of generator should be co-ordinate with associated equipment's.
This document describes various protection schemes for transformers, including differential, restricted earth fault, overcurrent, and thermal protection.
1) Differential protection compares currents entering and leaving the transformer zone to detect internal faults. It provides the best protection for internal faults.
2) Restricted earth fault protection is used to detect high-resistance winding-to-core faults not detectable by differential relays. It uses a neutral current transformer and is sensitive to internal earth faults.
3) Overcurrent protection uses relays with current coils to detect overloads and faults above a pickup threshold. It also includes ground-fault protection.
This document provides an overview of generator basics, including:
1) Descriptions of synchronous generator types and connections to power systems such as direct connected and unit connected configurations.
2) Explanations of generator excitation and automatic voltage regulator (AVR) control systems.
3) Discussions of generator grounding methods like low impedance, high impedance, and dual grounding; and considerations for multiple generator installations.
4) Details on generator protection devices and multifunction digital relays, appropriate levels of redundancy, and potential VT connection issues.
The control panel specifications require a cubical panel made of 16 gauge sheet metal with hinged covers to house the control components above a base frame. Rubber pads will isolate the base frame from the panel supports. A manual bypass switch and earth stud shall be provided. The panel must achieve automatic control of an engine-alternator set through a microprocessor-based controller in auto mode, including starting the engine on mains failure and stopping it on restoration based on voltage and timing settings. Alarms and operational parameters shall be transmitted to a remote monitoring station via GSM modem using GPRS or SMS.
Variable Frequency Drives . Are they worth it?blenrayaust
VFDs (variable frequency drives) are often specified to control pump speed for various reasons, but they are not always the best or most energy efficient solution. Alternatives to consider include pressure/flow control valves, bypass valves, changing pump impeller size, using multiple pumps, or varying the pumped fluid properties/conditions. While VFDs can provide benefits in some cases, they also have downsides such as increased capital and operating costs, reduced motor lifespan, and lower combined motor/VFD efficiency compared to running a properly sized pump at its best efficiency point. Engineers should evaluate all options before specifying a VFD and ensure the electrical design considers potential issues from voltage harmonics and other factors.
Varaible Speed Drives for Motor Driven Fire PumpsJames S Nasby
Variable speed fire pump controllers can use variable frequency drives (VFDs) to control pump speed. VFDs have several elements including rectifiers, DC links, and inverters. They provide soft starting for motors but can also affect motors and electrical systems. Proper motor requirements, testing, and system tuning are needed for fire pump applications.
This document provides guidance on proper grounding practices for on-site power systems. It discusses the differences between equipment grounding and system grounding, and explains that both are important for safety and proper operation of ground fault detection. Key points covered include the importance of a single grounding point, using 4-pole transfer switches for ground fault sensing, and considerations for paralleled generator sets. The document recommends solid equipment grounding practices and configuring systems to ensure ground fault current has a defined path to return to its source.
When designing generator systems, consulting engineers must ensure that the generators and the building electrical systems that they support are appropriate for the specific application. Whether providing standby power for health care facilities or prime power for rural processing plants, engineers must make decisions regarding generator sizing, load types, whether generators should be paralleled, fuel storage, switching scenarios, and many other criteria. In addition to being up to speed on the applicable codes, consulting engineers must work with the authorities having jurisdiction (AHJ) to ensure approval for the generator system is attained.
Nidec asi capability overview for lng and oil&gas applicationsNidec Corporation
Nidec ASI has over 40 years of experience serving the oil and gas industry. They provide electric drive systems, motors, and generators for applications across the oil and gas supply chain from extraction to distribution. Nidec takes an integrated engineering approach to design customized solutions that optimize performance, reliability, efficiency and costs.
DG synchronizing Panel Manufacturer and Suppliers in IndiaMohit Bathineni
Synchronization panels synchronize one or more generator breakers either manually or automatically. They are used to meet power system requirements and provide multiplexing solutions. Paralleling generators involves electrically coupling them to increase total capacity and allows load transfer without interruption. It requires that the generators have the same voltage, frequency, and phase before connecting. Synchronization can be checked manually with lamps or instruments, or automatically with a synchronization relay.
Nidec asi electric power solutions for pipeline applicationsNidec Corporation
Nidec ASI provides electric power solutions for pumps and compressors used in oil and gas pipelines. They have over 40 years of experience designing customized solutions that meet clients' needs in terms of power quality, network connection flexibility, maintenance costs, machine durability, and capital expenditures. Nidec ASI works closely with end users, engineers, and OEMs to develop optimal global solutions for pipeline operations. Their solutions include soft starters, variable frequency drives, and fully integrated packages for applications up to 30 MW. Nidec takes an integrated engineering approach considering mechanical, electrical, and site factors to optimize performance, reliability, and costs.
This document discusses variable speed fire pump controllers. It covers the components and operation of variable frequency drives (VFDs) and the requirements for a fire pump controller system using a VFD. Key points include an overview of VFD elements and operation, requirements for the controller system including isolation contactors and pressure monitoring, considerations for motor starting characteristics and coordination, and design factors such as cooling and pollution rating. Application-specific topics like hydraulic system tuning are also addressed.
The document provides an overview of inverter-based solar photovoltaic power plants. It discusses the key electrical components of a PV plant including the PV source, combiner boxes, power conversion stations, medium voltage transformers, and the central plant controller. The central controller manages plant control functions like active power control, voltage regulation, and power factor control. It also coordinates grid integration functions such as voltage and frequency ride-through. The document explains how inverters are used to interface DC power sources to the grid and discusses common inverter control functions including sequencing, protection, external references, monitoring, and regulating functions like current/voltage control loops.
This document discusses the debate around whether paralleling generators is a good idea for hospital standby power systems. It provides an overview of how generator paralleling works, including the requirements and components needed. The advantages of paralleling include increased reliability if one generator fails, more flexibility, and better overall system performance compared to a single generator. While paralleling equipment adds some costs, proponents argue the reliability benefits are worth it. However, some argue hospitals could save money by not using paralleling and instead implementing load shedding of lower priority equipment in an outage. The document examines both perspectives on this issue.
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...Ingeteam Wind Energy
DFIG topology wind turbines have been widely used in the wind energy market during the last years to cover the medium and lower power ranges, between 2 and 4 MW. Nowadays, this fact has changed and the OEMs are developing DFIG wind turbines that could go above power rates of 6 MW.
Ingeteam’s new generation of power converters apply the most advanced control strategies, state of the art semiconductor technologies and cooling strategies that solve the main constraints of the DFIG topology, allowing for an increase in the power rate of the new wind turbines above 6 MW.
This document contains a question bank for energy managers and energy auditors related to energy efficient technologies in electrical systems. It includes 20 multiple choice questions about topics like maximum demand controllers, power factor correction capacitors, automatic power factor controllers, energy efficient motors, variable frequency drives, and more. It also includes short answer questions about maximum demand control, automatic power factor controllers, areas for improvement with energy efficient motors, technical aspects of energy efficient motors, soft starters, variable torque loads, variable frequency drives, and applications of variable frequency drive control for pumps and fans.
This document contains a question bank for energy managers and energy auditors related to energy efficient technologies in electrical systems. It includes multiple choice, true/false, and short answer questions that cover topics like maximum demand controllers, power factor correction, variable speed drives, energy efficient motors and transformers, lighting controls, and other retrofit opportunities. Long answer questions provide more detailed explanations of demand controllers, automatic power factor control methods, soft starters, variable speed applications, and recommended retrofit actions for facilities. The question bank is intended to test knowledge of key electrical system optimization strategies.
www.Lucky-Bet.site => Bet on Sports - 50% Deposit Bonus
www.Lucky-Bet.site/casino => Online Casino - 5000$ Welcome Bonus
www.Lucky-Bet.site/lotto247 => Lotto247 - Win Big, Live Free
www.Lucky-Bet.site/eurobet => Best European Bookmaker
www.earnperhit.com/essay => Professional academic writing
Key Characteristics and Requirements of Diesel Fire Pump Engines
This document describes a pulse width modulation (PWM) solar charge controller. It begins with an introduction and objectives, then discusses the basic components and workings of solar charge controllers including PWM and MPPT types. The remainder of the document details the specific hardware components used in the implemented PWM solar charge controller prototype including an Arduino Nano microcontroller. It provides schematics, algorithms, and explanations of sections like voltage sensing, PWM signal generation, and MOSFET switching. The conclusion discusses expanding the design to be a hybrid PWM/MPPT controller to reduce costs for large-scale solar installations.
Bently Nevada provides online condition monitoring systems for wind turbine drive trains to help wind farm operators optimize maintenance. Their offerings include vibration monitoring transmitters installed up-tower on gearboxes, generators, and main bearings to detect emerging faults. The data is transmitted via SCADA networks to software that calculates diagnostic metrics to identify issues like planetary gear debris, dynamic energy index shifts indicating gearbox damage, and sideband energy ratios pointing to broken teeth. These early warnings allow repairs to be scheduled for downtimes when wind is low to minimize lost revenue. Case studies demonstrate how the system can provide advance notice of failures like sun gear cracks and enable cost-saving uptower fixes for issues like bearing electrical discharge machining.
This document provides guidelines for the design and production of low voltage power factor correction cubicles. It discusses key considerations for component selection and installation, including applicable standards, effects of harmonics, capacitor and reactor selection, contactor requirements, protection devices, power factor controller functions, and testing procedures. The document aims to help panel builders design and produce power factor correction panels that comply with relevant standards and address specific application needs and constraints.
Similar to ATS, Grounding Issues & Installation Considerations (20)
Auburn, NY - 200 Years of History 1793-1993michaeljmack
Auburn, New York celebrated its 200th anniversary in 1993. The city has a rich history dating back to its founding in 1792 by John L. Hardenbergh. Early settlers established homes, churches, mills and prioritized education. Auburn grew into an economic center, gaining a village charter in 1815. The state prison and Auburn Theological Seminary brought prestige. During the Civil War, Auburn supported the Union and industries like manufacturing flourished afterwards. While the economy has changed, Auburn looks to build on its cultural and educational strengths as it enters its third century.
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
This document is the yearbook from Auburn High School for the class of 1982. It contains photos, quotes, and information about various events and members of the senior class. The yearbook staff proudly presents "Images of Yesterday" to capture memories from the past year at A.H.S. It includes sections on beach day, typical school days, homecoming, and memories from the class of '82 as they prepare to graduate and go their separate ways.
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
This document appears to be from a high school yearbook. It lists various superlatives voted on by the graduating class such as "Most Humorous", "Best Looking", and "Most Likely to Succeed". It also includes photos and quotes from individual graduating students. The document celebrates the class of 1979 and recognizes various achievements and personalities of the students.
This document provides an overview of surge protection and transient surges. It defines a transient surge as a brief high-voltage spike lasting millionths of a second. The document discusses how surges can damage equipment and cost businesses billions annually. It describes how surge protective devices (SPDs) work by diverting damaging currents away from equipment. The document emphasizes that proper SPD location and installation is important for effective protection. It provides guidance on selecting appropriate protection levels based on surge risk and discusses relevant industry codes and standards.
Diesel Particulate Filters Control Systemsmichaeljmack
This document discusses diesel particulate filter systems from Rypos, Inc. for stationary diesel generators and port equipment. It provides an overview of regulatory requirements for particulate matter emissions in California, describes Rypos' active regeneration filter technology using electrical heating elements, and lists some customer installations of their diesel particulate filter systems on generators and rubber-tired gantries at various ports.
Five to 10 arc flash explosions occur daily in the US, often requiring specialized burn treatment. There are two types of faults that can cause arcs: bolted faults where current flows through a solid connection, and arcing faults where current arcs through ionized air. Arcing faults are more dangerous as the energy is released into the environment. Standards like NFPA 70E and OSHA requirements aim to protect workers by enforcing safety practices like arc flash analyses and requiring personal protective equipment suitable for the estimated incident energy levels. Proper maintenance and use of protective equipment can reduce arc flash exposure hazards.
This document provides information on Siemens medium-voltage gas-insulated arc-resistant switchgear. It discusses the switchgear's increased safety, reliability, and flexibility features. The document includes technical specifications, diagrams, and benefits such as its compact design, high personnel safety, minimized fire load, and maintenance-free components due to its SF6 gas insulation. It also describes innovative features like its video camera system for viewing the selector switch position and capacitive voltage indicators.
This document discusses transformer inrush current and its impact on differential relays. Transformer inrush occurs when the flux in the transformer core needs to be established, causing a large magnetizing current to flow. This inrush current appears as a differential current that can cause misoperation of transformer differential relays. The document examines characteristics of inrush current like the switching point, remnant flux, system impedance, and transformer design. It also discusses various harmonic-based methods for restraining differential relays during inrush like percentage of total harmonic, percentage of 2nd harmonic, and adaptive 2nd harmonic methods. The considerations for applying these methods include reliability, security, and speed of operation.
This document discusses Building Information Modeling (BIM) and its implications for electrical engineers. It begins with an overview of BIM, explaining that BIM provides a digital representation of a facility and its physical and functional characteristics. It then discusses how BIM can benefit owners, design engineers, and contractors by improving coordination, reducing risks and costs, and streamlining processes. The remainder of the document focuses on a case study of a large hospital project where BIM was used, highlighting lessons learned around project setup, managing limitations, and the importance of communication and proper planning when adopting BIM.
15 years of experience stator ground fault protectionmichaeljmack
The document discusses different methods for 100% stator ground fault protection on generators based on 15 years of experience. It describes conventional 59G protection that only covers 90-95% of the stator, as well as 3rd harmonic schemes that can provide full coverage but have limitations. Subharmonic injection was also used in Europe and provides full coverage independently of generator loading. While 3rd harmonic schemes require testing the generator's harmonic signature, subharmonic injection is preferable as it works regardless of loading and can detect faults offline or throughout the entire winding.
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
The document discusses the differences between emergency, legally required standby, and optional standby systems according to the 1999 NEC. Emergency systems are for life safety and are subject to more stringent requirements than standby systems. Legally required standby systems serve equipment important for safety but not critical for life, while optional standby systems are intended to minimize economic losses and protect facilities. The document provides detailed comparisons of the categories and guidance on proper system design and component selection.
Lighting Control Solutions for Daylit Spacesmichaeljmack
This document provides an overview of a webinar on lighting control solutions for daylit spaces. The webinar aims to teach participants how architectural daylighting design can impact daylight penetration and occupant comfort, how to circuit electric lighting to work with daylight, and how to design daylight-responsive lighting controls to save energy. The webinar covers topics like daylight benefits, linking daylighting design with electric lighting systems, control strategies, photosensor characteristics, and examples of control designs for different daylighting configurations.
COPS: An Arresting Look at NEC Article 708michaeljmack
The document discusses an arresting look at NEC Article 708 which establishes requirements for critical operations power systems. It provides an overview of a webcast on the topic with multiple presenters discussing key aspects of Article 708 such as operational availability, how it relates to other NEC articles, and ensuring public acceptance. The presenters aim to provide takeaways on several learning objectives related to understanding and implementing Article 708.
Seismic Compliance of Electrical Distributionmichaeljmack
This document discusses changes in seismic code requirements for electrical equipment from 2006 IBC and ASCE/SEI 7-05 standards. It highlights key events like the 1985 Mexico City earthquake that revealed issues with site effects and building resonances, driving later code revisions. The document outlines equipment qualification options in current codes including analysis, testing on a shake table, and presents considerations for developing a testing protocol aligned with building code seismic performance goals.
The document discusses generator set transient response to load changes. It notes that voltage level is more consistent than utilities but frequency control is poorer in responding to load changes. When load changes, both the frequency and voltage will change until the governor and AVR can increase fuel and excitation levels. The size of the load change and speed of responding fuel/excitation systems impact how much the voltage and frequency change. Proper transient response is important for motor starting and UPS operation. Test data is presented showing voltage dips and recovery times for different sized generator sets and loads. The conclusions emphasize specifying generator set performance according to NFPA 110 standards and testing at factory and jobsite to verify transient response capabilities.
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
1. The document describes modeling a digital protective relay in a real-time digital simulator (RTDS) to test the relay's performance under various system disturbances without needing physical hardware.
2. Key modules of the simulated relay include differential protection, external fault detection, internal fault detection, directional logic, and open current transformer detection.
3. Testing results found the simulated relay responded within reasonable tolerance of an actual hardware relay for various faults like internal faults, evolving faults, and open current transformers. This allows protective algorithms to be developed and verified in software first before hardware realization.
This document discusses how wind turbines can provide grid support functions similar to Flexible AC Transmission Systems (FACTS) devices through advanced controls of the power electronics and generator systems. It describes how doubly-fed induction generator wind turbines can regulate voltage and reactive power at the point of interconnection, provide inertial response during frequency disturbances, limit ramp rates during changes in wind speed, and improve transient stability compared to synchronous generators. The document argues that these grid support functions allow high levels of wind power to be integrated onto the grid in a reliable manner without compromising system performance.
1) Many power plant events are complex to analyze and often involve human error, especially during commissioning of new plants. Accurately documenting events and sharing lessons learned is important.
2) Protective relays and their coordination, along with oscillographic records, play a key role in preventing damage and speeding return to service after events occur.
3) Common event types discussed include multi-phase faults, stator ground faults, inadvertent energizing, overexcitation, loss-of-field, and generator breaker failures. Close attention to relay settings and logic is needed to mitigate risks.
1) Voltage collapse is a major cause of recent blackouts due to increased reliance on remote generation and lack of transmission expansion. As transmission lines trip, reactive power losses increase, reducing voltage.
2) Generators provide reactive power (VARs) to support system voltage through their automatic voltage regulators (AVRs). During low voltage events, AVRs and generator protection systems may not be able to maintain stable operation.
3) Undervoltage load shedding is used to prevent total system collapse by automatically removing certain loads if voltage drops below a threshold for a set time period. This helps restore the balance between generation and load.
Transformers transfer energy from one circuit to another through magnetic coupling and are used to transform voltage levels for transmission and distribution. They operate on the principles that voltage in equals voltage out and turns ratio determines the voltage transformation. Transformers are widely used throughout power systems and come in different configurations, ratings, and winding arrangements to serve various applications including generation, transmission, distribution, and end use.
Using recycled concrete aggregates (RCA) for pavements is crucial to achieving sustainability. Implementing RCA for new pavement can minimize carbon footprint, conserve natural resources, reduce harmful emissions, and lower life cycle costs. Compared to natural aggregate (NA), RCA pavement has fewer comprehensive studies and sustainability assessments.
Low power architecture of logic gates using adiabatic techniquesnooriasukmaningtyas
The growing significance of portable systems to limit power consumption in ultra-large-scale-integration chips of very high density, has recently led to rapid and inventive progresses in low-power design. The most effective technique is adiabatic logic circuit design in energy-efficient hardware. This paper presents two adiabatic approaches for the design of low power circuits, modified positive feedback adiabatic logic (modified PFAL) and the other is direct current diode based positive feedback adiabatic logic (DC-DB PFAL). Logic gates are the preliminary components in any digital circuit design. By improving the performance of basic gates, one can improvise the whole system performance. In this paper proposed circuit design of the low power architecture of OR/NOR, AND/NAND, and XOR/XNOR gates are presented using the said approaches and their results are analyzed for powerdissipation, delay, power-delay-product and rise time and compared with the other adiabatic techniques along with the conventional complementary metal oxide semiconductor (CMOS) designs reported in the literature. It has been found that the designs with DC-DB PFAL technique outperform with the percentage improvement of 65% for NOR gate and 7% for NAND gate and 34% for XNOR gate over the modified PFAL techniques at 10 MHz respectively.
Harnessing WebAssembly for Real-time Stateless Streaming PipelinesChristina Lin
Traditionally, dealing with real-time data pipelines has involved significant overhead, even for straightforward tasks like data transformation or masking. However, in this talk, we’ll venture into the dynamic realm of WebAssembly (WASM) and discover how it can revolutionize the creation of stateless streaming pipelines within a Kafka (Redpanda) broker. These pipelines are adept at managing low-latency, high-data-volume scenarios.
Embedded machine learning-based road conditions and driving behavior monitoringIJECEIAES
Car accident rates have increased in recent years, resulting in losses in human lives, properties, and other financial costs. An embedded machine learning-based system is developed to address this critical issue. The system can monitor road conditions, detect driving patterns, and identify aggressive driving behaviors. The system is based on neural networks trained on a comprehensive dataset of driving events, driving styles, and road conditions. The system effectively detects potential risks and helps mitigate the frequency and impact of accidents. The primary goal is to ensure the safety of drivers and vehicles. Collecting data involved gathering information on three key road events: normal street and normal drive, speed bumps, circular yellow speed bumps, and three aggressive driving actions: sudden start, sudden stop, and sudden entry. The gathered data is processed and analyzed using a machine learning system designed for limited power and memory devices. The developed system resulted in 91.9% accuracy, 93.6% precision, and 92% recall. The achieved inference time on an Arduino Nano 33 BLE Sense with a 32-bit CPU running at 64 MHz is 34 ms and requires 2.6 kB peak RAM and 139.9 kB program flash memory, making it suitable for resource-constrained embedded systems.
Introduction- e - waste – definition - sources of e-waste– hazardous substances in e-waste - effects of e-waste on environment and human health- need for e-waste management– e-waste handling rules - waste minimization techniques for managing e-waste – recycling of e-waste - disposal treatment methods of e- waste – mechanism of extraction of precious metal from leaching solution-global Scenario of E-waste – E-waste in India- case studies.
Advanced control scheme of doubly fed induction generator for wind turbine us...IJECEIAES
This paper describes a speed control device for generating electrical energy on an electricity network based on the doubly fed induction generator (DFIG) used for wind power conversion systems. At first, a double-fed induction generator model was constructed. A control law is formulated to govern the flow of energy between the stator of a DFIG and the energy network using three types of controllers: proportional integral (PI), sliding mode controller (SMC) and second order sliding mode controller (SOSMC). Their different results in terms of power reference tracking, reaction to unexpected speed fluctuations, sensitivity to perturbations, and resilience against machine parameter alterations are compared. MATLAB/Simulink was used to conduct the simulations for the preceding study. Multiple simulations have shown very satisfying results, and the investigations demonstrate the efficacy and power-enhancing capabilities of the suggested control system.
1. Automatic Transfer Switches , Grounding Issues &
Installation Considerations for Standby Power Systems
Paul O’Hara, GM
Cummins Cal Pacific
May 15, 2014
3. Grounding Discussion Agenda
General Requirements & Terminology
The Two Big Rules
Applications
Hardware Requirements
Recommendations
4. Terminology
3-phase 3-wire System (Neutral Not Used)
Generator May Be Solidly-Grounded (Shown), Resistance Grounded, or
Ungrounded.
Generator side of system is separately derived
– No neutral connection to the neutral which is bonded at the service entrance
3P ATS GenSet
To Loads
SERVICE
ENTRANCE
GEC GEC
Grounding Electrode System
EGC
MAIN
BONDING
JUMPER
TO
UTILITY
5. Terminology
3-Phase/4-wire system & loads
Not Separately Derived
– Common neutral for entire system
– (NEC 250-20 (d) FPN No. 1)/(CEC 10-204 (4))
3P/4W ATS GenSet
To 3-Phase/4wire
Loads
TO
UTILITY
6. The Two Big Rules
for grounding and bonding low voltage generator systems
There shall be one, and only one neutral-to-ground
bond on any neutral bus
– There are some exceptions, such as impedance-grounded
systems and floating systems, but these don’t allow use of
neutral to serve loads.
When ground fault equipment is used, the bonding
point must be between the sensor and the source.
– During all operation modes…more on that later
7. Grounding Rule #1
There can be only one neutral to ground bonding
jumper on any neutral bus
– 4-pole switches or 3 phase/3-wire loads
ATS GenSet
To Loads (3-phase/4W with gnd)
TO
UTILITY
GEC
GEC
EGC SYSTEM
BONDING
JUMPER
MAIN
BONDING
JUMPER
8. Breaking the First Big Rule…
Parallel Path for IGF on the Neutral
GFP Does Not Sense All Fault Current
Solution: Remove Bond on Generator
ATS GenSet
To Loads
10. Breaking the 2nd Big Rule…
The GF sensor must be downstream from the
bonding/grounding point
– GF sensor for a specific source must have bonding point
between the sensor and the source.
ATS GenSet
GND
FAULT
11. Function of 4-Pole Switches
Fourth Pole Opens the Path on Neutral, isolating utility neutral
from generator neutral
Allows Accurate GFP Sensing, Both Sides
ATS GenSet
To Loads
12. Multiple ATS Applications
2 levels of GFP and 2 or more 3-pole ATS
Neutral Current May Nuisance Trip Feeder GFP
3P ATS
GenSet
3P ATS
Unbalanced
Load
13. Conclusion: 4-Pole Switches
Should Be Used on Any 3-Phase 4-Wire System
– Especially when 480VAC with ground fault
– When Used, Generator Is Separately-Derived
Assures Proper GFP Sensing
– (NEC 230-95 FPN No. 3) (CEC 14-102)
– Solidly Grounded Wye
– More Than 150 Volts to Ground (277/480
347/600VAC)
– OCD Rating 1000A or More (CEC 120/208VAC &
2000A)
Used If Outdoor Generator conductors pass
through a service entrance into the building
14. 4-pole Switches
Used With GF Indication on Generator (NEC 700-7(d))
Used With Multi-Level GFP and Multiple ATS
Not Used With Existing 3-Pole Switches
– Exception: Second Separately-Derived Normal Source
– Exception: All 3-Pole Switches Serve 3-Wire Loads
Other Possible Methods
– 3-Wire System Feeding Transformers
– Use OCD Less Than 1000 A
15. SUSE Breaker or Connection Box Requirements
Ground Bus
Electrically solid to alternator
frame & genset frame
Neutral to Gnd Link
Ground Fault
Provisions
Adequate Lug Space
Required Labels
UL, Protection, Etc.
Wire Bend Space
(Top or Bottom Connect)
Bracing & Spacing
Supply Side Barriers for
SUSE (Not Shown)
Overcurrent function: here
provided by a breaker
16. Article 250 Grounding and Bonding
16
Grounding (Outdoor) Separately Derived Sources
NFPA 70 250.30
Grounding Electrode
connection must be made
at the service disconnect
or first disconnect means
for outdoor generators
17. GES Physical Provisions (Outdoor Generators)
Grounding Electrode System
– Ground Rod at Generator Disconnect
• Must be Suitable for Use as Service Equipment (SUSE)
– Ground Rod at Generator set
• New requirement for 2011
18.
19.
20.
21.
22. Parallel Generators
Not specifically
addressed in code
Many opinions on
best practice
Best to consider
the BUS as the
source, and apply
rules from there
– As long as the AHJ
agrees…
GF SENSOR
23. GenSet GenSet
Y Y
U1
51G 51G
51G
51G
Zero Sequence Detected Zero Sequence Detected
Utility Service 1 Utility Service 2
GM1 U2GM2
G1 G2
GFI on Utility Mains and Generator Breakers
24. Recommendations
Keep in mind proper terminology
Remember & use the two big rules:
– Single neutral to ground bonding connection on any neutral bus
• This is for safety and reliability of the distribution system
• Bond is usually in the switchgear for low voltage generator systems—
NOT at each generator
– For ground fault sensing to work, the bonding connection must
be between the source and the GF sensor
Recommend the use of 4-pole (switched neutral)
switches for any system requiring ground fault alarm or
protection
For multiple source systems, design considering the bus
as the source, and follow the two big rules
25. Hospital –Gen 2 Short Circuit
(Actual incident June 22, 2010)
Ground
Fault
Occurs
Ground
Current
Path
(Relay Trips
turned off)
Generator
Control Shuts
down genset on
Short Circuit Fault
(>175%)
Neutral
Grounding
Resistor Fails
(>200 Amps)
26. NFPA110 Overview
NFPA 110
Requirements to achieve
maximum on-site power
system reliability
System Focus
Practical, but not cheap
See appendix for some
practical advice on power
system design and
operation
31. Chapter 4 - Class, Type and Level of EPSS
Class – minimum time
emergency power is to
operate
Type – maximum time load
won’t have power
Level – importance of
system to human life
– 1 – Critical to human life
– 2 – Less critical to life & safety
5/15/2014 Cummins Confidential31
Typical systems for us are Type 10, and Level 1,
and Class based on fuel capacity desired
32. Chap 5 – Energy Sources, Converters & Acc’s
5/15/2014 Cummins Confidential32
33. Chap 5 – Energy Sources, Converters & Acc’s
5/15/2014 Cummins Confidential33
34. Ref: Page 120, T-030
Electrical Interconnections
Each installation
different
Ampacity of
Supply Circuit is
GenSet Specific
Note Some
Circuits Fed by
GenSet, others by
Utility
35. Chap 5 – Energy Sources, Converters & Acc’s
5/15/2014 Cummins Confidential35
37. Fuel Systems
Why Gas?
– Fewer fuel storage
concerns
– Lower Emissions
Why not Gas?
– Seismic shutoff valves
– State code for on-site
fuel storage
– Cost (Gensets >100
kW)
Why Diesel?
– Not as dependent on
outside fuel source
– Fast starting with proper
fuels
– Long life
– Usually better transient
performance
– Usually better frequency
stability
38. Large Gas vs.
Diesel Gensets
with Tier 4 final
Aftertreatment
Most Data Centers
have standardized
on Diesel Fuel
Most use Tier 2
and are limited to
emergency use
Some use Tier 4 to
limit emissions
NFPA110 Overview
Criteria Nat Gas T4f Diesel
Comparitive Models (Cummins) C1700N6 1500DQGAE
Performance
10 sec to start and full load no yes
Transient performance poor good
Codes
Meets CEC for life safety loads no yes
UL2200 Listed no yes
Seismic Certified no yes
On site storage required per code yes yes
Exhaust Emissions (gm/hp-hr)
Oxides of Nitrogen (NOx) 1.73 0.38
Particulate Matter (PM) negligble 0.00
Unburned Hydrocarbons (NMHC) negligble 0.02
Carbon monoxide (CO) 3 1.02
Installation Related
Physical Characteristics
Length (inches) 522 370
Width (inches) 144 129
Height (inches) 166 154
Weight (lbs - less fuel tank) 56493 38747
Cost
Approximate costkW* 1,276,000$ 872,414$
*Cost includes 75dbA enclosure and fuel storage tank for diesel
39. Diesel Fuel Systems
Reliable fuel supply depends on:
– no air in fuel
– fuel temperature
– proper volume delivered to engine
– fuel quality
System Design Greatly Affected by Local Codes and
Interpretation
System Design Should Meet NFPA 37
40. (kW)*(57) BTU/Min
Assume 140,000 Btu/Gal diesel fuel, and 35%
overall efficiency
Estimating Diesel Fuel Consumption
Rule of Thumb:
Multiply the standby KW times .07…
that’s the fuel consumption (gph)
Mechanical Energy
Fuel (BTU) In
Power Out 35%
41. What Size Fuel Tank?
Decision based on:
– GenSet Fuel Consumption
– Application Type
– Expected Duration of Outage
– Priority and time to Re-Fuel
Recommendations
– Plan for Fuel Maintenance
• Fuel testing
• Fuel polishing
12 and 24 hour capacity unit mounted (sub-base)
24 hour tanks are very common
High Rise Buildings (CFC)
42. Major fuel storage issues to pay attention to
Stairs and platforms
are required when sub-
base fuel tanks raise
controls and output
breakers to over 78”
from ground
Although not in state
code, overfill prevention
(valves) and spill
protection are required
by several authorities
43. Chap 5 – Energy Sources, Converters & Acc’s
5/15/2014 Cummins Confidential43
44. Chap 5 – Energy Sources, Converters & Acc’s
5/15/2014 Cummins Confidential44
66. Seismic concerns
All emergency equipment for legally required
systems need to be seismically certified to meet
IBC/CBC seismic withstand requirements. Can be
by analysis
All emergency equipment California OSHPD
overseen installations need to be listed with an OSP
by OSHPD. These items need to be shake table
tested
– OSP-0028 and 268 Generators
– OSP-0029 Automatic Transfer Switches
– OSP-0030 Paralleling Controls
NFPA110 Overview
69. Airborne Noise
130 Pneumatic Riveter (130)
120
110
100 Jet @ 1000ft (103)
90 Power Mower (96)
80 Heavy Street Traffic (85)
70
60 Normal Conversation (65)
50 Light Traffic @ 100ft (55)
40 Library (40)
30
20 Broadcast Studio (20)
• Primarily a problem in outdoor
gensets
• A System is Too Noisy IF:
– Local Codes Exceeded (may be
in 40-50 dBA range)
• Someone thinks it is
• Aftertreatment is
EXPENSIVE
– Hearing Protection Required in
Generator Rooms per OSHA
• Amount and Perception
Depends on Background Noise
Level
• Logarithmic Basis is Hard for
Laymen to Understand
71. Adding Noise Levels
DIFFERENCE IN dB(A) BETWEEN VALUES BEING
1 2 3 4 5 6 7 8 9 10
0.2
0.4
0.6
0.8
1.0
2.0
3.0
1.2
1.4
1.6
1.8
2.2
2.4
2.6
2.8 dB
(A
)
T
O
A
D
D
T
O
TH
E
G
R
E
AT
E
R
V
AL
U
IncrementinDecibels
tobeaddedtohigherlevel
Difference in dB(A) between values being added
DIFFERENCE IN dB(A) BETWEEN VALUES BEING
1 2 3 4 5 6 7 8 9 10
0.2
0.4
0.6
0.8
1.0
2.0
3.0
1.2
1.4
1.6
1.8
2.2
2.4
2.6
2.8 dB
(A
)
T
O
A
D
D
T
O
TH
E
G
R
E
AT
E
R
V
AL
U
72. Sound Attenuation Strategies
Total Noise Level is SUM of all the Sources
• Mechanical Engine Noise
• Fan Noise
• Exhaust
Consider all the parts operating together to get to desired result.
Exhaust 94
dB(A)
Fan 86 dB(A)
Engine 80
dB(A)
89 dB(A)
79 dB(A)
87 dB(A)
Install 15 dB
Std. Muffler
75. Reducing the Noise by Site Design
Increase Distance from Receiver
Insert High Mass, Absorptive Barriers
Direct Noise Away From Sensitive
Locations
Watch for Hard, Reflective Surfaces
Rule of Thumb:
Sound power drops 6dBA at 2 times distance.
Rule of Thumb:
Sound power increases 3dBA for two equal sources.
76. +5 dBA
Effect of Reverberation
The noise source is effectively duplicated by
hard walls.
+3 dBA
77. For further information
New On-Line Library – PowerSuite 5.0
https://powersuite.cummins.com/
For additional help contact:
Guy Shullerts, Territory Manager, (510) 347-6664
John McWilliams, Application Engineer, (510) 347-6673
Paul O’Hara, GM Mission Critical/Tech Comm (949) 337-5393