SlideShare a Scribd company logo
Scheme LogicScheme Logic
I/O Point Purpose
IN1 Gen CB Status IPSLogic Functions IPS LOGIC Input(s) TDDO
IN2 86U Status 5A Trip Sequence & Governor in manaul IPS#1 Out4/Out5/Out15/Out21+ IN4
IN3 Sync Condense Status 86G Trip Sequence Initiate IPS#2 IN11
IN4 Governor in Manual 86GH Trip Sequence Initiate IPS#3 IN12 SV13
IN5 Wicket Gate at SNL 86N Trip Sequence Initiate IPS#4 IN13
IN7 Exciter Low Level 86NH Trip Sequence Initiate IPS#5 IN14 SV14
IN8 Sync Condense Status Trip Gen CB + Wicket Gate IPS#6 OUT16 + IN5 OUT16 contact Seal-in time set at desire time delay
IN11 86G Trip Sequence Initiate
IN12 86GH Trip Sequence Initiate
IN13 86N Trip Sequence Initiate
IN14 86NH Trip Sequence Initiate
TRIP#1 /Arm Fire Prot. SV13T SV14T
Supervised by 60FL 60FL 60FL+27 32+IN7 27+IN4 IN3 27+IN3
21 24-2 40-1&2 40-2 59-1 59-2 87-1/2 IPS#1 IPS#2 59N-1&2 27TN-1&2 81-1 IPS#4 32-1 78 46-2 81-2 25 IPS#3 IPS#5 IPS#6
Out1 Arm Fire Prot. X, X X, X X, X
Out2 Arm Fire Prot. X, X X, X X, X
Out3 Test point
Out4 PML Alarm X X X X
Out5 UCC PLC X X X X
Out6 BF Initiate X X X X X X X X X X X X X X
Out7 BF Initiate X
Out8 Trip Gen CB X
Out9 Trip Field CB X
Out10 Close PIV X
Out11 Trip 86U X X X X X X X X X X X X X X X
Out12 Trip Gen CB X X X X X X X X X X X X X X
Out14 Trip Field CB X X X X X X X X X
Out15 De Excite X X X X
Out16 IPSLogic#6 X X X X X
Out17
Out10 X
Out18
Out19
Out20 Block TIV X X
Out21 PAM PLC X X X X
Out22 Sync Check X
BC Hydro application requires Seal-in of the ARM Fire Protection and Block TIV trip outputs.
Out1,Out2 and Out20 have output contact seal-in setting time of 1 - 8160 cycles.
TRIP#3TRIP#2 / Arm Fire Prot.
Seal-In Logic
ARM Fire Protection Block TIV
Out2
Seal-in
1 - 8160
cycles
Out1
Seal-in
1 - 8160
cycles
Out20
Seal-in
1 - 8160
cycles
Contacts Latch
or use TDDO
86U
IN4
Out4
Out5
Out15
Out21
OR
AND Output(s)
IPSLogic#1
IN11 Output(s)
IPSLogic#2
IN13 Output(s)
IPSLogic#4
IN14 Output(s)
IPSLogic#5
TDDO
IN12 Output(s)
IPSLogic#3
TDDO IN15
Out16
IPSLogic#6
AND Output(s)
Seal-in
M-3425A Trip Matrix Logic
Scheme Logic
IN204
IN203
IN202
IN201
IN207
IN205
IN104
IN103
IN101
IN102
Customer
Input
BECO
Sync Condense StatusIN8
86NH Trip Sequence InitiateIN14
86N Trip Sequence InitiateIN13
86GH Trip Sequence InitiateIN12
86G Trip Sequence InitiateIN11
Exciter Low LevelIN7
Wicket Gate at SNLIN5
Governor in ManualIN4
Sync Condense StatusIN3
86U StatusIN2
Gen CB StatusIN1
Description/PurposeInput
Customer Scheme Inputs
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Purpose
Arm Fire Prot.
Output
Out1
Customer BECO
Out212
Out211
Out210
Out207
Out205
Out204
Out202
Out201
Out106
Out105
Out104
Out103
Out102
Output
Out101
Customer Scheme Outputs
Scheme Logic
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
81-246-27832-1
27+IN8IN3
TRIP#3
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
Customer Scheme Trip #3
Scheme Logic
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
81-246-27832-1
27+IN8IN3
TRIP#3
Customer Logic
BECO Logic
Customer Scheme Trip #3
OOST
4602T
IN103
32PIT
IN103
27B81P
81D2T
AND
OR
AND
AND
TRIP3
78
46-2
IN3
32-1
IN8
27
81-2
AND
OR
AND
AND
TRIP3
Scheme Logic
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
81-246-27832-1
27+IN8IN3
TRIP#3
BECO Logic
IN11 IN3 IN8
Sync Condenser Status
IN3 active
contact closed
IN8 active
contact open
Input Contact Activation State
Customer Scheme Trip #3
78
46-2
IN3
32-1
IN8
27
81-2
AND
OR
AND
AND
TRIP3
Scheme Logic
BECO Input Contact Logic
Customer Scheme Trip #3
IN3 active
when closed
IN8 active
when open
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
X
X
32-1
IN3
BECO Logic
IN3
Customer Scheme Trip #3 (32-1)
IN3
32-1
AND
OR
TRIP3
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
X
X
81-2
27+IN3
81 function internal cutoff voltage is 5-15V
BECO Logic
IN8
Customer Scheme Trip #3 (81-2)
IN8
27-1
81-2
OR
AND
AND
TRIP3
Scheme Logic
81 function internal cutoff voltage is 5-15V
Customer Scheme Trip #3 (81-2)
81 Function Cutoff Voltage
0
5
10
15
20
0 10 20 30 40 50 60 70
Frequency
CutoffVoltage
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
XXXXXXXXXTrip Field CBOut14
XXXXXXXXXTrip Gen CBOut12
XXXXXXXXXTrip 86UOut11
XXXXXXXXXBF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
X, XArm Fire Prot.Out2
X, XArm Fire Prot.Out1
IPS#2IPS#187-1/259-259-140-240-1&224-221
60FL+2760FL60FLSupervised by
TRIP#1/Arm Fire Prot
Customer Scheme Trip #1
Scheme Logic
60LOP
40Z1T
AND AND
TRIP1
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
40-1
60FL
40-160FL
Customer Scheme Trip #1 (40-1)
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
40-2
60FL+27
40-2
Voltage
Control
Output
Customer Scheme Trip #1 (40-2)
TRIP1
OR
27
60LFL
40-2
AND
60LFL
40-2 AND
T1
T2
Scheme Logic
IN11 OR
TRIP1
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
IPS#2IPSLogic#2
IN11 Output(s)
IPSLogic#2
Customer Logic
Customer Scheme Trip #1 (IPS#2)
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
IN12
SV13T
TDDO
86U
IN12 Output(s)
IPSLogic#3
TDDO
Customer Logic
X
X
X
X
X
X
IPS#3
SV13T
IPSLogic#3
Dropout Time Delay
Customer Scheme SV13T (IPS#3)
Scheme Logic
IN14
SV14T
TDDO
86U
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
IN14 Output(s)
IPSLogic#5
TDDO
Customer Logic
X
X
X
X
IPS#5
SV14T
IPSLogic#5
Dropout Time Delay
OR
Customer Scheme SV14T (IPS#5)
Scheme Logic
IN4
TRIP1
AND
Trip#3
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
IPS#1
IPSLogic#1 Initiating Outputs
IN4
Out4
Out5
Out15
Out21
OR
AND Output(s)
IPSLogic#1
Customer Logic
Initiating Inputs
AND
Customer Scheme Trip #1 (IPS#1)
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
XXXX
XXXX
X, XX, X
X, XX, X
IPS#481-127TN-1&259N-1/2
27+IN432+IN7
TRIP#2 / Arm Fire Prot.
Customer Scheme Trip #2
Scheme Logic
Customer Logic
BECO Logic
XXXX
XXXX
X, XX, X
X, XX, X
IPS#481-127TN-1&259N-1/2
27+IN432+IN7
TRIP#2 / Arm Fire Prot.
Customer Scheme Trip #2
IN207
32P2T AND OR
TRIP2
64G1T
64G2T
IN203
IN104
27B81P
81D1T
AND
AND
IN7
32P2T AND OR
TRIP2
59N1
27TN
IN13
IN4
27
81-1 AND
IPSlogic#4
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
X
X
X
X
27TN-1&2
32+IN7
BECO Logic
32 Supervision
Customer Scheme Trip #2 (27TN)
IN7
32-2 AND OR
TRIP2
27TN
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
87U2
59N2
AND
AND
IN2
OR
Arm Fire
Protection
32
IN7
AND
27TN2
IN2
Latching Outputs
or time delayed dropout
1 to 8160 cycles
Customer Logic
BECO Logic
Seal-in Circuit
XX
XX
X, XX, X
X, XX, X
27TN-1&259N-1&2
32+IN7
Customer Scheme Trip #2 (Arm Fire)
87U
32P2T
IN207
AND
OR
64G2
64G1
IN101
87R
AND
Arm Fire
Protection
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised by
Customer Logic
BECO Logic
IPS#3
OR
IPS#5
Block TIV
Out20 86U
Seal-in Circuit
Latching Output
or time delayed dropou
1 to 8160 cycles
XX
XX
X
X
X
XX
X
IPS#5IPS#3
SV14TSV13T
Customer Scheme Block TIV
SV13T
OR
IN101
SV14T
AND
Block TIV
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised byCustomer Logic
BECO Logic
Customer Scheme Trip 86U
Trip1
86U
IN204
IN203
Trip2
IN202
IN201
OR
Trip1
86U
IPS#5
IPS#4
Trip2
IPS#3
IPS#2
OR
IPS#1
Scheme Logic
Sync CheckOut22
PAM PLCOut21
Block TIVOut20
Close PIVOut17
IPSLogic#6Out16
De ExciteOut15
Trip Field CBOut14
Trip Gen CBOut12
Trip 86UOut11
BF InitiateOut6
UCC PLCOut5
PML AlarmOut4
Test pointOut3
Arm Fire Prot.Out2
Arm Fire Prot.Out1
Supervised byCustomer Logic
BECO Logic
Trip1
86U
IPS#5
IPS#4
Trip2
IPS#3
IPS#2
OR
IPS#1
Customer Scheme Trip 86U
Trip1
86U
IN204
IN203
Trip2
IN202
IN201
OR
Scheme Logic
Customer Logic
BECO Logic
IN205
Trip2
SV14T OR
AND
SV7DO
AND
OR
Trip3
SV13T
Trip1
Trip Gen
Breaker
BFI
OR
SV13T
Trip1
Trip Gen
Breaker
BFI
IN5
AND
Trip3
Trip2
IPS#5 OR
OUT16 TDDO
1 - 8160 ~
IPSLogic#6
Customer Scheme Trip Gen Breaker
Scheme Logic
Sync Check
PAM PLC
Block TIV
Close PIV
IPSLogic#6
De Excite
Trip Field CB
Trip Gen CB
Trip 86U
BF Initiate
UCC PLC
PML Alarm
Test point
Arm Fire Prot.
Arm Fire Prot.
Supervised by
X
X
IPS#6
Seal in time
Customer Scheme IPSLogic #6
IN5
AND
OUT16 TDDO
1 - 8160 ~
Outputs
IPSLogic#6
Scheme Logic
THE ENDTHE END
Scheme Logic
©2008 Beckwith Electric Co., Inc.

More Related Content

What's hot

Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysis
michaeljmack
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
karikalan123
 
Auto synch considerations methods
Auto synch considerations methodsAuto synch considerations methods
Auto synch considerations methods
michaeljmack
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
Thien Phan Bản
 
AC Voltage Controller.pptx
AC Voltage Controller.pptxAC Voltage Controller.pptx
AC Voltage Controller.pptx
AbdulBasitMemon12
 
ETAP - Coordination and protecion
ETAP -  Coordination and protecionETAP -  Coordination and protecion
ETAP - Coordination and protecion
Himmelstern
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
michaeljmack
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Power System Operation
 
Substations
SubstationsSubstations
Substations
ducusin_kevin07
 
Power quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSPower quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUS
MOHANASUNDARAM ANTHONY
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
System Protection
 
Código Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdf
Código Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdfCódigo Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdf
Código Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdf
JosRodrguez706755
 
ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)
ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)
ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)
Himmelstern
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
Himmelstern
 
ETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctricoETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctrico
Himmelstern
 
Design of transformer
Design of transformerDesign of transformer
Design of transformer
Subrata Dey
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
SHIMI S L
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
michaeljmack
 
ETAP - Transient stability 2
ETAP - Transient stability 2ETAP - Transient stability 2
ETAP - Transient stability 2
Himmelstern
 

What's hot (20)

Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysis
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
Auto synch considerations methods
Auto synch considerations methodsAuto synch considerations methods
Auto synch considerations methods
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
 
AC Voltage Controller.pptx
AC Voltage Controller.pptxAC Voltage Controller.pptx
AC Voltage Controller.pptx
 
ETAP - Coordination and protecion
ETAP -  Coordination and protecionETAP -  Coordination and protecion
ETAP - Coordination and protecion
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Substations
SubstationsSubstations
Substations
 
Out of step
Out of stepOut of step
Out of step
 
Power quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSPower quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUS
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
Código Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdf
Código Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdfCódigo Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdf
Código Eléctrico Nacional 8va Revisión FONDONORMA 200-2009.pdf
 
ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)
ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)
ETAP - Iec 60364 - cable sizing (dimensionamiento de cables)
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
 
ETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctricoETAP - Coordinación de protecciones y arco eléctrico
ETAP - Coordinación de protecciones y arco eléctrico
 
Design of transformer
Design of transformerDesign of transformer
Design of transformer
 
Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)Flexible AC Transmission (FACTS)
Flexible AC Transmission (FACTS)
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
ETAP - Transient stability 2
ETAP - Transient stability 2ETAP - Transient stability 2
ETAP - Transient stability 2
 

Similar to Scheme logic implement pwr plant cntrl

Digital logic design lecture 05
Digital logic design   lecture 05 Digital logic design   lecture 05
Digital logic design lecture 05
FarhatUllah27
 
Sequntial logic design
Sequntial logic designSequntial logic design
Sequntial logic design
Pavan Mukku
 
P89v51rd2
P89v51rd2P89v51rd2
P89v51rd2
Jagadeesh Kumar
 
8051 microcontroller
8051 microcontroller 8051 microcontroller
8051 microcontroller
Gaurav Verma
 
74ls390
74ls39074ls390
2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC
2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC
2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC
Shawn Lee
 
GPIO In Arm cortex-m4 tiva-c
GPIO In Arm cortex-m4 tiva-cGPIO In Arm cortex-m4 tiva-c
GPIO In Arm cortex-m4 tiva-c
Zakaria Gomaa
 
At 89c51
At 89c51At 89c51
At 89c51
Mr Giap
 
74ls373
74ls37374ls373
74ls373
holinh7
 
Pe 3231 week 15 18 plc
Pe 3231 week 15 18  plcPe 3231 week 15 18  plc
Pe 3231 week 15 18 plc
Charlton Inao
 
854F wiring.pdf
854F wiring.pdf854F wiring.pdf
854F wiring.pdf
thang tong
 
Sequential circuits digital logic sesign
Sequential circuits digital logic sesignSequential circuits digital logic sesign
Sequential circuits digital logic sesign
FazalHameed14
 
PowerMate15 Technical Specification
PowerMate15 Technical SpecificationPowerMate15 Technical Specification
PowerMate15 Technical Specification
Rimsky Cheng
 
Sua chua may lanh cua daikin
Sua chua may lanh cua daikinSua chua may lanh cua daikin
Sua chua may lanh cua daikin
suadiennuochanoi.vn
 
854 f wiring
854 f wiring854 f wiring
854 f wiring
thang tong
 
Guia de configuracao_ms9520
Guia de configuracao_ms9520Guia de configuracao_ms9520
Guia de configuracao_ms9520plisleo
 
Lec12
Lec12Lec12
3.81 inch Amoled(1080x1200) VR Datasheet
3.81 inch Amoled(1080x1200) VR Datasheet3.81 inch Amoled(1080x1200) VR Datasheet
3.81 inch Amoled(1080x1200) VR Datasheet
Panox Display
 
Keypad interfacing 8051 -NANOCDAC
Keypad interfacing 8051 -NANOCDACKeypad interfacing 8051 -NANOCDAC
Keypad interfacing 8051 -NANOCDAC
nanocdac
 

Similar to Scheme logic implement pwr plant cntrl (20)

Digital logic design lecture 05
Digital logic design   lecture 05 Digital logic design   lecture 05
Digital logic design lecture 05
 
Sequntial logic design
Sequntial logic designSequntial logic design
Sequntial logic design
 
P89v51rd2
P89v51rd2P89v51rd2
P89v51rd2
 
8051 microcontroller
8051 microcontroller 8051 microcontroller
8051 microcontroller
 
74ls390
74ls39074ls390
74ls390
 
2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC
2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC
2.8 Inch LCD 320X240 C0283QGL-SPIRGB To Replace CMEL 2.8 C0283QGLC
 
GPIO In Arm cortex-m4 tiva-c
GPIO In Arm cortex-m4 tiva-cGPIO In Arm cortex-m4 tiva-c
GPIO In Arm cortex-m4 tiva-c
 
At 89c51
At 89c51At 89c51
At 89c51
 
74ls373
74ls37374ls373
74ls373
 
Pe 3231 week 15 18 plc
Pe 3231 week 15 18  plcPe 3231 week 15 18  plc
Pe 3231 week 15 18 plc
 
A TRAFFIC LIGHT CONTROL SYSTEM USING PROGRAMMABLE LOGIC CONTROLLER
A TRAFFIC LIGHT CONTROL SYSTEM USING PROGRAMMABLE LOGIC CONTROLLERA TRAFFIC LIGHT CONTROL SYSTEM USING PROGRAMMABLE LOGIC CONTROLLER
A TRAFFIC LIGHT CONTROL SYSTEM USING PROGRAMMABLE LOGIC CONTROLLER
 
854F wiring.pdf
854F wiring.pdf854F wiring.pdf
854F wiring.pdf
 
Sequential circuits digital logic sesign
Sequential circuits digital logic sesignSequential circuits digital logic sesign
Sequential circuits digital logic sesign
 
PowerMate15 Technical Specification
PowerMate15 Technical SpecificationPowerMate15 Technical Specification
PowerMate15 Technical Specification
 
Sua chua may lanh cua daikin
Sua chua may lanh cua daikinSua chua may lanh cua daikin
Sua chua may lanh cua daikin
 
854 f wiring
854 f wiring854 f wiring
854 f wiring
 
Guia de configuracao_ms9520
Guia de configuracao_ms9520Guia de configuracao_ms9520
Guia de configuracao_ms9520
 
Lec12
Lec12Lec12
Lec12
 
3.81 inch Amoled(1080x1200) VR Datasheet
3.81 inch Amoled(1080x1200) VR Datasheet3.81 inch Amoled(1080x1200) VR Datasheet
3.81 inch Amoled(1080x1200) VR Datasheet
 
Keypad interfacing 8051 -NANOCDAC
Keypad interfacing 8051 -NANOCDACKeypad interfacing 8051 -NANOCDAC
Keypad interfacing 8051 -NANOCDAC
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
michaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
michaeljmack
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
michaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
michaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
michaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
michaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
michaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
michaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
michaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
michaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
michaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
michaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
michaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
michaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
michaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
michaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
michaeljmack
 
Arc Flash
Arc FlashArc Flash
Arc Flash
michaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 

Recently uploaded

DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
ML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptxML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptx
Vijay Dialani, PhD
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
thanhdowork
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
AP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specificAP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specific
BrazilAccount1
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
Osamah Alsalih
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
manasideore6
 

Recently uploaded (20)

DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
ML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptxML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptx
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
AP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specificAP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specific
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
 

Scheme logic implement pwr plant cntrl

  • 2. I/O Point Purpose IN1 Gen CB Status IPSLogic Functions IPS LOGIC Input(s) TDDO IN2 86U Status 5A Trip Sequence & Governor in manaul IPS#1 Out4/Out5/Out15/Out21+ IN4 IN3 Sync Condense Status 86G Trip Sequence Initiate IPS#2 IN11 IN4 Governor in Manual 86GH Trip Sequence Initiate IPS#3 IN12 SV13 IN5 Wicket Gate at SNL 86N Trip Sequence Initiate IPS#4 IN13 IN7 Exciter Low Level 86NH Trip Sequence Initiate IPS#5 IN14 SV14 IN8 Sync Condense Status Trip Gen CB + Wicket Gate IPS#6 OUT16 + IN5 OUT16 contact Seal-in time set at desire time delay IN11 86G Trip Sequence Initiate IN12 86GH Trip Sequence Initiate IN13 86N Trip Sequence Initiate IN14 86NH Trip Sequence Initiate TRIP#1 /Arm Fire Prot. SV13T SV14T Supervised by 60FL 60FL 60FL+27 32+IN7 27+IN4 IN3 27+IN3 21 24-2 40-1&2 40-2 59-1 59-2 87-1/2 IPS#1 IPS#2 59N-1&2 27TN-1&2 81-1 IPS#4 32-1 78 46-2 81-2 25 IPS#3 IPS#5 IPS#6 Out1 Arm Fire Prot. X, X X, X X, X Out2 Arm Fire Prot. X, X X, X X, X Out3 Test point Out4 PML Alarm X X X X Out5 UCC PLC X X X X Out6 BF Initiate X X X X X X X X X X X X X X Out7 BF Initiate X Out8 Trip Gen CB X Out9 Trip Field CB X Out10 Close PIV X Out11 Trip 86U X X X X X X X X X X X X X X X Out12 Trip Gen CB X X X X X X X X X X X X X X Out14 Trip Field CB X X X X X X X X X Out15 De Excite X X X X Out16 IPSLogic#6 X X X X X Out17 Out10 X Out18 Out19 Out20 Block TIV X X Out21 PAM PLC X X X X Out22 Sync Check X BC Hydro application requires Seal-in of the ARM Fire Protection and Block TIV trip outputs. Out1,Out2 and Out20 have output contact seal-in setting time of 1 - 8160 cycles. TRIP#3TRIP#2 / Arm Fire Prot. Seal-In Logic ARM Fire Protection Block TIV Out2 Seal-in 1 - 8160 cycles Out1 Seal-in 1 - 8160 cycles Out20 Seal-in 1 - 8160 cycles Contacts Latch or use TDDO 86U IN4 Out4 Out5 Out15 Out21 OR AND Output(s) IPSLogic#1 IN11 Output(s) IPSLogic#2 IN13 Output(s) IPSLogic#4 IN14 Output(s) IPSLogic#5 TDDO IN12 Output(s) IPSLogic#3 TDDO IN15 Out16 IPSLogic#6 AND Output(s) Seal-in M-3425A Trip Matrix Logic Scheme Logic
  • 3. IN204 IN203 IN202 IN201 IN207 IN205 IN104 IN103 IN101 IN102 Customer Input BECO Sync Condense StatusIN8 86NH Trip Sequence InitiateIN14 86N Trip Sequence InitiateIN13 86GH Trip Sequence InitiateIN12 86G Trip Sequence InitiateIN11 Exciter Low LevelIN7 Wicket Gate at SNLIN5 Governor in ManualIN4 Sync Condense StatusIN3 86U StatusIN2 Gen CB StatusIN1 Description/PurposeInput Customer Scheme Inputs Scheme Logic
  • 4. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Purpose Arm Fire Prot. Output Out1 Customer BECO Out212 Out211 Out210 Out207 Out205 Out204 Out202 Out201 Out106 Out105 Out104 Out103 Out102 Output Out101 Customer Scheme Outputs Scheme Logic
  • 5. XXXX XXXX XXXX XXXX XXXX XXXX 81-246-27832-1 27+IN8IN3 TRIP#3 Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by Customer Scheme Trip #3 Scheme Logic
  • 6. XXXX XXXX XXXX XXXX XXXX XXXX 81-246-27832-1 27+IN8IN3 TRIP#3 Customer Logic BECO Logic Customer Scheme Trip #3 OOST 4602T IN103 32PIT IN103 27B81P 81D2T AND OR AND AND TRIP3 78 46-2 IN3 32-1 IN8 27 81-2 AND OR AND AND TRIP3 Scheme Logic
  • 7. XXXX XXXX XXXX XXXX XXXX XXXX 81-246-27832-1 27+IN8IN3 TRIP#3 BECO Logic IN11 IN3 IN8 Sync Condenser Status IN3 active contact closed IN8 active contact open Input Contact Activation State Customer Scheme Trip #3 78 46-2 IN3 32-1 IN8 27 81-2 AND OR AND AND TRIP3 Scheme Logic
  • 8. BECO Input Contact Logic Customer Scheme Trip #3 IN3 active when closed IN8 active when open Scheme Logic
  • 9. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X X X 32-1 IN3 BECO Logic IN3 Customer Scheme Trip #3 (32-1) IN3 32-1 AND OR TRIP3 Scheme Logic
  • 10. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X X X 81-2 27+IN3 81 function internal cutoff voltage is 5-15V BECO Logic IN8 Customer Scheme Trip #3 (81-2) IN8 27-1 81-2 OR AND AND TRIP3 Scheme Logic
  • 11. 81 function internal cutoff voltage is 5-15V Customer Scheme Trip #3 (81-2) 81 Function Cutoff Voltage 0 5 10 15 20 0 10 20 30 40 50 60 70 Frequency CutoffVoltage Scheme Logic
  • 12. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 XXXXXXXXXTrip Field CBOut14 XXXXXXXXXTrip Gen CBOut12 XXXXXXXXXTrip 86UOut11 XXXXXXXXXBF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 X, XArm Fire Prot.Out2 X, XArm Fire Prot.Out1 IPS#2IPS#187-1/259-259-140-240-1&224-221 60FL+2760FL60FLSupervised by TRIP#1/Arm Fire Prot Customer Scheme Trip #1 Scheme Logic
  • 13. 60LOP 40Z1T AND AND TRIP1 Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X 40-1 60FL 40-160FL Customer Scheme Trip #1 (40-1) Scheme Logic
  • 14. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X 40-2 60FL+27 40-2 Voltage Control Output Customer Scheme Trip #1 (40-2) TRIP1 OR 27 60LFL 40-2 AND 60LFL 40-2 AND T1 T2 Scheme Logic
  • 15. IN11 OR TRIP1 Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X IPS#2IPSLogic#2 IN11 Output(s) IPSLogic#2 Customer Logic Customer Scheme Trip #1 (IPS#2) Scheme Logic
  • 16. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by IN12 SV13T TDDO 86U IN12 Output(s) IPSLogic#3 TDDO Customer Logic X X X X X X IPS#3 SV13T IPSLogic#3 Dropout Time Delay Customer Scheme SV13T (IPS#3) Scheme Logic
  • 17. IN14 SV14T TDDO 86U Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by IN14 Output(s) IPSLogic#5 TDDO Customer Logic X X X X IPS#5 SV14T IPSLogic#5 Dropout Time Delay OR Customer Scheme SV14T (IPS#5) Scheme Logic
  • 18. IN4 TRIP1 AND Trip#3 Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X IPS#1 IPSLogic#1 Initiating Outputs IN4 Out4 Out5 Out15 Out21 OR AND Output(s) IPSLogic#1 Customer Logic Initiating Inputs AND Customer Scheme Trip #1 (IPS#1) Scheme Logic
  • 19. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by XXXX XXXX X, XX, X X, XX, X IPS#481-127TN-1&259N-1/2 27+IN432+IN7 TRIP#2 / Arm Fire Prot. Customer Scheme Trip #2 Scheme Logic
  • 20. Customer Logic BECO Logic XXXX XXXX X, XX, X X, XX, X IPS#481-127TN-1&259N-1/2 27+IN432+IN7 TRIP#2 / Arm Fire Prot. Customer Scheme Trip #2 IN207 32P2T AND OR TRIP2 64G1T 64G2T IN203 IN104 27B81P 81D1T AND AND IN7 32P2T AND OR TRIP2 59N1 27TN IN13 IN4 27 81-1 AND IPSlogic#4 Scheme Logic
  • 21. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by X X X X 27TN-1&2 32+IN7 BECO Logic 32 Supervision Customer Scheme Trip #2 (27TN) IN7 32-2 AND OR TRIP2 27TN Scheme Logic
  • 22. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by 87U2 59N2 AND AND IN2 OR Arm Fire Protection 32 IN7 AND 27TN2 IN2 Latching Outputs or time delayed dropout 1 to 8160 cycles Customer Logic BECO Logic Seal-in Circuit XX XX X, XX, X X, XX, X 27TN-1&259N-1&2 32+IN7 Customer Scheme Trip #2 (Arm Fire) 87U 32P2T IN207 AND OR 64G2 64G1 IN101 87R AND Arm Fire Protection Scheme Logic
  • 23. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised by Customer Logic BECO Logic IPS#3 OR IPS#5 Block TIV Out20 86U Seal-in Circuit Latching Output or time delayed dropou 1 to 8160 cycles XX XX X X X XX X IPS#5IPS#3 SV14TSV13T Customer Scheme Block TIV SV13T OR IN101 SV14T AND Block TIV Scheme Logic
  • 24. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised byCustomer Logic BECO Logic Customer Scheme Trip 86U Trip1 86U IN204 IN203 Trip2 IN202 IN201 OR Trip1 86U IPS#5 IPS#4 Trip2 IPS#3 IPS#2 OR IPS#1 Scheme Logic
  • 25. Sync CheckOut22 PAM PLCOut21 Block TIVOut20 Close PIVOut17 IPSLogic#6Out16 De ExciteOut15 Trip Field CBOut14 Trip Gen CBOut12 Trip 86UOut11 BF InitiateOut6 UCC PLCOut5 PML AlarmOut4 Test pointOut3 Arm Fire Prot.Out2 Arm Fire Prot.Out1 Supervised byCustomer Logic BECO Logic Trip1 86U IPS#5 IPS#4 Trip2 IPS#3 IPS#2 OR IPS#1 Customer Scheme Trip 86U Trip1 86U IN204 IN203 Trip2 IN202 IN201 OR Scheme Logic
  • 26. Customer Logic BECO Logic IN205 Trip2 SV14T OR AND SV7DO AND OR Trip3 SV13T Trip1 Trip Gen Breaker BFI OR SV13T Trip1 Trip Gen Breaker BFI IN5 AND Trip3 Trip2 IPS#5 OR OUT16 TDDO 1 - 8160 ~ IPSLogic#6 Customer Scheme Trip Gen Breaker Scheme Logic
  • 27. Sync Check PAM PLC Block TIV Close PIV IPSLogic#6 De Excite Trip Field CB Trip Gen CB Trip 86U BF Initiate UCC PLC PML Alarm Test point Arm Fire Prot. Arm Fire Prot. Supervised by X X IPS#6 Seal in time Customer Scheme IPSLogic #6 IN5 AND OUT16 TDDO 1 - 8160 ~ Outputs IPSLogic#6 Scheme Logic
  • 28. THE ENDTHE END Scheme Logic ©2008 Beckwith Electric Co., Inc.