SlideShare a Scribd company logo
1 of 77
Download to read offline
Differential Relays
2.1 Differential Relay Settings Calculations MiCOM P63X
Relay Type: MICOM P63X
Required Data
Ratings of the Power and Current Transformers
MVA
Voltage Ratio
Rated Voltage in kV (HV Side)
Rated Voltage in kV (LV Side)
Vector Group
CT Ratio (HV Side)
CT HV Side Vector Group
CT Ratio (LV Side)
CT LV Side Vector Group
Minimum Tap = - %
Maximum Tap = +%
Rated Current (HV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Required Ratio Compensation = 1/ Current on CT secondary (HV)
Rated Current (LV Side) = MVA / (√3*kV)
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
Required Ratio Compensation = 1/ Current on CT Secondary (LV)
Relay current on LV side I2 = Current on CT secondary LV side / Ratio compensation for LV side
Calculations for OLTC tap setting -% and +%
Full load Current (- % or +% HV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Relay Current for HV side I1= Current on Ct secondary (HV)/ Ratio compensation for HV side
I1 is calculated for extreme transformer taps
The differential current is = I1-I2
Bias current I bias = (I1+I2)/2
Differential current I dif and Ibias is calculated foe extreme Transformer taps
Therefore the operating current of the relay
If Ibias < 2
= Is + m1* I bias
If Ibias > 2
= m2*( Ibias – 2)+ m1 * 2
Where m1 and m2 are the slope of relay char
Pick up setting is chosen such that the Differential current at worst tap condition should not be more than
90% of operating current for better stability
Substation Name : 220 kV GSS Debari
Relay Type: MICOM P633
Ratings of the Power and Current Transformers
Transformer Name: CROMPTON
MVA = 100
Voltage Ratio = 220/132/11
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNA0d11
CT Ratio (HV Side) = 300/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.4319 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.4319/300
=0.875 A
Required Ratio Compensation = 1/ 0.875
= 1.143 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.38 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.38 /500
= 0.875 A
Required Ratio Compensation = 1/ 0.875
=1.143 A
Calculations for OLTC tap setting -10%
Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.9*kV)
=100*10^6/ (√3*220*0.85*10^3)
=308.743 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.743 /300
=1.029 A
As the adopted ratio correction is 1.143 A the current to relay bias terminal
= 1.029 * 1.43
=1.176 A
Hence the differential current is = 1.176 – 1
= 0. 176 A
Bias current = (I1+I2)/2
= (1.176+1)/2
= 1.088 A
[Since the bias current is less than 1.5 A the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* I bias)
= 0.2 + (0.3 * 1.088)
= 0.526 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it s less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.15*kV)
=100*10^6/ (√3*220*1.10*10^3)
=238.54A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.54 /300
=0.795 A
As the adopted ratio correction is 1.143 A the current to relay bias terminal
= 0.795* 1.143
=0.909A
Hence the differential current is = 1 - 0.909
= 0.091 A
Bias current = (I1+I2)/2
= (0.909 +1)/2
= 0.955 A
[Since the bias current is less than 1.5 A the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* I bias)
= 0.2 + (0.3 * 0.93)
= 0.48 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it s less than 90% so the setting is acceptable.
2.2 Procedure for Relay Setting of Transformer Differential Relay MBCH
Data Required
MVA Rating
Voltage ratio
Vector group
CT ratio on HV Side
Winding connection of CT on HV side
ICT ratio on HV Side
Winding connection of ICT on HV side
CT ratio on LV Side
Winding connection of CT on LV side
Transformer Tap
Min -% OLTC Tap and max % OLTC tap
At Normal tap
Rated current (HV Side) = MVA / (3*Rated voltage (HV side))
Rated current (LV Side) = MVA / (3*Rated voltage (LV side))
If CT is Star/Star
Current on CT Secondary (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
If CT is Star/Delta the current shall be multiplied by 3.
Current on the secondary of ICT for Star/Star = Current on CT Secondary (HV Side) / ICT Ratio (HV
Side)
For Star/Delta the current shall be multiplied by 3.
The same procedure is followed for getting the relay current on LV side also.
Idiff = Relay Current = Difference between the HV and LV Current (Current at the secondary of ICT’s)
To make sure that the relay does not operate when the Transformer taps are changed the currents are
calculated at extreme taps.
At Tap on -%
Voltage corresponding to the above tap,
Full load current = MVA / 3 * Voltage corresponding to –ve tap.
At Tap on +%
Voltage corresponding to the above tap,
Full load current = MVA / 3 * Voltage corresponding to +ve tap.
Currents at the CT Secondary and ICT Secondary are calculated by using the above procedure. For
extreme +ve and extreme –ve tap.
Relay current I1= the difference between the HV and LV Currents for extreme +ive tap.
I2= The difference between the HV and LV Currents for extreme +ve tap.
MBCH has an adjustable basic threshold setting of 10% to 50% current I selectable in 10% steps.
Dual Slope – 20% Slope upto In.
- 80% Slope for Current > In.
Relay operating current = Pickup setting + Bias Setting * Bias current
Bias Current = (I1+I2)/2
I Operating 1A = Pickup setting + 0.20 * Bias Current less than 1A +0.8*current above 1A
Bias current = (I1+I2)/2
I Difference = I1- I2
Operating current at extreme taps is calculated with the same procedure.
The pick up setting is acceptable if the I operating is less than the bias current at extreme taps.
Differential Relay Settings Calculations
Substation Name: 220 kV GSS Debari
Relay Type: MBCH
Ratings of the Power and Current Transformer
MVA = 50
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNa0d1
CT Ratio (HV Side) = 150
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 300
CT LV Side Vector Group = Star/Star
CT Ratio (HV Side) = 150
CT Ratio (LV Side) = 300
Rated Current (HV Side) = MVA / (√3*kV)
=50*10^6/ (√3*220*10^3)
= 131.22 A
Rated Current (LV Side) = MVA / (√3*kV)
=50*10^6/ (√3*132*10^3)
= 218.6 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 131.22/150
= 0.87 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=218.6/300
= 0.73 A
Interposing CT (HV Side) = 0.87/0.58
Vector Group Interposing CT (HV Side) = Star/Delta
Interposing CT (LV Side) = 0.73/0.58
Vector Group Interposing CT (LV Side) = Star/Delta
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT
(HV Side))
=√3*(0.87/0.58)
=1.01
Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT
(LV Side))
=√3*(0.73/0.58)
=1.00
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
= 1.01-1.00
=0.01 A
Calculations for OLTC tap setting -12%
Full load Current for 220 kV %( HV Side) Winding at -12% = MVA / (√3*0.88*kV)
=50*10^6/ (√3*220*0.88*10^3)
= 149.11 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 149.11 /150
=0.99 A
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side))
=√3*(0.99 /(0.87/0.58))
=1.15 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT
Secondary (LV)
= 1.15 – 1.00
= 0.15 A
I bias = (I1+I2)/2
= (1.00 + 1.15)/2
=1.075 A
Consider the setting of Is = 0.1
The I Operating Current = 0.1 + (0.2 * 1) + (0.8*(1.075-1)
= 0.1 + 0.2 + 0.8*0.075
=0. 36A
At tap of -12% with full load the relay require a current of 0.36 A at Is = 0.1
Since I1-I2 = 0.15 which is less than relay operating value, relay will not operate.
So a setting Is = 0.1 is acceptable.
Calculations for OLTC tap setting +5%
Full load Current for 220 kV %( HV Side) Winding at +5% = MVA / (√3*1.05*kV)
=50*10^6/ (√3*220*1.05*10^3)
=124.97 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 124.97 /150
=0.83 A
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side))
=√3*(0.83 /(0.87/0.58))
=0.96 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary
= 1.00-0.96
= 0.04 A
I bias = (I1+I2)/2
= (0.96+1.00)/2
=0.98 A
Consider the setting of Is = 0.1
The I Operating Current = 0.1 + (0.2 * 0.98)
= 0.1 + 0.196
= 0.296 A
At tap of +5% with full load the relay require a current of 0.29 A at Is = 0.1
Since I1-I2 = 0.04 which is less than relay operating value, relay will not operate.
So a setting Is = 0.1 is acceptable.
2.3 Procedure for Relay Setting of Transformer Differential Relay KBCH
Data Required
MVA Rating
Voltage ratio
Vector group
HV voltage
LV voltage
Transformer percentage impedance:
Transformer vector group:
OLTC Tap: +% OLTC Tap: -%
CT ratio and winding configuration
HV side
LV side
At Normal tap
HV Side full load current = MVA / 3*kV
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
N1=Required ratio compensation = 1/ Ict sec
Assuming Relay current = 1A
N1 is set on the relay
Current on HV side = Current on CT secondary (HV)/ N1
At Normal tap low voltage side
LV Side full load current = MVA / (3*kV)
Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side)
N2=Required ratio compensation = 1/ Ict sec (LV)
N2 is set on the relay
Current on LV side = Current on CT secondary (LV)/N2
At -% Tap
HV side current = MVA / (3*kV
Where kV is the voltage corresponding to -% tap on HV side
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ict sec /N1
At Tap on +%
HV side current = MVA / (3*kV )
Where kV is the voltage corresponding to +% tap on HV side
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ict sec /N1
Differential current at extreme taps
At -% tap =Idiff1 =IHV-ILV
At +% tap =Idiff2 =IHV-ILV
Ibias = IHV+ILV /2
Operating current of Relay
I Operating = Pickup setting + 0.20 * Bias Current less than 1A +0.8*current above 1A
Relay Operating current current is calculated using the above equation.
For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will
not operate for extreme taps
Differential Relay Settings Calculations
Substation Name: 220 kV GSS Nagaur
Relay Type: KBCH (Areva)
Ratings of the Power and Current Transformers
Transformer Name: Transformer 2
MVA = 100
Voltage Ratio = 220/132 kV
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNa0d1
CT Ratio (HV Side) = 400/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 600/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43/400
=0.66 A
Required Ratio Compensation = 1/ 0.66
=1.52
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/600
= 0.73 A
Required Ratio Compensation = 1/ 0.73
=1.37 A
Calculations for OLTC tap setting -10%
Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
=308.74 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.74 /400
= 0.77 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.77 * 1.52
=1.18 A
Hence the differential current is = 1.18 – 1
= 0.18 A
Bias current = (I1+I2)/2
= (1.18+1)/2
= 1.09 A
[Since the bias current is less than 1.5 A the slope will be within 20%]
Therefore the operating current of the relay will be = Is + (0.2* I bias)
= 0.1 + (0.2 * 1.09)
= 0.37 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=100*10^6/ (√3*220*1.1*10^3)
= 237.26 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.57 /400
= 0.60 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.60 * 1.52
= 0.82 A
Hence the differential current is = 1 – 0.82
= 0.18 A
Bias current = (I1+I2)/2
= (0.82 +1)/2
= 0.91 A
[Since the bias current is less than 1.5 A the slope will be within 20%]
Therefore the operating current of the relay will be = Is + (0.2* I bias)
= 0.1 + (0.2 * 0.91)
= 0.28 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
2.4 Procedure for Relay Setting of Transformer Differential Relay DTH 31/32
Data Required
MVA Rating
Voltage ratio
Vector group
CT ratio on HV Side
Winding connection of CT on HV side
ICT ratio on HV Side
Winding connection of ICT on HV side
CT ratio on LV Side
Winding connection of CT on LV side
Transformer Tap
Min -% or OLTC Tap max +%
Rated current (HV Side) = MVA / (3*Rated voltage (HV side))
Rated current (LV Side) = MVA / (3*Rated voltage (LV side))
If CT is Star/Star
Current on CT Secondary (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
If CT is Star/Delta the current shall be multiplied by 3.
Current on the secondary of ICT for Star/Star = Current on CT Secondary (HV Side) / ICT Ratio (HV
Side)
For Star/Delta the current shall be multiplied by 3.
The same procedure is followed for getting the relay current on LV side also.
Idiff = Relay Current = Difference between the HV and LV Current (Current at the secondary of ICT’s)
To make sure that the relay does not operate when the Transformer taps are changed the currents are
calculated at extreme taps.
At Tap on -%
Voltage corresponding to the above tap,
Full load current = MVA / 3 * Voltage corresponding to –ve tap.
At Tap on +%
Voltage corresponding to the above tap,
Full load current = MVA / 3 * Voltage corresponding to +ve tap.
Currents at the CT Secondary and ICT Secondary are calculated by using the above procedure. For
extreme +ive and extreme –ive tap.
Relay current I1= The difference between the HV and LV Currents for extreme +ive tap.
I2= The difference between the HV and LV Currents for extreme +ive tap.
DTH 31 relay has a fixed pick up setting and variable single slope bias setting.
For setting the Bias Setting
The operating current of DTH 31 is given by the equation
Relay operating current = Pickup setting + Bias Setting * Bias current
The pickup setting in DTH 31 = 0.15 (constant)
Bias Current = (I1+I2)/2
Operating Current at normal tap with Bias setting Is = 0.15(or) 0.3
I Operating 1A = 0.15 + 0.15 * Bias Current
Bias current = (I1+I2)/2
I Difference 1A = I1- I2
Operating current at extreme taps is calculated with the same procedure.
Operating current at extreme taps is calculated with the same procedure.
Operating Current at extreme Minimum tap
I Operating 2A.
I Difference 2A = I1 – I2.
Operating Current at extreme Maximum tap
I Operating 3A.
I difference 3A = I1 – I2.
In each of the above cases IOperating current >IDifference + Tolerance
If the above is true a setting of 0.15 for bias is selected. In case the above is not true. Similar calculation is
carried out for the next Bias Setting.
Bhinmal Differential Relay Settings Calculations
Relay Type: DTH31
Station Name : 220 kV GSS Modak
Ratings of the Power and Current Transformers
Transformer Name: NGEF
MVA = 100
Voltage Ratio = 220/132 kV
Rated Voltage in kV (HV Side) = 220 kV
Rated Voltage in kV (LV Side) = 132 KV
Vector Group = YNyn0d1
CT Ratio (HV Side) = 300/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 600/1
CT LV Side Vector Group = Star/Star
ICT Ratio (HV Side) = 7.3/5
ICT Ratio (LV Side) = 3.6/2.89
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.4319 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.4319/300
=0.874 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/600
= 0.728 A
Interposing CT (HV Side) =
= 7.3/5
Vector Group Interposing CT (HV Side) = Star/Delta
Interposing CT (LV Side) = 3.65/2.89
Vector Group Interposing CT (LV Side) = Star/Delta
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT
(HV Side))
=√3*(0.656/1.128)
=1.03 A
Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT
(LV Side))
=√3*(0.728/1.261)
= 0.99 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) –
Current on ICT Secondary (LV)
= 1.03 – .99
=0.04
Calculations for OLTC tap setting -15%
Full load Current for 220 kV %( HV Side) Winding at -10% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
=308.743 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.74 /300
=1.029 A
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV
Side))
=√3*1.029=1.22 A
Current on ICT Secondary (LV) = 1.00 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
= 1.22- 1.00
= 0.22 A
Ibias = ( I1 + I2 ) /2
= ( 1.22+ 1 ) /2
= 1.11 A
Operating Current = Bias setting + Slope 1 * I bias
= 0.15 +0.15*1.11
= 0.3165 A
As Id= 0.22, Operating current = 0.31, Hence stable
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +15% = MVA / (√3*1.10*kV)
=100*10^6/ (√3*220*1.10*10^3)
= 238.57A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 228.20 /300
= 0.795 A
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV
Side))
=0.9434
Current on ICT Secondary (LV) = 1.00 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
=1- 0.9434
= 0.056 A
At Tap of -10 % I bias = (I1+I2)/2
= (1+0.9434)/2 A =0 .97 A
Consider a bias setting of Is = 0.30
The I Operating Current = 0.15 + Is * I bias
= 0.15 + 0.15* 0.97
=0.29 A
At tap of -10% with full load the relay require a current 0.47 A at Is = 0.30.
Since I1-I2 = 0.056 which is less than the operating value, relay will not operate.
So a setting Is = 0.30 is acceptable.
2.5 Differential Relay Settings Calculations RET 670
Differential Relay Settings Calculation Procedure
Relay Type: RET 670
Required Data
Ratings of the Power and Current Transformers
MVA
Voltage Ratio
Rated Voltage in kV (HV Side)
Rated Voltage in kV (LV Side)
Vector Group
CT Ratio (HV Side)
CT HV Side Vector Group
CT Ratio (LV Side)
CT LV Side Vector Group
CT resistance value (Rct)
Lead resistance value (Rl)
Minimum Tap = - %
Maximum Tap = +%
Rated Current (HV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Required Ratio Compensation = 1/ Current on CT secondary (HV)
Rated Current (LV Side) = MVA / (√3*kV)
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
Required Ratio Compensation = 1/ Current on CT Secondary (LV)
Relay current on LV side I2 = Current on CT secondary LV side / Ratio compensation for LV side
Calculations for OLTC tap setting -% and +%
Full load Current (- % or +% HV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Relay Current for HV side I1= Current on Ct secondary (HV)/ Ratio compensation for HV side
I1 is calculated for extreme transformer taps
The differential current is = I1-I2
Bias current I bias = (I1+I2)/2
Differential current I dif and Ibias is calculated foe extreme Transformer taps
Therefore the operating current of the relay
= Is + m1* I bias for current less than (4.Iref) + m2* Ibias for current greater than (4 Iref)
Where m1 and m2 are the slope of relay char
Pick up setting is chosen such that the Differential current at worst tap condition should not be more than
90% of operating current for better stability..
Sample Calculation for ABB RET 670
A) Biased Differential
Substation Name : 220 kV GSS Rajwest
Relay Type: ABB RET 670
Ratings of the Power and Current Transformers
Transformer Name: TELK
MVA = 315
Voltage Ratio = 400/220/33
Rated Voltage in kV (HV Side) = 400
Rated Voltage in kV (LV Side) = 220
Vector Group = YNA0d11
CT Ratio (HV Side) = 1000/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 1000/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -10
Maximum Tap = +15
Rated Current (HV Side) = MVA / (√3*kV)
=315*10^6/ (√3*400*10^3)
=454.66 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 454.66/1000
=0.454 A
Required Ratio Compensation = 1/ 0.454
= 2.199 A
Rated Current (LV Side) = MVA / (√3*kV)
=315*10^6/ (√3*220*10^3)
=826.66 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=826.66/1000
= 0.826 A
Required Ratio Compensation = 1/ 0.826
=1.209 A
Compensated current on LV side=√3*0.826/1.209
Calculations for OLTC tap setting -10%
Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=315*10^6/ (√3*400*0.85*10^3)
=534.89 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 534.89 /1000
=0.534 A
Inter posing CT (HV) winding = √3*Current on CT sec (HV)/Ratio correction factor
=√3*0.534/2.199
=0.421 A
Hence the differential current is = ABS (0.421– 1.183)
= 0. 762 A
Bias current = (I1+I2)/2
= (0.421+1.183)/2
= 0.802 A
[Since the bias current is less than 1.5 A the slope will be within 40%]
Therefore the operating current of the relay will be = Is + (1.5* M1)+M2*Ibias
= 0.1 + (0.4 * 1.5)*0.8*0.697
= 1.25 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it s less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=315*10^6/ (√3*400*1.1*10^3)
=413.33 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 413.33 /1000
=0.413 A
Interposing HV winding current=√3*0.413/2.199
=0.325
I bias = (interposing CT HV current side+ Interposed LV side CT current side)/2
= (0.325+1.183)/2
= 0.754 A
Hence the differential current is = 1.183-0.325
= 0.858 A
[Since the bias current is less than 1.5 A the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (m1+m2)* I bias
= 0.1 + (0.4 +0.8) * 0.754
= 1.01 A
The operating value is larger than the differential value hence the system is Stable for the MAX tap
condition.
B) High Impedance Differential
Substation Name : 220 kV GSS Rajwest
Relay Type: ABB RET 670
Ratings of the Power and Current Transformers
Transformer Name: TELK
MVA = 315
Voltage Ratio = 400/220/33
Rated Voltage in kV (HV Side) = 400
Rated Voltage in kV (LV Side) = 220
Vector Group = YNA0d11
% Impedance of the transformer=0.1198
CT Ratio (HV Side) = 1000/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 1000/1
CT LV Side Vector Group = Star/Star
CT resistance (Rct) =4Ω
Lead Resistance value=1.5 Ω
Rated Current (HV Side) = MVA / (√3*kV)
=315*10^6/ (√3*400*10^3)
=454.66 A
Maximum fault current contributed =Rated current /Percentage Impedance
=454.66/0.1198
=3795.15 A
Maximum fault current contributed secondary=3795.15/1000
= 3.795 A
Operating Voltage =3.795*(4+2*1.5)
=26.57V
Rstab = 250Ω
Stabilizing resistance value (Rstab) to be set as per the operating voltage range given in the technical
reference manual table provided by the manufacturer.
2.6 Procedure for Relay setting of Transformer Differential Relay ABB RADSB
Substation : 220kV GSS Dausa
Tranformer Name : CGL
Relay Type: RADSB [ABB]
Data Required
MVA Rating
Voltage ratio
Vector group
CT ratio on HV Side
Winding connection of CT on HV side
ICT ratio on HV Side
Winding connection of ICT on HV side
CT ratio on LV Side
Winding connection of CT on LV side
Transformer Tap
Min -% OLTC Tap and max % OLTC tap
Calculation
Rated Current (HV Side) = MVA / (√3*kV)
Rated Current (LV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
Interposing CT (HV Side) = Current on CT Secondary (HV) / ICT ratio on HV side
Interposing CT (LV Side) = Current on CT Secondary (LV) /0.578
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT
(HV Side))
Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT
(LV Side))
Difference between HV side and LV side currents = Current on ICT Secondary (HV) –
Current on ICT Secondary (LV)
Calculations for OLTC tap setting -%
Voltage corresponding to the above tap,
Full load current = MVA / 3 * Voltage corresponding to –ve tap.
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Current on ICT Secondary (HV) in A
= √3*(Current on CT Secondary (HV)/ Interposing CT
(HVSide))
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
Calculations for OLTC tap setting +%
Voltage corresponding to the above tap,
Full load current = MVA / 3 * Voltage corresponding to +ve tap.
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Current on ICT Secondary (HV) in A = √3*(Current on CT Secondary (HV)/ Interposing
CT (HVSide))
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
Relay setting range available : Operating value can be Settable 20, 25, 35, or 50% of In
Id = (I1-I2)
Ibias = ( I1+I2)/2
Operating current = 0.25+ Slope1 setting * I bias
Id should be less than I operating current
The setting shall be selected in such a way that the relay shall not operate for the extreme tap
positions
Differential Relay Settings Calculations
Relay Type: RADSB [ABB]
Substation : 220kV GSS Dausa
Tranformer Name : CGL
Ratings of the Power and Current Transformers
Transformer Name: CGL
MVA = 100
Voltage Ratio = 220/132kV
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YnYa0
CT Ratio (HV Side) = 300/5
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 600/5
CT LV Side Vector Group = Star/Star
ICT Ratio (HV Side) = 4.37/2.88
ICT Ratio (LV Side) = 3.64/2.88
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.4319 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
= 437.39A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.4319/(300/5)
= 4.37 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/(600/5)
= 3.64 A
Interposing CT (HV Side) = 4.37/2.88
= 1.517
Interposing CT (LV Side) = 3.64/2.88
=1.263
Current on ICT Secondary (HV) = (Current on CT Secondary (HV)*Interposing CT
(HV Side))
=4.37/(4.37 /2.88)
= 2.88 A
Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT
(LV Side))
=3.64/(3.64/1.263)
=2.88 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) –
Current on ICT Secondary (LV)
= 4.9891 – 4.9916
= 0.0019606708 A
Calculations for OLTC tap setting -15%
Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
=308.74 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.74/(300/5)
=5.15 A
Current on ICT Secondary (HV) = (Current on CT Secondary (HV)/ Interposing CT (HV side )
=5.15/(4.862 /1.517)
=3.39 A
Current on ICT Secondary (LV) =(Current on CT Secondary (HV)/ Interposing CT (HV side)
= 2.88 A
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
= 3.39-2.88
= 0.51 A
I bias = ( I1+I2)/2 = (3.39+2.88)/2 = 3.34
Operating current = 0.25+0.2*3.34 = 0.88 A
Id = 0.51 is less than I operating = 0.88, hence stable
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=100*10^6/ (√3*220*1.1*10^3)
= 238.57 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.57 /(300/5)
=3.98 A
Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV
Side))
=3.98/(3.954 / 1.517)
=2.62 A
Current on ICT Secondary (LV) = 2.88
Difference between HV side and LV side currents = Current on ICT Secondary (HV) -
Current on ICT Secondary (LV)
= 2.88-2.62
= 0.26
I bias =( I1+I2) /2
= ( 2.88+2.62) /2 = 2.75 A
I operating = 0.25 + 0.2* 2.75 = 0.8 A
Id= 0.26 is less than I operating = 0.8 A, hence stable
2.7 Procedure for Relay Setting of Transformer Differential Relay GE T60
Data Required
MVA Rating
Voltage ratio
Vector group
HV voltage
LV voltage
Transformer percentage impedance:
Transformer vector group:
OLTC Tap: +% OLTC Tap: -%
CT ratio and winding configuration
HV side
LV side
At Normal tap
HV Side full load current = MVA / 3*kV
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
N1=Required ratio compensation = 1/ Ict sec
Assuming Relay current = 1A
N1 is set on the relay
Current on HV side = Current on CT secondary (HV)/ N1
At Normal tap low voltage side
LV Side full load current = MVA / (3*kV)
Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side)
N2=Required ratio compensation = 1/ Ict sec (LV)
N2 is set on the relay
Current onLV side = Current on CT secondary (LV)/N2
At -% Tap
HV side current = MVA / (3*kV
Where kV is the voltage corresponding to -% tap on HV side
Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
At Tap on +%
HV side current = MVA / (3*kV )
Where kV is the voltage corresponding to +% tap on HV side
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
Differential current at extreme taps
At -% tap =Idiff1 =IHV-ILV
At +% tap =Idiff2 =IHV-ILV
Ibias = IHV+ILV
Operating current of Relay
I Operating = Pickup setting + 0.3 * Bias Current for Bias current less than Break Point
I Operating = Pickup setting + 0.3 * Bias Current + 0.8 (Bias current – Break point) for Bias current greater
than Break point.
Relay Operating current current is calculated using the above equation.
For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will
not operate for extreme taps.
Differential Relay Settings Calculations
Substation Name: 220 kV GSS Kushkhera
Relay Type: GE T60
Ratings of the Power and Current Transformers
Differential Current Setting = 0.25 A
Break Point = 2
Slope1 = 0.3
Slope 2= 0.8
Transformer Name: IMP
MVA = 100
Voltage Ratio = 220/132 kV
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNa0d1
CT Ratio (HV Side) = 400/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43/400
=0.66 A
Required Ratio Compensation = 1/ 0.66
=1.52
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.874 A
Required Ratio Compensation = 1/ 0.874
=1.143 A
Calculations for OLTC at Nominal tap setting
Full load Current for 220 kV %( HV Side) Winding = MVA / (√3*0.9*kV)
=100*10^6/ (√3*220*10^3)
= 262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43 /400
= 0.656 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.656 * 1.52
Compensated current internally = 0.9972 A
Hence the differential current is = 0.9972 – 1
= 0.0027A
Bias current = Max (I1, I2)
= (0.9972, 1)
= 1 A
[Since the bias current is less than Break point (2) the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* I bias)
= 0.25 + (0.3* 0.9972)
= 0.549 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting -15%
Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
= 308.74 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.74 /400
= 0.772 A
As the adopted compensation is 1.33 A the current to relay bias terminal
= 0.772 * 1.33
Compensated current internally =1.029 A
Hence the differential current is = 1.029 – 0.87
= 0.15 A
Bias current = Maximum of (I1, I2)
= Maximum of (1.029, 0.87)
= 1.029 A
[Since the bias current is less than Break point (2) the slope will be within 25%]
Therefore the operating current of the relay will be = Is + (0.2* I bias)
= 0.25 + (0.3 *1.029)
= 0.558 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=100*10^6/ (√3*220*1.1*10^3)
= 238.57A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.57 /400
= 0.5964 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.596 * 1.52
Compensated current internally = 0.905 A
Hence the differential current is = 1-0.905
= 0.095 A
Bias current = Maximum of (I1, I2)
= Maximum of (0.905, 1)
= 1 A
[Since the bias current is less than Break point (2) the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* I bias)
= 0.25 + (0.3 * 1)
= 0.55 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
2.8 Procedure for Relay Setting of Transformer Differential Relay CSC326
Data Required
MVA Rating
Voltage ratio
Vector group
HV voltage
LV voltage
Transformer percentage impedance:
Transformer vector group:
OLTC Tap: +% OLTC Tap: -%
CT ratio and winding configuration
HV side
LV side
At Normal tap
HV Side full load current = MVA / 3*kV
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
N1=Required ratio compensation = 1/ Ict sec
Assuming Relay current = 1A
N1 is set on the relay
Current on HV side = Current on CT secondary (HV)/ N1
At Normal tap low voltage side
LV Side full load current = MVA / (3*kV)
Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side)
N2=Required ratio compensation = 1/ Ict sec (LV)
N2 is set on the relay
Current onLV side = Current on CT secondary (LV)/N2
At -% Tap
HV side current = MVA / (3*kV
Where kV is the voltage corresponding to -% tap on HV side
Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
At Tap on +%
HV side current = MVA / (3*kV )
Where kV is the voltage corresponding to +% tap on HV side
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
Differential current at extreme taps
At -% tap =Idiff1 =IHV-ILV
At +% tap =Idiff2 =IHV-ILV
Ibias = IHV+ILV
Operating current of Relay
I Operating = Pickup setting + 0 * Bias Current if less than 0.656
I Operating = Pickup setting + (0.3 * Bias Current -0.656) if greater than 0.656
I Operating = Pickup setting + 0.7 * (Bias Current-4) + 0.3*4
Relay Operating current current is calculated using the above equation.
For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will
not operate for extreme taps.
Differential protection characteristics for transformers:
Differential Relay Settings Calculations
Substation Name: 220 kV GSS Bharathpur
Relay Type: CSC326
Ratings of the Power and Current Transformers
Differential Current Setting = 0.2 A
Transformer Name: CGL
MVA = 100
Voltage Ratio = 220/132 kV
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNa0d1
CT Ratio (HV Side) = 400/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43/400
=0.66 A
Required Ratio Compensation = 1/ 0.66
=1.52
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.8747 A
Required Ratio Compensation = 1/0.8747
= 1.143 A
Calculations for OLTC Nominal tap setting:
Full load Current for 220 kV %( HV Side) Winding at = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3*)
= 262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43 /400
= 0.656 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.656 * 1.52
= 0.997 A
Compensated current internally on HV =0.997 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.8747 A
Required Ratio Compensation = 1/0.8747
= 1.143 A
Compensated current on LV = 0.8747 * 1.143
= 0.9993
Hence the differential current is = (0.9973 – 0.9993 )
= 0.002 A
Bias current = (I1+I2)/2
= (0.656+0.8747)/2
= 0.765 A
[Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656)
= 0.2 + (0.3 *0.109)
= 0.232 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting -15%
Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
= 308.74 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.74 /400
= 0.772 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.772 * 1.52
= 1.18 A
Compensated current internally on HV =1.18 A
Hence the differential current is = (1.18– 1.0 )
= 0.18 A
Bias current = (I1+I2)/2
= (1.18+1)/2
= 1.09 A
[Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656)
= 0.2 + (0.3 *0.434)
= 0.33 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=100*10^6/ (√3*220*1.1*10^3)
= 238.5 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.574 /400
= 0.596 A
As the adopted ratio correction is 1 A the current to relay bias terminal
= 0.596 * 1.52
Compensated current internally = 0.905 A
Differential current = I1- I2 = 1-0.905 = 0.095 A
Bias current = (I1+I2)/2
= (0.905 +1)/2
= 0.952 A
[Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656)
= 0.2 + (0.3*(0.952- 0.656))
= 0.288 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable
2.9 Procedure for Relay Setting of Transformer Differential Relay DUOBIAS
Data Required
MVA Rating
Voltage ratio
Vector group
HV voltage
LV voltage
Transformer percentage impedance:
Transformer vector group:
OLTC Tap: +% OLTC Tap: -%
CT ratio and winding configuration
HV side
LV side
At Normal tap
HV Side full load current = MVA / 3*kV
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
N1=Required ratio compensation = 1/ Ict sec
Assuming Relay current = 1A
N1 is set on the relay
Current on HV side = Current on CT secondary (HV)/ N1
At Normal tap low voltage side
LV Side full load current = MVA / (3*kV)
Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side)
N2=Required ratio compensation = 1/ Ict sec (LV)
N2 is set on the relay
Current onLV side = Current on CT secondary (LV)/N2
At -% Tap
HV side current = MVA / (3*kV
Where kV is the voltage corresponding to -% tap on HV side
Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
At Tap on +%
HV side current = MVA / (3*kV )
Where kV is the voltage corresponding to +% tap on HV side
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
Differential current at extreme taps
At -% tap =Idiff1 =IHV-ILV
At +% tap =Idiff2 =IHV-ILV
Ibias = IHV+ILV
Operating current of Relay
I Operating = Pickup setting + 0 * Bias Current if less than 0.656
I Operating = Pickup setting + (0.3 * Bias Current -0.656) if greater than 0.656
I Operating = Pickup setting + 0.7 * (Bias Current-4) + 0.3*4
Relay Operating current current is calculated using the above equation.
For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will
not operate for extreme taps.
Differential protection characteristics for transformers:
Differential Relay Settings Calculations
Substation Name: 220 kV GSS Neemrana
Relay Type: DUOBIAS
Ratings of the Power and Current Transformers
Differential Current Setting = 0.25 A
Transformer Name: CGL
MVA = 100
Voltage Ratio = 220/132 kV
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNa0d1
CT Ratio (HV Side) = 400/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43/400
=0.66 A
Required Ratio Compensation = 1/ 0.66
=1.52
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.8747 A
Required Ratio Compensation = 1/0.8747
= 1.143 A
Calculations for OLTC Nominal tap setting:
Full load Current for 220 kV ( HV Side) Winding = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3*)
= 262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43 /400
= 0.656 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.656 * 1.52* √3
= 1.727 A
Compensated current internally on HV = 1.727 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.8747 A
Required Ratio Compensation = 1/0.8747
= 1.143 A
Compensated current on LV = 0.8747 * 1.143
= 1
Hence the differential current is = (1 – 1 )
= 0 A
Bias current = (I1+I2)/2
= (1+1)/2
= 1 A
[Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* ( I bias)
= 0.2 + (0.3*1)
= 0.5A
Calculations for OLTC tap setting -15%
Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
= 308.743 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.743 /400
= 0.771 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.771 * 1.52
= 0.888 A
Compensated current internally on HV =0.888 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.8747 A
Required Ratio Compensation = 1/0.8747
= 1.143 A
Compensated current on LV = 0.874* 1.143
= 0.998 A
Hence the differential current is = (1.0-0.888)
= 0.12 A
Bias current = (I1+I2)/2
= (0.888+1)/2
= 0.944 A
[Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%]
Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656)
= 0.2 + (0.3 *0.28)
= 0.284 A
Id= 0.12 is less than I operating current = 0.284 A, hence Stable
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=100*10^6/ (√3*220*1.1*10^3)
= 238.5 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.5 /400
= 0.56 A
As the adopted ratio correction is 1 A the current to relay bias terminal
= 0.56 * 1.52
Compensated current internally = 0.8512 A
Compensated current internally on LV = 0.851*1.143
= 1 A
Hence the differential current is = 1-0.8512
= 0.1488 A
Bias current = (I1+I2)/2
= (1 +0.1488)/2
= 0.574 A
[Since the bias current is less than 0.656 the slope will be zero.
Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656)
= 0.2 + (0.3*(0.574))
= 0.2A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
2.10 Procedure for Relay Setting of Transformer Differential Relay
7UT61X/7UT51X
Data Required
MVA Rating
Voltage ratio
Vector group
HV voltage
LV voltage
Transformer percentage impedance:
Transformer vector group:
OLTC Tap: +% OLTC Tap: -%
CT ratio and winding configuration
HV side
LV side
At Normal tap
HV Side full load current = MVA / 3*kV
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
N1=Required ratio compensation = 1/ Ict sec
Assuming Relay current = 1A
N1 is set on the relay
Current on HV side = Current on CT secondary (HV)/ N1
At Normal tap low voltage side
LV Side full load current = MVA / (3*kV)
Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side)
N2=Required ratio compensation = 1/ Ict sec (LV)
N2 is set on the relay
Current onLV side = Current on CT secondary (LV)/N2
At -% Tap
HV side current = MVA / (3*kV
Where kV is the voltage corresponding to -% tap on HV side
Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
At Tap on +%
HV side current = MVA / (3*kV )
Where kV is the voltage corresponding to +% tap on HV side
Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side)
With ratio compensation
Current on CT Secondary =Ratio of compensation * CT secondary current
Differential current at extreme taps
At -% tap =Idiff1 =IHV-ILV
At +% tap =Idiff2 =IHV-ILV
Ibias = IHV+ILV
Operating current of Relay
I Operating = Pickup setting + 0.25 * Bias Current if less than 2.5A
I Operating = Pickup setting + 0.25 * Bias Current + 0.5 ( Bias current above 2.5 A )
Relay Operating current is calculated using the above equation.
For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will
not operate for extreme taps
Differential Relay Settings Calculations
Substation Name: 220 kV GSS Nagaur
Relay Type: SIPROTECH 7UT61X
Ratings of the Power and Current Transformers
Differential Current Setting = 0.2 A
Transformer Name: BHEL -II
MVA = 100
Voltage Ratio = 220/132 kV
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNa0d1
CT Ratio (HV Side) = 400/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.43 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.43/400
=0.66 A
Required Ratio Compensation = 1/ 0.66
=1.52
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.39 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.39/500
= 0.73 A
Required Ratio Compensation = 1/ 0.73
=1.14 A
Calculations for OLTC tap setting -10%
Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.9*kV)
=100*10^6/ (√3*220*0.85*10^3)
= 308.74 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.74 /400
= 0.77 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.77 * 1.52
Compensated current internally =1.18 A
Hence the differential current is = 1.18 – 1
= 0.18 A
Bias current = (I1+I2)
= (1.18 +1)
= 2.18 A
[Since the bias current is less than 2.5 A the slope will be within 25%]
Therefore the operating current of the relay will be = Is + (0.5* I bias)
= 0.2 + (0.25 *2.18)
= 0.74 A
Differential current at w tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV)
=100*10^6/ (√3*220*1.1*10^3)
= 238.5 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.5 /400
= 0.60 A
As the adopted ratio correction is 1.52 A the current to relay bias terminal
= 0.60 * 1.14
Compensated current internally = 0.68 A
Hence the differential current is = 1 – 0.68
= 0.32 A
Bias current = (I1+I2)
= (0.68 +1)
= 1.68 A
[Since the bias current is less than 2.5 A the slope will be within 25%]
Therefore the operating current of the relay will be = Is + (0.25* I bias)
= 0.2 + (0.25 * 1.68)
= 0.62 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it is less than 90% so the setting is acceptable.
2.11 Differential Relay Settings Calculations GE SR745
Relay Type: GE SR745
Required Data
Ratings of the Power and Current Transformers
MVA
Voltage Ratio
Rated Voltage in kV (HV Side)
Rated Voltage in kV (LV Side)
Vector Group
CT Ratio (HV Side)
CT HV Side Vector Group
CT Ratio (LV Side)
CT LV Side Vector Group
Minimum Tap = - %
Maximum Tap = +%
Break point
Rated Current (HV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Required Ratio Compensation = 1/ Current on CT secondary (HV)
Rated Current (LV Side) = MVA / (√3*kV)
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
Required Ratio Compensation = 1/ Current on CT Secondary (LV)
Relay current on LV side I2 = Current on CT secondary LV side * Ratio compensation for LV side
Calculations for OLTC tap setting -% and +%
Full load Current (- % or +% HV Side) = MVA / (√3*kV)
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
Relay Current for HV side I1= Current on Ct secondary (HV)* Ratio compensation for HV side
I1 is calculated for extreme transformer taps
The differential current is = I1-I2
Bias current I bias = Maximum of(I1,I2)
Differential current I dif andIbias is calculated foe extreme Transformer taps
Therefore the operating current of the relay
= Is + Slope1* I bias for I bias current less than Break point And Is + Slope1*Break point + Slope2* (Ibias-
Break point) for I biascurrent greater than Break point.
Pick up setting is chosen such that the Differential current at worst tap condition should not be more than
90% of operating current for better stability.
Sample Calculation of GE SR 745
Substation Name : 220 kV GSS Khinwasar
Relay Type: GE SR745
Ratings of the Power and Current Transformers
Transformer Name: EMCO
MVA = 100
Voltage Ratio = 220/132
Rated Voltage in kV (HV Side) = 220
Rated Voltage in kV (LV Side) = 132
Vector Group = YNA0d1
CT Ratio (HV Side) = 400/1
CT HV Side Vector Group = Star/Star
CT Ratio (LV Side) = 500/1
CT LV Side Vector Group = Star/Star
Minimum Tap = -15
Maximum Tap = +10
Break point=2
Is=0.2, m1=25%, m2=80%
Rated Current (HV Side) = MVA / (√3*kV)
=100*10^6/ (√3*220*10^3)
=262.4319 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 262.4319/400
=0.65607 A
Required Ratio Compensation = 1/ 0.65607
= 1.5242 A
Rated Current (LV Side) = MVA / (√3*kV)
=100*10^6/ (√3*132*10^3)
=437.38 A
Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
=437.38 /500
= 0.875 A
Required Ratio Compensation = 1/ 0.875
=1.143 A
As the adopted ratio correction is 1.143 A the current to relay bias terminal
= 0.875 * 1.143
I1=1 A
Calculations for OLTC tap setting -15%
Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV)
=100*10^6/ (√3*220*0.85*10^3)
=308.743 A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 308.743 /400
=0.7719 A
As the adopted ratio correction is 1.5242 A the current to relay bias terminal
= 0.7719 * 1.5242
I2=1.176 A
Hence the differential current is = (I1-I2) =1.176 – 1
= 0. 176 A
Bias currentIbias = Max(I1,I2)
= (1.176,1)
= 1.176 A
[Since the bias current is less than Break point the slope will be within 25%]
Therefore the operating current of the relay will be = Is + (0.25* I bias)
= 0.2 + (0.25 * 1.176)
= 0.494 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it s less than 90% so the setting is acceptable.
Calculations for OLTC tap setting +10%
Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.15*kV)
=100*10^6/ (√3*220*1.1*10^3)
=238.574A
Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
= 238.574 /400
=0.5964 A
As the adopted ratio correction is 1.5242 A the current to relay bias terminal
= 0.5964* 1.5242
I2=0.909 A
Hence the differential current is= (I1-I2) = 1 - 0.909
= 0.091 A
Bias current Ibias = Max(I1,I2)
= (1, 0.909)
= 1 A
[Since the bias current is less than Break point the slope will be within 25%]
Therefore the operating current of the relay will be = Is + (0.25* I bias)
= 0.2 + (0.25 * 1)
= 0.45 A
Differential current at worst tap condition should not be more than 90% of operating current for better
stability. Here it s less than 90% so the setting is acceptable.

More Related Content

What's hot

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformerKapil Singh
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformerSantu Mondal
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxMUHAMMAD TAHIR
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protectionmichaeljmack
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level CalculationDinesh Sarda
 
Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settingsH. Kheir
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformervikasgupta1965
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformersZiyaulhaq
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 

What's hot (20)

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformer
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformer
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
 
testing formats
testing formatstesting formats
testing formats
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settings
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Transformer
TransformerTransformer
Transformer
 

Similar to Sample calculation-for-differential-relays

Chapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfChapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfLiewChiaPing
 
CURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxCURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxManishPandya29
 
controlled Full Bridge Rectifier
controlled Full Bridge Rectifiercontrolled Full Bridge Rectifier
controlled Full Bridge RectifierJen Trần
 
A presentation on inverter by manoj
A presentation on inverter by manojA presentation on inverter by manoj
A presentation on inverter by manojIACM SmartLearn Ltd.
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6Nageswar Rao
 
Unit-5 AC-AC Cycloconverter
Unit-5 AC-AC CycloconverterUnit-5 AC-AC Cycloconverter
Unit-5 AC-AC Cycloconverterjohny renoald
 
Power system safety and protection
Power system safety and protectionPower system safety and protection
Power system safety and protectionHakim Futra
 
Chapter two Part two.pptx
Chapter two Part two.pptxChapter two Part two.pptx
Chapter two Part two.pptxAbdalleAidrous
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculationsmichaeljmack
 
Space Vector Modulation(SVM) Technique for PWM Inverter
Space Vector Modulation(SVM) Technique for PWM InverterSpace Vector Modulation(SVM) Technique for PWM Inverter
Space Vector Modulation(SVM) Technique for PWM InverterPurushotam Kumar
 
Power Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPower Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPoornima D
 
Flexible Alternating Transmission Systems
Flexible Alternating Transmission SystemsFlexible Alternating Transmission Systems
Flexible Alternating Transmission SystemsGUNDEMADHURI
 
Transient response of RC , RL circuits with step input
Transient response of RC , RL circuits  with step inputTransient response of RC , RL circuits  with step input
Transient response of RC , RL circuits with step inputDr.YNM
 
Rectifiers (ac dc)
Rectifiers (ac dc) Rectifiers (ac dc)
Rectifiers (ac dc) Taimur Ijaz
 

Similar to Sample calculation-for-differential-relays (20)

Chapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfChapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdf
 
CURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxCURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptx
 
controlled Full Bridge Rectifier
controlled Full Bridge Rectifiercontrolled Full Bridge Rectifier
controlled Full Bridge Rectifier
 
A presentation on inverter by manoj
A presentation on inverter by manojA presentation on inverter by manoj
A presentation on inverter by manoj
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
 
Unit-5 AC-AC Cycloconverter
Unit-5 AC-AC CycloconverterUnit-5 AC-AC Cycloconverter
Unit-5 AC-AC Cycloconverter
 
Power system safety and protection
Power system safety and protectionPower system safety and protection
Power system safety and protection
 
Chapter two Part two.pptx
Chapter two Part two.pptxChapter two Part two.pptx
Chapter two Part two.pptx
 
Ppt 2
Ppt 2Ppt 2
Ppt 2
 
Bridge rectifier
Bridge rectifierBridge rectifier
Bridge rectifier
 
Converters
ConvertersConverters
Converters
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
 
Space Vector Modulation(SVM) Technique for PWM Inverter
Space Vector Modulation(SVM) Technique for PWM InverterSpace Vector Modulation(SVM) Technique for PWM Inverter
Space Vector Modulation(SVM) Technique for PWM Inverter
 
transformers
 transformers transformers
transformers
 
Power Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPower Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptx
 
Flexible Alternating Transmission Systems
Flexible Alternating Transmission SystemsFlexible Alternating Transmission Systems
Flexible Alternating Transmission Systems
 
Transient response of RC , RL circuits with step input
Transient response of RC , RL circuits  with step inputTransient response of RC , RL circuits  with step input
Transient response of RC , RL circuits with step input
 
Lm331
Lm331Lm331
Lm331
 
B1103021427
B1103021427B1103021427
B1103021427
 
Rectifiers (ac dc)
Rectifiers (ac dc) Rectifiers (ac dc)
Rectifiers (ac dc)
 

Recently uploaded

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 

Recently uploaded (20)

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 

Sample calculation-for-differential-relays

  • 2. 2.1 Differential Relay Settings Calculations MiCOM P63X Relay Type: MICOM P63X Required Data Ratings of the Power and Current Transformers MVA Voltage Ratio Rated Voltage in kV (HV Side) Rated Voltage in kV (LV Side) Vector Group CT Ratio (HV Side) CT HV Side Vector Group CT Ratio (LV Side) CT LV Side Vector Group Minimum Tap = - % Maximum Tap = +% Rated Current (HV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Required Ratio Compensation = 1/ Current on CT secondary (HV) Rated Current (LV Side) = MVA / (√3*kV) Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
  • 3. Required Ratio Compensation = 1/ Current on CT Secondary (LV) Relay current on LV side I2 = Current on CT secondary LV side / Ratio compensation for LV side Calculations for OLTC tap setting -% and +% Full load Current (- % or +% HV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Relay Current for HV side I1= Current on Ct secondary (HV)/ Ratio compensation for HV side I1 is calculated for extreme transformer taps The differential current is = I1-I2 Bias current I bias = (I1+I2)/2 Differential current I dif and Ibias is calculated foe extreme Transformer taps Therefore the operating current of the relay If Ibias < 2 = Is + m1* I bias If Ibias > 2 = m2*( Ibias – 2)+ m1 * 2 Where m1 and m2 are the slope of relay char Pick up setting is chosen such that the Differential current at worst tap condition should not be more than 90% of operating current for better stability Substation Name : 220 kV GSS Debari Relay Type: MICOM P633 Ratings of the Power and Current Transformers Transformer Name: CROMPTON MVA = 100
  • 4. Voltage Ratio = 220/132/11 Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNA0d11 CT Ratio (HV Side) = 300/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 500/1 CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.4319 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.4319/300 =0.875 A Required Ratio Compensation = 1/ 0.875 = 1.143 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.38 A
  • 5. Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.38 /500 = 0.875 A Required Ratio Compensation = 1/ 0.875 =1.143 A Calculations for OLTC tap setting -10% Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.9*kV) =100*10^6/ (√3*220*0.85*10^3) =308.743 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.743 /300 =1.029 A As the adopted ratio correction is 1.143 A the current to relay bias terminal = 1.029 * 1.43 =1.176 A Hence the differential current is = 1.176 – 1 = 0. 176 A Bias current = (I1+I2)/2 = (1.176+1)/2 = 1.088 A [Since the bias current is less than 1.5 A the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* I bias)
  • 6. = 0.2 + (0.3 * 1.088) = 0.526 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it s less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.15*kV) =100*10^6/ (√3*220*1.10*10^3) =238.54A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.54 /300 =0.795 A As the adopted ratio correction is 1.143 A the current to relay bias terminal = 0.795* 1.143 =0.909A Hence the differential current is = 1 - 0.909 = 0.091 A Bias current = (I1+I2)/2 = (0.909 +1)/2 = 0.955 A [Since the bias current is less than 1.5 A the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* I bias) = 0.2 + (0.3 * 0.93) = 0.48 A
  • 7. Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it s less than 90% so the setting is acceptable. 2.2 Procedure for Relay Setting of Transformer Differential Relay MBCH Data Required MVA Rating Voltage ratio Vector group CT ratio on HV Side Winding connection of CT on HV side ICT ratio on HV Side Winding connection of ICT on HV side CT ratio on LV Side Winding connection of CT on LV side Transformer Tap Min -% OLTC Tap and max % OLTC tap At Normal tap Rated current (HV Side) = MVA / (3*Rated voltage (HV side)) Rated current (LV Side) = MVA / (3*Rated voltage (LV side)) If CT is Star/Star Current on CT Secondary (HV) = Rated Current (HV Side) / CT Ratio (HV Side) If CT is Star/Delta the current shall be multiplied by 3.
  • 8. Current on the secondary of ICT for Star/Star = Current on CT Secondary (HV Side) / ICT Ratio (HV Side) For Star/Delta the current shall be multiplied by 3. The same procedure is followed for getting the relay current on LV side also. Idiff = Relay Current = Difference between the HV and LV Current (Current at the secondary of ICT’s) To make sure that the relay does not operate when the Transformer taps are changed the currents are calculated at extreme taps. At Tap on -% Voltage corresponding to the above tap, Full load current = MVA / 3 * Voltage corresponding to –ve tap. At Tap on +% Voltage corresponding to the above tap, Full load current = MVA / 3 * Voltage corresponding to +ve tap. Currents at the CT Secondary and ICT Secondary are calculated by using the above procedure. For extreme +ve and extreme –ve tap. Relay current I1= the difference between the HV and LV Currents for extreme +ive tap. I2= The difference between the HV and LV Currents for extreme +ve tap. MBCH has an adjustable basic threshold setting of 10% to 50% current I selectable in 10% steps. Dual Slope – 20% Slope upto In. - 80% Slope for Current > In. Relay operating current = Pickup setting + Bias Setting * Bias current
  • 9. Bias Current = (I1+I2)/2 I Operating 1A = Pickup setting + 0.20 * Bias Current less than 1A +0.8*current above 1A Bias current = (I1+I2)/2 I Difference = I1- I2 Operating current at extreme taps is calculated with the same procedure. The pick up setting is acceptable if the I operating is less than the bias current at extreme taps. Differential Relay Settings Calculations Substation Name: 220 kV GSS Debari Relay Type: MBCH Ratings of the Power and Current Transformer MVA = 50 Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNa0d1 CT Ratio (HV Side) = 150 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 300 CT LV Side Vector Group = Star/Star CT Ratio (HV Side) = 150 CT Ratio (LV Side) = 300 Rated Current (HV Side) = MVA / (√3*kV)
  • 10. =50*10^6/ (√3*220*10^3) = 131.22 A Rated Current (LV Side) = MVA / (√3*kV) =50*10^6/ (√3*132*10^3) = 218.6 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 131.22/150 = 0.87 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =218.6/300 = 0.73 A Interposing CT (HV Side) = 0.87/0.58 Vector Group Interposing CT (HV Side) = Star/Delta Interposing CT (LV Side) = 0.73/0.58 Vector Group Interposing CT (LV Side) = Star/Delta Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =√3*(0.87/0.58) =1.01 Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT (LV Side)) =√3*(0.73/0.58)
  • 11. =1.00 Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) = 1.01-1.00 =0.01 A Calculations for OLTC tap setting -12% Full load Current for 220 kV %( HV Side) Winding at -12% = MVA / (√3*0.88*kV) =50*10^6/ (√3*220*0.88*10^3) = 149.11 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 149.11 /150 =0.99 A Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =√3*(0.99 /(0.87/0.58)) =1.15 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) = 1.15 – 1.00 = 0.15 A I bias = (I1+I2)/2 = (1.00 + 1.15)/2 =1.075 A Consider the setting of Is = 0.1
  • 12. The I Operating Current = 0.1 + (0.2 * 1) + (0.8*(1.075-1) = 0.1 + 0.2 + 0.8*0.075 =0. 36A At tap of -12% with full load the relay require a current of 0.36 A at Is = 0.1 Since I1-I2 = 0.15 which is less than relay operating value, relay will not operate. So a setting Is = 0.1 is acceptable. Calculations for OLTC tap setting +5% Full load Current for 220 kV %( HV Side) Winding at +5% = MVA / (√3*1.05*kV) =50*10^6/ (√3*220*1.05*10^3) =124.97 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 124.97 /150 =0.83 A Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =√3*(0.83 /(0.87/0.58)) =0.96 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary = 1.00-0.96 = 0.04 A I bias = (I1+I2)/2 = (0.96+1.00)/2
  • 13. =0.98 A Consider the setting of Is = 0.1 The I Operating Current = 0.1 + (0.2 * 0.98) = 0.1 + 0.196 = 0.296 A At tap of +5% with full load the relay require a current of 0.29 A at Is = 0.1 Since I1-I2 = 0.04 which is less than relay operating value, relay will not operate. So a setting Is = 0.1 is acceptable.
  • 14. 2.3 Procedure for Relay Setting of Transformer Differential Relay KBCH Data Required MVA Rating Voltage ratio Vector group HV voltage LV voltage Transformer percentage impedance: Transformer vector group: OLTC Tap: +% OLTC Tap: -% CT ratio and winding configuration HV side LV side At Normal tap HV Side full load current = MVA / 3*kV Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) N1=Required ratio compensation = 1/ Ict sec Assuming Relay current = 1A N1 is set on the relay Current on HV side = Current on CT secondary (HV)/ N1
  • 15. At Normal tap low voltage side LV Side full load current = MVA / (3*kV) Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side) N2=Required ratio compensation = 1/ Ict sec (LV) N2 is set on the relay Current on LV side = Current on CT secondary (LV)/N2 At -% Tap HV side current = MVA / (3*kV Where kV is the voltage corresponding to -% tap on HV side Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ict sec /N1 At Tap on +% HV side current = MVA / (3*kV ) Where kV is the voltage corresponding to +% tap on HV side Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ict sec /N1 Differential current at extreme taps At -% tap =Idiff1 =IHV-ILV At +% tap =Idiff2 =IHV-ILV Ibias = IHV+ILV /2
  • 16. Operating current of Relay I Operating = Pickup setting + 0.20 * Bias Current less than 1A +0.8*current above 1A Relay Operating current current is calculated using the above equation. For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will not operate for extreme taps Differential Relay Settings Calculations Substation Name: 220 kV GSS Nagaur Relay Type: KBCH (Areva) Ratings of the Power and Current Transformers Transformer Name: Transformer 2 MVA = 100 Voltage Ratio = 220/132 kV Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNa0d1 CT Ratio (HV Side) = 400/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 600/1 CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3)
  • 17. =262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43/400 =0.66 A Required Ratio Compensation = 1/ 0.66 =1.52 Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/600 = 0.73 A Required Ratio Compensation = 1/ 0.73 =1.37 A Calculations for OLTC tap setting -10% Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) =308.74 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.74 /400 = 0.77 A As the adopted ratio correction is 1.52 A the current to relay bias terminal
  • 18. = 0.77 * 1.52 =1.18 A Hence the differential current is = 1.18 – 1 = 0.18 A Bias current = (I1+I2)/2 = (1.18+1)/2 = 1.09 A [Since the bias current is less than 1.5 A the slope will be within 20%] Therefore the operating current of the relay will be = Is + (0.2* I bias) = 0.1 + (0.2 * 1.09) = 0.37 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =100*10^6/ (√3*220*1.1*10^3) = 237.26 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.57 /400 = 0.60 A
  • 19. As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.60 * 1.52 = 0.82 A Hence the differential current is = 1 – 0.82 = 0.18 A Bias current = (I1+I2)/2 = (0.82 +1)/2 = 0.91 A [Since the bias current is less than 1.5 A the slope will be within 20%] Therefore the operating current of the relay will be = Is + (0.2* I bias) = 0.1 + (0.2 * 0.91) = 0.28 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable.
  • 20. 2.4 Procedure for Relay Setting of Transformer Differential Relay DTH 31/32 Data Required MVA Rating Voltage ratio Vector group CT ratio on HV Side Winding connection of CT on HV side ICT ratio on HV Side Winding connection of ICT on HV side CT ratio on LV Side Winding connection of CT on LV side Transformer Tap Min -% or OLTC Tap max +% Rated current (HV Side) = MVA / (3*Rated voltage (HV side)) Rated current (LV Side) = MVA / (3*Rated voltage (LV side)) If CT is Star/Star Current on CT Secondary (HV) = Rated Current (HV Side) / CT Ratio (HV Side) If CT is Star/Delta the current shall be multiplied by 3. Current on the secondary of ICT for Star/Star = Current on CT Secondary (HV Side) / ICT Ratio (HV Side)
  • 21. For Star/Delta the current shall be multiplied by 3. The same procedure is followed for getting the relay current on LV side also. Idiff = Relay Current = Difference between the HV and LV Current (Current at the secondary of ICT’s) To make sure that the relay does not operate when the Transformer taps are changed the currents are calculated at extreme taps. At Tap on -% Voltage corresponding to the above tap, Full load current = MVA / 3 * Voltage corresponding to –ve tap. At Tap on +% Voltage corresponding to the above tap, Full load current = MVA / 3 * Voltage corresponding to +ve tap. Currents at the CT Secondary and ICT Secondary are calculated by using the above procedure. For extreme +ive and extreme –ive tap. Relay current I1= The difference between the HV and LV Currents for extreme +ive tap. I2= The difference between the HV and LV Currents for extreme +ive tap. DTH 31 relay has a fixed pick up setting and variable single slope bias setting. For setting the Bias Setting The operating current of DTH 31 is given by the equation
  • 22. Relay operating current = Pickup setting + Bias Setting * Bias current The pickup setting in DTH 31 = 0.15 (constant) Bias Current = (I1+I2)/2 Operating Current at normal tap with Bias setting Is = 0.15(or) 0.3 I Operating 1A = 0.15 + 0.15 * Bias Current Bias current = (I1+I2)/2 I Difference 1A = I1- I2 Operating current at extreme taps is calculated with the same procedure. Operating current at extreme taps is calculated with the same procedure. Operating Current at extreme Minimum tap I Operating 2A. I Difference 2A = I1 – I2. Operating Current at extreme Maximum tap I Operating 3A. I difference 3A = I1 – I2. In each of the above cases IOperating current >IDifference + Tolerance If the above is true a setting of 0.15 for bias is selected. In case the above is not true. Similar calculation is carried out for the next Bias Setting. Bhinmal Differential Relay Settings Calculations Relay Type: DTH31 Station Name : 220 kV GSS Modak Ratings of the Power and Current Transformers
  • 23. Transformer Name: NGEF MVA = 100 Voltage Ratio = 220/132 kV Rated Voltage in kV (HV Side) = 220 kV Rated Voltage in kV (LV Side) = 132 KV Vector Group = YNyn0d1 CT Ratio (HV Side) = 300/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 600/1 CT LV Side Vector Group = Star/Star ICT Ratio (HV Side) = 7.3/5 ICT Ratio (LV Side) = 3.6/2.89 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.4319 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.4319/300 =0.874 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio
  • 24. =437.39/600 = 0.728 A Interposing CT (HV Side) = = 7.3/5 Vector Group Interposing CT (HV Side) = Star/Delta Interposing CT (LV Side) = 3.65/2.89 Vector Group Interposing CT (LV Side) = Star/Delta Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =√3*(0.656/1.128) =1.03 A Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT (LV Side)) =√3*(0.728/1.261) = 0.99 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) – Current on ICT Secondary (LV) = 1.03 – .99 =0.04
  • 25. Calculations for OLTC tap setting -15% Full load Current for 220 kV %( HV Side) Winding at -10% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) =308.743 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.74 /300 =1.029 A Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =√3*1.029=1.22 A Current on ICT Secondary (LV) = 1.00 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) = 1.22- 1.00 = 0.22 A Ibias = ( I1 + I2 ) /2 = ( 1.22+ 1 ) /2 = 1.11 A Operating Current = Bias setting + Slope 1 * I bias = 0.15 +0.15*1.11 = 0.3165 A As Id= 0.22, Operating current = 0.31, Hence stable
  • 26. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +15% = MVA / (√3*1.10*kV) =100*10^6/ (√3*220*1.10*10^3) = 238.57A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 228.20 /300 = 0.795 A Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =0.9434 Current on ICT Secondary (LV) = 1.00 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) =1- 0.9434 = 0.056 A At Tap of -10 % I bias = (I1+I2)/2 = (1+0.9434)/2 A =0 .97 A Consider a bias setting of Is = 0.30 The I Operating Current = 0.15 + Is * I bias = 0.15 + 0.15* 0.97 =0.29 A At tap of -10% with full load the relay require a current 0.47 A at Is = 0.30.
  • 27. Since I1-I2 = 0.056 which is less than the operating value, relay will not operate. So a setting Is = 0.30 is acceptable. 2.5 Differential Relay Settings Calculations RET 670 Differential Relay Settings Calculation Procedure Relay Type: RET 670 Required Data Ratings of the Power and Current Transformers MVA Voltage Ratio Rated Voltage in kV (HV Side) Rated Voltage in kV (LV Side) Vector Group CT Ratio (HV Side) CT HV Side Vector Group CT Ratio (LV Side) CT LV Side Vector Group CT resistance value (Rct) Lead resistance value (Rl) Minimum Tap = - % Maximum Tap = +% Rated Current (HV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
  • 28. Required Ratio Compensation = 1/ Current on CT secondary (HV) Rated Current (LV Side) = MVA / (√3*kV) Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio Required Ratio Compensation = 1/ Current on CT Secondary (LV) Relay current on LV side I2 = Current on CT secondary LV side / Ratio compensation for LV side Calculations for OLTC tap setting -% and +% Full load Current (- % or +% HV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Relay Current for HV side I1= Current on Ct secondary (HV)/ Ratio compensation for HV side I1 is calculated for extreme transformer taps The differential current is = I1-I2 Bias current I bias = (I1+I2)/2 Differential current I dif and Ibias is calculated foe extreme Transformer taps Therefore the operating current of the relay = Is + m1* I bias for current less than (4.Iref) + m2* Ibias for current greater than (4 Iref) Where m1 and m2 are the slope of relay char Pick up setting is chosen such that the Differential current at worst tap condition should not be more than 90% of operating current for better stability.. Sample Calculation for ABB RET 670 A) Biased Differential Substation Name : 220 kV GSS Rajwest Relay Type: ABB RET 670 Ratings of the Power and Current Transformers
  • 29. Transformer Name: TELK MVA = 315 Voltage Ratio = 400/220/33 Rated Voltage in kV (HV Side) = 400 Rated Voltage in kV (LV Side) = 220 Vector Group = YNA0d11 CT Ratio (HV Side) = 1000/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 1000/1 CT LV Side Vector Group = Star/Star Minimum Tap = -10 Maximum Tap = +15 Rated Current (HV Side) = MVA / (√3*kV) =315*10^6/ (√3*400*10^3) =454.66 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 454.66/1000 =0.454 A Required Ratio Compensation = 1/ 0.454 = 2.199 A Rated Current (LV Side) = MVA / (√3*kV)
  • 30. =315*10^6/ (√3*220*10^3) =826.66 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =826.66/1000 = 0.826 A Required Ratio Compensation = 1/ 0.826 =1.209 A Compensated current on LV side=√3*0.826/1.209 Calculations for OLTC tap setting -10% Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =315*10^6/ (√3*400*0.85*10^3) =534.89 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 534.89 /1000 =0.534 A Inter posing CT (HV) winding = √3*Current on CT sec (HV)/Ratio correction factor =√3*0.534/2.199 =0.421 A Hence the differential current is = ABS (0.421– 1.183) = 0. 762 A Bias current = (I1+I2)/2
  • 31. = (0.421+1.183)/2 = 0.802 A [Since the bias current is less than 1.5 A the slope will be within 40%] Therefore the operating current of the relay will be = Is + (1.5* M1)+M2*Ibias = 0.1 + (0.4 * 1.5)*0.8*0.697 = 1.25 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it s less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =315*10^6/ (√3*400*1.1*10^3) =413.33 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 413.33 /1000 =0.413 A Interposing HV winding current=√3*0.413/2.199 =0.325 I bias = (interposing CT HV current side+ Interposed LV side CT current side)/2 = (0.325+1.183)/2 = 0.754 A Hence the differential current is = 1.183-0.325 = 0.858 A
  • 32. [Since the bias current is less than 1.5 A the slope will be within 30%] Therefore the operating current of the relay will be = Is + (m1+m2)* I bias = 0.1 + (0.4 +0.8) * 0.754 = 1.01 A The operating value is larger than the differential value hence the system is Stable for the MAX tap condition. B) High Impedance Differential Substation Name : 220 kV GSS Rajwest Relay Type: ABB RET 670 Ratings of the Power and Current Transformers Transformer Name: TELK MVA = 315 Voltage Ratio = 400/220/33 Rated Voltage in kV (HV Side) = 400 Rated Voltage in kV (LV Side) = 220 Vector Group = YNA0d11 % Impedance of the transformer=0.1198 CT Ratio (HV Side) = 1000/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 1000/1 CT LV Side Vector Group = Star/Star CT resistance (Rct) =4Ω Lead Resistance value=1.5 Ω
  • 33. Rated Current (HV Side) = MVA / (√3*kV) =315*10^6/ (√3*400*10^3) =454.66 A Maximum fault current contributed =Rated current /Percentage Impedance =454.66/0.1198 =3795.15 A Maximum fault current contributed secondary=3795.15/1000 = 3.795 A Operating Voltage =3.795*(4+2*1.5) =26.57V Rstab = 250Ω Stabilizing resistance value (Rstab) to be set as per the operating voltage range given in the technical reference manual table provided by the manufacturer.
  • 34. 2.6 Procedure for Relay setting of Transformer Differential Relay ABB RADSB Substation : 220kV GSS Dausa Tranformer Name : CGL Relay Type: RADSB [ABB] Data Required MVA Rating Voltage ratio Vector group CT ratio on HV Side Winding connection of CT on HV side ICT ratio on HV Side Winding connection of ICT on HV side CT ratio on LV Side Winding connection of CT on LV side Transformer Tap Min -% OLTC Tap and max % OLTC tap Calculation Rated Current (HV Side) = MVA / (√3*kV) Rated Current (LV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
  • 35. Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio Interposing CT (HV Side) = Current on CT Secondary (HV) / ICT ratio on HV side Interposing CT (LV Side) = Current on CT Secondary (LV) /0.578 Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT (LV Side)) Difference between HV side and LV side currents = Current on ICT Secondary (HV) – Current on ICT Secondary (LV) Calculations for OLTC tap setting -% Voltage corresponding to the above tap, Full load current = MVA / 3 * Voltage corresponding to –ve tap. Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Current on ICT Secondary (HV) in A = √3*(Current on CT Secondary (HV)/ Interposing CT (HVSide)) Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) Calculations for OLTC tap setting +% Voltage corresponding to the above tap, Full load current = MVA / 3 * Voltage corresponding to +ve tap.
  • 36. Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Current on ICT Secondary (HV) in A = √3*(Current on CT Secondary (HV)/ Interposing CT (HVSide)) Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) Relay setting range available : Operating value can be Settable 20, 25, 35, or 50% of In Id = (I1-I2) Ibias = ( I1+I2)/2 Operating current = 0.25+ Slope1 setting * I bias Id should be less than I operating current The setting shall be selected in such a way that the relay shall not operate for the extreme tap positions Differential Relay Settings Calculations Relay Type: RADSB [ABB] Substation : 220kV GSS Dausa Tranformer Name : CGL Ratings of the Power and Current Transformers Transformer Name: CGL MVA = 100 Voltage Ratio = 220/132kV Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YnYa0 CT Ratio (HV Side) = 300/5
  • 37. CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 600/5 CT LV Side Vector Group = Star/Star ICT Ratio (HV Side) = 4.37/2.88 ICT Ratio (LV Side) = 3.64/2.88 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.4319 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) = 437.39A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.4319/(300/5) = 4.37 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/(600/5) = 3.64 A Interposing CT (HV Side) = 4.37/2.88 = 1.517 Interposing CT (LV Side) = 3.64/2.88 =1.263
  • 38. Current on ICT Secondary (HV) = (Current on CT Secondary (HV)*Interposing CT (HV Side)) =4.37/(4.37 /2.88) = 2.88 A Current on ICT Secondary (LV) = √3*(Current on CT Secondary (LV)/ Interposing CT (LV Side)) =3.64/(3.64/1.263) =2.88 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) – Current on ICT Secondary (LV) = 4.9891 – 4.9916 = 0.0019606708 A Calculations for OLTC tap setting -15% Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) =308.74 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.74/(300/5) =5.15 A Current on ICT Secondary (HV) = (Current on CT Secondary (HV)/ Interposing CT (HV side ) =5.15/(4.862 /1.517)
  • 39. =3.39 A Current on ICT Secondary (LV) =(Current on CT Secondary (HV)/ Interposing CT (HV side) = 2.88 A Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) = 3.39-2.88 = 0.51 A I bias = ( I1+I2)/2 = (3.39+2.88)/2 = 3.34 Operating current = 0.25+0.2*3.34 = 0.88 A Id = 0.51 is less than I operating = 0.88, hence stable Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =100*10^6/ (√3*220*1.1*10^3) = 238.57 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.57 /(300/5) =3.98 A Current on ICT Secondary (HV) = √3*(Current on CT Secondary (HV)/ Interposing CT (HV Side)) =3.98/(3.954 / 1.517) =2.62 A
  • 40. Current on ICT Secondary (LV) = 2.88 Difference between HV side and LV side currents = Current on ICT Secondary (HV) - Current on ICT Secondary (LV) = 2.88-2.62 = 0.26 I bias =( I1+I2) /2 = ( 2.88+2.62) /2 = 2.75 A I operating = 0.25 + 0.2* 2.75 = 0.8 A Id= 0.26 is less than I operating = 0.8 A, hence stable
  • 41. 2.7 Procedure for Relay Setting of Transformer Differential Relay GE T60 Data Required MVA Rating Voltage ratio Vector group HV voltage LV voltage Transformer percentage impedance: Transformer vector group: OLTC Tap: +% OLTC Tap: -% CT ratio and winding configuration HV side LV side At Normal tap HV Side full load current = MVA / 3*kV Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) N1=Required ratio compensation = 1/ Ict sec Assuming Relay current = 1A N1 is set on the relay Current on HV side = Current on CT secondary (HV)/ N1
  • 42. At Normal tap low voltage side LV Side full load current = MVA / (3*kV) Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side) N2=Required ratio compensation = 1/ Ict sec (LV) N2 is set on the relay Current onLV side = Current on CT secondary (LV)/N2 At -% Tap HV side current = MVA / (3*kV Where kV is the voltage corresponding to -% tap on HV side Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current At Tap on +% HV side current = MVA / (3*kV ) Where kV is the voltage corresponding to +% tap on HV side Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current Differential current at extreme taps At -% tap =Idiff1 =IHV-ILV At +% tap =Idiff2 =IHV-ILV Ibias = IHV+ILV
  • 43. Operating current of Relay I Operating = Pickup setting + 0.3 * Bias Current for Bias current less than Break Point I Operating = Pickup setting + 0.3 * Bias Current + 0.8 (Bias current – Break point) for Bias current greater than Break point. Relay Operating current current is calculated using the above equation. For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will not operate for extreme taps. Differential Relay Settings Calculations Substation Name: 220 kV GSS Kushkhera Relay Type: GE T60 Ratings of the Power and Current Transformers
  • 44. Differential Current Setting = 0.25 A Break Point = 2 Slope1 = 0.3 Slope 2= 0.8 Transformer Name: IMP MVA = 100 Voltage Ratio = 220/132 kV Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNa0d1 CT Ratio (HV Side) = 400/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 500/1 CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43/400 =0.66 A
  • 45. Required Ratio Compensation = 1/ 0.66 =1.52 Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.874 A Required Ratio Compensation = 1/ 0.874 =1.143 A Calculations for OLTC at Nominal tap setting Full load Current for 220 kV %( HV Side) Winding = MVA / (√3*0.9*kV) =100*10^6/ (√3*220*10^3) = 262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43 /400 = 0.656 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.656 * 1.52
  • 46. Compensated current internally = 0.9972 A Hence the differential current is = 0.9972 – 1 = 0.0027A Bias current = Max (I1, I2) = (0.9972, 1) = 1 A [Since the bias current is less than Break point (2) the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* I bias) = 0.25 + (0.3* 0.9972) = 0.549 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable. Calculations for OLTC tap setting -15% Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) = 308.74 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.74 /400 = 0.772 A As the adopted compensation is 1.33 A the current to relay bias terminal = 0.772 * 1.33
  • 47. Compensated current internally =1.029 A Hence the differential current is = 1.029 – 0.87 = 0.15 A Bias current = Maximum of (I1, I2) = Maximum of (1.029, 0.87) = 1.029 A [Since the bias current is less than Break point (2) the slope will be within 25%] Therefore the operating current of the relay will be = Is + (0.2* I bias) = 0.25 + (0.3 *1.029) = 0.558 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =100*10^6/ (√3*220*1.1*10^3) = 238.57A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.57 /400 = 0.5964 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.596 * 1.52
  • 48. Compensated current internally = 0.905 A Hence the differential current is = 1-0.905 = 0.095 A Bias current = Maximum of (I1, I2) = Maximum of (0.905, 1) = 1 A [Since the bias current is less than Break point (2) the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* I bias) = 0.25 + (0.3 * 1) = 0.55 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable.
  • 49. 2.8 Procedure for Relay Setting of Transformer Differential Relay CSC326 Data Required MVA Rating Voltage ratio Vector group HV voltage LV voltage Transformer percentage impedance: Transformer vector group: OLTC Tap: +% OLTC Tap: -% CT ratio and winding configuration HV side LV side At Normal tap HV Side full load current = MVA / 3*kV Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) N1=Required ratio compensation = 1/ Ict sec Assuming Relay current = 1A N1 is set on the relay Current on HV side = Current on CT secondary (HV)/ N1
  • 50. At Normal tap low voltage side LV Side full load current = MVA / (3*kV) Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side) N2=Required ratio compensation = 1/ Ict sec (LV) N2 is set on the relay Current onLV side = Current on CT secondary (LV)/N2 At -% Tap HV side current = MVA / (3*kV Where kV is the voltage corresponding to -% tap on HV side Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current At Tap on +% HV side current = MVA / (3*kV ) Where kV is the voltage corresponding to +% tap on HV side Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current Differential current at extreme taps At -% tap =Idiff1 =IHV-ILV At +% tap =Idiff2 =IHV-ILV Ibias = IHV+ILV
  • 51. Operating current of Relay I Operating = Pickup setting + 0 * Bias Current if less than 0.656 I Operating = Pickup setting + (0.3 * Bias Current -0.656) if greater than 0.656 I Operating = Pickup setting + 0.7 * (Bias Current-4) + 0.3*4 Relay Operating current current is calculated using the above equation. For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will not operate for extreme taps. Differential protection characteristics for transformers: Differential Relay Settings Calculations Substation Name: 220 kV GSS Bharathpur Relay Type: CSC326 Ratings of the Power and Current Transformers Differential Current Setting = 0.2 A Transformer Name: CGL
  • 52. MVA = 100 Voltage Ratio = 220/132 kV Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNa0d1 CT Ratio (HV Side) = 400/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 500/1 CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43/400 =0.66 A Required Ratio Compensation = 1/ 0.66 =1.52 Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A
  • 53. Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.8747 A Required Ratio Compensation = 1/0.8747 = 1.143 A Calculations for OLTC Nominal tap setting: Full load Current for 220 kV %( HV Side) Winding at = MVA / (√3*kV) =100*10^6/ (√3*220*10^3*) = 262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43 /400 = 0.656 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.656 * 1.52 = 0.997 A Compensated current internally on HV =0.997 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A
  • 54. Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.8747 A Required Ratio Compensation = 1/0.8747 = 1.143 A Compensated current on LV = 0.8747 * 1.143 = 0.9993 Hence the differential current is = (0.9973 – 0.9993 ) = 0.002 A Bias current = (I1+I2)/2 = (0.656+0.8747)/2 = 0.765 A [Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656) = 0.2 + (0.3 *0.109) = 0.232 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable.
  • 55. Calculations for OLTC tap setting -15% Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) = 308.74 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.74 /400 = 0.772 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.772 * 1.52 = 1.18 A Compensated current internally on HV =1.18 A Hence the differential current is = (1.18– 1.0 ) = 0.18 A Bias current = (I1+I2)/2 = (1.18+1)/2 = 1.09 A [Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656) = 0.2 + (0.3 *0.434) = 0.33 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable.
  • 56. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =100*10^6/ (√3*220*1.1*10^3) = 238.5 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.574 /400 = 0.596 A As the adopted ratio correction is 1 A the current to relay bias terminal = 0.596 * 1.52 Compensated current internally = 0.905 A Differential current = I1- I2 = 1-0.905 = 0.095 A Bias current = (I1+I2)/2 = (0.905 +1)/2 = 0.952 A [Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656) = 0.2 + (0.3*(0.952- 0.656)) = 0.288 A
  • 57. Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable 2.9 Procedure for Relay Setting of Transformer Differential Relay DUOBIAS Data Required MVA Rating Voltage ratio Vector group HV voltage LV voltage Transformer percentage impedance: Transformer vector group: OLTC Tap: +% OLTC Tap: -% CT ratio and winding configuration HV side LV side At Normal tap HV Side full load current = MVA / 3*kV Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) N1=Required ratio compensation = 1/ Ict sec Assuming Relay current = 1A N1 is set on the relay Current on HV side = Current on CT secondary (HV)/ N1
  • 58. At Normal tap low voltage side LV Side full load current = MVA / (3*kV) Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side) N2=Required ratio compensation = 1/ Ict sec (LV) N2 is set on the relay Current onLV side = Current on CT secondary (LV)/N2 At -% Tap HV side current = MVA / (3*kV Where kV is the voltage corresponding to -% tap on HV side Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current At Tap on +% HV side current = MVA / (3*kV ) Where kV is the voltage corresponding to +% tap on HV side Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current Differential current at extreme taps At -% tap =Idiff1 =IHV-ILV At +% tap =Idiff2 =IHV-ILV Ibias = IHV+ILV
  • 59. Operating current of Relay I Operating = Pickup setting + 0 * Bias Current if less than 0.656 I Operating = Pickup setting + (0.3 * Bias Current -0.656) if greater than 0.656 I Operating = Pickup setting + 0.7 * (Bias Current-4) + 0.3*4 Relay Operating current current is calculated using the above equation. For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will not operate for extreme taps. Differential protection characteristics for transformers:
  • 60. Differential Relay Settings Calculations Substation Name: 220 kV GSS Neemrana Relay Type: DUOBIAS Ratings of the Power and Current Transformers Differential Current Setting = 0.25 A Transformer Name: CGL MVA = 100 Voltage Ratio = 220/132 kV Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNa0d1 CT Ratio (HV Side) = 400/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 500/1 CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.43 A
  • 61. Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43/400 =0.66 A Required Ratio Compensation = 1/ 0.66 =1.52 Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.8747 A Required Ratio Compensation = 1/0.8747 = 1.143 A Calculations for OLTC Nominal tap setting: Full load Current for 220 kV ( HV Side) Winding = MVA / (√3*kV) =100*10^6/ (√3*220*10^3*) = 262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43 /400 = 0.656 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.656 * 1.52* √3
  • 62. = 1.727 A Compensated current internally on HV = 1.727 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.8747 A Required Ratio Compensation = 1/0.8747 = 1.143 A Compensated current on LV = 0.8747 * 1.143 = 1 Hence the differential current is = (1 – 1 ) = 0 A Bias current = (I1+I2)/2 = (1+1)/2 = 1 A [Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* ( I bias) = 0.2 + (0.3*1) = 0.5A
  • 63. Calculations for OLTC tap setting -15% Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) = 308.743 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.743 /400 = 0.771 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.771 * 1.52 = 0.888 A Compensated current internally on HV =0.888 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.8747 A Required Ratio Compensation = 1/0.8747 = 1.143 A Compensated current on LV = 0.874* 1.143
  • 64. = 0.998 A Hence the differential current is = (1.0-0.888) = 0.12 A Bias current = (I1+I2)/2 = (0.888+1)/2 = 0.944 A [Since the bias current is less than 4 A and greater than 0.656 the slope will be within 30%] Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656) = 0.2 + (0.3 *0.28) = 0.284 A Id= 0.12 is less than I operating current = 0.284 A, hence Stable Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =100*10^6/ (√3*220*1.1*10^3) = 238.5 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.5 /400 = 0.56 A As the adopted ratio correction is 1 A the current to relay bias terminal = 0.56 * 1.52 Compensated current internally = 0.8512 A
  • 65. Compensated current internally on LV = 0.851*1.143 = 1 A Hence the differential current is = 1-0.8512 = 0.1488 A Bias current = (I1+I2)/2 = (1 +0.1488)/2 = 0.574 A [Since the bias current is less than 0.656 the slope will be zero. Therefore the operating current of the relay will be = Is + (0.3* ( I bias-0.656) = 0.2 + (0.3*(0.574)) = 0.2A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable.
  • 66. 2.10 Procedure for Relay Setting of Transformer Differential Relay 7UT61X/7UT51X Data Required MVA Rating Voltage ratio Vector group HV voltage LV voltage Transformer percentage impedance: Transformer vector group: OLTC Tap: +% OLTC Tap: -% CT ratio and winding configuration HV side LV side At Normal tap HV Side full load current = MVA / 3*kV Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) N1=Required ratio compensation = 1/ Ict sec Assuming Relay current = 1A N1 is set on the relay
  • 67. Current on HV side = Current on CT secondary (HV)/ N1 At Normal tap low voltage side LV Side full load current = MVA / (3*kV) Current on CT Secondary Ict (LV) = Rated Current (LV Side) / CT Ratio (LV Side) N2=Required ratio compensation = 1/ Ict sec (LV) N2 is set on the relay Current onLV side = Current on CT secondary (LV)/N2 At -% Tap HV side current = MVA / (3*kV Where kV is the voltage corresponding to -% tap on HV side Current on CT Secondary = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current At Tap on +% HV side current = MVA / (3*kV ) Where kV is the voltage corresponding to +% tap on HV side Current on CT Secondary Ict (HV) = Rated Current (HV Side) / CT Ratio (HV Side) With ratio compensation Current on CT Secondary =Ratio of compensation * CT secondary current Differential current at extreme taps At -% tap =Idiff1 =IHV-ILV
  • 68. At +% tap =Idiff2 =IHV-ILV Ibias = IHV+ILV Operating current of Relay I Operating = Pickup setting + 0.25 * Bias Current if less than 2.5A I Operating = Pickup setting + 0.25 * Bias Current + 0.5 ( Bias current above 2.5 A ) Relay Operating current is calculated using the above equation. For extreme taps the Idiff and Ibias current are calculated., the pick up setting is chosen such that it will not operate for extreme taps Differential Relay Settings Calculations Substation Name: 220 kV GSS Nagaur Relay Type: SIPROTECH 7UT61X Ratings of the Power and Current Transformers Differential Current Setting = 0.2 A Transformer Name: BHEL -II MVA = 100 Voltage Ratio = 220/132 kV Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNa0d1 CT Ratio (HV Side) = 400/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 500/1
  • 69. CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3) =262.43 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.43/400 =0.66 A Required Ratio Compensation = 1/ 0.66 =1.52 Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.39 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.39/500 = 0.73 A Required Ratio Compensation = 1/ 0.73 =1.14 A Calculations for OLTC tap setting -10%
  • 70. Full load Current for 400 kV %( HV Side) Winding at -15% = MVA / (√3*0.9*kV) =100*10^6/ (√3*220*0.85*10^3) = 308.74 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 308.74 /400 = 0.77 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.77 * 1.52 Compensated current internally =1.18 A Hence the differential current is = 1.18 – 1 = 0.18 A Bias current = (I1+I2) = (1.18 +1) = 2.18 A [Since the bias current is less than 2.5 A the slope will be within 25%] Therefore the operating current of the relay will be = Is + (0.5* I bias) = 0.2 + (0.25 *2.18) = 0.74 A Differential current at w tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.1*kV) =100*10^6/ (√3*220*1.1*10^3)
  • 71. = 238.5 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.5 /400 = 0.60 A As the adopted ratio correction is 1.52 A the current to relay bias terminal = 0.60 * 1.14 Compensated current internally = 0.68 A Hence the differential current is = 1 – 0.68 = 0.32 A Bias current = (I1+I2) = (0.68 +1) = 1.68 A [Since the bias current is less than 2.5 A the slope will be within 25%] Therefore the operating current of the relay will be = Is + (0.25* I bias) = 0.2 + (0.25 * 1.68) = 0.62 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it is less than 90% so the setting is acceptable.
  • 72. 2.11 Differential Relay Settings Calculations GE SR745 Relay Type: GE SR745 Required Data Ratings of the Power and Current Transformers MVA Voltage Ratio Rated Voltage in kV (HV Side) Rated Voltage in kV (LV Side) Vector Group CT Ratio (HV Side) CT HV Side Vector Group CT Ratio (LV Side) CT LV Side Vector Group Minimum Tap = - % Maximum Tap = +% Break point Rated Current (HV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Required Ratio Compensation = 1/ Current on CT secondary (HV) Rated Current (LV Side) = MVA / (√3*kV)
  • 73. Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio Required Ratio Compensation = 1/ Current on CT Secondary (LV) Relay current on LV side I2 = Current on CT secondary LV side * Ratio compensation for LV side Calculations for OLTC tap setting -% and +% Full load Current (- % or +% HV Side) = MVA / (√3*kV) Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio Relay Current for HV side I1= Current on Ct secondary (HV)* Ratio compensation for HV side I1 is calculated for extreme transformer taps The differential current is = I1-I2 Bias current I bias = Maximum of(I1,I2) Differential current I dif andIbias is calculated foe extreme Transformer taps Therefore the operating current of the relay = Is + Slope1* I bias for I bias current less than Break point And Is + Slope1*Break point + Slope2* (Ibias- Break point) for I biascurrent greater than Break point. Pick up setting is chosen such that the Differential current at worst tap condition should not be more than 90% of operating current for better stability.
  • 74. Sample Calculation of GE SR 745 Substation Name : 220 kV GSS Khinwasar Relay Type: GE SR745 Ratings of the Power and Current Transformers Transformer Name: EMCO MVA = 100 Voltage Ratio = 220/132 Rated Voltage in kV (HV Side) = 220 Rated Voltage in kV (LV Side) = 132 Vector Group = YNA0d1 CT Ratio (HV Side) = 400/1 CT HV Side Vector Group = Star/Star CT Ratio (LV Side) = 500/1 CT LV Side Vector Group = Star/Star Minimum Tap = -15 Maximum Tap = +10 Break point=2 Is=0.2, m1=25%, m2=80% Rated Current (HV Side) = MVA / (√3*kV) =100*10^6/ (√3*220*10^3)
  • 75. =262.4319 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 262.4319/400 =0.65607 A Required Ratio Compensation = 1/ 0.65607 = 1.5242 A Rated Current (LV Side) = MVA / (√3*kV) =100*10^6/ (√3*132*10^3) =437.38 A Current on CT Secondary (LV) = Rated Current (LV Side)/CT Ratio =437.38 /500 = 0.875 A Required Ratio Compensation = 1/ 0.875 =1.143 A As the adopted ratio correction is 1.143 A the current to relay bias terminal = 0.875 * 1.143 I1=1 A Calculations for OLTC tap setting -15% Full load Current for 220 kV %( HV Side) Winding at -15% = MVA / (√3*0.85*kV) =100*10^6/ (√3*220*0.85*10^3) =308.743 A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio
  • 76. = 308.743 /400 =0.7719 A As the adopted ratio correction is 1.5242 A the current to relay bias terminal = 0.7719 * 1.5242 I2=1.176 A Hence the differential current is = (I1-I2) =1.176 – 1 = 0. 176 A Bias currentIbias = Max(I1,I2) = (1.176,1) = 1.176 A [Since the bias current is less than Break point the slope will be within 25%] Therefore the operating current of the relay will be = Is + (0.25* I bias) = 0.2 + (0.25 * 1.176) = 0.494 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it s less than 90% so the setting is acceptable. Calculations for OLTC tap setting +10% Full load Current for 220 kV %( HV Side) Winding at +10% = MVA / (√3*1.15*kV) =100*10^6/ (√3*220*1.1*10^3) =238.574A Current on CT Secondary (HV) = Rated Current (HV Side)/CT Ratio = 238.574 /400
  • 77. =0.5964 A As the adopted ratio correction is 1.5242 A the current to relay bias terminal = 0.5964* 1.5242 I2=0.909 A Hence the differential current is= (I1-I2) = 1 - 0.909 = 0.091 A Bias current Ibias = Max(I1,I2) = (1, 0.909) = 1 A [Since the bias current is less than Break point the slope will be within 25%] Therefore the operating current of the relay will be = Is + (0.25* I bias) = 0.2 + (0.25 * 1) = 0.45 A Differential current at worst tap condition should not be more than 90% of operating current for better stability. Here it s less than 90% so the setting is acceptable.