2. FIRE HYDRANT SYSTEM SCHEMATIC DIAGRAM
SFP = 1900 L / M
DFP = 1900 L / M
JP = 200 L / M
FIRE PUMP CAPACITY
SFD
DFP
JP
WORKING PRESSURE = 7 Kg / CM2
FHB = 4.5 Kg / CM2
FHB = 4.5 Kg / CM2
FHB = 4.5 Kg / CM2
OHB = 4.5 Kg / CM2
OHB = 4.5 Kg / CM2
FHB = 4.5 Kg / CM2
AUTOMATIC AIR
RELIEF VALVE
3.
4. FIRE PROTECTION PUMP STATION
PUMP ROOM AREA
***OPERATION SEQUENCE***
JOCKEY ELECTRIC PUMP (JP)
PUMP CAPACITY : 200 L / M
MOTOR POWER : 5.5 KW / 380V / 3P
********OPERATION SEQUENCE********
PUMP “ON” : 6 Kg/Cm2
PUMP “OFF” : 8 Kg/Cm2
DIESEL FIRE PUMP (DFP)
PUMP CAPACITY : 1900 L / M
MOTOR POWER : 55 KW / 380V / 3P
*******OPERATION SEQUENCE*******
PUMP “ON” : 4 Kg/Cm2 ( AUTOMATIC )
PUMP “OFF” : DONE MANUALLY
ELECTRIC FIRE PUMP (EFP)
PUMP CAPACITY : 1900 L / M
MOTOR POWER : 55 KW / 380V / 3P
******OPERATION SEQUENCE*******
PUMP “ON” : 5 Kg/Cm2 ( AUTOMATIC )
PUMP “OFF” : DONE MANUALLY
DFP
EFP
JP
5. FIRE PTROTECTION PIPE INSTALLATION
Branch Sprinkler Pipe Main Line Pipe
Automatic Air Relief Valve Fire Pump
10. HYDRANT BOX INDOOR & OUTDOOR TYPE
Indoor Fire Hydrant Box FHB hose and valve
Outdoor Fire Hydrant Box Outdoor Fire Hydrant Box
11. INDOOR FIRE HYDRANT BOX TYPE
Wall type Indoor FHB Wall type Indoor FHB hose & valve
Indoor Fire hydrant box Indoor FHB hose & valve
12. Siamesse Connection
DKI FIRE SIMULATION EXERCISE AT SIAMESE CONNECTION
Outdoor Fire Hydrant Box
DKI Fire simulation team
13. FIRE PUMP CONTROL PANEL
PP - UTILITY
FIRE HYDRANT PANEL
INSIDE PP - UTILITY
INSIDE FIRE HYDRANT PANEL
14. FIRE EXTINGUSHER / APAR
• APAR (Alat Pemadam Api Ringan )
• TYPE : ABC POWDER
• CAPACITY : 2.50 Kg
• APAR (Alat Pemadam Api Ringan )
• TYPE : CO
• CAPACITY : 4 Kg AND 6 Kg
15. FIRE PROTECTION SYSTEM
( OPERATION PROCEDURE)
Dalam rancangan pembuatan gedung kantor & gudang di kumon indonesia education untuk memproteksi
gedung dari bahaya kebakaran di dalam gedung telah tersedia installasi System pemadam api yaitu :