IMPROVING POWER
SYSTEM STABILITY
By Ghulam Rasool
Methods of Improving Power System Stability:
There are Basic three methods
• Automatic Voltage Regulators (AVR)
• Load Frequency Control (LFC)
• Power System Stabilizer (PSS)
Automatic Voltage Regulators (AVR):
• Automatic voltage regulator (AVR) maintains the Generator
terminal voltage at a given value automatically by changing the
excitation current to the Generator field.
• The AVR supplies the required D.C. to the Generator field
depending on the load, power factor etc. to maintain a constant
terminal voltage.
Types of AVR:
Single
Channel
AVR
Dual
Channel
AVR
Twin
Channel
AVR
Function of AVR:
• The major function of AVR is to
continually adjust the terminal
voltage to maintained at
preset value.
• Compares the Generator
terminal voltage with a preset
reference voltage.
• If the Generator terminal
voltage is less than the
reference voltage, the
AVR increases D.C. voltage
across the Generator field.
• Maintaining the constant
voltage as per the setting.
Functions of AVR:
• Challenges
The normal feedback control actions of (AVR) & Speed Governor
introducing negative damping which can cause undamped modes of
oscillations (Critically stable).
• Solution
Switching (AVR) from Auto/Manual.
However, removing AVR from service is not realistic solution to the
problem.
Supplementary feedback signal introduced to AVR as PSS.
Load Frequency Control:
• For large scale electric power systems with interconnected areas,
Load Frequency Control (LFC) is important to keep the system
frequency and the inter-area tie power as near to the scheduled
values as possible.
• The input mechanical power to the generators is used to control
the frequency of output electrical power and to maintain the
power exchange between the areas as scheduled.
• The change in frequency is sensed when the rotor angle ∂ is
• changed.
LFC cont.…..
• The change in frequency is sensed when the rotor angle ∂ is changed.
• The error signals are transformed into real power command signal, which is sent to
prime mover to call for an increment in the torque.
• The prime mover then brings change in the generator output by an amount which will
change the values of within the specified tolerance.
• Load frequency control is basic control mechanism in the power system operation.
Whenever there is variation in load demand on a generating unit, there is a
momentarily an occurrence of unbalance between real-power input and output. This
difference is being supplied by the stored energy of the rotating parts of the unit.
• Load Frequency Control (LFC) is being used for several years as part of the Automatic
Generation Control (AGC) scheme in electric power systems. One of the objectives of
AGC is to maintain the system frequency at nominal value (50 Hz).
Block diagram Load
frequency control:
• The frequency is sensed by frequency
sensor.
• The change in frequency and tie line real
power can be measured by change in rotor
angle δ.
• The load frequency controller amplify and
transform error signal, i.e., (Δfi and ΔPtie)
in to real power command signal ΔPci which
is sent to the prime mover via governor
(that control the valve mechanism).
• To call for an increment or decrement in
torque the prime mover balances the output
of governor which will compensate the
value of error signal that is Δfi and ΔPtie.
• The process continues till deviation in form
of Δfi and ΔPtie as well as the specified
tolerance.
Reasons for constant frequency:
• The speed of the alternating current motors depends on the
frequency of the power supply. There are situations where speed
consistency is expected to be of high order.
• If the normal frequency is 50 Hertz and the system frequency falls
below 47.5 Hertz or goes up above 52.5 Hertz then the blades of
the turbine are likely to get damaged so as to prevent the stalling
of the generator.
• Due to the subnormal frequency operation the blast of the
Induced Draft (ID) and Force Draft (FD) fans in the power stations
get reduced and thereby reduce the generation power in the
thermal plants.
AGC Automatic Generation
Control:
• Automatic generation control (AGC) is
defined as, the regulation of power
output of controllable generators
within a prescribed area.
• When system frequency is on
schedule, each area is expected
automatically to adjust its generation
to maintain its net transfer with other
areas on schedule, thereby absorbing
its own load variations.
• When system frequency is off-
schedule, because one or more areas
are not fulfilling their regulating
responsibilities, other areas are
expected automatically to shift their
respective net transfer schedules
proportionally to the system
frequency deviation and in direction
to assist the deficient areas and
hence restore system frequency.
Block diagram of a synchronous generator with
basic frequency control loops. AUTOMATIC
GENERATION CONTROL
Power System Stabilizer:
• The power system stabilizer (PSS) is a device that measures
improvements in system stability when added to a generator’s
automatic voltage regulator (AVR). Therefore, compared to
system reconstruction or enhancement, it offers
overwhelmingly superior cost performance.
• The Power System Stabilizer (PSS) is a supplementary excitation
controller used to damp generator electro-mechanical oscillations
in order to protect the shaft line and stabilise the grid. It
also damps generator rotor angle swings, which are of greater
range in frequencies in power system.
The Main Function of PSS:
• The objectives of PSS is to add damping to rotor oscillations. This
is achieved by modulating the voltage regulator set point to
produce torque variations in phase with speed.
• The PSS will produce variations in electrical torque in phase with
speed and acts to damped out oscillations.
Basic PSS Theory:
• A synchronous generator
working on the network is
principally an oscillating
structure.
• In order to produce a
torque the rotating
magnetic fields of the rotor
and the stator must form a
certain angle (the so called
load angle δ).
Basic PSS Theory: cont…….
• The electrical torque (Te) increases, as the angle (δ) increases,
just similar to a torsion spring. Because during steady-state
operation the electrical torque (Te) of the generator and the
mechanical driving torque (Tm) from the turbine are in
equilibrium, the load angle δ remains in a given position
• The dynamic of the mechanical power (Tm) , electrical power (Te)
, and rotor angular speed (ω) of the synchronous machine is an
origin for theoretical consideration and justifications of the PSS
processing signal.

Power System Control

  • 1.
  • 2.
    Methods of ImprovingPower System Stability: There are Basic three methods • Automatic Voltage Regulators (AVR) • Load Frequency Control (LFC) • Power System Stabilizer (PSS)
  • 3.
    Automatic Voltage Regulators(AVR): • Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing the excitation current to the Generator field. • The AVR supplies the required D.C. to the Generator field depending on the load, power factor etc. to maintain a constant terminal voltage.
  • 4.
  • 5.
    Function of AVR: •The major function of AVR is to continually adjust the terminal voltage to maintained at preset value. • Compares the Generator terminal voltage with a preset reference voltage. • If the Generator terminal voltage is less than the reference voltage, the AVR increases D.C. voltage across the Generator field. • Maintaining the constant voltage as per the setting.
  • 6.
    Functions of AVR: •Challenges The normal feedback control actions of (AVR) & Speed Governor introducing negative damping which can cause undamped modes of oscillations (Critically stable). • Solution Switching (AVR) from Auto/Manual. However, removing AVR from service is not realistic solution to the problem. Supplementary feedback signal introduced to AVR as PSS.
  • 7.
    Load Frequency Control: •For large scale electric power systems with interconnected areas, Load Frequency Control (LFC) is important to keep the system frequency and the inter-area tie power as near to the scheduled values as possible. • The input mechanical power to the generators is used to control the frequency of output electrical power and to maintain the power exchange between the areas as scheduled. • The change in frequency is sensed when the rotor angle ∂ is • changed.
  • 8.
    LFC cont.….. • Thechange in frequency is sensed when the rotor angle ∂ is changed. • The error signals are transformed into real power command signal, which is sent to prime mover to call for an increment in the torque. • The prime mover then brings change in the generator output by an amount which will change the values of within the specified tolerance. • Load frequency control is basic control mechanism in the power system operation. Whenever there is variation in load demand on a generating unit, there is a momentarily an occurrence of unbalance between real-power input and output. This difference is being supplied by the stored energy of the rotating parts of the unit. • Load Frequency Control (LFC) is being used for several years as part of the Automatic Generation Control (AGC) scheme in electric power systems. One of the objectives of AGC is to maintain the system frequency at nominal value (50 Hz).
  • 9.
    Block diagram Load frequencycontrol: • The frequency is sensed by frequency sensor. • The change in frequency and tie line real power can be measured by change in rotor angle δ. • The load frequency controller amplify and transform error signal, i.e., (Δfi and ΔPtie) in to real power command signal ΔPci which is sent to the prime mover via governor (that control the valve mechanism). • To call for an increment or decrement in torque the prime mover balances the output of governor which will compensate the value of error signal that is Δfi and ΔPtie. • The process continues till deviation in form of Δfi and ΔPtie as well as the specified tolerance.
  • 10.
    Reasons for constantfrequency: • The speed of the alternating current motors depends on the frequency of the power supply. There are situations where speed consistency is expected to be of high order. • If the normal frequency is 50 Hertz and the system frequency falls below 47.5 Hertz or goes up above 52.5 Hertz then the blades of the turbine are likely to get damaged so as to prevent the stalling of the generator. • Due to the subnormal frequency operation the blast of the Induced Draft (ID) and Force Draft (FD) fans in the power stations get reduced and thereby reduce the generation power in the thermal plants.
  • 11.
    AGC Automatic Generation Control: •Automatic generation control (AGC) is defined as, the regulation of power output of controllable generators within a prescribed area. • When system frequency is on schedule, each area is expected automatically to adjust its generation to maintain its net transfer with other areas on schedule, thereby absorbing its own load variations. • When system frequency is off- schedule, because one or more areas are not fulfilling their regulating responsibilities, other areas are expected automatically to shift their respective net transfer schedules proportionally to the system frequency deviation and in direction to assist the deficient areas and hence restore system frequency. Block diagram of a synchronous generator with basic frequency control loops. AUTOMATIC GENERATION CONTROL
  • 12.
    Power System Stabilizer: •The power system stabilizer (PSS) is a device that measures improvements in system stability when added to a generator’s automatic voltage regulator (AVR). Therefore, compared to system reconstruction or enhancement, it offers overwhelmingly superior cost performance. • The Power System Stabilizer (PSS) is a supplementary excitation controller used to damp generator electro-mechanical oscillations in order to protect the shaft line and stabilise the grid. It also damps generator rotor angle swings, which are of greater range in frequencies in power system.
  • 13.
    The Main Functionof PSS: • The objectives of PSS is to add damping to rotor oscillations. This is achieved by modulating the voltage regulator set point to produce torque variations in phase with speed. • The PSS will produce variations in electrical torque in phase with speed and acts to damped out oscillations.
  • 14.
    Basic PSS Theory: •A synchronous generator working on the network is principally an oscillating structure. • In order to produce a torque the rotating magnetic fields of the rotor and the stator must form a certain angle (the so called load angle δ).
  • 15.
    Basic PSS Theory:cont……. • The electrical torque (Te) increases, as the angle (δ) increases, just similar to a torsion spring. Because during steady-state operation the electrical torque (Te) of the generator and the mechanical driving torque (Tm) from the turbine are in equilibrium, the load angle δ remains in a given position • The dynamic of the mechanical power (Tm) , electrical power (Te) , and rotor angular speed (ω) of the synchronous machine is an origin for theoretical consideration and justifications of the PSS processing signal.