SlideShare a Scribd company logo
Mesurement Of High Voltages
& High Currents
Unit 3
High Voltage Measurement Techniques
2 8/8/2022
Sphere Gaps
 Applicatios:
 Voltage Measurement (Peak) - Peak values of voltages may be measured from 2 kV up to
about 2500 kV by means of spheres.
 Arrangements:
1. Vertically with lower sphere grounded (For Higher Voltages)
2. Horizontally with both spheres connected to the source voltage or one sphere grounded
(For Lower Voltages).
3 8/8/2022
 The arrangement is selected based on the relation between the peak voltage,
determined by sparkover between the spheres, and the reading of a voltmeter on the
primary or input side of the high-voltage source. This relation should be within 3%
(IEC, 1973).
 Standard values of sphere diameter are 6.25, 12.5, 25, 50, 75, 100, 150, and 200 cm.
 The Clearance around the sphere gaps:
4
Sphere Gaps
Fig C :Breakdown voltage characteristic of
sphere gaps
8/8/2022
 The effect of humidity is to increase the breakdown voltage of sphere gaps by up to
3%.
 Temperature and pressure, however, havea significant influenceo n breakdown
voltage.
 Breakdown Voltage under normal atmospheric conditions is, Vs=kVn where k is a
factor related to the relative air density (RAD) δ.
 The relation between the RAD(δ) and the correction factor k:
 Under impulse voltages, the voltage at which there is a 50% breakdown probability
is recognized as the breakdown level.
5
Sphere Gaps
8/8/2022
 Factors Influencing the Sparkover Voltage of Sphere Gaps
i. Nearby earthed objects,
ii. Atmospheric conditions and humidity,
iii. Irradiation, and
iv. Polarity and rise time of voltage waveforms.
 The limits of accuracy are dependant on the ratio of the spacing d to the sphere
diameter D, as follows:
 d < 0.5 D Accuracy = ± 3 %
 0.75 D > d > 0.5 D Accuracy = ± 5 %
 For accurate measurement purposes, gap distances in excess of 0.75D are not used
6
Sphere Gaps
8/8/2022
High Ohmic Series Resistance with
Microammeter
 Resistance (R) :
 Constructed with large wire wound
 Value: Few hundreds of Mega ohms –Selected to give (1-10μA) for FSD.
 Voltage drop in each element is chosen to avoid surface flashovers and discharges
(5kV/cm in air, 20kV/cm in oil is allowed)
 Provided with corona free terminals.
 Material: Carbon alloy with temperature coefficient of 10-4/oC .
 Resistance chain located in air tight oil filled PVC tube for 100kV operation with
good temp stability.
 Mircoammeter – MC type
 Voltage of source, V=IR
 Impedance of the meter is few ohms. i.e, very less compared to R so the
drop across the meter is negligible.
 Protection: Paper gap, Neon Glow tube, a zener diode with series resistance
– Gives protection when R fails.
7 8/8/2022
 Maximum voltage: 500kV with  0.2% accuracy.
 Limitations:
 Power dissipation & source loading
 Temp effects &
8
High Ohmic Series Resistance with
Microammeter
8/8/2022
Measurement Of High Dc Voltage
9
 Series resistance micrometer
 Resistance potential divider
 Generating voltmeter
 Sphere and other gaps
8/8/2022
SERIES RESISTANCE MICROMETER
10
 A very high resistance in series with a micrometer.
 Current through R is measured using micrometer.
 Voltage of source, V = IR
 The resistance is constructed from a large no. of wire
wound resistors in series.
 Can be operated upto 500kV (D.C)
 Accuracy = ±0.2%
 Selection of R value:
 Current allowed: 1 to 10A
 Corona free termination
 Temp. coefficient<10-4/0C : Carbon Alloy
 Placed in airtight, oil filled PVC tube to maintain temp.
stability
8/8/2022
RESISTANCE POTENTIAL DIVIDER
11
 It uses electrostatic voltmeter.
 Can be placed near the test object which might not
always be confined to one location
 Let, V2-Voltage across R2
 Sudden voltage changes during transients due to:
 Switching operation
 Flashover of test objects
 Damage due to stray capacitance across the elements & ground
capacitance
2
2
1
2
1
2
1
2
1
2
R
)
R
(R
X
V
V
magnitude,
voltage
High
)
R
(R
R
X
V
V




8/8/2022
GENERATING VOLTMETER
12
 Generating principle is used where direct loading or
direct connection is to be avoided.
 Generating voltmeter: A variable capacitor
electrostatic voltage generator.
 It generates current proportional to voltage under
measurement
 This arrangement provides loss free measurement of
DC and AC voltages
 It is driven by synch. motor, so doesn’t observe
power from the voltage measuring source
 The high voltage electrode and the grounded
electrode in fact constitute a capacitance system.
 The capacitance is a function of time as the area A
varies with time and, therefore, the charge q(t) is
given as,
8/8/2022
13
and,
For d.c. Voltages,
Hence
If the capacitance varies linearly with time and reaches its peak value Cm is time Tc /2 and
again reduces to zero linearly in time Tc /2, the capacitance is given as
If the capacitance C varies sinusoidally between the limits C0 and (C0 + Cm) then
C = C0 + Cm sin ωt
and the current ‘i' is then given as, i(t) = im cos ω t , where im = VCmω
Here ω is the angular frequency of variation of the capacitance.
 Generally the current is rectified and measured by a moving coil meter
 Generating voltmeters can be used for a.c. voltage measurement also provided the angular
frequency ω is the same or equal to half that of the voltage being measured.
 Above fig. shows the variations of C as a function of time together with a.c. voltage, the
frequency of which is twice the frequency of C (t).
GENERATING VOLTMETER
8/8/2022
 Instantaneous value of current i(t) = Cm fvV(t)
 where fv = 1/Tv the frequency of voltage.
 Since fv = 2fc and fc = 60/n we obtain,
I(t) = n/30 CmV(t)
 Fig. shows a schematic diagram of a generating voltmeter
which employs rotating vanes for variation of capacitance
 High voltage electrode is connected to a disc electrode D3
which is kept at a fixed distance on the axis of the other
low voltage electrodes D2, D1, and D0.
14
Generating Voltmeter
 The rotor D0 is driven at a suitable constant speed by a synchronous motor.
 Rotor vanes of D0 cause periodic change in capacitance between the insulated disc D2 and the
high voltage electrode D3.
 Number and shape of vanes are so designed that a suitable variation of capacitance (sinusodial
or linear) is achieved.
 The a.c. current is rectified and is measured using moving coil meters. If the current is small an
amplifier may be used before the current is measured.
8/8/2022
 Generating voltmeters are linear scale instruments and applicable over a wide range of
voltages.
 The sensitivity can be increased by increasing the area of the pick up electrode and by using
amplifier circuits
 Advantages:
i. scale is linear and can be extrapolated
ii. source loading is practically zero
iii. no direct connection to the high voltage electrode.
15
Generating Voltmeter
8/8/2022
Measurement Of High Ac Voltage
16
 Electrostatic voltmeter
 Series impedance voltmeter
 Potential dividers : Resistance or Capacitance type
 Potential transformers : Electromagnetic or CVT
 Sphere gaps
8/8/2022
Electrostatic Voltmeter
 One of the direct methods of measuring high
voltages is by means of electro-static voltmeters.
 For voltages above 10 kV, generally the attracted
disc type of electrostatic voltmeter is used.
 When two parallel conducting plates (cross
section area ‘A’ and spacing ‘s’) are charged q and
have a potential difference V, then the energy
stored in the is given by
17
Newton
s
V
A
2
1
F
s
A
ds
dC
s
A
C
e,
capacitanc
field
uniform
For
Newton
ds
dC
V
2
1
F
Force,
ds
F
dC
V
dW
CV
W
2
2



























2
2
2
2
ε
ε
ε
2
1
2
1
 It is thus seen that the force of attraction is proportional to the square of the potential difference
applied, so that the meter reads the square value (or can be marked to read the rms value).
8/8/2022
Electrostatic Voltmeter
 Electrostatic voltmeters of the attracted disc type may be connected across the high
voltage circuit directly to measure up to about 200 kV, without the use of any
potential divider or other reduction method. [The force in these electrostatic
instruments can be used to measure both a.c. and d.c. voltages].
 The right hand electrode forms the high voltage plate.
 The centre portion of the left hand disc is cut away and encloses a small disc which
is movable and is geared to the pointer of the instrument.
 The range of the instrument can be altered by setting the right hand disc at pre-
marked distances.
 The force of attraction F(t) created by the applied voltage causes the movable part-to
which a mirror is attached-to assume a position at which a balance of forces takes
place.
 An incident light beam will therefore be reflected toward a scale calibrated to read
the applied voltage magnitude.
18 8/8/2022
 Advantages:
i. Low loading effect
ii. Active power losses are negligibly small
iii. Voltage source loading is limited to the reactive power needed to
charge the system capacitance.(i.e., For 1V Voltmeter-
Capacitance is few Pico farad)
iv. Voltages upto 600kV can be measured.
 Disadvantage:
i. For constant distance ‘s’, F α V2, the sensitivity is small. This can
be overcome by varying the gap distance d in appropriate steps.
19
Electrostatic Voltmeter
Absolute Electrostatic Voltmeter
8/8/2022
Series Impedance Voltmeter
 For power frequency a.c. measurements the series impedance may be a pure
resistance or a reactance.
 But use of resistances yields the followings,
 Power losses
 Temperature problem
 Residual inductance of the resistance gives rise to an impedance different from its ohmic
resistance.
 High resistance units for high voltages have stray capacitances and hence a unit
resistance will have an equivalent circuit as shown in Fig.
 At any frequency ω of the a.c. voltage, R+jXL is connected in parallel with –jXC.
20
 
 
 
 
CR
j
L
j
R
Z
CR
j
LC
Since
CR
j
LC
L
j
R
C
j
L
j
R
C
j
L
j
R
Z
ω
1
ω
,
ω
ω
,
ω
ω
1
ω
ω
1
ω
ω
1
ω
2
2













8/8/2022
Series Impedance Voltmeter
 






































CR
R
L
angle
Phase
where
CR
R
L
j
R
CR
j
L
j
R
Z
R
C
LCR
CR
j
L
j
R
Z
CR
j
CR
j
CR
j
L
j
R
Z
ω
ω
tan
φ
,
,
ω
ω
1
ω
ω
ω
1
ω
ω
ω
ω
1
ω
1
ω
1
ω
1
2
2
2
2
2
2
 Extended Series Resistance neglecting inductance is shown in figures.
 Resistor unit then has to be taken as a transmission line equivalent, for calculating
the effective resistance.
 Ground or stray capacitance of each element influences the current flowing in the
unit, and the indication of the meter results in an error.
 Stray ground capacitance effects can be removed by shielding the resistor ‘R’ by a
second surrounding spiral RS which shunts the actual resistor but does not
contribute to the current through the instrument.
21 8/8/2022
 By tuning the resistors Ra the shielding resistor end potentials may be adjusted with
respect to the actual measuring resistor so that the resulting compensation currents
between the shield and the measuring resistors provide a minimum phase angle.
22
Series Impedance Voltmeter
8/8/2022
Series Capacitance Voltmeter
 To avoid the drawbacks pointed out Series impedance voltmeter, a series
capacitor is used instead of a resistor for a.c. high voltage measurements.
 Current through the instrument, Ic=jωCV
 The rms value of the voltage V with harmonics is given by,
where V1,V2 ,... ,Vn represent the rms value of the fundamental, second...
and nth harmonics.
 The currents due to these harmonics are
I1=ωCV1 , I2=2ωCV2 , ……In=nωCVn
 With a 10% fifth harmonic only, the current is 11.2% higher, and hence
the error is 11.2% in the voltage measurement
 Not recommended when a.c. voltages are not pure sinusoidal waves but
contain considerable harmonics.
 Used for measuring rms values up to 1000 kV.
23
2
2
2
2
1 n
rms V
V
V
V 


 
   2
2
2
2
1 2
ω n
rms nV
V
V
C
I 


 
8/8/2022
Series Capacitance Voltmeter
 A rectifier ammeter was used as an indicating instrument and was directly calibrated
in high voltage rms value.
 The meter was usually a (0-100)μA moving coil meter and the over all error was
about 2%.
24 8/8/2022
Peak Reading Voltmeters
 For Sine wave,
 Peak Value=RMS Value X 2
 Maximum dielectric strength may be obtained by non-sine wave. In that case,
 Peak Value ≠ RMS Value X 2
 Therefore, peak measurement is important.
 Types:
 Series Capacitance Peak Voltmeter (Chubb-Frotscue Method)
 Digital Peak Voltmeter
 Peak Voltmeter with potential divider
25 8/8/2022
Peak Reading Voltmeters
Chubb Frotscue Method:
 Chubb and Fortescue suggested a simple and accurate
method of measuring peak value of a.c. voltages.
 The basic circuit consists of a standard capacitor, two diodes
and a current integrating ammeter (MC ammeter) as shown
in Fig. 4.11 (a).
 The displacement current ic(t), Fig. 4.12 is given by the rate
of change of the charge and hence the voltage V(t) to be
measured flows through the high voltage capacitor C and is
subdivided into positive and negative components by the
back to back connected diodes
 The voltage drop across these diodes can be neglected (1 V for Si diodes) as compared with
the voltage to be measured
 The measuring instrument (M.C. ammeter) is included in one of the branches. The
ammeter reads the mean value of the current,
 An increased current would be obtained if the current reaches zero more than once during
one half cycle
26 8/8/2022
27
(Chubb Frotscue Method Continued…)
 This means the wave shapes of the voltage would contain more than one maxima per half cycle.
 The standard a.c. voltages for testing should not contain any harmonics and, therefore, there could
be very short and rapid voltages caused by the heavy predischarges, within the test circuit which
could introduce errors in measurements.
 To eliminate this problem filtering of a.c. voltage is carried out by introducing a damping resistor
in between the capacitor and the diode circuit, Fig. 4.11 (b).
 The measurement of symmetrical a.c. voltages using Chubb and Fortescue method is quite
accurate and it can be used for calibration of other peak voltage measuring devices.
Peak Reading Voltmeters
8/8/2022
28
Digital Peak Voltmeter:
 In contrast to the method discussed just now, the rectified current is not
measured directly, instead a proportional analog voltage signal is derived
which is then converted into a proportional medium frequency for using a
voltage to frequency convertor (Block A in Fig. 4.13).
 The frequency ratio fm/f is measured with a gate circuit controlled by the a.c.
power frequency (supply frequency f) and a counter that opens for an
adjustable number of period Δt = p/f. The number of cycles n counted during
this interval is
 where ‘p’ is a constant of the instrument.
Peak Reading Voltmeters
8/8/2022
29
 
C
f
V
2
to
nal
proportio
i
i.e.,
C
f
π
2
V
X
V
i
AP
CR
2V
n
Therefore,
A
CR
2V
f
f
i.e.,
C
V
2R
1
f
f
R
through
Current
Rectified
i
C
f
V
2
R
f
Ri
f
A
factor
convertion
frequency
to
Voltage
m
m
m
C
m
m
m
m
m
m
m
m
m
m
m
m














 By proper selection of R and P, Voltage can be measured immediately.
 Accuracy is less than 0.35%
Digital Peak Voltmeter continued….
Peak Reading Voltmeters
8/8/2022
30
Peak voltmeter with Potential divider:
 Diode D is used for rectification
 Voltage across C2 is used to charge C3
 Resistance Rd permits the variation of Vm when
V2 is reduced
 Electrostatic Voltmeter as indicating instrument
 Voltage across Cs  Peak value to be measured
 Discharge time constant=CsRd1 to 10 sec
 This arrangement gives discharge error.
 Discharge error depends on frequency of the supply
Peak Reading Voltmeters
8/8/2022
Measurement of High Currents
Type of Current Method used
D.C Current 1. Resistant shunt
2. Hall Generator
High Power frequency A.C Current Transformer with electro-optical
technique
High frequency and impulse currents 1. Resistive shunts
2. Magnetic potentiometers or probes
3. Magnetic links
4. Hall generators
5. Faraday Generators
Impulse Voltages and Currents Cathode Ray Oscilloscope
31 8/8/2022
Hall Generators
 Hall effect is used to measure very
high direct current.
 Whenever electric current flows
through a metal plate placed in a
magnetic field perpendicular to it,
Lorenz force will deflect the electrons
in the metal structure in a direction
perpendicular to the direction of both
the magnetic field and the flow of
current.
 The change in displacement generates
an e.m.f called “Hall Voltage”
32 8/8/2022
 Hall Voltage,
where, B-Magnetic Flux density
I-Current
d-Thickness of the metal plate
R-Hall Coefficient (depends on
Material of the plate &
temperature)
R is small for metals and High for
semiconductors
33
Hall Generators
d
BI
R
V
d
BI
α
V
H
H


 When large d.c. currents are to be measured the current
carrying conductor is passed through an iron cored magnetic
circuit
8/8/2022
 The magnetic field intensity produced by the conductor in the
air gap at a depth ‘d’ is given by,
 The Hall element is placed in the air gap and a small constant
d.c. current is passed through the element.
 The voltage developed across the Hall element is measured and
by using the expression for Hall voltage the flux density B is
calculated and hence the value of current I is obtained.
34
d
2
1
H


Hall Generators
8/8/2022
Faraday Generator or Magneto Optic Method
 These methods of current measurement use the rotation of the plane
of polarisation in materials by the magnetic field which is
proportional to the current (Faraday effect).
 When a linearly polarised light beam passes through a transparent
crystal in the presence of a magnetic field, the plane of polarisation
of the light beam undergoes rotation. The angle of rotation is given
by,
θ = α Bl
where,
α = A constant of the cyrstal which is a function of the wave length of the
light.
B = Magnetic flux density due to the current to be measured in this case.
l = Length of the crystal.
35 8/8/2022
 Fig. shows a schematic diagram of Magneto-optic method.
 Crystal C is placed parallel to the magnetic field produced by the
current to be measured.
 A beam of light from a stabilised light source is made incident on the
crystal C after it is passed through the polariser P1.
 The light beam undergoes rotation of its plane of polarisation.
 After the beam passes through the analyser P2, the beamis focussed on a
photomultiplier, the output of which is fed to a CRO.
36
Faraday Generator or Magneto Optic Method
8/8/2022
 The filter F allows only the monochromatic light to pass through it.
Photoluminescent diodes too, the momentary light emission of which is
proportional to the current flowing through them, can be used for
current measurement.
 Advantages:
1. It provides isolation of the measuring set up from the main current circuit.
2. It is insensitive to overloading.
3. As the signal transmission is through an optical system no insulation problem is
faced. However, this device does not operate for D.C current.
37
Faraday Generator or Magneto Optic Method
8/8/2022
Magnetic Potentiometer(Rogowski Coil)
 If the current to be measured is flowing through a conductor which is
surrounded by a coil as shown in Fig.
 and M is the mutual inductance between the coil and the conductor, the
voltage across the coil terminals will be:
 Usually the coil is wound on a non-magnetic former in the form of a
toroid and has a large number of turns, to have sufficient voltage
induced which could be recorded.
38
dt
di
M
v(t) 
8/8/2022
 The coil is wound cross-cross to reduce the leakage inductance.
 If N is the number of turns of the coil, A the coil area and lm its mean
length, the mutual inductance is given by
 Usually an integrating circuit RC is employed as shown in Fig to obtain
the output voltage proportional to the current to be measured. The
output voltage is given by
 The frequency response of the Rogowski coil is flat upto 100 MHz but
beyond that it is affected by the stray electric and magnetic fields and
also by the skin effect.
39
m
0
l
NA
μ
M 
i(t)
RC
M
di
RC
M
dt
dt
di
M
RC
1
v(t)dt
RC
1
(t)
v
t
0
0 

 




Magnetic Potentiometer(Rogowski Coil)
8/8/2022
Resistive Shunt
40 8/8/2022
SERIES IMPEDANCE VOLTMETER
41
Extended series
impedance with
inductance
neglected
8/8/2022
SERIES CAPACITOR PEAK
VOLTMETER
42
C – capacitor
D1,D2 – Diodes
OP – Protective devices
I – indicating meter
V(t) – voltage waveform
Ic(t) – capacitor current
waveform
T – period
8/8/2022
PEAK READING AC VOLTMETER
43 8/8/2022
PEAK READING AC VOLTMETER
44 8/8/2022
SPHERE GAPS MEASUREMENT
45
Ub = kd Ub0
8/8/2022
SPHERE GAPS
46 8/8/2022
Potential divider for impulse voltage
measurement
47 8/8/2022
MEASUREMENT OF HIGH DIRECT CURRENTS
48
HALL GENERATORS FOR D.C CURRENT MEASUREMENTS
 Hall effect principle is used.If an electric current flows through a metal plate
located in a magnetic field perpendicular to it,Lorenz forces will deflect the
electrons in the metal structure in a direction normal to the direction of both
the current and magnetic field.
 The charge displacement generates an emf in the normal direction (Hall
voltage).
 VH=RBi/d
 H=I/δ
8/8/2022
MEASUREMENT OF HIGH POWER FREQUENCY
ALTERNATING CURRENTS
49
 Current transformer is used.it uses electro optical technique.
 A voltage signal proportional to the measuring current is generated and it is
transmitted to the ground side through electro optical device.
 Light pulses proportional to the voltage signal are transmitted by a glass
optical fibre bundle to a photo detector and converted back into an analog
voltage signal.
8/8/2022
SPHERE GAP
 The sphere gap method of measuring high voltage is the most reliable and is used as the
standard for calibration purposes.
 breakdown strength of a gas depends on the ionisation of the gas molecules, and on the density
of the gas.
 As such, the breakdown voltage varies with the gap spacing; and for a uniform field gap, a
high consistency could be obtained, so that the sphere gap is very useful as a measuring
device.
 In the measuring device, two metal spheres are used, separated by a gas-gap. The potential
difference between the spheres is raised until a spark passes between them.
 The breakdown strength of a gas depends on the size of the spheres, their distance apart and a
number of other factors.
 A spark gap may be used for the determination of the peak value of a voltage wave, and for the
checking and calibrating of voltmeters and other voltage measuring devices.
 The density of the gas (generally air) affects the spark-over voltage for a given gap setting.
 Thus the correction for any air density change must be made. The air density correction factor
δ must be used.
50 8/8/2022
 The spark over voltage for a given gap setting under the standard conditions (760
torr pressure and at 20oC) must be multiplied by the correction factor to obtain the
actual spark-over voltage.
 The breakdown voltage of the sphere gap (Figure:a) is almost independent of
humidity of the atmosphere, but the presence of dew on the surface lowers the
breakdown voltage and hence invalidates the calibrations.
 The breakdown voltage characteristic (figure 6.3) has been determined for similar
pairs of spheres (diameters 62.5 mm, 125 mm, 250 mm, 500 mm, 1 m and 2 m)
51
Fig.b:Breakdown voltage characteristic of sphere gaps
Figure. a:- Measuring spheres
SPHERE GAP
8/8/2022
 In sphere gaps used in measurement, to obtain high accuracy, the
minimum clearance to be maintained between the spheres and the
neighbouring bodies and the diameter of shafts are also specified, since
these also affect the accuracy (Figure:d).
 There is also a tolerance specified for the radius of curvature of the
spheres.
 Peak values of voltages may be measured from 2 kV up to about 2500
kV by means of spheres.
 One sphere may be earthed with the other being the high voltage
electrode, or both may be supplied with equal positive and negative
voltages with respect to earth (symmetrical gap).
 Needle gaps may also be used in the measurement of voltages up to
about 50 kV, but errors are caused by the variation of the sharpness of
the needle gaps, and by the corona forming at the points before the gap
actually sparks over.
 Also the effect of the variation of the humidity of the atmosphere on
such gaps is much greater.
52
SPHERE GAP
Figure. d: Sphere gap
8/8/2022
 When the gap distance is increased, the uniform field between the spheres becomes
distorted, and accuracy falls.
 The limits of accuracy are dependant on the ratio of the spacing d to the sphere
diameter D, as follows:
 d < 0.5 D Accuracy = ± 3 %
 0.75 D > d > 0.5 D Accuracy = ± 5 %
 For accurate measurement purposes, gap distances in excess of 0.75D are not used
 Breakdown voltage characteristic is also dependant on the polarity of the high
voltage sphere in the case of asymmetrical gaps, in a symmetrical gap, then the
polarity has no effect.
53 Figure . C:- Breakdown voltage characteristics 8/8/2022

More Related Content

What's hot

Chapter 06 - Generation of High Direct Current Voltages
Chapter 06 - Generation of High Direct Current VoltagesChapter 06 - Generation of High Direct Current Voltages
Chapter 06 - Generation of High Direct Current Voltages
MUET SZAB Campus Khairpur Mir's Sindh Pakistan
 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
Vinod Srivastava
 
Chapter 2 breakdown in liquids
Chapter 2 breakdown in liquidsChapter 2 breakdown in liquids
Chapter 2 breakdown in liquids
mukund mukund.m
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllersAyyarao T S L V
 
Introduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerIntroduction to reactive power control in electrical power
Introduction to reactive power control in electrical power
Dr.Raja R
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1
JayakalyanReddy
 
Voltage and Frequency Control of the Grid
Voltage and Frequency Control of the GridVoltage and Frequency Control of the Grid
Voltage and Frequency Control of the Grid
Leonardo ENERGY
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
Rahul Aman
 
Methods of voltage control
Methods of voltage controlMethods of voltage control
Methods of voltage control
v Kalairajan
 
Power Quality
Power QualityPower Quality
Power Quality
Elshemy Mohamed
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
Kabilesh K
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
PremanandDesai
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
jawaharramaya
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
PremanandDesai
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
Chandan Singh
 
surge diverters
surge diverterssurge diverters
surge diverters
nehakardam
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
MUET SZAB Campus Khairpur Mir's Sindh Pakistan
 
Chapter1 breakdown in gases
Chapter1 breakdown in gasesChapter1 breakdown in gases
Chapter1 breakdown in gases
mukund mukund.m
 
Streamer theory of breakdown
Streamer theory of breakdownStreamer theory of breakdown
Streamer theory of breakdown
vishalgohel12195
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
Karthik Bharadwaj
 

What's hot (20)

Chapter 06 - Generation of High Direct Current Voltages
Chapter 06 - Generation of High Direct Current VoltagesChapter 06 - Generation of High Direct Current Voltages
Chapter 06 - Generation of High Direct Current Voltages
 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
 
Chapter 2 breakdown in liquids
Chapter 2 breakdown in liquidsChapter 2 breakdown in liquids
Chapter 2 breakdown in liquids
 
Basic types of facts controllers
Basic types of facts controllersBasic types of facts controllers
Basic types of facts controllers
 
Introduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerIntroduction to reactive power control in electrical power
Introduction to reactive power control in electrical power
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1
 
Voltage and Frequency Control of the Grid
Voltage and Frequency Control of the GridVoltage and Frequency Control of the Grid
Voltage and Frequency Control of the Grid
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Methods of voltage control
Methods of voltage controlMethods of voltage control
Methods of voltage control
 
Power Quality
Power QualityPower Quality
Power Quality
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
surge diverters
surge diverterssurge diverters
surge diverters
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
 
Chapter1 breakdown in gases
Chapter1 breakdown in gasesChapter1 breakdown in gases
Chapter1 breakdown in gases
 
Streamer theory of breakdown
Streamer theory of breakdownStreamer theory of breakdown
Streamer theory of breakdown
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
 

Similar to unit-iii- Sphere Gap.ppt

Dc voltage
Dc voltageDc voltage
Dc voltage
sarunkutti
 
eem-2020309.pdf
eem-2020309.pdfeem-2020309.pdf
eem-2020309.pdf
SACHCHIDANAND JHA
 
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET Journal
 
Frequency dependency analysis for differential capacitive sensor
Frequency dependency analysis for differential capacitive sensorFrequency dependency analysis for differential capacitive sensor
Frequency dependency analysis for differential capacitive sensor
journalBEEI
 
High voltage module
High voltage moduleHigh voltage module
High voltage module
GARANG MABIOR
 
Comparision methods of measurements
Comparision methods of measurementsComparision methods of measurements
Comparision methods of measurements
PrabhaMaheswariM
 
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATORUNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
ijiert bestjournal
 
Ac voltage
Ac voltageAc voltage
Ac voltage
sarunkutti
 
Ac voltage
Ac voltageAc voltage
Ac voltage
sarunkutti
 
Mw &dc lab (90) iv i
Mw &dc lab (90) iv iMw &dc lab (90) iv i
Mw &dc lab (90) iv i
Prabhu Kiran
 
“Microcontroller Based Substation Monitoring system with gsm modem”.
“Microcontroller Based Substation Monitoring system with gsm modem”.“Microcontroller Based Substation Monitoring system with gsm modem”.
“Microcontroller Based Substation Monitoring system with gsm modem”.
Priya Rachakonda
 
AC and DC BridgePPT for engineering students
AC and DC BridgePPT for engineering studentsAC and DC BridgePPT for engineering students
AC and DC BridgePPT for engineering students
National Institute of Technolgy(REC) warangal
 
STRAIN GAUGES-ppt1.ppt
STRAIN GAUGES-ppt1.pptSTRAIN GAUGES-ppt1.ppt
STRAIN GAUGES-ppt1.ppt
JehadYamin1
 
dt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdfdt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdf
ssuserbfa471
 
Av335 instrumentation lab report
Av335 instrumentation lab reportAv335 instrumentation lab report
Av335 instrumentation lab reportGaurav Vaibhav
 
Measurement of resistance
Measurement of resistanceMeasurement of resistance
Measurement of resistance
ANKUR GHEEWALA
 
Simple 100 w inverter circuit
Simple 100 w inverter circuitSimple 100 w inverter circuit
Simple 100 w inverter circuit
Narasimha Reddy
 
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
IRJET Journal
 

Similar to unit-iii- Sphere Gap.ppt (20)

Dc voltage
Dc voltageDc voltage
Dc voltage
 
eem-2020309.pdf
eem-2020309.pdfeem-2020309.pdf
eem-2020309.pdf
 
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
 
Frequency dependency analysis for differential capacitive sensor
Frequency dependency analysis for differential capacitive sensorFrequency dependency analysis for differential capacitive sensor
Frequency dependency analysis for differential capacitive sensor
 
2 dc meter
2 dc meter 2 dc meter
2 dc meter
 
High voltage module
High voltage moduleHigh voltage module
High voltage module
 
Comparision methods of measurements
Comparision methods of measurementsComparision methods of measurements
Comparision methods of measurements
 
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATORUNDERGROUND CABLE FAULT DISTANCE LOCATOR
UNDERGROUND CABLE FAULT DISTANCE LOCATOR
 
Ac voltage
Ac voltageAc voltage
Ac voltage
 
Ac voltage
Ac voltageAc voltage
Ac voltage
 
Mw &dc lab (90) iv i
Mw &dc lab (90) iv iMw &dc lab (90) iv i
Mw &dc lab (90) iv i
 
“Microcontroller Based Substation Monitoring system with gsm modem”.
“Microcontroller Based Substation Monitoring system with gsm modem”.“Microcontroller Based Substation Monitoring system with gsm modem”.
“Microcontroller Based Substation Monitoring system with gsm modem”.
 
AC and DC BridgePPT for engineering students
AC and DC BridgePPT for engineering studentsAC and DC BridgePPT for engineering students
AC and DC BridgePPT for engineering students
 
STRAIN GAUGES-ppt1.ppt
STRAIN GAUGES-ppt1.pptSTRAIN GAUGES-ppt1.ppt
STRAIN GAUGES-ppt1.ppt
 
dt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdfdt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdf
 
3059
30593059
3059
 
Av335 instrumentation lab report
Av335 instrumentation lab reportAv335 instrumentation lab report
Av335 instrumentation lab report
 
Measurement of resistance
Measurement of resistanceMeasurement of resistance
Measurement of resistance
 
Simple 100 w inverter circuit
Simple 100 w inverter circuitSimple 100 w inverter circuit
Simple 100 w inverter circuit
 
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
 

Recently uploaded

Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
ankuprajapati0525
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdfGoverning Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
WENKENLI1
 
Investor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptxInvestor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptx
AmarGB2
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
Kerry Sado
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
SupreethSP4
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
ydteq
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
AP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specificAP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specific
BrazilAccount1
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
Jayaprasanna4
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 

Recently uploaded (20)

Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdfGoverning Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
 
Investor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptxInvestor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptx
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
AP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specificAP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specific
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 

unit-iii- Sphere Gap.ppt

  • 1. Mesurement Of High Voltages & High Currents Unit 3
  • 2. High Voltage Measurement Techniques 2 8/8/2022
  • 3. Sphere Gaps  Applicatios:  Voltage Measurement (Peak) - Peak values of voltages may be measured from 2 kV up to about 2500 kV by means of spheres.  Arrangements: 1. Vertically with lower sphere grounded (For Higher Voltages) 2. Horizontally with both spheres connected to the source voltage or one sphere grounded (For Lower Voltages). 3 8/8/2022
  • 4.  The arrangement is selected based on the relation between the peak voltage, determined by sparkover between the spheres, and the reading of a voltmeter on the primary or input side of the high-voltage source. This relation should be within 3% (IEC, 1973).  Standard values of sphere diameter are 6.25, 12.5, 25, 50, 75, 100, 150, and 200 cm.  The Clearance around the sphere gaps: 4 Sphere Gaps Fig C :Breakdown voltage characteristic of sphere gaps 8/8/2022
  • 5.  The effect of humidity is to increase the breakdown voltage of sphere gaps by up to 3%.  Temperature and pressure, however, havea significant influenceo n breakdown voltage.  Breakdown Voltage under normal atmospheric conditions is, Vs=kVn where k is a factor related to the relative air density (RAD) δ.  The relation between the RAD(δ) and the correction factor k:  Under impulse voltages, the voltage at which there is a 50% breakdown probability is recognized as the breakdown level. 5 Sphere Gaps 8/8/2022
  • 6.  Factors Influencing the Sparkover Voltage of Sphere Gaps i. Nearby earthed objects, ii. Atmospheric conditions and humidity, iii. Irradiation, and iv. Polarity and rise time of voltage waveforms.  The limits of accuracy are dependant on the ratio of the spacing d to the sphere diameter D, as follows:  d < 0.5 D Accuracy = ± 3 %  0.75 D > d > 0.5 D Accuracy = ± 5 %  For accurate measurement purposes, gap distances in excess of 0.75D are not used 6 Sphere Gaps 8/8/2022
  • 7. High Ohmic Series Resistance with Microammeter  Resistance (R) :  Constructed with large wire wound  Value: Few hundreds of Mega ohms –Selected to give (1-10μA) for FSD.  Voltage drop in each element is chosen to avoid surface flashovers and discharges (5kV/cm in air, 20kV/cm in oil is allowed)  Provided with corona free terminals.  Material: Carbon alloy with temperature coefficient of 10-4/oC .  Resistance chain located in air tight oil filled PVC tube for 100kV operation with good temp stability.  Mircoammeter – MC type  Voltage of source, V=IR  Impedance of the meter is few ohms. i.e, very less compared to R so the drop across the meter is negligible.  Protection: Paper gap, Neon Glow tube, a zener diode with series resistance – Gives protection when R fails. 7 8/8/2022
  • 8.  Maximum voltage: 500kV with  0.2% accuracy.  Limitations:  Power dissipation & source loading  Temp effects & 8 High Ohmic Series Resistance with Microammeter 8/8/2022
  • 9. Measurement Of High Dc Voltage 9  Series resistance micrometer  Resistance potential divider  Generating voltmeter  Sphere and other gaps 8/8/2022
  • 10. SERIES RESISTANCE MICROMETER 10  A very high resistance in series with a micrometer.  Current through R is measured using micrometer.  Voltage of source, V = IR  The resistance is constructed from a large no. of wire wound resistors in series.  Can be operated upto 500kV (D.C)  Accuracy = ±0.2%  Selection of R value:  Current allowed: 1 to 10A  Corona free termination  Temp. coefficient<10-4/0C : Carbon Alloy  Placed in airtight, oil filled PVC tube to maintain temp. stability 8/8/2022
  • 11. RESISTANCE POTENTIAL DIVIDER 11  It uses electrostatic voltmeter.  Can be placed near the test object which might not always be confined to one location  Let, V2-Voltage across R2  Sudden voltage changes during transients due to:  Switching operation  Flashover of test objects  Damage due to stray capacitance across the elements & ground capacitance 2 2 1 2 1 2 1 2 1 2 R ) R (R X V V magnitude, voltage High ) R (R R X V V     8/8/2022
  • 12. GENERATING VOLTMETER 12  Generating principle is used where direct loading or direct connection is to be avoided.  Generating voltmeter: A variable capacitor electrostatic voltage generator.  It generates current proportional to voltage under measurement  This arrangement provides loss free measurement of DC and AC voltages  It is driven by synch. motor, so doesn’t observe power from the voltage measuring source  The high voltage electrode and the grounded electrode in fact constitute a capacitance system.  The capacitance is a function of time as the area A varies with time and, therefore, the charge q(t) is given as, 8/8/2022
  • 13. 13 and, For d.c. Voltages, Hence If the capacitance varies linearly with time and reaches its peak value Cm is time Tc /2 and again reduces to zero linearly in time Tc /2, the capacitance is given as If the capacitance C varies sinusoidally between the limits C0 and (C0 + Cm) then C = C0 + Cm sin ωt and the current ‘i' is then given as, i(t) = im cos ω t , where im = VCmω Here ω is the angular frequency of variation of the capacitance.  Generally the current is rectified and measured by a moving coil meter  Generating voltmeters can be used for a.c. voltage measurement also provided the angular frequency ω is the same or equal to half that of the voltage being measured.  Above fig. shows the variations of C as a function of time together with a.c. voltage, the frequency of which is twice the frequency of C (t). GENERATING VOLTMETER 8/8/2022
  • 14.  Instantaneous value of current i(t) = Cm fvV(t)  where fv = 1/Tv the frequency of voltage.  Since fv = 2fc and fc = 60/n we obtain, I(t) = n/30 CmV(t)  Fig. shows a schematic diagram of a generating voltmeter which employs rotating vanes for variation of capacitance  High voltage electrode is connected to a disc electrode D3 which is kept at a fixed distance on the axis of the other low voltage electrodes D2, D1, and D0. 14 Generating Voltmeter  The rotor D0 is driven at a suitable constant speed by a synchronous motor.  Rotor vanes of D0 cause periodic change in capacitance between the insulated disc D2 and the high voltage electrode D3.  Number and shape of vanes are so designed that a suitable variation of capacitance (sinusodial or linear) is achieved.  The a.c. current is rectified and is measured using moving coil meters. If the current is small an amplifier may be used before the current is measured. 8/8/2022
  • 15.  Generating voltmeters are linear scale instruments and applicable over a wide range of voltages.  The sensitivity can be increased by increasing the area of the pick up electrode and by using amplifier circuits  Advantages: i. scale is linear and can be extrapolated ii. source loading is practically zero iii. no direct connection to the high voltage electrode. 15 Generating Voltmeter 8/8/2022
  • 16. Measurement Of High Ac Voltage 16  Electrostatic voltmeter  Series impedance voltmeter  Potential dividers : Resistance or Capacitance type  Potential transformers : Electromagnetic or CVT  Sphere gaps 8/8/2022
  • 17. Electrostatic Voltmeter  One of the direct methods of measuring high voltages is by means of electro-static voltmeters.  For voltages above 10 kV, generally the attracted disc type of electrostatic voltmeter is used.  When two parallel conducting plates (cross section area ‘A’ and spacing ‘s’) are charged q and have a potential difference V, then the energy stored in the is given by 17 Newton s V A 2 1 F s A ds dC s A C e, capacitanc field uniform For Newton ds dC V 2 1 F Force, ds F dC V dW CV W 2 2                            2 2 2 2 ε ε ε 2 1 2 1  It is thus seen that the force of attraction is proportional to the square of the potential difference applied, so that the meter reads the square value (or can be marked to read the rms value). 8/8/2022
  • 18. Electrostatic Voltmeter  Electrostatic voltmeters of the attracted disc type may be connected across the high voltage circuit directly to measure up to about 200 kV, without the use of any potential divider or other reduction method. [The force in these electrostatic instruments can be used to measure both a.c. and d.c. voltages].  The right hand electrode forms the high voltage plate.  The centre portion of the left hand disc is cut away and encloses a small disc which is movable and is geared to the pointer of the instrument.  The range of the instrument can be altered by setting the right hand disc at pre- marked distances.  The force of attraction F(t) created by the applied voltage causes the movable part-to which a mirror is attached-to assume a position at which a balance of forces takes place.  An incident light beam will therefore be reflected toward a scale calibrated to read the applied voltage magnitude. 18 8/8/2022
  • 19.  Advantages: i. Low loading effect ii. Active power losses are negligibly small iii. Voltage source loading is limited to the reactive power needed to charge the system capacitance.(i.e., For 1V Voltmeter- Capacitance is few Pico farad) iv. Voltages upto 600kV can be measured.  Disadvantage: i. For constant distance ‘s’, F α V2, the sensitivity is small. This can be overcome by varying the gap distance d in appropriate steps. 19 Electrostatic Voltmeter Absolute Electrostatic Voltmeter 8/8/2022
  • 20. Series Impedance Voltmeter  For power frequency a.c. measurements the series impedance may be a pure resistance or a reactance.  But use of resistances yields the followings,  Power losses  Temperature problem  Residual inductance of the resistance gives rise to an impedance different from its ohmic resistance.  High resistance units for high voltages have stray capacitances and hence a unit resistance will have an equivalent circuit as shown in Fig.  At any frequency ω of the a.c. voltage, R+jXL is connected in parallel with –jXC. 20         CR j L j R Z CR j LC Since CR j LC L j R C j L j R C j L j R Z ω 1 ω , ω ω , ω ω 1 ω ω 1 ω ω 1 ω 2 2              8/8/2022
  • 21. Series Impedance Voltmeter                                         CR R L angle Phase where CR R L j R CR j L j R Z R C LCR CR j L j R Z CR j CR j CR j L j R Z ω ω tan φ , , ω ω 1 ω ω ω 1 ω ω ω ω 1 ω 1 ω 1 ω 1 2 2 2 2 2 2  Extended Series Resistance neglecting inductance is shown in figures.  Resistor unit then has to be taken as a transmission line equivalent, for calculating the effective resistance.  Ground or stray capacitance of each element influences the current flowing in the unit, and the indication of the meter results in an error.  Stray ground capacitance effects can be removed by shielding the resistor ‘R’ by a second surrounding spiral RS which shunts the actual resistor but does not contribute to the current through the instrument. 21 8/8/2022
  • 22.  By tuning the resistors Ra the shielding resistor end potentials may be adjusted with respect to the actual measuring resistor so that the resulting compensation currents between the shield and the measuring resistors provide a minimum phase angle. 22 Series Impedance Voltmeter 8/8/2022
  • 23. Series Capacitance Voltmeter  To avoid the drawbacks pointed out Series impedance voltmeter, a series capacitor is used instead of a resistor for a.c. high voltage measurements.  Current through the instrument, Ic=jωCV  The rms value of the voltage V with harmonics is given by, where V1,V2 ,... ,Vn represent the rms value of the fundamental, second... and nth harmonics.  The currents due to these harmonics are I1=ωCV1 , I2=2ωCV2 , ……In=nωCVn  With a 10% fifth harmonic only, the current is 11.2% higher, and hence the error is 11.2% in the voltage measurement  Not recommended when a.c. voltages are not pure sinusoidal waves but contain considerable harmonics.  Used for measuring rms values up to 1000 kV. 23 2 2 2 2 1 n rms V V V V         2 2 2 2 1 2 ω n rms nV V V C I      8/8/2022
  • 24. Series Capacitance Voltmeter  A rectifier ammeter was used as an indicating instrument and was directly calibrated in high voltage rms value.  The meter was usually a (0-100)μA moving coil meter and the over all error was about 2%. 24 8/8/2022
  • 25. Peak Reading Voltmeters  For Sine wave,  Peak Value=RMS Value X 2  Maximum dielectric strength may be obtained by non-sine wave. In that case,  Peak Value ≠ RMS Value X 2  Therefore, peak measurement is important.  Types:  Series Capacitance Peak Voltmeter (Chubb-Frotscue Method)  Digital Peak Voltmeter  Peak Voltmeter with potential divider 25 8/8/2022
  • 26. Peak Reading Voltmeters Chubb Frotscue Method:  Chubb and Fortescue suggested a simple and accurate method of measuring peak value of a.c. voltages.  The basic circuit consists of a standard capacitor, two diodes and a current integrating ammeter (MC ammeter) as shown in Fig. 4.11 (a).  The displacement current ic(t), Fig. 4.12 is given by the rate of change of the charge and hence the voltage V(t) to be measured flows through the high voltage capacitor C and is subdivided into positive and negative components by the back to back connected diodes  The voltage drop across these diodes can be neglected (1 V for Si diodes) as compared with the voltage to be measured  The measuring instrument (M.C. ammeter) is included in one of the branches. The ammeter reads the mean value of the current,  An increased current would be obtained if the current reaches zero more than once during one half cycle 26 8/8/2022
  • 27. 27 (Chubb Frotscue Method Continued…)  This means the wave shapes of the voltage would contain more than one maxima per half cycle.  The standard a.c. voltages for testing should not contain any harmonics and, therefore, there could be very short and rapid voltages caused by the heavy predischarges, within the test circuit which could introduce errors in measurements.  To eliminate this problem filtering of a.c. voltage is carried out by introducing a damping resistor in between the capacitor and the diode circuit, Fig. 4.11 (b).  The measurement of symmetrical a.c. voltages using Chubb and Fortescue method is quite accurate and it can be used for calibration of other peak voltage measuring devices. Peak Reading Voltmeters 8/8/2022
  • 28. 28 Digital Peak Voltmeter:  In contrast to the method discussed just now, the rectified current is not measured directly, instead a proportional analog voltage signal is derived which is then converted into a proportional medium frequency for using a voltage to frequency convertor (Block A in Fig. 4.13).  The frequency ratio fm/f is measured with a gate circuit controlled by the a.c. power frequency (supply frequency f) and a counter that opens for an adjustable number of period Δt = p/f. The number of cycles n counted during this interval is  where ‘p’ is a constant of the instrument. Peak Reading Voltmeters 8/8/2022
  • 30. 30 Peak voltmeter with Potential divider:  Diode D is used for rectification  Voltage across C2 is used to charge C3  Resistance Rd permits the variation of Vm when V2 is reduced  Electrostatic Voltmeter as indicating instrument  Voltage across Cs  Peak value to be measured  Discharge time constant=CsRd1 to 10 sec  This arrangement gives discharge error.  Discharge error depends on frequency of the supply Peak Reading Voltmeters 8/8/2022
  • 31. Measurement of High Currents Type of Current Method used D.C Current 1. Resistant shunt 2. Hall Generator High Power frequency A.C Current Transformer with electro-optical technique High frequency and impulse currents 1. Resistive shunts 2. Magnetic potentiometers or probes 3. Magnetic links 4. Hall generators 5. Faraday Generators Impulse Voltages and Currents Cathode Ray Oscilloscope 31 8/8/2022
  • 32. Hall Generators  Hall effect is used to measure very high direct current.  Whenever electric current flows through a metal plate placed in a magnetic field perpendicular to it, Lorenz force will deflect the electrons in the metal structure in a direction perpendicular to the direction of both the magnetic field and the flow of current.  The change in displacement generates an e.m.f called “Hall Voltage” 32 8/8/2022
  • 33.  Hall Voltage, where, B-Magnetic Flux density I-Current d-Thickness of the metal plate R-Hall Coefficient (depends on Material of the plate & temperature) R is small for metals and High for semiconductors 33 Hall Generators d BI R V d BI α V H H    When large d.c. currents are to be measured the current carrying conductor is passed through an iron cored magnetic circuit 8/8/2022
  • 34.  The magnetic field intensity produced by the conductor in the air gap at a depth ‘d’ is given by,  The Hall element is placed in the air gap and a small constant d.c. current is passed through the element.  The voltage developed across the Hall element is measured and by using the expression for Hall voltage the flux density B is calculated and hence the value of current I is obtained. 34 d 2 1 H   Hall Generators 8/8/2022
  • 35. Faraday Generator or Magneto Optic Method  These methods of current measurement use the rotation of the plane of polarisation in materials by the magnetic field which is proportional to the current (Faraday effect).  When a linearly polarised light beam passes through a transparent crystal in the presence of a magnetic field, the plane of polarisation of the light beam undergoes rotation. The angle of rotation is given by, θ = α Bl where, α = A constant of the cyrstal which is a function of the wave length of the light. B = Magnetic flux density due to the current to be measured in this case. l = Length of the crystal. 35 8/8/2022
  • 36.  Fig. shows a schematic diagram of Magneto-optic method.  Crystal C is placed parallel to the magnetic field produced by the current to be measured.  A beam of light from a stabilised light source is made incident on the crystal C after it is passed through the polariser P1.  The light beam undergoes rotation of its plane of polarisation.  After the beam passes through the analyser P2, the beamis focussed on a photomultiplier, the output of which is fed to a CRO. 36 Faraday Generator or Magneto Optic Method 8/8/2022
  • 37.  The filter F allows only the monochromatic light to pass through it. Photoluminescent diodes too, the momentary light emission of which is proportional to the current flowing through them, can be used for current measurement.  Advantages: 1. It provides isolation of the measuring set up from the main current circuit. 2. It is insensitive to overloading. 3. As the signal transmission is through an optical system no insulation problem is faced. However, this device does not operate for D.C current. 37 Faraday Generator or Magneto Optic Method 8/8/2022
  • 38. Magnetic Potentiometer(Rogowski Coil)  If the current to be measured is flowing through a conductor which is surrounded by a coil as shown in Fig.  and M is the mutual inductance between the coil and the conductor, the voltage across the coil terminals will be:  Usually the coil is wound on a non-magnetic former in the form of a toroid and has a large number of turns, to have sufficient voltage induced which could be recorded. 38 dt di M v(t)  8/8/2022
  • 39.  The coil is wound cross-cross to reduce the leakage inductance.  If N is the number of turns of the coil, A the coil area and lm its mean length, the mutual inductance is given by  Usually an integrating circuit RC is employed as shown in Fig to obtain the output voltage proportional to the current to be measured. The output voltage is given by  The frequency response of the Rogowski coil is flat upto 100 MHz but beyond that it is affected by the stray electric and magnetic fields and also by the skin effect. 39 m 0 l NA μ M  i(t) RC M di RC M dt dt di M RC 1 v(t)dt RC 1 (t) v t 0 0         Magnetic Potentiometer(Rogowski Coil) 8/8/2022
  • 41. SERIES IMPEDANCE VOLTMETER 41 Extended series impedance with inductance neglected 8/8/2022
  • 42. SERIES CAPACITOR PEAK VOLTMETER 42 C – capacitor D1,D2 – Diodes OP – Protective devices I – indicating meter V(t) – voltage waveform Ic(t) – capacitor current waveform T – period 8/8/2022
  • 43. PEAK READING AC VOLTMETER 43 8/8/2022
  • 44. PEAK READING AC VOLTMETER 44 8/8/2022
  • 45. SPHERE GAPS MEASUREMENT 45 Ub = kd Ub0 8/8/2022
  • 47. Potential divider for impulse voltage measurement 47 8/8/2022
  • 48. MEASUREMENT OF HIGH DIRECT CURRENTS 48 HALL GENERATORS FOR D.C CURRENT MEASUREMENTS  Hall effect principle is used.If an electric current flows through a metal plate located in a magnetic field perpendicular to it,Lorenz forces will deflect the electrons in the metal structure in a direction normal to the direction of both the current and magnetic field.  The charge displacement generates an emf in the normal direction (Hall voltage).  VH=RBi/d  H=I/δ 8/8/2022
  • 49. MEASUREMENT OF HIGH POWER FREQUENCY ALTERNATING CURRENTS 49  Current transformer is used.it uses electro optical technique.  A voltage signal proportional to the measuring current is generated and it is transmitted to the ground side through electro optical device.  Light pulses proportional to the voltage signal are transmitted by a glass optical fibre bundle to a photo detector and converted back into an analog voltage signal. 8/8/2022
  • 50. SPHERE GAP  The sphere gap method of measuring high voltage is the most reliable and is used as the standard for calibration purposes.  breakdown strength of a gas depends on the ionisation of the gas molecules, and on the density of the gas.  As such, the breakdown voltage varies with the gap spacing; and for a uniform field gap, a high consistency could be obtained, so that the sphere gap is very useful as a measuring device.  In the measuring device, two metal spheres are used, separated by a gas-gap. The potential difference between the spheres is raised until a spark passes between them.  The breakdown strength of a gas depends on the size of the spheres, their distance apart and a number of other factors.  A spark gap may be used for the determination of the peak value of a voltage wave, and for the checking and calibrating of voltmeters and other voltage measuring devices.  The density of the gas (generally air) affects the spark-over voltage for a given gap setting.  Thus the correction for any air density change must be made. The air density correction factor δ must be used. 50 8/8/2022
  • 51.  The spark over voltage for a given gap setting under the standard conditions (760 torr pressure and at 20oC) must be multiplied by the correction factor to obtain the actual spark-over voltage.  The breakdown voltage of the sphere gap (Figure:a) is almost independent of humidity of the atmosphere, but the presence of dew on the surface lowers the breakdown voltage and hence invalidates the calibrations.  The breakdown voltage characteristic (figure 6.3) has been determined for similar pairs of spheres (diameters 62.5 mm, 125 mm, 250 mm, 500 mm, 1 m and 2 m) 51 Fig.b:Breakdown voltage characteristic of sphere gaps Figure. a:- Measuring spheres SPHERE GAP 8/8/2022
  • 52.  In sphere gaps used in measurement, to obtain high accuracy, the minimum clearance to be maintained between the spheres and the neighbouring bodies and the diameter of shafts are also specified, since these also affect the accuracy (Figure:d).  There is also a tolerance specified for the radius of curvature of the spheres.  Peak values of voltages may be measured from 2 kV up to about 2500 kV by means of spheres.  One sphere may be earthed with the other being the high voltage electrode, or both may be supplied with equal positive and negative voltages with respect to earth (symmetrical gap).  Needle gaps may also be used in the measurement of voltages up to about 50 kV, but errors are caused by the variation of the sharpness of the needle gaps, and by the corona forming at the points before the gap actually sparks over.  Also the effect of the variation of the humidity of the atmosphere on such gaps is much greater. 52 SPHERE GAP Figure. d: Sphere gap 8/8/2022
  • 53.  When the gap distance is increased, the uniform field between the spheres becomes distorted, and accuracy falls.  The limits of accuracy are dependant on the ratio of the spacing d to the sphere diameter D, as follows:  d < 0.5 D Accuracy = ± 3 %  0.75 D > d > 0.5 D Accuracy = ± 5 %  For accurate measurement purposes, gap distances in excess of 0.75D are not used  Breakdown voltage characteristic is also dependant on the polarity of the high voltage sphere in the case of asymmetrical gaps, in a symmetrical gap, then the polarity has no effect. 53 Figure . C:- Breakdown voltage characteristics 8/8/2022