UNIT -III
GENERATOR AND TRANSFORMER
PROTECTION (PART I)
Presented by,
Dr. Rohit Babu, Associate Professor
Department of Electrical and Electronics Engineering
Syllabus
Department of Electrical and Electronics Engineering
Part 1. Generator Protection
―Protection of generators against stator faults
―Rotor faults and abnormal conditions
―Restricted earth fault and inter turn fault protection
―Numerical examples
Part 2. Transformer Protection
―Percentage differential protection
―Design of CT’s ratio
―Buchholz relay protection
―Numerical examples
Part 1. Generator Protection
Department of Electrical and Electronics Engineering
―Protection of generators against stator faults
―Rotor faults and abnormal conditions
―Restricted earth fault and inter turn fault protection
―Numerical examples
Generator Protection
Department of Electrical and Electronics Engineering
A modern generating set is generally provided with the following protective schemes.
(i) Stator protection
(a) Percentage differential protection
(b) Protection against stator inter-turn faults
(c) Stator-overheating protection
(ii) Rotor protection
(a) Field ground-fault protection
(b) Loss of excitation protection
(c) Protection against rotor overheating because of unbalanced three-phase stator currents
(iii) Miscellaneous
(a) Overvoltage protection
(b) Overspeed protection
(c) Protection against motoring
(d) Protection against vibration
(e) Bearing-overheating protection
(f) Protection against auxiliary failure
(g) Protection against voltage regulator failure
Stator Protection
Department of Electrical and Electronics Engineering
(A) Percentage Differential Protection
Fig. 1 Percentage differential protection for external fault condition
(instantaneous current directions shown for external fault condition)
• It is used for the protection of generators above 1
MW.
• It protects against winding faults, i.e. phase to phase
and phase to ground faults.
• This is also called biased differential protection or
longitudinal differential protection.
• The polarity of the secondary voltage of CTs at a
particular moment for an external fault has been
shown in the figure.
• In the operating coil, the current sent by the upper
CT is cancelled by the current sent by the lower CT
and the relay does not operate.
Stator Protection
Department of Electrical and Electronics Engineering
Fig. 2 Percentage differential protection of generator
(instantaneous current directions shown for internal fault
condition)
• For an internal fault, the polarity of the secondary
voltage of the upper CT is reversed, as shown in Fig. 2.
• The operating coil carries the sum of the currents sent
by the upper CT and the lower CT and it operates and
trips the circuit breaker.
• The percentage differential protection does not
respond to external faults and overloads.
• It provides complete protection against phase to phase
faults.
• It provides protection against ground faults to about 80
to 85 per cent of the generator windings.
Stator Protection
Department of Electrical and Electronics Engineering
• It does not provide protection to 100 per cent of the winding because it is influenced by the
magnitude of the earth fault current which depends upon the method of neutral grounding.
• Due to the difference in the magnetizing currents of the upper and the lower CTs, the current
through the operating coil will not be zero even under normal loading conditions or during
external fault conditions.
• In case of stator faults, the tripping of circuit breaker to isolate the faulty generator is not
sufficient to prevent further damage as the generator will still continue to supply power to the
fault until its field excitation is suppressed.
Stator Protection
Department of Electrical and Electronics Engineering
Restricted earth-fault protection by differential system
Fig. 3 Percentage of unprotected winding against phase to ground fault
• When the neutral is solidly grounded, it is possible to
provide protection to complete winding of the generator
against ground faults.
• However, the neutral is grounded through resistance to
limit ground fault currents.
• With resistance grounding it is not possible to protect the
complete winding against ground faults.
• The percentage of winding protected depends on the
value of the neutral grounding resistor and the relay
setting.
• The usual practice is to protect 80 to 85% of the generator winding against ground fault. The remaining 15-20%
from neutral end is left unprotected.
• In Fig. 3 for phase to ground fault, it can be seen that the relay setting for the differential protection is determined
by the value of the neutral grounding resistor and the percentage of winding to be protected.
Stator Protection
Department of Electrical and Electronics Engineering
In Fig. 3, let p% of the winding from the neutral remains unprotected. Then (100 – p)% of the winding
is protected. The ground fault current If is given by
where, V is the line to neutral voltage and Rn is the neutral grounding resistance.
For the operation of the relay, the fault current must be greater than the relay pick-up current.
Stator Protection
Department of Electrical and Electronics Engineering
Percentage differential protection for a Y-connected generator with only four leads brought out
• When the neutral connection is made within the
generator and only the neutral terminal is brought
out, the percentage differential protection can be
provided, as shown in Fig. 4.
Fig. 4 Percentage differential protection for Y connected
generator with only four leads brought out
• This scheme protects the generator winding only
against ground faults.
• It does not protect it against phase faults.
Generator-transformer unit protection
Stator Protection
Department of Electrical and Electronics Engineering
(B) Protection against Stator Interturn Faults
• Longitudinal percentage differential protection does
not detect stator interturn faults.
• A transverse percentage differential protection, as
shown in Fig. 5 is employed for the protection of the
generator against stator interturn faults.
Fig. 5 Transverse percentage differential protection for multi-
winding generators
Stator Protection
Department of Electrical and Electronics Engineering
• A faster and more sensitive split-phase
protection as shown in Fig. 6 can be employed.
• In this scheme, a single CT having double
primary is used.
• No bias is necessary because a common CT is
employed so that errors due to CT differences
do not occur.
Fig. 6 Split-phase protection of generator using double primary CTs
Stator Protection
Department of Electrical and Electronics Engineering
Interturn protection based on zero-sequence component
• If generators do not have access to parallel
windings, a method based on zero-sequence
voltage measurement can be employed for
the protection against stator interturn faults.
• This type of scheme will also be applicable to
single winding generators having multi-turn
per phase per slot to protect against interturn
faults.
• Figure 7 shows the schematic diagram of
interturn protection by zero-sequence
• voltage measurement across the machine.
Fig. 7 Interturn protection of generator using zero-sequence voltage
Stator Protection
Department of Electrical and Electronics Engineering
(C) Stator-overheating Protection
Modern generators employ two methods to detect overheating both being used in large generators
(above 2 MW).
First Method, the inlet and outlet temperatures of the cooling medium which may be hydrogen/
water are compared for detecting overheating.
Second Method, the temperature sensing elements are embedded in the stator slots to sense the
temperature.
Stator Protection
Department of Electrical and Electronics Engineering
Fig. 8 Stator-overheating protection
• When the temperature exceeds a certain preset maximum
temperature limit, the relay sounds an alarm.
• The scheme employs a temperature detector unit, relay
and Wheatstone-bridge for the purpose.
• The temperature sensing elements may either be
thermistors, thermocouples or resistance temperature
indicators.
• They are embedded in the stator slots at different
locations.
• These elements are connected to a multi-way selector
switch which checks each one in turn for a period long
enough to operate an alarm relay.
Rotor Protection
Department of Electrical and Electronics Engineering
(A) Field Ground-fault Protection
As the field circuit is operated ungrounded, a single ground fault does not
affect the operation of the generator or cause any damage.
• A dc voltage is impressed between the field circuit and earth through a
polarised moving iron relay.
• It is not necessary to trip the machine when a single field earth fault occurs.
• Usually an alarm is sounded. Then immediate steps are taken to transfer
the load from the faulty generator and to shut it down as quickly.
• In case of brushless machines, the main field circuit is not accessible.
Fig. 9 Earth fault protection
• If there is a partial field failure due to short-circuiting of turns in the main field winding, it is detected by the
increase in level of the field current.
• A severe fault or short-circuiting of the diode is detected by a relay monitoring the current in the exciter control
circuit.
Rotor Protection
Department of Electrical and Electronics Engineering
(B) Loss of Excitation
• When the excitation of a generator is lost, it speeds up slightly and
operates as an induction generator.
• Round-rotor generators do not have damper windings and hence they
are not suitable for such an operation.
• The rotor is overheated quickly due to heavy induced currents in the
rotor iron.
• The rotors of salient pole generators are not overheated because they
have damper windings which carry induced currents.
• The stators of both salient and non-salient pole generators are
overheated due to wattless current drawn by the machines as
magnetising current from the system.
• The stator overheating does not occur as quickly as rotor overheating.
Fig. 10 Loss of excitation relay characteristic
Rotor Protection
Department of Electrical and Electronics Engineering
(c) Protection against Rotor Overheating because of Unbalanced Three-phase Stator Currents
Fig. 11 Protection against unbalanced stator currents
• The overcurrent relay used in the negative phase sequence protection
has a long operating time
• A typical time range of the relay is 0.2 to 2000 s.
• It has a typical construction with a special electromagnet.
• It has shaded pole construction with a Mu-metal shunt.
• The negative sequence filter gives an output proportional to I2.
• It actuates an alarm as well as the time-current relay which has a very
inverse characteristic.
• The alarm unit also starts a timer which is adjustable from 8% to 40% of
negative sequence component.
• The timer makes a delay in the alarm to prevent the alarm from
sounding unnecessarily on unbalanced loads of short duration.
Miscellaneous
Department of Electrical and Electronics Engineering
A. Overvoltage Protection-
• Overvoltage may be caused by a defective voltage regulator or it may occur due to sudden loss of
electrical load on generators.
• Overvoltage relays are provided with hydro and gas-turbine sets.
• Overvoltage relays are not commonly used with turbo-alternators.
B. Overspeed Protection-
• A turbo-generator is provided with a mechanical overspeed device.
• The speed governor normally controls its speed.
• It is designed to prevent any speed rise even with a 100 per cent load rejection.
• An emergency centrifugal overspeed device is also incorporated to trip emergency steam valves
when the speed exceeds 110 percent.
Miscellaneous
Department of Electrical and Electronics Engineering
C. Protection against Motoring-
• When the steam supply is cut off, the generator runs as a motor.
• The steam turbine gets overheated because insufficient steam passes through the turbine to carry
away the heat generated by windage loss.
• Therefore, a protective relay is required for the protection of the steam turbine.
• Generally, the relay operates when power output falls below 3%.
• A sensitive reverse power relay is available which has an operating setting of about 0.5% of the
generator’s output.
D. Protection against Vibration and Distortion of Rotor-
• Vibration is caused by overheating of the rotor or some mechanical failure or abnormality.
Miscellaneous
Department of Electrical and Electronics Engineering
E. Bearing Overheating Protection-
• Temperature of the bearing is detected by inserting a temperature sensing device in a hole in the
bearing.
• For large machines where lubricating oil is circulated through the bearing, an oil flow device is
used to detect the failure of oil cooling equipment.
F. Protection against Auxiliary Failure-
• The power plant auxiliaries are very important for the running of the generating sets.
• High grade protective equipment is employed for their reliable operation.
• For large generating sets, protection against loss of vacuum and loss of boiler pressure are
provided. Such failures are due to the failure of the associated auxiliaries.
Miscellaneous
Department of Electrical and Electronics Engineering
G. Protection against Voltage Regulator Failure-
• Modern quick response automatic voltage regulators are very complex.
• They are subject to component failures.
• Suitable protective devices are provided against their failure.
• A definite time dc overcurrent relay is provided which operates when there is overcurrent in the
rotor circuit for a period longer than a prescribed limit.
• In such a situation, the excitation is switched to a predetermined value for manual control.
Miscellaneous
Department of Electrical and Electronics Engineering
H. Protection against Pole Slipping
• In case of system disturbances after the operation of circuit breaker or when heavy load is thrown or
switched on, the generator rotor may oscillate.
• Consequently, variations in current, voltage and power factor may take place.
• Such oscillations may disappear in a few seconds.
• Therefore, in such a situation, tripping is not desired.
• In some cases, angular displacement of the rotor exceeds the stability limit and the rotor slips a pole
pitch.
• If the disturbance is over, the generator may regain synchronism.
• If it does not, it should be tripped.
Miscellaneous
Department of Electrical and Electronics Engineering
I. Field Suppression
• When a fault occurs in the generator winding, the circuit breaker trips and the generator is
isolated from the system.
• However, the generator still continues to feed the fault as long as the excitation is maintained, and
the damage increases.
• Therefore, it is desirable to suppress the field as quickly as possible.
J. Back-up Protection
• Overcurrent relays are used as back-up protection.
• As the synchronous impedance of a turbo-generator is more than 100%, the fault current,
• may fall below the normal load current.
• Therefore, standard time-overcurrent relays cannot be employed for back-up protection.
• A voltage controlled overcurrent can be employed for such a purpose.
• A better alternative is to use reactance or impedance type distance relays.
Thank you

More Related Content

What's hot

Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars PremanandDesai
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformerSumeet Ratnawat
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zonesSlides Hub
 
Alternator protection
Alternator protectionAlternator protection
Alternator protectionjawaharramaya
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of GeneratorRahuldey1991
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protectionSalim Palayi
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)Dr. Rohit Babu
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its typesSlides Hub
 
Motor protection principles
Motor protection principlesMotor protection principles
Motor protection principlesAtiq Sayal
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideSourabh Ghosh
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protectionNischal Popat
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternatorBiswajit Pratihari
 
distance relay
distance relaydistance relay
distance relaySURAJ PRASAD
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part ISlides Hub
 

What's hot (20)

Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
Motor protection principles
Motor protection principlesMotor protection principles
Motor protection principles
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protection
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
distance relay
distance relaydistance relay
distance relay
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 

Similar to Generator and Transformer Protection (PART 1)

Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Abhishek Choksi
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. katoAgrey Kato
 
Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsArjay Automation
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Dr. Rohit Babu
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.pptsanipriadi1
 
Generator protection
Generator protectionGenerator protection
Generator protectionChetan Patil
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2Rahaf Waheep
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorCS V
 
Equipment protection
Equipment protectionEquipment protection
Equipment protectionSlides Hub
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
 
class on Protection.pptx
class on Protection.pptxclass on Protection.pptx
class on Protection.pptxSubhroSen9
 
presentation_generator_protection.pptx
presentation_generator_protection.pptxpresentation_generator_protection.pptx
presentation_generator_protection.pptxvasan35
 
LECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptxLECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptxLoitaFredy
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxrajkumarmaurya31
 
4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptxNoname812799
 
WIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUESWIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUESEMERSON EDUARDO RODRIGUES
 
Generator protection
Generator protectionGenerator protection
Generator protectionSSVASAVA
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
 
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODSLOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODSJayant Suthar
 

Similar to Generator and Transformer Protection (PART 1) (20)

Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Advanced Generator Ground Fault Protections
Advanced Generator Ground Fault ProtectionsAdvanced Generator Ground Fault Protections
Advanced Generator Ground Fault Protections
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt442639191-Generator-Protection-ppt.ppt
442639191-Generator-Protection-ppt.ppt
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
Equipment protection
Equipment protectionEquipment protection
Equipment protection
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
class on Protection.pptx
class on Protection.pptxclass on Protection.pptx
class on Protection.pptx
 
presentation_generator_protection.pptx
presentation_generator_protection.pptxpresentation_generator_protection.pptx
presentation_generator_protection.pptx
 
LECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptxLECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptx
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
 
4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx4 PROTECTION OF ALTERNATOR.pptx
4 PROTECTION OF ALTERNATOR.pptx
 
WIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUESWIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUES
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODSLOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
LOW VOLTAGE CONTROL PANEL, SWITHGEAR, OVERLOAD PROTECTION, STARTING METHODS
 

More from Dr. Rohit Babu

EDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptxEDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptxDr. Rohit Babu
 
EDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptxEDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptxDr. Rohit Babu
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxDr. Rohit Babu
 
EDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptxEDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptxDr. Rohit Babu
 
HVDC Syllabus.pptx
HVDC Syllabus.pptxHVDC Syllabus.pptx
HVDC Syllabus.pptxDr. Rohit Babu
 
Electrical Distribution Systems: Syllabus
Electrical Distribution Systems: SyllabusElectrical Distribution Systems: Syllabus
Electrical Distribution Systems: SyllabusDr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2Dr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1Dr. Rohit Babu
 
STATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYSSTATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYSDr. Rohit Babu
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION Dr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGDr. Rohit Babu
 
Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)Dr. Rohit Babu
 
SGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-KSGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-KDr. Rohit Babu
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Dr. Rohit Babu
 
Circuit Breaker: Part 2
Circuit Breaker: Part 2Circuit Breaker: Part 2
Circuit Breaker: Part 2Dr. Rohit Babu
 

More from Dr. Rohit Babu (18)

EDS Unit 6.pptx
EDS Unit 6.pptxEDS Unit 6.pptx
EDS Unit 6.pptx
 
EDS Unit 5.pptx
EDS Unit 5.pptxEDS Unit 5.pptx
EDS Unit 5.pptx
 
EDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptxEDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptx
 
EDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptxEDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptx
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptx
 
EDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptxEDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptx
 
HVDC Syllabus.pptx
HVDC Syllabus.pptxHVDC Syllabus.pptx
HVDC Syllabus.pptx
 
Electrical Distribution Systems: Syllabus
Electrical Distribution Systems: SyllabusElectrical Distribution Systems: Syllabus
Electrical Distribution Systems: Syllabus
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
 
STATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYSSTATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYS
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)
 
SGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-KSGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-K
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)
 
Circuit Breaker: Part 2
Circuit Breaker: Part 2Circuit Breaker: Part 2
Circuit Breaker: Part 2
 
Circuit Breaker
Circuit BreakerCircuit Breaker
Circuit Breaker
 

Recently uploaded

Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 

Recently uploaded (20)

Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 

Generator and Transformer Protection (PART 1)

  • 1. LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY Jonnada, Andhra Pradesh- 535005 UNIT -III GENERATOR AND TRANSFORMER PROTECTION (PART I) Presented by, Dr. Rohit Babu, Associate Professor Department of Electrical and Electronics Engineering
  • 2. Syllabus Department of Electrical and Electronics Engineering Part 1. Generator Protection ―Protection of generators against stator faults ―Rotor faults and abnormal conditions ―Restricted earth fault and inter turn fault protection ―Numerical examples Part 2. Transformer Protection ―Percentage differential protection ―Design of CT’s ratio ―Buchholz relay protection ―Numerical examples
  • 3. Part 1. Generator Protection Department of Electrical and Electronics Engineering ―Protection of generators against stator faults ―Rotor faults and abnormal conditions ―Restricted earth fault and inter turn fault protection ―Numerical examples
  • 4. Generator Protection Department of Electrical and Electronics Engineering A modern generating set is generally provided with the following protective schemes. (i) Stator protection (a) Percentage differential protection (b) Protection against stator inter-turn faults (c) Stator-overheating protection (ii) Rotor protection (a) Field ground-fault protection (b) Loss of excitation protection (c) Protection against rotor overheating because of unbalanced three-phase stator currents (iii) Miscellaneous (a) Overvoltage protection (b) Overspeed protection (c) Protection against motoring (d) Protection against vibration (e) Bearing-overheating protection (f) Protection against auxiliary failure (g) Protection against voltage regulator failure
  • 5. Stator Protection Department of Electrical and Electronics Engineering (A) Percentage Differential Protection Fig. 1 Percentage differential protection for external fault condition (instantaneous current directions shown for external fault condition) • It is used for the protection of generators above 1 MW. • It protects against winding faults, i.e. phase to phase and phase to ground faults. • This is also called biased differential protection or longitudinal differential protection. • The polarity of the secondary voltage of CTs at a particular moment for an external fault has been shown in the figure. • In the operating coil, the current sent by the upper CT is cancelled by the current sent by the lower CT and the relay does not operate.
  • 6. Stator Protection Department of Electrical and Electronics Engineering Fig. 2 Percentage differential protection of generator (instantaneous current directions shown for internal fault condition) • For an internal fault, the polarity of the secondary voltage of the upper CT is reversed, as shown in Fig. 2. • The operating coil carries the sum of the currents sent by the upper CT and the lower CT and it operates and trips the circuit breaker. • The percentage differential protection does not respond to external faults and overloads. • It provides complete protection against phase to phase faults. • It provides protection against ground faults to about 80 to 85 per cent of the generator windings.
  • 7. Stator Protection Department of Electrical and Electronics Engineering • It does not provide protection to 100 per cent of the winding because it is influenced by the magnitude of the earth fault current which depends upon the method of neutral grounding. • Due to the difference in the magnetizing currents of the upper and the lower CTs, the current through the operating coil will not be zero even under normal loading conditions or during external fault conditions. • In case of stator faults, the tripping of circuit breaker to isolate the faulty generator is not sufficient to prevent further damage as the generator will still continue to supply power to the fault until its field excitation is suppressed.
  • 8. Stator Protection Department of Electrical and Electronics Engineering Restricted earth-fault protection by differential system Fig. 3 Percentage of unprotected winding against phase to ground fault • When the neutral is solidly grounded, it is possible to provide protection to complete winding of the generator against ground faults. • However, the neutral is grounded through resistance to limit ground fault currents. • With resistance grounding it is not possible to protect the complete winding against ground faults. • The percentage of winding protected depends on the value of the neutral grounding resistor and the relay setting. • The usual practice is to protect 80 to 85% of the generator winding against ground fault. The remaining 15-20% from neutral end is left unprotected. • In Fig. 3 for phase to ground fault, it can be seen that the relay setting for the differential protection is determined by the value of the neutral grounding resistor and the percentage of winding to be protected.
  • 9. Stator Protection Department of Electrical and Electronics Engineering In Fig. 3, let p% of the winding from the neutral remains unprotected. Then (100 – p)% of the winding is protected. The ground fault current If is given by where, V is the line to neutral voltage and Rn is the neutral grounding resistance. For the operation of the relay, the fault current must be greater than the relay pick-up current.
  • 10. Stator Protection Department of Electrical and Electronics Engineering Percentage differential protection for a Y-connected generator with only four leads brought out • When the neutral connection is made within the generator and only the neutral terminal is brought out, the percentage differential protection can be provided, as shown in Fig. 4. Fig. 4 Percentage differential protection for Y connected generator with only four leads brought out • This scheme protects the generator winding only against ground faults. • It does not protect it against phase faults. Generator-transformer unit protection
  • 11. Stator Protection Department of Electrical and Electronics Engineering (B) Protection against Stator Interturn Faults • Longitudinal percentage differential protection does not detect stator interturn faults. • A transverse percentage differential protection, as shown in Fig. 5 is employed for the protection of the generator against stator interturn faults. Fig. 5 Transverse percentage differential protection for multi- winding generators
  • 12. Stator Protection Department of Electrical and Electronics Engineering • A faster and more sensitive split-phase protection as shown in Fig. 6 can be employed. • In this scheme, a single CT having double primary is used. • No bias is necessary because a common CT is employed so that errors due to CT differences do not occur. Fig. 6 Split-phase protection of generator using double primary CTs
  • 13. Stator Protection Department of Electrical and Electronics Engineering Interturn protection based on zero-sequence component • If generators do not have access to parallel windings, a method based on zero-sequence voltage measurement can be employed for the protection against stator interturn faults. • This type of scheme will also be applicable to single winding generators having multi-turn per phase per slot to protect against interturn faults. • Figure 7 shows the schematic diagram of interturn protection by zero-sequence • voltage measurement across the machine. Fig. 7 Interturn protection of generator using zero-sequence voltage
  • 14. Stator Protection Department of Electrical and Electronics Engineering (C) Stator-overheating Protection Modern generators employ two methods to detect overheating both being used in large generators (above 2 MW). First Method, the inlet and outlet temperatures of the cooling medium which may be hydrogen/ water are compared for detecting overheating. Second Method, the temperature sensing elements are embedded in the stator slots to sense the temperature.
  • 15. Stator Protection Department of Electrical and Electronics Engineering Fig. 8 Stator-overheating protection • When the temperature exceeds a certain preset maximum temperature limit, the relay sounds an alarm. • The scheme employs a temperature detector unit, relay and Wheatstone-bridge for the purpose. • The temperature sensing elements may either be thermistors, thermocouples or resistance temperature indicators. • They are embedded in the stator slots at different locations. • These elements are connected to a multi-way selector switch which checks each one in turn for a period long enough to operate an alarm relay.
  • 16. Rotor Protection Department of Electrical and Electronics Engineering (A) Field Ground-fault Protection As the field circuit is operated ungrounded, a single ground fault does not affect the operation of the generator or cause any damage. • A dc voltage is impressed between the field circuit and earth through a polarised moving iron relay. • It is not necessary to trip the machine when a single field earth fault occurs. • Usually an alarm is sounded. Then immediate steps are taken to transfer the load from the faulty generator and to shut it down as quickly. • In case of brushless machines, the main field circuit is not accessible. Fig. 9 Earth fault protection • If there is a partial field failure due to short-circuiting of turns in the main field winding, it is detected by the increase in level of the field current. • A severe fault or short-circuiting of the diode is detected by a relay monitoring the current in the exciter control circuit.
  • 17. Rotor Protection Department of Electrical and Electronics Engineering (B) Loss of Excitation • When the excitation of a generator is lost, it speeds up slightly and operates as an induction generator. • Round-rotor generators do not have damper windings and hence they are not suitable for such an operation. • The rotor is overheated quickly due to heavy induced currents in the rotor iron. • The rotors of salient pole generators are not overheated because they have damper windings which carry induced currents. • The stators of both salient and non-salient pole generators are overheated due to wattless current drawn by the machines as magnetising current from the system. • The stator overheating does not occur as quickly as rotor overheating. Fig. 10 Loss of excitation relay characteristic
  • 18. Rotor Protection Department of Electrical and Electronics Engineering (c) Protection against Rotor Overheating because of Unbalanced Three-phase Stator Currents Fig. 11 Protection against unbalanced stator currents • The overcurrent relay used in the negative phase sequence protection has a long operating time • A typical time range of the relay is 0.2 to 2000 s. • It has a typical construction with a special electromagnet. • It has shaded pole construction with a Mu-metal shunt. • The negative sequence filter gives an output proportional to I2. • It actuates an alarm as well as the time-current relay which has a very inverse characteristic. • The alarm unit also starts a timer which is adjustable from 8% to 40% of negative sequence component. • The timer makes a delay in the alarm to prevent the alarm from sounding unnecessarily on unbalanced loads of short duration.
  • 19. Miscellaneous Department of Electrical and Electronics Engineering A. Overvoltage Protection- • Overvoltage may be caused by a defective voltage regulator or it may occur due to sudden loss of electrical load on generators. • Overvoltage relays are provided with hydro and gas-turbine sets. • Overvoltage relays are not commonly used with turbo-alternators. B. Overspeed Protection- • A turbo-generator is provided with a mechanical overspeed device. • The speed governor normally controls its speed. • It is designed to prevent any speed rise even with a 100 per cent load rejection. • An emergency centrifugal overspeed device is also incorporated to trip emergency steam valves when the speed exceeds 110 percent.
  • 20. Miscellaneous Department of Electrical and Electronics Engineering C. Protection against Motoring- • When the steam supply is cut off, the generator runs as a motor. • The steam turbine gets overheated because insufficient steam passes through the turbine to carry away the heat generated by windage loss. • Therefore, a protective relay is required for the protection of the steam turbine. • Generally, the relay operates when power output falls below 3%. • A sensitive reverse power relay is available which has an operating setting of about 0.5% of the generator’s output. D. Protection against Vibration and Distortion of Rotor- • Vibration is caused by overheating of the rotor or some mechanical failure or abnormality.
  • 21. Miscellaneous Department of Electrical and Electronics Engineering E. Bearing Overheating Protection- • Temperature of the bearing is detected by inserting a temperature sensing device in a hole in the bearing. • For large machines where lubricating oil is circulated through the bearing, an oil flow device is used to detect the failure of oil cooling equipment. F. Protection against Auxiliary Failure- • The power plant auxiliaries are very important for the running of the generating sets. • High grade protective equipment is employed for their reliable operation. • For large generating sets, protection against loss of vacuum and loss of boiler pressure are provided. Such failures are due to the failure of the associated auxiliaries.
  • 22. Miscellaneous Department of Electrical and Electronics Engineering G. Protection against Voltage Regulator Failure- • Modern quick response automatic voltage regulators are very complex. • They are subject to component failures. • Suitable protective devices are provided against their failure. • A definite time dc overcurrent relay is provided which operates when there is overcurrent in the rotor circuit for a period longer than a prescribed limit. • In such a situation, the excitation is switched to a predetermined value for manual control.
  • 23. Miscellaneous Department of Electrical and Electronics Engineering H. Protection against Pole Slipping • In case of system disturbances after the operation of circuit breaker or when heavy load is thrown or switched on, the generator rotor may oscillate. • Consequently, variations in current, voltage and power factor may take place. • Such oscillations may disappear in a few seconds. • Therefore, in such a situation, tripping is not desired. • In some cases, angular displacement of the rotor exceeds the stability limit and the rotor slips a pole pitch. • If the disturbance is over, the generator may regain synchronism. • If it does not, it should be tripped.
  • 24. Miscellaneous Department of Electrical and Electronics Engineering I. Field Suppression • When a fault occurs in the generator winding, the circuit breaker trips and the generator is isolated from the system. • However, the generator still continues to feed the fault as long as the excitation is maintained, and the damage increases. • Therefore, it is desirable to suppress the field as quickly as possible. J. Back-up Protection • Overcurrent relays are used as back-up protection. • As the synchronous impedance of a turbo-generator is more than 100%, the fault current, • may fall below the normal load current. • Therefore, standard time-overcurrent relays cannot be employed for back-up protection. • A voltage controlled overcurrent can be employed for such a purpose. • A better alternative is to use reactance or impedance type distance relays.