SlideShare a Scribd company logo
INTRODUCTION
TO
CURRENT TRANSFORMER
PERFORMANCE ANALYSIS
Hands on workshop developed for field relay techs practical approach
Yellow Brick Road
• INTRODUCTION
• DEFINITIONS
• PERFORMANCE CALCULATIONS
• RATIO SELECTION CONSIDERATIONS
• VARIOUS TOPICS
• TEST
Z = V/I --- accurate value of I
DISTANCE ~ Z
INTRODUCTION
• IEEE Standard Requirements for Instrument
Transformers C57.13
• IEEE Guide for the Application of Current
Transformers Used for Protective Relaying
Purposes C37.110
INTRODUCTION
• Bushing, internal to Breakers and
Transformers
• Free standing, used with live tank breakers.
• Slipover, mounted externally on
breaker/transformers bushings.
• Window or Bar - single primary turn
• Wound Primary
• Optic
MAGNETO-OPTIC CT
• Light polarization passing through an
optically active material in the presence of a
magnetic field .
• Passive sensor at line voltage is connected to
substation equipment by fiber cable.
• Low energy output used for microprocessor
relays
• Eliminates heavy support for iron.
DEFINITIONS
• EXCITATION CURVE
• EXCITATION VOLTAGE
• EXCITATION CURRENT
• EXCITATION IMPEDANCE
DEFINITIONS
• EQUIVALENT CIRCUIT/DIAGRAM
• POLARITY
• BURDEN
• TERMINAL VOLTAGE
• CLASSIFICATIONS T AND C
DEFINITIONS
• KNEE POINT
• RELAYACCURACY CLASS
• MULTI-TAPS ACCURACY
• SATURATION ERROR - RATIO/ANGLE
EXCITATION CURVE
f
Ip
Ie Ze
Xp
Rp e Rs
Sec
g
h
c
d
Pri
Is
EQUIVALENT DIAGRAM
Ve = EXCITATION VOLTAGE Vef
Ie = CURRENT (read a few values)
Ze = IMPEDANCE
Vt = TERMINAL VOLTAGE Vgh
POLARITY - next
TYPICAL EXCITATION BBC
CURRENT vs VOLTAGE
V (volts) Ie(amps) Ze(ohms)
3.0 0.004 750
7.5 0.007 1071
15 0.011 1364
42 ------ -----
85 ------ -----
180 ------ ------
310 ------ 3100
400 0.25 1600
425 ------ ------
450 ------ ------
500 5.0 100.0
520 10.0 52.0
CURRENT vs VOLTAGE
V (volts) Ie(amps) Ze(ohms)
3.0 0.004 750
7.5 0.007 1071
15 0.011 1364
42 0.02 2100
85 0.03 2833
180 0.05 3600
310 0.1 3100
400 0.25 1600
425 0.5 850
450 1.00 450
500 5.0 100.0
520 10.0 52.0
N1
N2
I1 Ze
Ie
I2
Rsec
RB
LB
EXTERNAL
BURDEN {
Ie+I2
Zint
POLARITY
I1
DEFINITIONS
• EXCITATION CURVE
• EXCITATION VOLTAGE
• EXCITATION CURRENT
• EXCITATION IMPEDANCE
• EQUIVALENT CIRCUIT/DIAGRAM
• BURDEN - NEXT
BURDEN
• The impedances of loads are called BURDEN
• Individual devices or total connected load,
including sec impedance of instrument
transformer.
• For devices burden expressed in VA at
specified current or voltage, the burden
impedance Zb is:
• Zb = VA/IxI or VxV/VA
RB
LB
BURDEN
=
VA / I² {
EXTERNAL BURDEN
Burden: 0.27 VA @ 5A = …….. Ohms
2.51 VA @ 15A = …….. Ohms
I2
RB
CT winding resistance = 0.3 ohms
Lead length = 750 ft # 10 wire
Relay burden = 0.05 ohms
QUIZ
DEFINITIONS
• CLASSIFICATIONS T AND C
ANSI/IEEE STANDARD FOR
CLASSIFICATION T & C
• CLASS T: CTs that have
significant leakage flux within the
transformer core - class T; wound
CTs, with one or more primary-
winding turns mechanically
encircling the core. Performance
determined by test.
CLASS C
• CTs with very minimal leakage
flux in the core, such as the
through, bar, and bushing types.
Performance can be calculated.
KNEE POINT
DEFINITIONS
• KNEE POINT IEEE IEC - effective
saturation point
• Quiz- read a few knee point voltages and also
at 10 amps Ie.
ANSI/IEEE
KNEE POINT
Excitation
Volts
Knee
Point
Volts
45° LINE
QUIZ: READ THE KNEE POINT VOLTAGE
KNEE POINT OR EFFECTIVE
POINT OF SATURATION
• ANSI/IEEE: as the intersection of the curve
with a 45 tangent line
• IEC defines the knee point as the
intersection of straight lines extended from
non saturated and saturated parts of the
excitation curve.
• IEC knee is higher than ANSI - ANSI more
conservative.
IEC KNEE POINT
ANSI/IEE
KNEE POINT
EX: READ THE KNEE POINT VOLTAGE
DEFINITIONS
• EQUIVALENT CIRCUIT/DIAGRAM
• EXCITATION VOLTAGE, CURRENT,
IMPEDANCE
• TERMINAL VOLTAGE
• BURDEN
• CLASSIFICATIONS T AND C
• EXCITATION CURVE
• KNEE POINT IEEE IEC
• ACCURACY CLASS
CT ACCURACY CLASSIFICATION
The measure of a CT performance is its
ability to reproduce accurately the primary
current in secondary amperes both is wave
shape and in magnitude. There are two
parts:
• Performance on symmetrical ac component.
• Performance on offset dc component. Go over the
paper
ANSI/IEEE ACCURACY CLASS
• ANSI/IEEE CLASS DESIGNATION C200:
INDICATES THE CT WILL DELIVER A
SECONDARY TERMINAL VOLTAGE OF
200V
• TO A STANDARD BURDEN B - 2 (2.0 ) AT
20 TIMES THE RATED SECONDARY
CURRENT
• WITHOUT EXCEEDING 10% RATIO
CORRECTION ERROR. Pure sine wave
Standard defines max error, it does not specify the actual error.
ACCURACY CLASS C
STANDARD BURDEN
• ACCURACY CLASS: C100, C200, C400, & C800 AT POWER
FACTOR OF 0.5.
• STANDARD BURDEN B-1, B-2, B-4 AND B-8 THESE
CORRESPOND TO 1, 2, 4 AND 8.
• EXAMPLE STANDARD BURDEN FOR C100 IS 1 , FOR C200
IS 2 , FOR C400 IS 4  AND FOR C800 IS 8 .
• ACCURACY CLASS APPLIES TO FULL WINDING, AND ARE
REDUCED PROPORTIONALLY WITH LOWER TAPS.
• EFFECTIVE ACCURACY =
TAP USED*C-CLASS/MAX RATIO
AN EXERCISE
• 2000/5 MR C800 tap used*c-class/max ratio
TAPS KNEE POINT EFFECTIVE ACCURACY
2000/5 ……………….. ……………...
1500/5 ……………….. ……………...
1100/5 ……………….. ……………...
500/5 ……………….. ……………...
300/5 ……………….. ……………...
AN EXERCISE
• 2000/5 MR C800 tap used*c-class/max ratio
TAPS KNEE POINT EFFECTIVE ACCURACY
2000/5 590 800
1500/5 390 600
1100/5 120 440
500/5 132 200
300/5 78 120
AN EXERCISE
• 2000/5 MR C400 tap used*c-class/max ratio
TAPS KNEE POINT EFFECTIVE ACCURACY
2000/5 ……………….. ……………...
1500/5 ……………….. ……………...
1100/5 ……………….. ……………...
500/5 ……………….. ……………...
300/5 ……………….. ……………...
AN EXERCISE
• 2000/5 MR C400 tap used*c-class/max ratio
TAPS KNEE POINT EFFECTIVE ACCURACY
2000/5 220 400
1500/5 170 300
1100/5 125 220
500/5 55 100
300/5 32 60
CT SELECTION
ACCURACY CLASS
POINT OF SATURATION : KNEE
POINT
IT IS DESIRABLE TO STAY
BELOW OR VERY CLOSE TO
KNEE POINT FOR THE
AVAILABLE CURRENT.
Recap
ANSI/IEEE ACCURACY
CLASS C400
• STANDARD BURDEN FOR C400: (4.0 )
• SECONDARY CURRENT RATING 5 A
• 20 TIMES SEC CURRENT: 100 AMPS
• SEC. VOLTAGE DEVELOPED: 400V
• MAXIMUM RATIO ERROR: 10%
• IF BURDEN 2 , FOR 400V, IT CAN SUPPLY
MORE THAN 100 AMPS SAY 200 AMPS
WITHOUT EXCEECING 10% ERROR.
N1
N2
I1 Ze
Ie <10
Isec = 100
Rsec
RB
LB
EXTERNAL
BURDEN
Ie+Isec
Zint
ACCURACY ACLASS: C200 RATED SEC CURRENT = 5 A
EXTERNALBURDEN = STANDARD BURDEN = 2 .0 OHMS
Ve=200 V Isec = 100 A Ie <10 Amps.
I1
PERFORMANCE
CALCULATIONS
BUT
THE REST OF US
“SHOW US THE DATA”
PERFORMANCE CRITERIA
• THE MEASURE OF A CT
PERFORMANCE IS ITS ABILITY TO
REPRODUCE ACCURATELY THE
PRIMARY CURRRENT IN SECONDARY
AMPERES - BOTH IN WAVE SHAPE
AND MAGNITUDE …. CORRECT
RATIO AND ANGLE.
CT SELECTION AND PERFORMANCE
EVALUATION FOR PHASE FAULTS
600/5 MR Accuracy class C100 is selected
Load Current= 90 A
Max 3 phase Fault Current= 2500 A
Min. Fault Current=350 A
STEPS:
CT Ratio selection
Relay Tap Selection
Determine Total Burden (Load)
CT Performance using ANSI/IEEE Standard
CT Performance using Excitation Curve
PERFORMANCE CALCULATION
STEPS:
CT Ratio selection
Relay Tap Selection
Determine Total Burden (Load)
CT Performance using ANSI/IEEE Standard
CT Performance using Excitation Curve
STEPS:
CT Ratio selection
- within short time and continuous current – thermal limits
- max load just under 5A
Load Current= 90 A
CT ratio selection : 100/5
PERFORMANCE CALCULATION
STEP: Relay Tap Selection
O/C taps – min pickup , higher than the max. load
167%, 150% of specified thermal loading.
Load Current= 90 A for 100/5 CT ratio = 4.5 A sec.
Select tap higher than max load say = 5.0
How much higher – relay characteristics, experience and
judgment.
Fault current: min: 350/20 = 17.5
Multiple of PU = 17.5/5 = 3.5
Multiple of PU = 17.5/6 = 2.9
PERFORMANCE CALCULATION
STEP: Determine Total Burden (Load)
Relay: 2.64 VA @ 5 A and 580 VA @ 100 A
Lead: 0.4 Ohms
Total to CT terminals:
(2.64/5*5 = 0.106) + 0.4 = 0.506 ohms @ 5A
(580/100*100 = 0.058) + 0.4 = 0.458 ohms @ 100 A
PERFORMANCE CALCULATION
STEPS:
CT Ratio selection
Relay Tap Selection
Determine Total Burden (Load)
CT Performance using ANSI/IEEE
Standard
CT Performance using Excitation
Curve
PERFORMANCE CALCULATION
STEP: CT Performance using ANSI/IEEE Standard
Ip
Ie Ze
Xp
Rp e Rs
Sec
g
h
c
d
Pri
Is
Determine voltage @ max fault current CT must develop
across its terminals gh
PERFORMANCE CALCULATION
STEP: Performance – ANSI/IEEE Standard
Vgh = 2500/20 * 0.458 = 57.25
600/5 MR C100 CT used at tap 100/5 -- effective
accuracy class
(100/600) x 100 = ?
CT is capable of developing 16.6 volts.
Severe Saturation. Cannot be used.
PERFORMANCE CALCULATION
STEP: Performance – ANSI/IEEE Standard
For microprocessor based relay:
Burden will change from 0.458 to o.4
Vgh = 2500/20 * 0.4 = 50.0
600/5 MR C100 CT used at tap 100/5 -- effective
accuracy class
(100/600) x 100 = ?
CT is capable of developing 16.6 volts.
Severe Saturation. Cannot be used.
PERFORMANCE CALCULATION
STEP: Performance – ANSI/IEEE Standard
Alternative: use 400/5 CT tap:
Max Load = 90 A
Relay Tap = 90/80 = 1.125 Use: 1.5 relay tap.
Min Fault Multiples of PU=(350/80=4.38, 4.38/1.5= 2.9)
Relay burden at this tap = 1.56 ohms
Total burden at CT terminals = 1.56 + 0.4 = 1.96
Vgh = 2500/80 * 1.96 = 61.25
600/5 MR C100 CT used at tap 400/5-- effective accuracy
class is = (400/600) x 100 = ?
CT is capable of developing 66.6 volts. Within CT capability
PERFORMANCE CALCULATION
STEP: CT Performance using Excitation Curve
ANSI/IEEE ratings “ballpark”. Excitation curve method provides relatively exact
method. Examine the curve
Burden = CT secondary resistance + lead resistance +
relay burden
Burden = 0.211 + 0.4 + 1.56 = 2.171
For load current 1.5 A:
Vgh = 1.5 * 2.171 = 3.26 V Ie = 0.024
Ip = (1.5+0.024) * 80 = 123 A
well below the min If = 350 A (350/123=2.84 multiple of
pick up)
PERFORMANCE CALCULATION
STEP: CT Performance using Excitation Curve
For max fault current
Burden = CT secondary resistance + lead resistance + relay burden
Burden = 0.211 + 0.4 + 1.56 = 2.171
Fault current 2500/80 = 31.25 A:
Vgh = 31.25 * 2.171 = 67.84 V Ie = 0.16
Beyond the knee of curve, small amount 0.5% does not significantly
decreases the fault current to the relay.
I2
RB
CT winding resistance = 0.3 ohms
Lead length = 750 ft # 10 wire
Relay burden = 0.05 ohms as constant
Fault current = 12500A/18000A
CT CLASS = C400/C800
2000/5 MR current transformer
CT RATIO = 800/5
TEST
Determine CT performance using Excitation Curve
method:
AN EXAMPLE – C400
• CT RESISTANCE 0.3 OHMS
• LEAD RESISTANCE 1.5 OHMS
• IMPEDANCE OF VARIOUS DEVICES 0.05
OHMS
• FAULT CURRENT 12500 AMPS
• CT RATIO 800/5
• ACCURACY CLASS C400
• supply curves C400/800
CALCULATIONS for 12500 A – C400
• BURDEN = ( Z-LEAD + Z - CT SEC + D -
DEVICES)
• Ve = (1.5 + 0.3 + 0.05 ) 12500/160
• Ve = 144.5 VOLTS Plot on curve
• Plot on C400
CALCULATIONS for 18000 –C400
• BURDEN = ( Z-LEAD + Z - CT SEC + D -
DEVICES)
• Ve = (1.5 + 0.3 + 0.05 ) 18000/160
• Ve = 209 VOLTS Plot on curve
• Plot on C400
ANOTHER EXAMPLE C800
• CT RESISTANCE 0.3 OHMS
• LEAD RESISTANCE 1.5 OHMS
• IMPEDANCE OF VARIOUS DEVICES 0.05
OHMS
• FAULT CURRENT 12500 AMPS
• CT RATIO 800/5
• ACCURACY CLASS C800
• supply curves C400/800
CALCULATIONS for 12500 A – C800
• BURDEN = ( Z-LEAD + Z - CT SEC + D -
DEVICES)
• Ve = (1.5 + 0.3 + 0.05 ) 12500/160
• Ve = 144.5 VOLTS Plot on curve
• Plot on C800
CALCULATIONS for 18000 A –C800
• BURDEN = ( Z-LEAD + Z - CT SEC + D -
DEVICES)
• Ve = (1.5 + 0.3 + 0.05 ) 18000/160
• For 18,000 A (Ve =209 V) Plot on curve
• Plot on C800
FAULT CURRENT
MAGNITUDES
• 25 -33 KA 8
• 20 - 25 KA 10
• 12.5 -20 KA 46
• 20 - 25 KA 35
• 10 -12.5 KA 35
• <10 KA +150
REFER TO PAGE 6 OF PAPER
RED DELICIOUS
C400
ZONE1
Z = V/A
DISTANCE ~ Z
STANDARD DATA FROM
MANUFACTURER
• ACCURACY:
– RELAY CLASS C200
– METERING CLASS, USE 0.15%
– 0.3%, 0.6% & 1.2% AVAIALABLE BUT NOT
RECOMMENDED
– 0.15% MEANS +/- 0.15% error at 100%
rated current and 0.30% error at 10% of rated
current ( double the error)
STANDARD DATA FROM
MANUFACTURER
• CONTINUOUS (Long Term) rating
– Primary
– Secondary, 5 Amp ( 1Amp)
– Rating factor (RF) of 2.0 provides Twice
Primary and Secondary rating continuous at
30degrees
STANDARD DATA FROM
MANUFACTURER
• SHORT TIME TERMINAL RATINGS
Transmission Voltage Applications
– One Second Rating = 80% Imax Fault, based
on IxIxT=K where T=36 cycles & I=Max fault
current
Distribution Voltage Applications
One Second Rating = Maximum Fault Current
level
RATIO CONSIDERATIONS
• CURRENT SHOULD NOT EXCEED
CONNECTED WIRING AND RELAY
RATINGS AT MAXIMUM LOAD. NOTE
DELTA CONNECTD CT’s PRODUCE
CURRENTS IN CABLES AND RELAYS
THAT ARE 1.732 TIMES THE
SECONDARY CURRENTS
RATIO CONSIDERATIONS
• SELECT RATIO TO BE GREATER THAN
THE MAXIMUM DESIGN CURRENT
RATINGS OF THE ASSOCIATED
BREAKERS AND TRANSFORMERS.
RATIO CONSIDERATIONS
• RATIOS SHOULD NOT BE SO HIGH AS
TO REDUCE RELAY SENSITIVITY,
TAKING INTO ACCOUNT AVAILABLE
RANGES.
RATIO CONSIDERATIONS
• THE MAXIMUM SECONDARY
CURRENT SHOULD NOT EXCEED 20
TIMES RATED CURRENT. (100 A FOR
5A RATED SECONDARY)
RATIO CONSIDERATIONS
• HIGHEST CT RATIO PERMISSIBLE
SHOULD BE USED TO MINIMIZE
WIRING BURDEN AND TO OBTAIN
THE HIGHEST CT CAPABILITYAND
PERFORMANCE.
RATIO CONSIDERATIONS
• FULL WINGING OF MULTI-RATIO CT’s
SHOULD BE SELECTED WHENEVER
POSSIBLE TO AVOID LOWERING OF
THE EFFECTIVE ACCURACY CLASS.
TESTING
•Core Demagnetizing
– The core should be demagnetized as the final
test before the equipment is put in service.
Using the Saturation test circuit, apply enough
voltage to the secondary of the CT to saturate
the core and produce a cecondary currrent of 3-
5 amps. Slowly reduce the voltage to zero
before turning off the variac.
TESTING
•Saturation
– The saturation point is reached when there is a rise
in the test current but not the voltage.
TESTING
•Flashing
• This test checks the polarity of the CT
•Ratio
•Insulation test
CT -As per IEEE.ppt

More Related Content

What's hot

CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
Nageswar Rao
 
RELAY
RELAYRELAY
Characteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relaysCharacteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relays
tahseen alshmary
 
Protection of alternator
Protection of alternator Protection of alternator
Protection of alternator
MILAN MANAVAR
 
Design of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction MotorDesign of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction Motor
Parth Patel
 
Generator Transformer Protections.
Generator Transformer  Protections.Generator Transformer  Protections.
Generator Transformer Protections.
Nischal Popat
 
Resistance potential divider
Resistance potential dividerResistance potential divider
Resistance potential divider
120101eer001
 
Clipper & Clamper
Clipper & ClamperClipper & Clamper
Switchgear and protection 4
Switchgear and protection 4Switchgear and protection 4
Switchgear and protection 4
Md Irshad Ahmad
 
DC DC Converter
DC DC ConverterDC DC Converter
DC DC Converter
Mengstu Fentaw
 
Load Characteristics
Load CharacteristicsLoad Characteristics
Load Characteristics
Ameen San
 
Ppt of current transformer
Ppt of current transformerPpt of current transformer
Ppt of current transformer
ROOPAL PANCHOLI
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
jibinjoy1988
 
over head insulators
over head insulatorsover head insulators
over head insulators
Fahad Rasheed
 
Phase Controlled Rectifiers
Phase Controlled RectifiersPhase Controlled Rectifiers
Phase Controlled Rectifiers
maneesh001
 
Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...
Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...
Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...
Mathankumar S
 
Power quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSPower quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMS
Charan Sai Jc
 
ANALOG TO DIGITAL CONVERTOR
ANALOG TO DIGITAL CONVERTORANALOG TO DIGITAL CONVERTOR
ANALOG TO DIGITAL CONVERTOR
Anil Yadav
 
Different methods of pwm for inverter control
Different methods of pwm for inverter controlDifferent methods of pwm for inverter control
Different methods of pwm for inverter control
Tushar Pandagre
 
Synchonous machine design selection of no of slots
Synchonous machine design selection of no of slotsSynchonous machine design selection of no of slots
Synchonous machine design selection of no of slots
Ajay Balar
 

What's hot (20)

CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
 
RELAY
RELAYRELAY
RELAY
 
Characteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relaysCharacteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relays
 
Protection of alternator
Protection of alternator Protection of alternator
Protection of alternator
 
Design of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction MotorDesign of stator & rotor for Wound Induction Motor
Design of stator & rotor for Wound Induction Motor
 
Generator Transformer Protections.
Generator Transformer  Protections.Generator Transformer  Protections.
Generator Transformer Protections.
 
Resistance potential divider
Resistance potential dividerResistance potential divider
Resistance potential divider
 
Clipper & Clamper
Clipper & ClamperClipper & Clamper
Clipper & Clamper
 
Switchgear and protection 4
Switchgear and protection 4Switchgear and protection 4
Switchgear and protection 4
 
DC DC Converter
DC DC ConverterDC DC Converter
DC DC Converter
 
Load Characteristics
Load CharacteristicsLoad Characteristics
Load Characteristics
 
Ppt of current transformer
Ppt of current transformerPpt of current transformer
Ppt of current transformer
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
 
over head insulators
over head insulatorsover head insulators
over head insulators
 
Phase Controlled Rectifiers
Phase Controlled RectifiersPhase Controlled Rectifiers
Phase Controlled Rectifiers
 
Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...
Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...
Power Systems Enginering - Transmission Line Parameter Calculation For 2- Con...
 
Power quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMSPower quality issues in POWER SYSTEMS
Power quality issues in POWER SYSTEMS
 
ANALOG TO DIGITAL CONVERTOR
ANALOG TO DIGITAL CONVERTORANALOG TO DIGITAL CONVERTOR
ANALOG TO DIGITAL CONVERTOR
 
Different methods of pwm for inverter control
Different methods of pwm for inverter controlDifferent methods of pwm for inverter control
Different methods of pwm for inverter control
 
Synchonous machine design selection of no of slots
Synchonous machine design selection of no of slotsSynchonous machine design selection of no of slots
Synchonous machine design selection of no of slots
 

Similar to CT -As per IEEE.ppt

ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
hiiarindam
 
E&i web cast
E&i web castE&i web cast
E&i web cast
jenelkins
 
Final esd lab manual (1)
Final esd lab manual (1)Final esd lab manual (1)
Final esd lab manual (1)
Deepak Jena
 
25471_ENERGY_CONVERSION_for any power system6.ppt
25471_ENERGY_CONVERSION_for any power system6.ppt25471_ENERGY_CONVERSION_for any power system6.ppt
25471_ENERGY_CONVERSION_for any power system6.ppt
alemaklil21
 
Voltage regulation techniques used in power systems
Voltage regulation techniques used in power systemsVoltage regulation techniques used in power systems
Voltage regulation techniques used in power systems
Dr. Amjad Hussain
 
T2000
T2000T2000
Ratio Burden Admittance Testing
Ratio Burden Admittance TestingRatio Burden Admittance Testing
Ratio Burden Admittance Testing
TESCO - The Eastern Specialty Company
 
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kVCooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Thorne & Derrick International
 
Aec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTUAec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTU
Gopal Krishna Murthy C R
 
Load Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by InterfaceLoad Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by Interface
Interface
 
TESCO Tuesday: Ratio, Burden and Admittance
TESCO Tuesday: Ratio, Burden and AdmittanceTESCO Tuesday: Ratio, Burden and Admittance
TESCO Tuesday: Ratio, Burden and Admittance
TESCO - The Eastern Specialty Company
 
Noiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkeiNoiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkei
NIHON DENKEI SINGAPORE
 
Noiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkeiNoiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkei
NIHON DENKEI SINGAPORE
 
Basic Electronic UNIT-IV PPT
Basic Electronic UNIT-IV PPTBasic Electronic UNIT-IV PPT
Basic Electronic UNIT-IV PPT
Praveen Kunda
 
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 NewOriginal Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
AUTHELECTRONIC
 
Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618
PT. Siwali Swantika
 
KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film CapacitorsKEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
Ivana Ivanovska
 
Transformers.pptx
Transformers.pptxTransformers.pptx
Transformers.pptx
MugeshSaravanan1
 
Fluke clamp meter selection guide
Fluke clamp meter selection guideFluke clamp meter selection guide
Fluke clamp meter selection guide
CoasttoCoastCape
 
Current Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirementsCurrent Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirements
ssuser39bdb9
 

Similar to CT -As per IEEE.ppt (20)

ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
 
E&i web cast
E&i web castE&i web cast
E&i web cast
 
Final esd lab manual (1)
Final esd lab manual (1)Final esd lab manual (1)
Final esd lab manual (1)
 
25471_ENERGY_CONVERSION_for any power system6.ppt
25471_ENERGY_CONVERSION_for any power system6.ppt25471_ENERGY_CONVERSION_for any power system6.ppt
25471_ENERGY_CONVERSION_for any power system6.ppt
 
Voltage regulation techniques used in power systems
Voltage regulation techniques used in power systemsVoltage regulation techniques used in power systems
Voltage regulation techniques used in power systems
 
T2000
T2000T2000
T2000
 
Ratio Burden Admittance Testing
Ratio Burden Admittance TestingRatio Burden Admittance Testing
Ratio Burden Admittance Testing
 
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kVCooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
Cooper Power Connectors - MV-HV Specifiers Guide 5kV-35kV
 
Aec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTUAec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTU
 
Load Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by InterfaceLoad Cell Lunch and Learn Presented by Interface
Load Cell Lunch and Learn Presented by Interface
 
TESCO Tuesday: Ratio, Burden and Admittance
TESCO Tuesday: Ratio, Burden and AdmittanceTESCO Tuesday: Ratio, Burden and Admittance
TESCO Tuesday: Ratio, Burden and Admittance
 
Noiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkeiNoiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkei
 
Noiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkeiNoiseken ins220 Impulse Noise Simulator denkei
Noiseken ins220 Impulse Noise Simulator denkei
 
Basic Electronic UNIT-IV PPT
Basic Electronic UNIT-IV PPTBasic Electronic UNIT-IV PPT
Basic Electronic UNIT-IV PPT
 
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 NewOriginal Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
 
Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke A40B. Hubungi PT. Siwali Swantika 021-45850618
 
KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film CapacitorsKEMET Webinar -C44U_C44P-R Power Can Film Capacitors
KEMET Webinar -C44U_C44P-R Power Can Film Capacitors
 
Transformers.pptx
Transformers.pptxTransformers.pptx
Transformers.pptx
 
Fluke clamp meter selection guide
Fluke clamp meter selection guideFluke clamp meter selection guide
Fluke clamp meter selection guide
 
Current Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirementsCurrent Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirements
 

Recently uploaded

Advanced control scheme of doubly fed induction generator for wind turbine us...
Advanced control scheme of doubly fed induction generator for wind turbine us...Advanced control scheme of doubly fed induction generator for wind turbine us...
Advanced control scheme of doubly fed induction generator for wind turbine us...
IJECEIAES
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
KrishnaveniKrishnara1
 
Textile Chemical Processing and Dyeing.pdf
Textile Chemical Processing and Dyeing.pdfTextile Chemical Processing and Dyeing.pdf
Textile Chemical Processing and Dyeing.pdf
NazakatAliKhoso2
 
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
ecqow
 
Generative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of contentGenerative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of content
Hitesh Mohapatra
 
CompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURS
CompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURSCompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURS
CompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURS
RamonNovais6
 
International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...
gerogepatton
 
Engine Lubrication performance System.pdf
Engine Lubrication performance System.pdfEngine Lubrication performance System.pdf
Engine Lubrication performance System.pdf
mamamaam477
 
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
171ticu
 
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressionsKuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
Victor Morales
 
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have oneISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
Las Vegas Warehouse
 
gray level transformation unit 3(image processing))
gray level transformation unit 3(image processing))gray level transformation unit 3(image processing))
gray level transformation unit 3(image processing))
shivani5543
 
Certificates - Mahmoud Mohamed Moursi Ahmed
Certificates - Mahmoud Mohamed Moursi AhmedCertificates - Mahmoud Mohamed Moursi Ahmed
Certificates - Mahmoud Mohamed Moursi Ahmed
Mahmoud Morsy
 
DEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODEL
DEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODELDEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODEL
DEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODEL
gerogepatton
 
LLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by Anant
LLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by AnantLLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by Anant
LLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by Anant
Anant Corporation
 
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024
Sinan KOZAK
 
ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024
Rahul
 
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
shadow0702a
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
SUTEJAS
 
Curve Fitting in Numerical Methods Regression
Curve Fitting in Numerical Methods RegressionCurve Fitting in Numerical Methods Regression
Curve Fitting in Numerical Methods Regression
Nada Hikmah
 

Recently uploaded (20)

Advanced control scheme of doubly fed induction generator for wind turbine us...
Advanced control scheme of doubly fed induction generator for wind turbine us...Advanced control scheme of doubly fed induction generator for wind turbine us...
Advanced control scheme of doubly fed induction generator for wind turbine us...
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
 
Textile Chemical Processing and Dyeing.pdf
Textile Chemical Processing and Dyeing.pdfTextile Chemical Processing and Dyeing.pdf
Textile Chemical Processing and Dyeing.pdf
 
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
 
Generative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of contentGenerative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of content
 
CompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURS
CompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURSCompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURS
CompEx~Manual~1210 (2).pdf COMPEX GAS AND VAPOURS
 
International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...
 
Engine Lubrication performance System.pdf
Engine Lubrication performance System.pdfEngine Lubrication performance System.pdf
Engine Lubrication performance System.pdf
 
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
 
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressionsKuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
 
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have oneISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
 
gray level transformation unit 3(image processing))
gray level transformation unit 3(image processing))gray level transformation unit 3(image processing))
gray level transformation unit 3(image processing))
 
Certificates - Mahmoud Mohamed Moursi Ahmed
Certificates - Mahmoud Mohamed Moursi AhmedCertificates - Mahmoud Mohamed Moursi Ahmed
Certificates - Mahmoud Mohamed Moursi Ahmed
 
DEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODEL
DEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODELDEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODEL
DEEP LEARNING FOR SMART GRID INTRUSION DETECTION: A HYBRID CNN-LSTM-BASED MODEL
 
LLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by Anant
LLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by AnantLLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by Anant
LLM Fine Tuning with QLoRA Cassandra Lunch 4, presented by Anant
 
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024
 
ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024
 
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
 
Curve Fitting in Numerical Methods Regression
Curve Fitting in Numerical Methods RegressionCurve Fitting in Numerical Methods Regression
Curve Fitting in Numerical Methods Regression
 

CT -As per IEEE.ppt

  • 1. INTRODUCTION TO CURRENT TRANSFORMER PERFORMANCE ANALYSIS Hands on workshop developed for field relay techs practical approach
  • 2. Yellow Brick Road • INTRODUCTION • DEFINITIONS • PERFORMANCE CALCULATIONS • RATIO SELECTION CONSIDERATIONS • VARIOUS TOPICS • TEST
  • 3. Z = V/I --- accurate value of I DISTANCE ~ Z
  • 4. INTRODUCTION • IEEE Standard Requirements for Instrument Transformers C57.13 • IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes C37.110
  • 5. INTRODUCTION • Bushing, internal to Breakers and Transformers • Free standing, used with live tank breakers. • Slipover, mounted externally on breaker/transformers bushings. • Window or Bar - single primary turn • Wound Primary • Optic
  • 6. MAGNETO-OPTIC CT • Light polarization passing through an optically active material in the presence of a magnetic field . • Passive sensor at line voltage is connected to substation equipment by fiber cable. • Low energy output used for microprocessor relays • Eliminates heavy support for iron.
  • 7. DEFINITIONS • EXCITATION CURVE • EXCITATION VOLTAGE • EXCITATION CURRENT • EXCITATION IMPEDANCE
  • 8. DEFINITIONS • EQUIVALENT CIRCUIT/DIAGRAM • POLARITY • BURDEN • TERMINAL VOLTAGE • CLASSIFICATIONS T AND C
  • 9. DEFINITIONS • KNEE POINT • RELAYACCURACY CLASS • MULTI-TAPS ACCURACY • SATURATION ERROR - RATIO/ANGLE
  • 11. f Ip Ie Ze Xp Rp e Rs Sec g h c d Pri Is EQUIVALENT DIAGRAM Ve = EXCITATION VOLTAGE Vef Ie = CURRENT (read a few values) Ze = IMPEDANCE Vt = TERMINAL VOLTAGE Vgh POLARITY - next
  • 12. TYPICAL EXCITATION BBC CURRENT vs VOLTAGE V (volts) Ie(amps) Ze(ohms) 3.0 0.004 750 7.5 0.007 1071 15 0.011 1364 42 ------ ----- 85 ------ ----- 180 ------ ------ 310 ------ 3100 400 0.25 1600 425 ------ ------ 450 ------ ------ 500 5.0 100.0 520 10.0 52.0
  • 13. CURRENT vs VOLTAGE V (volts) Ie(amps) Ze(ohms) 3.0 0.004 750 7.5 0.007 1071 15 0.011 1364 42 0.02 2100 85 0.03 2833 180 0.05 3600 310 0.1 3100 400 0.25 1600 425 0.5 850 450 1.00 450 500 5.0 100.0 520 10.0 52.0
  • 15. DEFINITIONS • EXCITATION CURVE • EXCITATION VOLTAGE • EXCITATION CURRENT • EXCITATION IMPEDANCE • EQUIVALENT CIRCUIT/DIAGRAM • BURDEN - NEXT
  • 16. BURDEN • The impedances of loads are called BURDEN • Individual devices or total connected load, including sec impedance of instrument transformer. • For devices burden expressed in VA at specified current or voltage, the burden impedance Zb is: • Zb = VA/IxI or VxV/VA
  • 17. RB LB BURDEN = VA / I² { EXTERNAL BURDEN Burden: 0.27 VA @ 5A = …….. Ohms 2.51 VA @ 15A = …….. Ohms
  • 18. I2 RB CT winding resistance = 0.3 ohms Lead length = 750 ft # 10 wire Relay burden = 0.05 ohms QUIZ
  • 20. ANSI/IEEE STANDARD FOR CLASSIFICATION T & C • CLASS T: CTs that have significant leakage flux within the transformer core - class T; wound CTs, with one or more primary- winding turns mechanically encircling the core. Performance determined by test.
  • 21. CLASS C • CTs with very minimal leakage flux in the core, such as the through, bar, and bushing types. Performance can be calculated. KNEE POINT
  • 22. DEFINITIONS • KNEE POINT IEEE IEC - effective saturation point • Quiz- read a few knee point voltages and also at 10 amps Ie.
  • 24. KNEE POINT OR EFFECTIVE POINT OF SATURATION • ANSI/IEEE: as the intersection of the curve with a 45 tangent line • IEC defines the knee point as the intersection of straight lines extended from non saturated and saturated parts of the excitation curve. • IEC knee is higher than ANSI - ANSI more conservative.
  • 25. IEC KNEE POINT ANSI/IEE KNEE POINT EX: READ THE KNEE POINT VOLTAGE
  • 26. DEFINITIONS • EQUIVALENT CIRCUIT/DIAGRAM • EXCITATION VOLTAGE, CURRENT, IMPEDANCE • TERMINAL VOLTAGE • BURDEN • CLASSIFICATIONS T AND C • EXCITATION CURVE • KNEE POINT IEEE IEC • ACCURACY CLASS
  • 27. CT ACCURACY CLASSIFICATION The measure of a CT performance is its ability to reproduce accurately the primary current in secondary amperes both is wave shape and in magnitude. There are two parts: • Performance on symmetrical ac component. • Performance on offset dc component. Go over the paper
  • 28. ANSI/IEEE ACCURACY CLASS • ANSI/IEEE CLASS DESIGNATION C200: INDICATES THE CT WILL DELIVER A SECONDARY TERMINAL VOLTAGE OF 200V • TO A STANDARD BURDEN B - 2 (2.0 ) AT 20 TIMES THE RATED SECONDARY CURRENT • WITHOUT EXCEEDING 10% RATIO CORRECTION ERROR. Pure sine wave Standard defines max error, it does not specify the actual error.
  • 29. ACCURACY CLASS C STANDARD BURDEN • ACCURACY CLASS: C100, C200, C400, & C800 AT POWER FACTOR OF 0.5. • STANDARD BURDEN B-1, B-2, B-4 AND B-8 THESE CORRESPOND TO 1, 2, 4 AND 8. • EXAMPLE STANDARD BURDEN FOR C100 IS 1 , FOR C200 IS 2 , FOR C400 IS 4  AND FOR C800 IS 8 . • ACCURACY CLASS APPLIES TO FULL WINDING, AND ARE REDUCED PROPORTIONALLY WITH LOWER TAPS. • EFFECTIVE ACCURACY = TAP USED*C-CLASS/MAX RATIO
  • 30. AN EXERCISE • 2000/5 MR C800 tap used*c-class/max ratio TAPS KNEE POINT EFFECTIVE ACCURACY 2000/5 ……………….. ……………... 1500/5 ……………….. ……………... 1100/5 ……………….. ……………... 500/5 ……………….. ……………... 300/5 ……………….. ……………...
  • 31. AN EXERCISE • 2000/5 MR C800 tap used*c-class/max ratio TAPS KNEE POINT EFFECTIVE ACCURACY 2000/5 590 800 1500/5 390 600 1100/5 120 440 500/5 132 200 300/5 78 120
  • 32. AN EXERCISE • 2000/5 MR C400 tap used*c-class/max ratio TAPS KNEE POINT EFFECTIVE ACCURACY 2000/5 ……………….. ……………... 1500/5 ……………….. ……………... 1100/5 ……………….. ……………... 500/5 ……………….. ……………... 300/5 ……………….. ……………...
  • 33. AN EXERCISE • 2000/5 MR C400 tap used*c-class/max ratio TAPS KNEE POINT EFFECTIVE ACCURACY 2000/5 220 400 1500/5 170 300 1100/5 125 220 500/5 55 100 300/5 32 60
  • 34. CT SELECTION ACCURACY CLASS POINT OF SATURATION : KNEE POINT IT IS DESIRABLE TO STAY BELOW OR VERY CLOSE TO KNEE POINT FOR THE AVAILABLE CURRENT. Recap
  • 35. ANSI/IEEE ACCURACY CLASS C400 • STANDARD BURDEN FOR C400: (4.0 ) • SECONDARY CURRENT RATING 5 A • 20 TIMES SEC CURRENT: 100 AMPS • SEC. VOLTAGE DEVELOPED: 400V • MAXIMUM RATIO ERROR: 10% • IF BURDEN 2 , FOR 400V, IT CAN SUPPLY MORE THAN 100 AMPS SAY 200 AMPS WITHOUT EXCEECING 10% ERROR.
  • 36. N1 N2 I1 Ze Ie <10 Isec = 100 Rsec RB LB EXTERNAL BURDEN Ie+Isec Zint ACCURACY ACLASS: C200 RATED SEC CURRENT = 5 A EXTERNALBURDEN = STANDARD BURDEN = 2 .0 OHMS Ve=200 V Isec = 100 A Ie <10 Amps. I1
  • 37.
  • 39.
  • 40. BUT THE REST OF US “SHOW US THE DATA”
  • 41. PERFORMANCE CRITERIA • THE MEASURE OF A CT PERFORMANCE IS ITS ABILITY TO REPRODUCE ACCURATELY THE PRIMARY CURRRENT IN SECONDARY AMPERES - BOTH IN WAVE SHAPE AND MAGNITUDE …. CORRECT RATIO AND ANGLE.
  • 42. CT SELECTION AND PERFORMANCE EVALUATION FOR PHASE FAULTS 600/5 MR Accuracy class C100 is selected Load Current= 90 A Max 3 phase Fault Current= 2500 A Min. Fault Current=350 A STEPS: CT Ratio selection Relay Tap Selection Determine Total Burden (Load) CT Performance using ANSI/IEEE Standard CT Performance using Excitation Curve
  • 43. PERFORMANCE CALCULATION STEPS: CT Ratio selection Relay Tap Selection Determine Total Burden (Load) CT Performance using ANSI/IEEE Standard CT Performance using Excitation Curve STEPS: CT Ratio selection - within short time and continuous current – thermal limits - max load just under 5A Load Current= 90 A CT ratio selection : 100/5
  • 44. PERFORMANCE CALCULATION STEP: Relay Tap Selection O/C taps – min pickup , higher than the max. load 167%, 150% of specified thermal loading. Load Current= 90 A for 100/5 CT ratio = 4.5 A sec. Select tap higher than max load say = 5.0 How much higher – relay characteristics, experience and judgment. Fault current: min: 350/20 = 17.5 Multiple of PU = 17.5/5 = 3.5 Multiple of PU = 17.5/6 = 2.9
  • 45. PERFORMANCE CALCULATION STEP: Determine Total Burden (Load) Relay: 2.64 VA @ 5 A and 580 VA @ 100 A Lead: 0.4 Ohms Total to CT terminals: (2.64/5*5 = 0.106) + 0.4 = 0.506 ohms @ 5A (580/100*100 = 0.058) + 0.4 = 0.458 ohms @ 100 A
  • 46. PERFORMANCE CALCULATION STEPS: CT Ratio selection Relay Tap Selection Determine Total Burden (Load) CT Performance using ANSI/IEEE Standard CT Performance using Excitation Curve
  • 47. PERFORMANCE CALCULATION STEP: CT Performance using ANSI/IEEE Standard Ip Ie Ze Xp Rp e Rs Sec g h c d Pri Is Determine voltage @ max fault current CT must develop across its terminals gh
  • 48. PERFORMANCE CALCULATION STEP: Performance – ANSI/IEEE Standard Vgh = 2500/20 * 0.458 = 57.25 600/5 MR C100 CT used at tap 100/5 -- effective accuracy class (100/600) x 100 = ? CT is capable of developing 16.6 volts. Severe Saturation. Cannot be used.
  • 49. PERFORMANCE CALCULATION STEP: Performance – ANSI/IEEE Standard For microprocessor based relay: Burden will change from 0.458 to o.4 Vgh = 2500/20 * 0.4 = 50.0 600/5 MR C100 CT used at tap 100/5 -- effective accuracy class (100/600) x 100 = ? CT is capable of developing 16.6 volts. Severe Saturation. Cannot be used.
  • 50. PERFORMANCE CALCULATION STEP: Performance – ANSI/IEEE Standard Alternative: use 400/5 CT tap: Max Load = 90 A Relay Tap = 90/80 = 1.125 Use: 1.5 relay tap. Min Fault Multiples of PU=(350/80=4.38, 4.38/1.5= 2.9) Relay burden at this tap = 1.56 ohms Total burden at CT terminals = 1.56 + 0.4 = 1.96 Vgh = 2500/80 * 1.96 = 61.25 600/5 MR C100 CT used at tap 400/5-- effective accuracy class is = (400/600) x 100 = ? CT is capable of developing 66.6 volts. Within CT capability
  • 51. PERFORMANCE CALCULATION STEP: CT Performance using Excitation Curve ANSI/IEEE ratings “ballpark”. Excitation curve method provides relatively exact method. Examine the curve Burden = CT secondary resistance + lead resistance + relay burden Burden = 0.211 + 0.4 + 1.56 = 2.171 For load current 1.5 A: Vgh = 1.5 * 2.171 = 3.26 V Ie = 0.024 Ip = (1.5+0.024) * 80 = 123 A well below the min If = 350 A (350/123=2.84 multiple of pick up)
  • 52. PERFORMANCE CALCULATION STEP: CT Performance using Excitation Curve For max fault current Burden = CT secondary resistance + lead resistance + relay burden Burden = 0.211 + 0.4 + 1.56 = 2.171 Fault current 2500/80 = 31.25 A: Vgh = 31.25 * 2.171 = 67.84 V Ie = 0.16 Beyond the knee of curve, small amount 0.5% does not significantly decreases the fault current to the relay.
  • 53. I2 RB CT winding resistance = 0.3 ohms Lead length = 750 ft # 10 wire Relay burden = 0.05 ohms as constant Fault current = 12500A/18000A CT CLASS = C400/C800 2000/5 MR current transformer CT RATIO = 800/5 TEST Determine CT performance using Excitation Curve method:
  • 54. AN EXAMPLE – C400 • CT RESISTANCE 0.3 OHMS • LEAD RESISTANCE 1.5 OHMS • IMPEDANCE OF VARIOUS DEVICES 0.05 OHMS • FAULT CURRENT 12500 AMPS • CT RATIO 800/5 • ACCURACY CLASS C400 • supply curves C400/800
  • 55. CALCULATIONS for 12500 A – C400 • BURDEN = ( Z-LEAD + Z - CT SEC + D - DEVICES) • Ve = (1.5 + 0.3 + 0.05 ) 12500/160 • Ve = 144.5 VOLTS Plot on curve • Plot on C400
  • 56. CALCULATIONS for 18000 –C400 • BURDEN = ( Z-LEAD + Z - CT SEC + D - DEVICES) • Ve = (1.5 + 0.3 + 0.05 ) 18000/160 • Ve = 209 VOLTS Plot on curve • Plot on C400
  • 57. ANOTHER EXAMPLE C800 • CT RESISTANCE 0.3 OHMS • LEAD RESISTANCE 1.5 OHMS • IMPEDANCE OF VARIOUS DEVICES 0.05 OHMS • FAULT CURRENT 12500 AMPS • CT RATIO 800/5 • ACCURACY CLASS C800 • supply curves C400/800
  • 58. CALCULATIONS for 12500 A – C800 • BURDEN = ( Z-LEAD + Z - CT SEC + D - DEVICES) • Ve = (1.5 + 0.3 + 0.05 ) 12500/160 • Ve = 144.5 VOLTS Plot on curve • Plot on C800
  • 59. CALCULATIONS for 18000 A –C800 • BURDEN = ( Z-LEAD + Z - CT SEC + D - DEVICES) • Ve = (1.5 + 0.3 + 0.05 ) 18000/160 • For 18,000 A (Ve =209 V) Plot on curve • Plot on C800
  • 60. FAULT CURRENT MAGNITUDES • 25 -33 KA 8 • 20 - 25 KA 10 • 12.5 -20 KA 46 • 20 - 25 KA 35 • 10 -12.5 KA 35 • <10 KA +150 REFER TO PAGE 6 OF PAPER
  • 63. STANDARD DATA FROM MANUFACTURER • ACCURACY: – RELAY CLASS C200 – METERING CLASS, USE 0.15% – 0.3%, 0.6% & 1.2% AVAIALABLE BUT NOT RECOMMENDED – 0.15% MEANS +/- 0.15% error at 100% rated current and 0.30% error at 10% of rated current ( double the error)
  • 64. STANDARD DATA FROM MANUFACTURER • CONTINUOUS (Long Term) rating – Primary – Secondary, 5 Amp ( 1Amp) – Rating factor (RF) of 2.0 provides Twice Primary and Secondary rating continuous at 30degrees
  • 65. STANDARD DATA FROM MANUFACTURER • SHORT TIME TERMINAL RATINGS Transmission Voltage Applications – One Second Rating = 80% Imax Fault, based on IxIxT=K where T=36 cycles & I=Max fault current Distribution Voltage Applications One Second Rating = Maximum Fault Current level
  • 66. RATIO CONSIDERATIONS • CURRENT SHOULD NOT EXCEED CONNECTED WIRING AND RELAY RATINGS AT MAXIMUM LOAD. NOTE DELTA CONNECTD CT’s PRODUCE CURRENTS IN CABLES AND RELAYS THAT ARE 1.732 TIMES THE SECONDARY CURRENTS
  • 67. RATIO CONSIDERATIONS • SELECT RATIO TO BE GREATER THAN THE MAXIMUM DESIGN CURRENT RATINGS OF THE ASSOCIATED BREAKERS AND TRANSFORMERS.
  • 68. RATIO CONSIDERATIONS • RATIOS SHOULD NOT BE SO HIGH AS TO REDUCE RELAY SENSITIVITY, TAKING INTO ACCOUNT AVAILABLE RANGES.
  • 69. RATIO CONSIDERATIONS • THE MAXIMUM SECONDARY CURRENT SHOULD NOT EXCEED 20 TIMES RATED CURRENT. (100 A FOR 5A RATED SECONDARY)
  • 70. RATIO CONSIDERATIONS • HIGHEST CT RATIO PERMISSIBLE SHOULD BE USED TO MINIMIZE WIRING BURDEN AND TO OBTAIN THE HIGHEST CT CAPABILITYAND PERFORMANCE.
  • 71. RATIO CONSIDERATIONS • FULL WINGING OF MULTI-RATIO CT’s SHOULD BE SELECTED WHENEVER POSSIBLE TO AVOID LOWERING OF THE EFFECTIVE ACCURACY CLASS.
  • 72. TESTING •Core Demagnetizing – The core should be demagnetized as the final test before the equipment is put in service. Using the Saturation test circuit, apply enough voltage to the secondary of the CT to saturate the core and produce a cecondary currrent of 3- 5 amps. Slowly reduce the voltage to zero before turning off the variac.
  • 73. TESTING •Saturation – The saturation point is reached when there is a rise in the test current but not the voltage.
  • 74. TESTING •Flashing • This test checks the polarity of the CT •Ratio •Insulation test