Indonesian Journal of Electrical Engineering and Computer Science
Vol. 8, No. 3, December 2017, pp. 751 ~ 756
DOI: 10.11591/ijeecs.v8.i3.pp751-755  751
Received August 29, 2017; Revised October 5, 2017; Accepted November 23, 2017
Capacitive and Inductive Line Reactance for Network
Reconfiguration
Aiman Suhailah Saifuddin*
, Karmila Kamil, Halimatun Hashim, Ruthraganapathy
Radhakrishnan
Electrical Power Engineering Department, Universiti Tenaga Nasional,
43000 Kajang, Malaysia.
Corresponding author, *e-mail: Aiman_Suhailah@uniten.edu.my
Abstract
Solar PV may cause power congestion to occur in a transmission line when there is high solar
irradiance that causing solar PV to generate more power flow than demanded power flow. Transmission
line congestion that can be made worst by adding extra power generating farm such as centralized PV
farm of renewable energy which helps to deliver customers with the demand or load required. The power
generated coming from solar PV is depending on the weather and can definitely worsen the flow in
transmission line due to the power captured. In this case, the high solar irradiance can affect the power
generated from solar PV and will cause power congestion when power generated is higher than the load
demanded. In this paper, the proposed method used to overcome the power congestion in a transmission
line is by rerouting the excess power from the overloaded line to underloaded line by changing the line
reactance of the line. An IEEE 30 bus test system is developed in PSS/E software as the test system. The
output monitored is the line stability index of the affected line before and after rerouting process.
Keywords: power congestion; network reconfiguration; line stability
Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved.
1. Introduction
Distributed generation is an upcoming renewable energy which is widely used in this
modernized world and it is defined as generation of power from a few kilowatts up to 100MW by
International Council on Large Electricity System [1]. For a higher load requirement which the
generation is more than 100MW, the power will be injected directly to the transmission system.
A scenario when power system generated is more than the demanded power system is a
concern in power system analysis study for future power generation. Power congestion is a
situation when the power generated is more than power demanded by the loads and it will
cause overburdened to the power system. Power congestion can cause the voltage collapse to
occur in a power system and the system will be interrupted. Besides that, in deregulated
systems, line congestion apart from causing stability problems can increase the cost of
electricity [2-7]. To overcome power congestion in a power system network, rerouting of power
flow from the overloaded transmission line to the underloaded transmission line is proposed.
This paper will focus on rerouting the excess power flow by changing the line reactance of the
affected line. Network reconfiguration method is employed for loss minimization and exhaustive
technique is also applied to achieve the minimal loss switching scheme [8-10].
In the real application, the equipment that might be used to change the line reactance is
Distributed Series Reactor that provide control of one or more AC Transmission System
parameters to enhance controllability and increase capability in transmitting power supply by
IEEE. Mainly there are three types of Distributed Series FACTS Devices. Distributed Series
Reactor (DSR) is known to be the most flexible device since it can be implemented either in
meshes or interconnected power system configuration. The flexibility of a DSR is determined
when it only works with the conjunction of an inductor. Whereas, DSI or other distributed FACTS
requires both capacitor and inductor to provide the function. Besides just being flexible, DSR
does not need communication system in its topology to direct power flow in cables since it is
able to automatically alter each module of DSR in a system or specifically on transmission lines.
 ISSN: 2502-4752
IJEECS Vol. 8, No. 3, December 2017 : 751 – 755
752
The mechanism or function of DSR is simple as it will inject inductance to lines which faces over
current or exceed the current carrying capability [11-15].
Power flow of a system can be altered and controlled by changing impedance of each
transmission lines. Power flow will be distributed equally with the decrement and increment of
impedance values in the transmission lines. Therefore, in order to take charge of power flow
between buses, capacitive or inductive injection in the networks can be implemented to change
impedance. Main reason to take such action is to avoid the breakdown of the system due to
imbalance power flow. Imbalance of power flow causes transmission lines to be worse in a long
period of time as it will be carrying current exceeding its capability. Faulted lines will be switched
out whenever there is occurrence of breakdown so that there would not be any disturbance to
the supply and that has been a reliability issue. Although disturbance can be avoided, it is
always better to completely cure the system rather than avoiding. Therefore, lines which faces
high imbalance power can be corrected by diverting the excessive power to other neighbouring
lines which has extra capacity to handle more power. When current is excessive in a
transmission line, there will also be higher losses according to the power loss equation,
𝑃𝑙𝑜𝑠𝑠 = 𝐼2
𝑅 (1)
The discussion about the line impedance theory earlier is a technique used by changing the line
reactance using Distributed Series Reactor to control the real power. Besides that, DSR also
helps to reconfigure and reroute power flow if there is breakdown occurrence [7].
𝑋 𝐿 = 𝑗(2𝜋𝑓) 𝐿 (2)
Where,
𝑋 𝐿 – Impedance of inductor
L – Inductance
All lines should only accept current according to its limit or predetermined value for safety
purposes. By increasing the impedance, excessive current from that transmission line will be
diverted to under-utilized line so that line burdening can be reduced. The line congestion occurs
at few different occasion of the day depending on the load demand needed by users. Therefore,
by sharing loads almost equally between lines, transmission capacity and reliability can be
enhanced. Besides that, the condition of lines can be kept safe and also increase the life span
of each transmission lines.
2. Research Method
Test system used for the simulation is IEEE 30 bus test system. Fig. 1 shows the IEEE
30 Bus Test System in PSS®E. The test system including of 6 synchronous generators at bus
1, 2, 13, 23, 22 and 27. Power System Simulator for Engineering (PSS®E) is being used to
simulate the test system and parameters of line voltage, sending real power and receiving
reactive power are monitored to check the voltage stability of the line. These parameters are
then used to check the voltage stability of the line using the formula of Line Stability Index, LQP.
For a stable system, the value of LQP must be in between 0 to 1. However, for this paper, the
rerouting process will be done once the value of LQP is more than 0.5.
𝐿𝑄𝑃 = 4 [
𝑋 𝐿
𝑉𝑖
2 ] [
𝑋 𝐿
𝑉𝑖
2 𝑃𝑖
2
+ 𝑄𝑗] (3)
Solar PV is connected randomly at bus 2, 8 and 12. The real power from the Solar PV is
increased to a certain level which is more than the maximim power set for the busses and until
the line stability index of the affected line exceed 0.5. Once it exceeds 0.5, the line reactance is
changed, the power flow is monitored and the line stability index is calculated. The comparison
of the line stability index of the lines between with and without rerouting is done from the
simulation result.
IJEECS ISSN: 2502-4752 
Capacitive and Inductive Line Reactance for Network … (Aiman Suhailah Saifuddin)
753
Figure 1. IEEE 30 Bus Test System
3. Results and Analysis
The comparison of the line stability index before and after rerouting is done for each line
that connected to the bus injected with excess real power in order to monitor the effect of
changing the line reactance for rerouting purpose.
Table 1 shows the changes after rerouting the power. As it can be seen the line stability
index from bus 2 to 1 is exceed 0.5. The inductive line reactance of this line is increased which
causes the power to divert the direction to flow from bus 2 to 4 which increased the index of bus
2 to 4 and reduce the index of line from bus 2 to 1. However, there is no changes in the index
for the line for the connection of bus 2 to 6 and 2 to 5. It means that the power is not divert to
these 2 lines.
Table 1. Result between Bus Connections at Bus 2
Bus connection LQP value
before rerouting
LQP value
after rerouting
Changes
2 to 1 0.51 0.48 Decrease
2 to 4 0.05 0.13 Increase
2 to 6 0.02 0.02 No changes
2 to 5 0.1 0.1 No changes
Table 2 shows the power flow between lines connected to bus 8. In this case, there are
only 2 lines connected to bus 8. Before rerouting the index is exceeded 0.5 on the line from bus
8 to 6 and after rerouting the index is reduced to lower value. The index for the line from bus 8
to bus 28 is increased from lower value to higher value which show the excess power flow to
this line.
 ISSN: 2502-4752
IJEECS Vol. 8, No. 3, December 2017 : 751 – 755
754
Table 2. Result between Bus Connections at Bus 8
Bus connection LQP value
before rerouting
LQP value
after rerouting
Changes
8 to 6 0.53 0.46 Decrease
8 to 28 0.04 0.38 Increase
Table 3 shows the result for the lines connected to bus number 12. There are 5 busses
connected to bus 12. The index for line that connects bus 12 to 13 is exceeded 0.5 before
rerouting and others are below 0.5. After increasing the inductive line reactance of the line, the
index is reduced while the index of the lines that connect bus 12 to 4 and 12 to 15 increased but
still within the limit of less than 0.5.
Table 3. Result between Bus Connections at Bus 12
Bus connection LQP value
before rerouting
LQP value
after rerouting
Changes
12 to 4 0.08 0.15 Increase
12 to 13 0.52 0.25 Decrease
12 to 14 0.01 0.01 No changes
12 to 15 0.02 0.04 Increase
12 to 16 0.06 0.06 No changes
4. Conclusion and Recommendation
Power congestion between lines can be solved with the idea of rerouting the excess
power to the nearest line(s). It is important to maintain the allowed capacity to flow in the lines in
order to maintain the life span of transmission lines and to prevent power losses in the system
by mechanism of diverting power from over utilized to under-utilized lines. Finally, power
supplies by solar photovoltaic will be a very big plus point to Malaysia as it is placed near to the
equator and sun energy can be captured at high rating. The only important factors to be
controlled are losses and the life span of lines. This is due to the high-power conversion of solar
from sun energy which can cause tremendous of power to flow in lines but at the same time
cause losses and reduce the life span of lines.
In the future works, author would like recommend other researchers to studying the
numerical value of line reactance should the system has in order to reroute. The author also
recommends other researchers to monitor the best line to receive the excess power by studying
the impact of changing both the inductive and capacitive line reactance in the system in details.
Acknowledgement
The authors would like to thank the Ministry of Education, Malaysia for funding this project under
the Fundamental Research Grant Scheme (20140135FRGS) and Universiti Tenaga Nasional
for their full support in publishing this paper.
References
[1] T. Ackermann, G. Andersson, L. Soder. Distributed Generation: A Definition. Electrical Power
System Research. 2001; 57: 195-204.
[2] Large-Scale Solar Technology and Policy Forum, April 8-9, 2010.
[3] Hua Wan, James D. McCalley, Vijay Vittal. Increasing Thermal Rating by Risk Analysis.
Transaction on Power Systems. 1999; 4(3): 815-828.
[4] Mulukutla S.Sarma, Thomas J. Overbye, J. Duncan Glover. Power System Analysis and Design
Engage Learning, Stamford, 2012.
[5] C. Hitaj. Renewable Power Effects on Electricity Transmission Congestion and Emissions. College
Park, Maryland, 2012.
[6] CEC, "Transmission Congestion and Renewable Generation," Clean Energy Council, Victoria,
2010.
[7] Anthony F. Sleva, Protective Relay Principles, FL: CRC Press, 2009.
[8] A. Mohamed Imran, M. K. (2014). A New Power System Reconfiguration Scheme for Power Loss
Minimization and Voltage Profile Enhancement Using Fireworks Algorithm. Electrical Power and
Energy Systems, 62, pg. 312-322.
IJEECS ISSN: 2502-4752 
Capacitive and Inductive Line Reactance for Network … (Aiman Suhailah Saifuddin)
755
[9] Chanda, S., & De, A. Congestion Relief of Contingent Power Network with Evolutionary
Optimization Algorithm. TELKOMNIKA (Telecommunication, Computing, Electronics and Control).
2012; 10(1). doi:10.12928/telkomnika.v10i1.142
[10] Myint, S. M., & Naing, S. W. Network Reconfiguration for Loss Reduction and Voltage Profile
Improvement of 110-Bus Radial Distribution System Using Exhaustive Search Techniques.
International Journal of Electrical and Computer Engineering. 2015; 5(4): 788-797
[11] Deepak Divan, Harjeet Johal. Distributed FACTS - A New Concept for Realizing Grid Power Flow
Control. Transaction on Power Electronics. 2007; 22(6): 2253-2259.
[12] H. Johal. Distributed Series Reactance: A New Approach to Realize Grid Power Flow Control. Ph.
D Thesis. Georgia Institute of Technology. 2008.
[13] Sandeep R. Gaigowal, M. M. Renge. Some Studies of Distributed Series FACTS Controller to
control active Power Flow through Transmission Line. International Conference on Power, Energy
and Control. 2012.
[14] Er. Qasim Kamil Mohsin, Jyoti Shrivastava. AC Power Flow Control of Grid by Series D-Fact. 2013;
2 (4); 245-250.
[15] L.E. College, Morbi, "D-FACTS - Distributed Static Series Compensator (DSSC) and Distributed
Series Reactor (DSR)," International Journal for Scientific Research and Development. 2014; 2(3);
838-840.

More Related Content

What's hot

8575R 50% Complete
8575R 50% Complete8575R 50% Complete
8575R 50% Complete
hiidrasidi
 
Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...
IAEME Publication
 
Power System Operation and Control
Power System Operation and ControlPower System Operation and Control
Power System Operation and Control
Biswajit Pratihari
 

What's hot (20)

IRJET- Load Balancing using Fact Devices
IRJET- Load Balancing using Fact DevicesIRJET- Load Balancing using Fact Devices
IRJET- Load Balancing using Fact Devices
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
 
Design and Analysis of Capacitive Power Transfer System with and without the ...
Design and Analysis of Capacitive Power Transfer System with and without the ...Design and Analysis of Capacitive Power Transfer System with and without the ...
Design and Analysis of Capacitive Power Transfer System with and without the ...
 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
 
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
 
Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...
 
8575R 50% Complete
8575R 50% Complete8575R 50% Complete
8575R 50% Complete
 
A010410109
A010410109A010410109
A010410109
 
Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...Optimal placement and sizing of ht shunt capacitors for transmission loss min...
Optimal placement and sizing of ht shunt capacitors for transmission loss min...
 
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOMIRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
 
F021201048053
F021201048053F021201048053
F021201048053
 
12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOM
 
Passive Damper Network in a Simple DC Distribution Power System
Passive Damper Network in a Simple DC Distribution Power System Passive Damper Network in a Simple DC Distribution Power System
Passive Damper Network in a Simple DC Distribution Power System
 
Power System Operation and Control
Power System Operation and ControlPower System Operation and Control
Power System Operation and Control
 
Design & Simulation of Energy Storage Unified Power Quality Conditioner (EUPQ...
Design & Simulation of Energy Storage Unified Power Quality Conditioner (EUPQ...Design & Simulation of Energy Storage Unified Power Quality Conditioner (EUPQ...
Design & Simulation of Energy Storage Unified Power Quality Conditioner (EUPQ...
 
Base paper
Base paperBase paper
Base paper
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
Application of Distribution Power Electronic Transformer for Medium Voltage
Application of Distribution Power Electronic Transformer for Medium VoltageApplication of Distribution Power Electronic Transformer for Medium Voltage
Application of Distribution Power Electronic Transformer for Medium Voltage
 
05617901
0561790105617901
05617901
 

Similar to 44 capacitive paper id 0007 edit septian

Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
International Journal of Power Electronics and Drive Systems
 
Flexible AC Transmission Sytstem
Flexible AC Transmission Sytstem Flexible AC Transmission Sytstem
Flexible AC Transmission Sytstem
ganeshbehera6
 

Similar to 44 capacitive paper id 0007 edit septian (20)

Simulation of different power transmission systems and their capacity of redu...
Simulation of different power transmission systems and their capacity of redu...Simulation of different power transmission systems and their capacity of redu...
Simulation of different power transmission systems and their capacity of redu...
 
A performance comparison of transformer-less grid tied PV system using diode ...
A performance comparison of transformer-less grid tied PV system using diode ...A performance comparison of transformer-less grid tied PV system using diode ...
A performance comparison of transformer-less grid tied PV system using diode ...
 
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
 
1743 1748
1743 17481743 1748
1743 1748
 
1743 1748
1743 17481743 1748
1743 1748
 
Aq33247251
Aq33247251Aq33247251
Aq33247251
 
Aq33247251
Aq33247251Aq33247251
Aq33247251
 
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
 
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
 
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOM
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOMOptimal Reactive Power Compensation in Electric Transmission Line using STATCOM
Optimal Reactive Power Compensation in Electric Transmission Line using STATCOM
 
Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...
 
Improving Distribution Feeders for Photovoltaic Generation by Loop Power Cont...
Improving Distribution Feeders for Photovoltaic Generation by Loop Power Cont...Improving Distribution Feeders for Photovoltaic Generation by Loop Power Cont...
Improving Distribution Feeders for Photovoltaic Generation by Loop Power Cont...
 
[IJET-V1I4P7] Authors :Su Mon Myint
[IJET-V1I4P7] Authors :Su Mon Myint[IJET-V1I4P7] Authors :Su Mon Myint
[IJET-V1I4P7] Authors :Su Mon Myint
 
Flexible AC Transmission Sytstem
Flexible AC Transmission Sytstem Flexible AC Transmission Sytstem
Flexible AC Transmission Sytstem
 
Optimum Reactive Power Calculation for Reducing Power System Operation Cost
Optimum Reactive Power Calculation for Reducing Power System Operation CostOptimum Reactive Power Calculation for Reducing Power System Operation Cost
Optimum Reactive Power Calculation for Reducing Power System Operation Cost
 
Facts unit 1
Facts unit 1Facts unit 1
Facts unit 1
 
The Impact of Line Resistance on the Performance of Controllable Series Compe...
The Impact of Line Resistance on the Performance of Controllable Series Compe...The Impact of Line Resistance on the Performance of Controllable Series Compe...
The Impact of Line Resistance on the Performance of Controllable Series Compe...
 
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
 
Power Flow Control using Quadrature Boosters
Power Flow Control using Quadrature BoostersPower Flow Control using Quadrature Boosters
Power Flow Control using Quadrature Boosters
 
Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...Power System Stability Enhancement Using Static Synchronous Series Compensato...
Power System Stability Enhancement Using Static Synchronous Series Compensato...
 

More from IAESIJEECS

08 20314 electronic doorbell...
08 20314 electronic doorbell...08 20314 electronic doorbell...
08 20314 electronic doorbell...
IAESIJEECS
 
06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...
IAESIJEECS
 
06 20273 37746-1-ed
06 20273 37746-1-ed06 20273 37746-1-ed
06 20273 37746-1-ed
IAESIJEECS
 
03 20270 true power loss reduction
03 20270 true power loss reduction03 20270 true power loss reduction
03 20270 true power loss reduction
IAESIJEECS
 

More from IAESIJEECS (20)

08 20314 electronic doorbell...
08 20314 electronic doorbell...08 20314 electronic doorbell...
08 20314 electronic doorbell...
 
07 20278 augmented reality...
07 20278 augmented reality...07 20278 augmented reality...
07 20278 augmented reality...
 
06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...06 17443 an neuro fuzzy...
06 17443 an neuro fuzzy...
 
05 20275 computational solution...
05 20275 computational solution...05 20275 computational solution...
05 20275 computational solution...
 
04 20268 power loss reduction ...
04 20268 power loss reduction ...04 20268 power loss reduction ...
04 20268 power loss reduction ...
 
03 20237 arduino based gas-
03 20237 arduino based gas-03 20237 arduino based gas-
03 20237 arduino based gas-
 
02 20274 improved ichi square...
02 20274 improved ichi square...02 20274 improved ichi square...
02 20274 improved ichi square...
 
01 20264 diminution of real power...
01 20264 diminution of real power...01 20264 diminution of real power...
01 20264 diminution of real power...
 
08 20272 academic insight on application
08 20272 academic insight on application08 20272 academic insight on application
08 20272 academic insight on application
 
07 20252 cloud computing survey
07 20252 cloud computing survey07 20252 cloud computing survey
07 20252 cloud computing survey
 
06 20273 37746-1-ed
06 20273 37746-1-ed06 20273 37746-1-ed
06 20273 37746-1-ed
 
05 20261 real power loss reduction
05 20261 real power loss reduction05 20261 real power loss reduction
05 20261 real power loss reduction
 
04 20259 real power loss
04 20259 real power loss04 20259 real power loss
04 20259 real power loss
 
03 20270 true power loss reduction
03 20270 true power loss reduction03 20270 true power loss reduction
03 20270 true power loss reduction
 
02 15034 neural network
02 15034 neural network02 15034 neural network
02 15034 neural network
 
01 8445 speech enhancement
01 8445 speech enhancement01 8445 speech enhancement
01 8445 speech enhancement
 
08 17079 ijict
08 17079 ijict08 17079 ijict
08 17079 ijict
 
07 20269 ijict
07 20269 ijict07 20269 ijict
07 20269 ijict
 
06 10154 ijict
06 10154 ijict06 10154 ijict
06 10154 ijict
 
05 20255 ijict
05 20255 ijict05 20255 ijict
05 20255 ijict
 

Recently uploaded

Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..
MaherOthman7
 
Complex plane, Modulus, Argument, Graphical representation of a complex numbe...
Complex plane, Modulus, Argument, Graphical representation of a complex numbe...Complex plane, Modulus, Argument, Graphical representation of a complex numbe...
Complex plane, Modulus, Argument, Graphical representation of a complex numbe...
MohammadAliNayeem
 

Recently uploaded (20)

Geometric constructions Engineering Drawing.pdf
Geometric constructions Engineering Drawing.pdfGeometric constructions Engineering Drawing.pdf
Geometric constructions Engineering Drawing.pdf
 
Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1
 
Intelligent Agents, A discovery on How A Rational Agent Acts
Intelligent Agents, A discovery on How A Rational Agent ActsIntelligent Agents, A discovery on How A Rational Agent Acts
Intelligent Agents, A discovery on How A Rational Agent Acts
 
RM&IPR M5 notes.pdfResearch Methodolgy & Intellectual Property Rights Series 5
RM&IPR M5 notes.pdfResearch Methodolgy & Intellectual Property Rights Series 5RM&IPR M5 notes.pdfResearch Methodolgy & Intellectual Property Rights Series 5
RM&IPR M5 notes.pdfResearch Methodolgy & Intellectual Property Rights Series 5
 
"United Nations Park" Site Visit Report.
"United Nations Park" Site  Visit Report."United Nations Park" Site  Visit Report.
"United Nations Park" Site Visit Report.
 
Fabrication Of Automatic Star Delta Starter Using Relay And GSM Module By Utk...
Fabrication Of Automatic Star Delta Starter Using Relay And GSM Module By Utk...Fabrication Of Automatic Star Delta Starter Using Relay And GSM Module By Utk...
Fabrication Of Automatic Star Delta Starter Using Relay And GSM Module By Utk...
 
Online book store management system project.pdf
Online book store management system project.pdfOnline book store management system project.pdf
Online book store management system project.pdf
 
Supermarket billing system project report..pdf
Supermarket billing system project report..pdfSupermarket billing system project report..pdf
Supermarket billing system project report..pdf
 
Quiz application system project report..pdf
Quiz application system project report..pdfQuiz application system project report..pdf
Quiz application system project report..pdf
 
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfInvolute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
 
Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..
 
Piping and instrumentation diagram p.pdf
Piping and instrumentation diagram p.pdfPiping and instrumentation diagram p.pdf
Piping and instrumentation diagram p.pdf
 
Filters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsFilters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility Applications
 
How to Design and spec harmonic filter.pdf
How to Design and spec harmonic filter.pdfHow to Design and spec harmonic filter.pdf
How to Design and spec harmonic filter.pdf
 
Software Engineering - Modelling Concepts + Class Modelling + Building the An...
Software Engineering - Modelling Concepts + Class Modelling + Building the An...Software Engineering - Modelling Concepts + Class Modelling + Building the An...
Software Engineering - Modelling Concepts + Class Modelling + Building the An...
 
Artificial Intelligence Bayesian Reasoning
Artificial Intelligence Bayesian ReasoningArtificial Intelligence Bayesian Reasoning
Artificial Intelligence Bayesian Reasoning
 
E-Commerce Shopping using MERN Stack where different modules are present
E-Commerce Shopping using MERN Stack where different modules are presentE-Commerce Shopping using MERN Stack where different modules are present
E-Commerce Shopping using MERN Stack where different modules are present
 
Electrostatic field in a coaxial transmission line
Electrostatic field in a coaxial transmission lineElectrostatic field in a coaxial transmission line
Electrostatic field in a coaxial transmission line
 
Insurance management system project report.pdf
Insurance management system project report.pdfInsurance management system project report.pdf
Insurance management system project report.pdf
 
Complex plane, Modulus, Argument, Graphical representation of a complex numbe...
Complex plane, Modulus, Argument, Graphical representation of a complex numbe...Complex plane, Modulus, Argument, Graphical representation of a complex numbe...
Complex plane, Modulus, Argument, Graphical representation of a complex numbe...
 

44 capacitive paper id 0007 edit septian

  • 1. Indonesian Journal of Electrical Engineering and Computer Science Vol. 8, No. 3, December 2017, pp. 751 ~ 756 DOI: 10.11591/ijeecs.v8.i3.pp751-755  751 Received August 29, 2017; Revised October 5, 2017; Accepted November 23, 2017 Capacitive and Inductive Line Reactance for Network Reconfiguration Aiman Suhailah Saifuddin* , Karmila Kamil, Halimatun Hashim, Ruthraganapathy Radhakrishnan Electrical Power Engineering Department, Universiti Tenaga Nasional, 43000 Kajang, Malaysia. Corresponding author, *e-mail: Aiman_Suhailah@uniten.edu.my Abstract Solar PV may cause power congestion to occur in a transmission line when there is high solar irradiance that causing solar PV to generate more power flow than demanded power flow. Transmission line congestion that can be made worst by adding extra power generating farm such as centralized PV farm of renewable energy which helps to deliver customers with the demand or load required. The power generated coming from solar PV is depending on the weather and can definitely worsen the flow in transmission line due to the power captured. In this case, the high solar irradiance can affect the power generated from solar PV and will cause power congestion when power generated is higher than the load demanded. In this paper, the proposed method used to overcome the power congestion in a transmission line is by rerouting the excess power from the overloaded line to underloaded line by changing the line reactance of the line. An IEEE 30 bus test system is developed in PSS/E software as the test system. The output monitored is the line stability index of the affected line before and after rerouting process. Keywords: power congestion; network reconfiguration; line stability Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved. 1. Introduction Distributed generation is an upcoming renewable energy which is widely used in this modernized world and it is defined as generation of power from a few kilowatts up to 100MW by International Council on Large Electricity System [1]. For a higher load requirement which the generation is more than 100MW, the power will be injected directly to the transmission system. A scenario when power system generated is more than the demanded power system is a concern in power system analysis study for future power generation. Power congestion is a situation when the power generated is more than power demanded by the loads and it will cause overburdened to the power system. Power congestion can cause the voltage collapse to occur in a power system and the system will be interrupted. Besides that, in deregulated systems, line congestion apart from causing stability problems can increase the cost of electricity [2-7]. To overcome power congestion in a power system network, rerouting of power flow from the overloaded transmission line to the underloaded transmission line is proposed. This paper will focus on rerouting the excess power flow by changing the line reactance of the affected line. Network reconfiguration method is employed for loss minimization and exhaustive technique is also applied to achieve the minimal loss switching scheme [8-10]. In the real application, the equipment that might be used to change the line reactance is Distributed Series Reactor that provide control of one or more AC Transmission System parameters to enhance controllability and increase capability in transmitting power supply by IEEE. Mainly there are three types of Distributed Series FACTS Devices. Distributed Series Reactor (DSR) is known to be the most flexible device since it can be implemented either in meshes or interconnected power system configuration. The flexibility of a DSR is determined when it only works with the conjunction of an inductor. Whereas, DSI or other distributed FACTS requires both capacitor and inductor to provide the function. Besides just being flexible, DSR does not need communication system in its topology to direct power flow in cables since it is able to automatically alter each module of DSR in a system or specifically on transmission lines.
  • 2.  ISSN: 2502-4752 IJEECS Vol. 8, No. 3, December 2017 : 751 – 755 752 The mechanism or function of DSR is simple as it will inject inductance to lines which faces over current or exceed the current carrying capability [11-15]. Power flow of a system can be altered and controlled by changing impedance of each transmission lines. Power flow will be distributed equally with the decrement and increment of impedance values in the transmission lines. Therefore, in order to take charge of power flow between buses, capacitive or inductive injection in the networks can be implemented to change impedance. Main reason to take such action is to avoid the breakdown of the system due to imbalance power flow. Imbalance of power flow causes transmission lines to be worse in a long period of time as it will be carrying current exceeding its capability. Faulted lines will be switched out whenever there is occurrence of breakdown so that there would not be any disturbance to the supply and that has been a reliability issue. Although disturbance can be avoided, it is always better to completely cure the system rather than avoiding. Therefore, lines which faces high imbalance power can be corrected by diverting the excessive power to other neighbouring lines which has extra capacity to handle more power. When current is excessive in a transmission line, there will also be higher losses according to the power loss equation, 𝑃𝑙𝑜𝑠𝑠 = 𝐼2 𝑅 (1) The discussion about the line impedance theory earlier is a technique used by changing the line reactance using Distributed Series Reactor to control the real power. Besides that, DSR also helps to reconfigure and reroute power flow if there is breakdown occurrence [7]. 𝑋 𝐿 = 𝑗(2𝜋𝑓) 𝐿 (2) Where, 𝑋 𝐿 – Impedance of inductor L – Inductance All lines should only accept current according to its limit or predetermined value for safety purposes. By increasing the impedance, excessive current from that transmission line will be diverted to under-utilized line so that line burdening can be reduced. The line congestion occurs at few different occasion of the day depending on the load demand needed by users. Therefore, by sharing loads almost equally between lines, transmission capacity and reliability can be enhanced. Besides that, the condition of lines can be kept safe and also increase the life span of each transmission lines. 2. Research Method Test system used for the simulation is IEEE 30 bus test system. Fig. 1 shows the IEEE 30 Bus Test System in PSS®E. The test system including of 6 synchronous generators at bus 1, 2, 13, 23, 22 and 27. Power System Simulator for Engineering (PSS®E) is being used to simulate the test system and parameters of line voltage, sending real power and receiving reactive power are monitored to check the voltage stability of the line. These parameters are then used to check the voltage stability of the line using the formula of Line Stability Index, LQP. For a stable system, the value of LQP must be in between 0 to 1. However, for this paper, the rerouting process will be done once the value of LQP is more than 0.5. 𝐿𝑄𝑃 = 4 [ 𝑋 𝐿 𝑉𝑖 2 ] [ 𝑋 𝐿 𝑉𝑖 2 𝑃𝑖 2 + 𝑄𝑗] (3) Solar PV is connected randomly at bus 2, 8 and 12. The real power from the Solar PV is increased to a certain level which is more than the maximim power set for the busses and until the line stability index of the affected line exceed 0.5. Once it exceeds 0.5, the line reactance is changed, the power flow is monitored and the line stability index is calculated. The comparison of the line stability index of the lines between with and without rerouting is done from the simulation result.
  • 3. IJEECS ISSN: 2502-4752  Capacitive and Inductive Line Reactance for Network … (Aiman Suhailah Saifuddin) 753 Figure 1. IEEE 30 Bus Test System 3. Results and Analysis The comparison of the line stability index before and after rerouting is done for each line that connected to the bus injected with excess real power in order to monitor the effect of changing the line reactance for rerouting purpose. Table 1 shows the changes after rerouting the power. As it can be seen the line stability index from bus 2 to 1 is exceed 0.5. The inductive line reactance of this line is increased which causes the power to divert the direction to flow from bus 2 to 4 which increased the index of bus 2 to 4 and reduce the index of line from bus 2 to 1. However, there is no changes in the index for the line for the connection of bus 2 to 6 and 2 to 5. It means that the power is not divert to these 2 lines. Table 1. Result between Bus Connections at Bus 2 Bus connection LQP value before rerouting LQP value after rerouting Changes 2 to 1 0.51 0.48 Decrease 2 to 4 0.05 0.13 Increase 2 to 6 0.02 0.02 No changes 2 to 5 0.1 0.1 No changes Table 2 shows the power flow between lines connected to bus 8. In this case, there are only 2 lines connected to bus 8. Before rerouting the index is exceeded 0.5 on the line from bus 8 to 6 and after rerouting the index is reduced to lower value. The index for the line from bus 8 to bus 28 is increased from lower value to higher value which show the excess power flow to this line.
  • 4.  ISSN: 2502-4752 IJEECS Vol. 8, No. 3, December 2017 : 751 – 755 754 Table 2. Result between Bus Connections at Bus 8 Bus connection LQP value before rerouting LQP value after rerouting Changes 8 to 6 0.53 0.46 Decrease 8 to 28 0.04 0.38 Increase Table 3 shows the result for the lines connected to bus number 12. There are 5 busses connected to bus 12. The index for line that connects bus 12 to 13 is exceeded 0.5 before rerouting and others are below 0.5. After increasing the inductive line reactance of the line, the index is reduced while the index of the lines that connect bus 12 to 4 and 12 to 15 increased but still within the limit of less than 0.5. Table 3. Result between Bus Connections at Bus 12 Bus connection LQP value before rerouting LQP value after rerouting Changes 12 to 4 0.08 0.15 Increase 12 to 13 0.52 0.25 Decrease 12 to 14 0.01 0.01 No changes 12 to 15 0.02 0.04 Increase 12 to 16 0.06 0.06 No changes 4. Conclusion and Recommendation Power congestion between lines can be solved with the idea of rerouting the excess power to the nearest line(s). It is important to maintain the allowed capacity to flow in the lines in order to maintain the life span of transmission lines and to prevent power losses in the system by mechanism of diverting power from over utilized to under-utilized lines. Finally, power supplies by solar photovoltaic will be a very big plus point to Malaysia as it is placed near to the equator and sun energy can be captured at high rating. The only important factors to be controlled are losses and the life span of lines. This is due to the high-power conversion of solar from sun energy which can cause tremendous of power to flow in lines but at the same time cause losses and reduce the life span of lines. In the future works, author would like recommend other researchers to studying the numerical value of line reactance should the system has in order to reroute. The author also recommends other researchers to monitor the best line to receive the excess power by studying the impact of changing both the inductive and capacitive line reactance in the system in details. Acknowledgement The authors would like to thank the Ministry of Education, Malaysia for funding this project under the Fundamental Research Grant Scheme (20140135FRGS) and Universiti Tenaga Nasional for their full support in publishing this paper. References [1] T. Ackermann, G. Andersson, L. Soder. Distributed Generation: A Definition. Electrical Power System Research. 2001; 57: 195-204. [2] Large-Scale Solar Technology and Policy Forum, April 8-9, 2010. [3] Hua Wan, James D. McCalley, Vijay Vittal. Increasing Thermal Rating by Risk Analysis. Transaction on Power Systems. 1999; 4(3): 815-828. [4] Mulukutla S.Sarma, Thomas J. Overbye, J. Duncan Glover. Power System Analysis and Design Engage Learning, Stamford, 2012. [5] C. Hitaj. Renewable Power Effects on Electricity Transmission Congestion and Emissions. College Park, Maryland, 2012. [6] CEC, "Transmission Congestion and Renewable Generation," Clean Energy Council, Victoria, 2010. [7] Anthony F. Sleva, Protective Relay Principles, FL: CRC Press, 2009. [8] A. Mohamed Imran, M. K. (2014). A New Power System Reconfiguration Scheme for Power Loss Minimization and Voltage Profile Enhancement Using Fireworks Algorithm. Electrical Power and Energy Systems, 62, pg. 312-322.
  • 5. IJEECS ISSN: 2502-4752  Capacitive and Inductive Line Reactance for Network … (Aiman Suhailah Saifuddin) 755 [9] Chanda, S., & De, A. Congestion Relief of Contingent Power Network with Evolutionary Optimization Algorithm. TELKOMNIKA (Telecommunication, Computing, Electronics and Control). 2012; 10(1). doi:10.12928/telkomnika.v10i1.142 [10] Myint, S. M., & Naing, S. W. Network Reconfiguration for Loss Reduction and Voltage Profile Improvement of 110-Bus Radial Distribution System Using Exhaustive Search Techniques. International Journal of Electrical and Computer Engineering. 2015; 5(4): 788-797 [11] Deepak Divan, Harjeet Johal. Distributed FACTS - A New Concept for Realizing Grid Power Flow Control. Transaction on Power Electronics. 2007; 22(6): 2253-2259. [12] H. Johal. Distributed Series Reactance: A New Approach to Realize Grid Power Flow Control. Ph. D Thesis. Georgia Institute of Technology. 2008. [13] Sandeep R. Gaigowal, M. M. Renge. Some Studies of Distributed Series FACTS Controller to control active Power Flow through Transmission Line. International Conference on Power, Energy and Control. 2012. [14] Er. Qasim Kamil Mohsin, Jyoti Shrivastava. AC Power Flow Control of Grid by Series D-Fact. 2013; 2 (4); 245-250. [15] L.E. College, Morbi, "D-FACTS - Distributed Static Series Compensator (DSSC) and Distributed Series Reactor (DSR)," International Journal for Scientific Research and Development. 2014; 2(3); 838-840.