SlideShare a Scribd company logo
STARTING & RECOMMENDED
INTERLOCKS FOR
AH, ID, FD, PA Fans & BD Valves
Manohar Tatwawadi
Director
total output power solutions
Flue gas Path
• Dampers Needed to be Opened before AH is
started
Dampers Open
AH Air
Motors
AH AC
Motors
Starting of Rotary APH
• The lub. Oil pumps of support and guide bearings can be started
from control room but preferably from Local for the first time .
• Start any one of the pump locally and see that there is no oil
leakage.
• Check the lub oil pressure .
• Stop the pump and start the other pump and see that the flow and
pressure is normal, and that there is no oil leakage.
Note: All the 8 Nos. pumps shall be started locally and checked before
giving clearance for remote operation. The stop push buttons shall be
kept in released condition.
• Now open the air valve for starting the air motor of APH A or B as
the case may be. As the main drives are not in service, the solenoid
will supply air to air motor.
• Check the operation of APH for any abnormal sound or abnormal
seal rubbing.
• If the performance is normal, the main drive can be started locally
or from remote.
Starting of Rotary APH
• Check the performance of APH on main drive-the load current and
abnormal sound and vibrations are to be watched.
• On starting the main drive, the Air motor shall stop. This can be
verified in control room by the indication given from the service air
pressure switch, provided in the line.
• Now stop the main drive from Control room and check that the Air
motor comes on Auto.
• The air preheater soot blowers are to operated at regular intervals,
after lighting up of the boiler.
• The DP across Air preheaters has to be watched closely to see that
the APHs are free from choking.
• The oxygen and carbon dioxide levels in flue gas, before and after
APH have to be measured once in a shift to see the performance of
the boiler as well as APH. Abnormal drop in carbon dioxide level
after APH shall indicate poor performance of the APH seals. Normal
Drop: 2%.
Rotary Air Heater Interlocks
Rotary AHs are the first auxiliary to start Boiler.
CONDITIONS BEFORE START UP OF AHS:
• Both AHS are off (both AC motors and Air motors are off)
• The inlet dampers and the outlet dampers in the gas path,
secondary air path, primary air path are in full open condition.
STARTING AH ‘A’ (AH ‘B’ IS OFF) OR AH ‘B’ (AH ‘A’ is OFF
• AH ‘A’/’B’ AC motor is started. If the temperature of the
bearings is less than 70 Deg.C
• Whenever AH AC motor trips impulse shall be given for
starting Air motor provided the temperature of support/guide
bearing of AH ‘A’ is less than 70 Deg. C.
• Impulse shall be given for closing of the inlet and outlet
dampers of AH which is off.
Tripping of Air heaters
TRIPPING OF AH ‘A’ (AH ‘B’ IS OFF)/TRIPPING OF AH ‘B’ (AH
‘A’ IS OFF)
• AH AC motor/Air motor shall trip manually when the
temperature of support/guide bearing of AH is very
high (i.e. greater than 70 Deg. C). Under this
condition AH Air motor shall be prohibited from
starting.
• Air motor shall trip automatically when AH AC motor
starts.
NOTE: Trip signal of AH is to be taken from both AC &
Air motors trip
Tripping Sequence Of Air Heaters
Condition A:- BOTH AHS ARE WORKING WHEN ONE TRIPS
AND OTHER AH CONTINUES TO RUN:
• The gas inlet damper the secondary air inlet
damper and primary air inlet damper of the
tripped AH shall automatically closed. The gas
outlet damper, the secondary air outlet damper
and PA outlet damper of the tripped AH need not
be closed.
• However, if the operator wants to manually close
these outlet dampers they can be closed
TRIPPING OF AIR HEATERS
Condition B:- ONE AH IS WORKING AND THE OTHER AH IS
OFF:
• If the working Airheater trips, the operator shall
try for restarting the AH.
• If the restarting is not within 5 minutes, the boiler
shall be tripped.
Condition C:- BOTH AHS ARE WORKING AND TRIPPED.
• If both AHS ‘A’ and ‘B’ trip the operator may try
for restarting the AHs. If any one of the AH is not
started within 5 minutes the operator shall
manually trip the boiler within 5 minutes.
INTERLOCKS FOR LUBE OIL PUMPS OF
SUPPORT & GUIDE BEARINGS OF AH A & B
2x100% lube oil pump have been provided for the
support bearing. Any of the two lubricating oil pumps can
be preselected as main pump and the other as standby.
Following interlocks shall be provided for lub oil pumps.
• Whenever the temperature of support bearing of air
heater A is high (350C), impulse shall be given to start
the main oil pump.
• The standby oil pump shall start when the main oil
pump fails to start or trips.
• The main oil pump / stand by oil pump shall trip when
the temperature of the support bearing falls below a
present value (300C)
Flue Gas Cycle.. Starting of ID Fans
Dampers Open
Dampers Closed
ID Fan Pre-checks
• Ensure the manholes are closed.
• Check the availability of instruments to measure flow, pressure,
temperature etc. of the ID fan and drive motor.
• Check the closing and the opening of the suction and discharge gates.
Keep them closed before starting the ID fan.
• Check healthiness of all the protections and interlocks for their
functioning.
• Ensure the local push button is in the released position.
• Check that the discharge dampers of blower motors are open and the
modules are kept ON for supply.
• Check that the flue gas path is made through
– APH inlet flue gas dampers are open .
– ESP inlet gates are open .
– ESP outlet gates are open .
• Check that the seal trough is filled with water and overflow is maintained.
• Start the ID fan after ensuring the healthiness of protections whenever the
fan is to be started after long shutdown.
Starting Permissive for ID Fan
Check that the final start permissive is available. The final start
permissive will get available if the following conditions are
satisfied,
• ID fan stopped.
• Cooling water to the coolers adequate.
• Suction gate closed.
• Discharge gate closed.
• Ensure VFD for minimum speed.
• ID fan tripped indication should not exist.
• Ensure 220 V DC control supply for the breaker of other ID
fans is available.
• Now the first ID fan can be started
Post Start Checks of ID Fans
• Check the opening of gates on interlock, after 10
secs.
• Check the performance of the motor.
• Check adequate lub. oil pressure.
• Check the starting of both the discharge gate
blower motors on interlock. If not , start
manually.
• Maintain the furnace vacuum at -12 mmWC by
suitable loading of the fan.
I.D. FAN INTERLOCKS
Conditions existing when the unit is shut
down and prior to starting of ID fans.
• Either or both AHs are running.
• I.D. Fan ‘A’ and ID Fan ‘B’ off.
• Regulating dampers of fans A&B open.
• Inlet gates of Fans A & B open.
• Outlet gates of fans A & B open.
• The regulating dampers will be on manual control
during shut down and impulse from furnace draft
control to regulating dampers of ID fans disconnected.
Starting ID Fan ‘A’ (ID Fan ‘B’ Off)
Interlocks
ID Fan ‘A’ shall be prohibited from starting till the
following conditions are satisfied.
1. Regulating damper of Fan-A in minimum
position.
2. Outlet gate of Fan-A closed.
3. Inlet gate of Fan-A closed.
4. Fan/fan motor bearing temperature not very
high.
5. One of the air preheaters running.
For starting ID Fan B ( ID Fan A is off)
Interlocks similar to those as above shall hold good of this conditions.
Starting ID Fan ‘A’
When ID fan ‘A’ is started (ID Fan B is off), impulses
shall be give for.
1. Opening the inlet gate and outlet gate of Fan A
after the motor reaches the rated speed.
2. Connecting the regulating damper of Fan A to
the auto control.
3. Closing the inlet gate and the outlet gate of ID
Fan B and bringin the regulating damper to
minimum position.
4. Permission to start either FD Fan A or FD Fan B.
Tripping of ID Fan A (ID fan B is off)
ID Fan ‘A’ shall trip automatically under following
conditions.
1. ID Fan A bearing temperature too high (prior to
this, ID Fan A bearing temperature high shall be
annunciated in UCB).
2. ID Fan A motor bearing temperature too high
(prior to this, ID Fan a motor bearing
temperature high shall be annunciated in UCB).
3. Post purge fan trip (contact from FSSS)
4. Vibration level of FAN/MOTOR very high.
Tripping of ID Fan B (ID Fan A is off):
Interlocks similar to those above shall hold good for this condition.
Tripping of ID Fan
When ID Fan A trips (ID Fan B is off) impulses shall be given for:
1. Opening the outlet gate of ID Fan B.
2. Opening the inlet gate of ID Fan B.
3. Opening the regulating damper of ID Fan B to wide open
position.
4. Disconnecting the regulators impulse from acting on
regulating damper of ID Fan A.
5. Opening the regulating damper of ID Fan A to wide open
position.
6. Tripping the working FD Fans.
7. Boiler tripping.
8. To keep the inlet gate and outlet gate of ID Fan A open.
Starting of ID Fan B (ID Fan A is on)
ID Fan B shall be prohibited from starting unless
the following conditions are satisfied.
1. Outlet gate of Fan B is closed.
2. Inlet gate of Fan B is closed.
3. Regulating damper of Fan Bareing minimum
position.
4. Fan/fan motor bearing temperature not very
high.
Starting of ID Fan A (ID fan B is on)
Interlocks similar to above shall hold good for this condition.
Both ID Fans Started
• When ID Fan B is started, impulses shall be
given for.
• Opening the inlet gate and outlet gate of Fan B
after the motor reaches rated speed.
• Connecting the regulating damper of Fan B to
auto control.
• Permission to start other FD Fan.
Tripping of ID Fan B (ID Fan A is on)
ID Fan B shall trip automatically under the
following conditions.
• Fan bearing temperature too high (prior to
this fan bearing temperature high shall be
annunciated in UCB)
• Fan motor bearing temperature too high
(Prior to this fan motor bearing temperature
high shall be annunciated in UCB)
• Vibration level of Fan/motor very high.
Tripping ID Fan A (ID fan B is on)
Interlocks similar to above shall hold good for this condition.
Post Purge Fan Trippings
When ID Fan B trips (ID Fan A is on) impulses shall
be given for:
1. Disconnecting the regulator from acting on the
regulating damper of Fan B.
2. Bringing the regulating damper of Fan B to the
minimum position.
3. Closing the inlet gate of Fan B.
4. Closing the outlet gate of Fan B.
5. Tripping the FD Fan B, provided FD Fan A is on.
6. Energisation of partial load relay.
FD Fans Starting
FD Fans Starting…. Prechecks
• Ensure No Permit is pending.
• Ensure the electric supply to the drives and equipment are available.
• Ensure the Air Heater flue gas inlet dampers the gas gates before and after
ESP are kept open.
• Ensure the secondary air dampers of Air Heaters A & B are kept open.
At least one pair should be kept open for starting the first FD fan.
• Ensure the Secondary air dampers in wind boxes are in open position as
per FSSS logic.
• Check healthiness of all the protections and interlocks for their
functioning.
• The suction and discharge dampers of the FD fan should be checked for its
operation and kept closed before starting the fan.
• Ensure at least one ID fan is in service to start the first FD fan. Both ID fan
should be in service to start second FD fan.
• Ensure bottom ash hopper seal water trough is filled with water and
maintain overflow.
FD Fan Start Permissive
• Blade pitch control servomotor is in minimum
position.
• FD fans discharge dampers are in closed
position.
• ID Fan is running.
• Bearing temperature of motor are within
permissible limit.
FD Fan Start Sequence
START SEQUENCE OF THE FAN:
a) Tank oil level > 50%
b) Tank oil temp > 25 deg C
c) Control oil pressure > 20 bar
d) Lub oil pressure > 4 bar
e) Bearing temp < 95 deg C
f) Control blade adjustment : Manual
g) Impeller blades position : Close
h) Discharge damper/gate : Close
i) Fan Motor : ON
After Starting FD Fan
When any FD fan is started impulses shall be given
for:
• Opening the outlet damper of the corresponding
FD fan after the motor reaches its rated speed.
(After 10 secs.)
• Connecting the blade pitch control drive of the
fan to auto control, if Auto/Manual station is
selected on Auto.
• Closing the atmospheric suction damper of
scanner fan if they are running with suction from
the atmosphere
FD FAN INTERLOCKS
CONDITIONS PRIOR TO STARTING FD FANS.
1. FD Fan A and FD Fan B off.
2. Fan impellers tilted to maximum opening.
3. Outlet dampers are fully open.
4. Fan impeller regulator disconnected.
5. Lube oil pumps of FD Fans off.
STARTING FD FAN A (FD FAN B IS OFF)
FD Fan A shall be prohibited from starting untill the
following conditions are satisfied.
1. ID Fan A or ID Fan B is on.
2. Control oil pressure adequate (8 kg/cm2)
(Control oil pressure adequate lamp indication
shall be provided on the control desk.)
3. Fan A impeller in the minimum position.
4. Outlet damper of Fan A is closed position.
5. Fan/Motor bearing temperature not “very high”.
STARTING FD FAN B (FD FAN A IS OFF)
Interlocks similar to above shall hold good for this condition.
FD Fan Starting Sequence
When FD Fan A is started (FD Fan B off) impulse
shall be given for:
• Outlet damper of Fan A to open after the
motor reaches the rated speed.
• The outlet damper of FD Fan B to close &
impeller blades of Fan B to be driven to
minimum position.
• Connecting the impeller of Fan A control drive
to auto control.
TRIPPING OF FD FAN A (FD FAN B IS OFF)
FD Fan A shall trip under the following conditions:
1. FD Fan a bearing temperature too high (Prior to this,
FD Fan A bearing temperature high will be annuciated
in UCB)
• NOTE: Oil pressure low shall be annunciated in UCB
1. FD Fan A motor bearing temperature too high (prior
to this, FD Fan A motor bearing temperature high will
be annunciated in UCB)
2. Both ID Fans trip.
3. Post purge fan trip (Contact from FSSS)
TRIPPING FD FAN B (FD FAN A IS OFF)
Interlocks similar to above shall hold good for this condition
FD Fan Tripping Sequence
1. When FD Fan A trip (FD Fan B is off) impulses shall be
given for:
2. Disconnecting the impeller control drive from the
regulator of Fan A.
3. Bringing the impeller of Fan A to the maximum position.
4. Bringing the impeller of FD Fan B to the maximum
position.
5. Opening the outlet damper of FD Fan B.
6. To open the emergency scanner air damper.
7. Boiler tripping.
8. The outlet damper of FD fan A shall remain open.
STARTING FD FAN B (FD FAN A IS ON)
FD Fan B (FD Fan A is on) shall be prohibited from
starting until the following conditions are satisfied.
1. Both ID Fans are on.
2. Control oil pressure adequate (8 kg/cm2)
(control oil pressure adequate lamp indication
shall be provided on the control desk).
3. Impeller of Fan B in the minimum position.
4. Outlet damper of Fan B in the closed position.
5. Fan/Fan motor bearing temperature not very
high
STARTING FD FAN A (FD FAN B IS ON)
Interlocks similar to those at 2.6 shall hold good for this condition.
Starting Sequence of FD Fan B
1. When FD Fan B is started (FD Fan A is on),
impulses shall be given for:
2. Opening the outlet damper of Fan B after the
fan reaches the rated speed.
3. Connecting the impeller control drive of Fan
B to auto control.
TRIPPING OF FD FAN B (FD FAN A IS ON)
FD Fan B shall trip when FD Fan A is on under the
following conditions.
1. ID Fan B trips.
2. FD Fan B motor bearing temperature too high (prior
to this, FD fan B motor bearing temperature high shall
be annunciated in UCB.
3. FD Fan B motor bearing temperature too high (Prior
to this, FD Fan B bearing temperature high shall be
annunciated in UCB).
4. Vibration level of Fan/Motor very high.
NOTE: Oil pressure low shall be annunciated at UCB.
TRIPPING OF FD FAN A (FD FAN B IS ON)
Interlocks similar to as above shall hold good for this condition
Tripping Sequence of FD Fan B
When FD Fan B trips (FD Fan A is on), impulses shall
be given for:
1. Disconnecting regulator impulse from acting on
impeller control drive of Fan B.
2. Bringing impeller of Fan B to the minimum
position.
3. Closing the outlet damper of Fan B.
4. Energisation of partial load relay.
5. Tripping mills working more than three through
FSSS.
ALARM & TRIP VALUES FD Fan
DESCRIPTION ALARM TRIP
Fan Bearing Temperature >= 95 deg C >= 105 deg C
Fan Bearing Vibration (Vel -rms) For
Fans erected on Solid Concrete
foundation.
>= 4.5 mm/s >= 9.0 mm/s
Fan Bearing Vibration (Vel - rms)
For Fans erected on Spring Isolator
>= 7.0 mm/S >= 14 mm/s
Differential Pressure across oil filter >= 5 bar ****
Lub Oil Pressure low <= 4 bar ****
Control Oil Pressure low <=14 bar ****
Oil Level In The Tank low < 50 % ****
Primary Air Fans
P.A. FANS INTERLOCKS
CONDITIONS PRIOR TO START:
1. PA Fan A and PA Fan B off.
2. Outlet dampers of Fan A and Fan B close.
3. Regulating damper of Fan A and Fan B is
closed position.
4. Regulating damper regulator disconnected.
STARTING PA FAN A (PA FAN B OFF)
PA Fan A shall be prohibited from starting until the
following conditions are satisfied.
1. Regulating damper of Fan A in the minimum position.
2. Outlet damper of Fan A in closed position.
3. Any one FD Fan is on.
4. Purge complete. (From FSSS)
5. PA Fan/fan motor bearing temperature not very high.
6. PA Fan lubricating oil pressure adequate.
NOTE: Signal from PA Fan A start PB shall simultaneously
go to start PA Fan A and seal air fan.
STARTING PA FAN B (PA FAN A IS OFF)
Interlocks similar to as above shall hold good for this condition
Starting Sequence of PA Fan A
When PA Fan A is started (PA Fan B is off), impulses
shall be given for:
1. Opening the outlet damper of Fan A after the
motor vehicles the rated speed.
2. Connecting the regulating damper of PA Fan B to
the minimum position.
3. Bringing the regulating damper of PA Fan B to
the minimum position.
4. Closing the outlet damper of PA Fan B.
5. Permission to start any three mills through FSSS
TRIPPING OF PA FAN A (PA FAN B IS OFF)
PA Fan A shall trip (PA Fan B is off) under the
following condition:
1. PA Fan A bearing temperature too high (prior to
this bearing temperature high shall be
annunciated in UCB)
2. PA Fan A motor bearing temperature too high.
(Prior to this motor bearing temperature high
shall be annunciated in UCB)
3. Boiler trips.
4. Vibrator level of Fan/Motor very high.
TRIPPING OF PA FAN B (PA FAN A IS OFF):
Interlocks similar to those as above shall hold good for this condition
Tripping Sequence of PA Fan A (Fan B Off)
When PA Fan A trips (PA Fan B is off), impulses shall be
given for:
1. Disconnecting the regulating damper of Fan A from
the auto control.
2. Bringing the regulating damper of Fan A to minimum
position.
3. Closing the outlet damper of PA Fan A.
4. Bringing the regulating damper PA Fan B to minimum
position.
5. Closing the outlet damper of PA Fan B.
6. Tripping all the operating mills (done through FSSS)
STARTING PA FAN B (PA FAN A IS ON)
PA Fan B shall be prohibited from starting unless
the following conditions are satisfied.
1. Any one FD Fan is ON.
2. Regulating damper of Fan B in the minimum
position.
3. Outlet damper of Fan B in closed position.
4. PA Fan B /Fan motor bearing temperature
not very high
STARTING OF PA FAN A (PA FAN B IS ON)
Interlocks similar to those as above shall hold good for this condition
Starting Sequence of PA Fan
When PA Fan B is started (PA Fan A is ON)
impulses shall be given for:
1. Opening the outlet damper of PA Fan B after
the motor reaches the rated speed.
2. Connecting the regulating damper of Fan B to
the auto controls.
3. Permission to start three more mills through
FSSS.
Tripping Of PA Fans
P.A. Fan B shall trip (PA Fan A is on) under the
following conditions
1. PA Fan B bearing temperature too high (prior to
this, fan bearing temperature high shall be
annunciated in UCB)
2. PA Fan B motor bearing temperature too high
(Prior to this, fan motor bearing temperature
high shall be annunciated in UCB)
3. Boiler trip.
4. Vibration level of Fan/Motor very high
• TRIPPING OF PA FAN A (PA FAN B IS ON)
Interlocks similar to those above shall hold good for this condition
• Both the PA Fans shall trip simultaneously when any boiler trip condition
is present (impulse from FSSS)
Tripping Sequence of PA Fan
• When PA Fan B trips (PA Fan A is ON) impulse
shall be given for:
• Disconnecting the regulating damper of Fan B
from the auto control.
• Bringing the regulation damper of Fan B to the
minimum position.
• Closing the outlet damper of fan B.
• Energisation of partial load relay.
• Bringing the regulating damper of PA Fan A to
max. safe position
Boiler Drum Drain
Blow
Down
Valves
BLOW DOWN VALVES BD8 & BD9
• When drum water level rises to 120 mm above
normal water level, an annunciation, Drum Level
High shall be given in UCB.
• When drum level rises to 25 mm above normal
water level, blow down valves B56 and B57 shall
open and this condition shall be annunciated.
• Blow down valves shall close automatically when
the water level falls down to NWL. One de-
interlock switch, shall be provided for both the
valves for manual operation.
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW Boiler

More Related Content

What's hot

Turbine Stress Control Logic, Calculation & Working
Turbine Stress Control Logic, Calculation & WorkingTurbine Stress Control Logic, Calculation & Working
Turbine Stress Control Logic, Calculation & Working
Tahoor Alam Khan
 
Boiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingBoiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & Working
Tahoor Alam Khan
 
Lmw turbine oprn. manual
Lmw turbine oprn. manualLmw turbine oprn. manual
Lmw turbine oprn. manual
Kattukolu Kishorereddy
 
Turbine safety protection
Turbine safety protectionTurbine safety protection
Turbine safety protection
VEERABHADRA SWAMY
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection system
Sachin Pyasi
 
boiler turbine emergency
boiler turbine emergencyboiler turbine emergency
boiler turbine emergency
mitravanu mishra
 
Hp/ lp bypass system for steam turbines
Hp/ lp bypass system for steam turbinesHp/ lp bypass system for steam turbines
Hp/ lp bypass system for steam turbines
Boben Anto Chemmannoor
 
FAQ on Turbines Part 2
FAQ on Turbines Part 2FAQ on Turbines Part 2
FAQ on Turbines Part 2
Manohar Tatwawadi
 
210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING 210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING
Nitin Patel
 
Boiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFTBoiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFT
Tahoor Alam Khan
 
Boiler safety protection
Boiler  safety protectionBoiler  safety protection
Boiler safety protection
VEERABHADRA SWAMY
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boilerKongkiert Tankayura
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)
Billa ParameswaraRao
 
Electrohydraulic governing system
Electrohydraulic governing systemElectrohydraulic governing system
Electrohydraulic governing system
Ashvani Shukla
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
SHIVAJI CHOUDHURY
 
Training material for air preheater
Training material for air preheaterTraining material for air preheater
Training material for air preheater
HOANG VAN DUC
 
Thermal Power Plant - Emergency situations
Thermal Power Plant   -   Emergency situations Thermal Power Plant   -   Emergency situations
Thermal Power Plant - Emergency situations
Ashish Kumar Jain
 
POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW
Manohar Tatwawadi
 
Turbine governing system an overview
Turbine governing system an overviewTurbine governing system an overview
Turbine governing system an overview
Gaurav Kaushik
 

What's hot (20)

Turbine Stress Control Logic, Calculation & Working
Turbine Stress Control Logic, Calculation & WorkingTurbine Stress Control Logic, Calculation & Working
Turbine Stress Control Logic, Calculation & Working
 
Boiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingBoiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & Working
 
Lmw turbine oprn. manual
Lmw turbine oprn. manualLmw turbine oprn. manual
Lmw turbine oprn. manual
 
Turbine safety protection
Turbine safety protectionTurbine safety protection
Turbine safety protection
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection system
 
boiler turbine emergency
boiler turbine emergencyboiler turbine emergency
boiler turbine emergency
 
Hp/ lp bypass system for steam turbines
Hp/ lp bypass system for steam turbinesHp/ lp bypass system for steam turbines
Hp/ lp bypass system for steam turbines
 
FAQ on Turbines Part 2
FAQ on Turbines Part 2FAQ on Turbines Part 2
FAQ on Turbines Part 2
 
210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING 210 mw LMZ Turbine rolling and its GOVERNING
210 mw LMZ Turbine rolling and its GOVERNING
 
Boiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFTBoiler Loss of Flame Protection- MFT
Boiler Loss of Flame Protection- MFT
 
Gas turbine course
Gas turbine courseGas turbine course
Gas turbine course
 
Boiler safety protection
Boiler  safety protectionBoiler  safety protection
Boiler safety protection
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boiler
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)
 
Electrohydraulic governing system
Electrohydraulic governing systemElectrohydraulic governing system
Electrohydraulic governing system
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
 
Training material for air preheater
Training material for air preheaterTraining material for air preheater
Training material for air preheater
 
Thermal Power Plant - Emergency situations
Thermal Power Plant   -   Emergency situations Thermal Power Plant   -   Emergency situations
Thermal Power Plant - Emergency situations
 
POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW POWER PLANT SIMULATOR 210 MW
POWER PLANT SIMULATOR 210 MW
 
Turbine governing system an overview
Turbine governing system an overviewTurbine governing system an overview
Turbine governing system an overview
 

Similar to Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW Boiler

Thermal Power Plant Simulator Operations Training
Thermal Power Plant Simulator Operations TrainingThermal Power Plant Simulator Operations Training
Thermal Power Plant Simulator Operations Training
Manohar Tatwawadi
 
Boiler p&i
Boiler p&iBoiler p&i
Boiler p&i
Akhilesh Kushwaha
 
49539990 burner-management-system
49539990 burner-management-system49539990 burner-management-system
49539990 burner-management-systemMowaten Masry
 
Final Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptxFinal Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptx
BhimarajuKanireddy
 
B737 NG Air Systems
B737 NG Air SystemsB737 NG Air Systems
B737 NG Air Systems
theoryce
 
Turbine operation.pptx
Turbine operation.pptxTurbine operation.pptx
Turbine operation.pptx
DhananjayaTripathy1
 
BMS FSSS.pptx
BMS FSSS.pptxBMS FSSS.pptx
BMS FSSS.pptx
ManzoorAlam40
 
Burner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptxBurner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptx
ManzoorAlam40
 
Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5
Manohar Tatwawadi
 
SEG Series.pptx
SEG Series.pptxSEG Series.pptx
SEG Series.pptx
JayeshChand2
 
Plant Air & Inst Air.ppt
Plant Air & Inst Air.pptPlant Air & Inst Air.ppt
Plant Air & Inst Air.ppt
MeherabHossainJihad
 
Hrsg startup proceudre
Hrsg startup proceudreHrsg startup proceudre
Hrsg startup proceudre
kamaraprasad
 
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdfEC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
suryanshsingh836763
 
171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt
ssuser9e9be71
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
Manohar Tatwawadi
 
A330 FuelDefuel.pptx
A330 FuelDefuel.pptxA330 FuelDefuel.pptx
A330 FuelDefuel.pptx
KumaresonKobarajah
 
Power Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the TurbogeneratorPower Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the Turbogenerator
Manohar Tatwawadi
 
Compressed Air system.pdf
Compressed Air system.pdfCompressed Air system.pdf
Compressed Air system.pdf
manotos
 
Main air compressors PPT.pptx
Main air compressors PPT.pptxMain air compressors PPT.pptx
Main air compressors PPT.pptx
deepu501949
 
The Heaters CPF AGADEM FIELD GOUMERI.ppt
The Heaters CPF AGADEM FIELD GOUMERI.pptThe Heaters CPF AGADEM FIELD GOUMERI.ppt
The Heaters CPF AGADEM FIELD GOUMERI.ppt
hicham benkhelifa
 

Similar to Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW Boiler (20)

Thermal Power Plant Simulator Operations Training
Thermal Power Plant Simulator Operations TrainingThermal Power Plant Simulator Operations Training
Thermal Power Plant Simulator Operations Training
 
Boiler p&i
Boiler p&iBoiler p&i
Boiler p&i
 
49539990 burner-management-system
49539990 burner-management-system49539990 burner-management-system
49539990 burner-management-system
 
Final Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptxFinal Turbine rolling ppt Akshay.pptx
Final Turbine rolling ppt Akshay.pptx
 
B737 NG Air Systems
B737 NG Air SystemsB737 NG Air Systems
B737 NG Air Systems
 
Turbine operation.pptx
Turbine operation.pptxTurbine operation.pptx
Turbine operation.pptx
 
BMS FSSS.pptx
BMS FSSS.pptxBMS FSSS.pptx
BMS FSSS.pptx
 
Burner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptxBurner Management System ( FSSS).pptx
Burner Management System ( FSSS).pptx
 
Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5Power Plant Simulator Day 3 Part 5
Power Plant Simulator Day 3 Part 5
 
SEG Series.pptx
SEG Series.pptxSEG Series.pptx
SEG Series.pptx
 
Plant Air & Inst Air.ppt
Plant Air & Inst Air.pptPlant Air & Inst Air.ppt
Plant Air & Inst Air.ppt
 
Hrsg startup proceudre
Hrsg startup proceudreHrsg startup proceudre
Hrsg startup proceudre
 
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdfEC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
EC8DE5D2-3B41-4599-8A5D-AB833F9397F5.pdf
 
171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt171839416-commissioning-of-hydro-ppt.ppt
171839416-commissioning-of-hydro-ppt.ppt
 
Handling of turbine side emergencies
Handling of turbine side emergenciesHandling of turbine side emergencies
Handling of turbine side emergencies
 
A330 FuelDefuel.pptx
A330 FuelDefuel.pptxA330 FuelDefuel.pptx
A330 FuelDefuel.pptx
 
Power Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the TurbogeneratorPower Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the Turbogenerator
 
Compressed Air system.pdf
Compressed Air system.pdfCompressed Air system.pdf
Compressed Air system.pdf
 
Main air compressors PPT.pptx
Main air compressors PPT.pptxMain air compressors PPT.pptx
Main air compressors PPT.pptx
 
The Heaters CPF AGADEM FIELD GOUMERI.ppt
The Heaters CPF AGADEM FIELD GOUMERI.pptThe Heaters CPF AGADEM FIELD GOUMERI.ppt
The Heaters CPF AGADEM FIELD GOUMERI.ppt
 

More from Manohar Tatwawadi

Power Plant Operations.pdf
Power Plant Operations.pdfPower Plant Operations.pdf
Power Plant Operations.pdf
Manohar Tatwawadi
 
Frequently Asked Questions on TURBINE Part 3
Frequently Asked Questions on TURBINE Part 3Frequently Asked Questions on TURBINE Part 3
Frequently Asked Questions on TURBINE Part 3
Manohar Tatwawadi
 
Green building concepts and good building practices
Green building concepts and good building practicesGreen building concepts and good building practices
Green building concepts and good building practices
Manohar Tatwawadi
 
Auxiliary Consumption and Saving due to Increase in Boiler Efficiency
Auxiliary Consumption and Saving due to Increase in Boiler EfficiencyAuxiliary Consumption and Saving due to Increase in Boiler Efficiency
Auxiliary Consumption and Saving due to Increase in Boiler Efficiency
Manohar Tatwawadi
 
COMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIES
COMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIESCOMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIES
COMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIES
Manohar Tatwawadi
 
Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1
Manohar Tatwawadi
 
Cooling towers in thermal power plants
Cooling towers in thermal power plantsCooling towers in thermal power plants
Cooling towers in thermal power plants
Manohar Tatwawadi
 
Electrical safety in power stations
Electrical safety in power stationsElectrical safety in power stations
Electrical safety in power stations
Manohar Tatwawadi
 
Cost accounting, cost control and cost reduction in TPS
Cost accounting, cost control and cost reduction in TPSCost accounting, cost control and cost reduction in TPS
Cost accounting, cost control and cost reduction in TPS
Manohar Tatwawadi
 
Environmental and pollution control in Thermal Power Stations
Environmental and pollution control in Thermal Power StationsEnvironmental and pollution control in Thermal Power Stations
Environmental and pollution control in Thermal Power Stations
Manohar Tatwawadi
 
Energy Audit & Energy Conservation Opportunities in Electrical Equipments ...
Energy Audit & Energy  Conservation  Opportunities in  Electrical Equipments ...Energy Audit & Energy  Conservation  Opportunities in  Electrical Equipments ...
Energy Audit & Energy Conservation Opportunities in Electrical Equipments ...
Manohar Tatwawadi
 
Fuels and Combustion Equations
Fuels and Combustion EquationsFuels and Combustion Equations
Fuels and Combustion Equations
Manohar Tatwawadi
 
Basics of thermal power stations
Basics of thermal power stationsBasics of thermal power stations
Basics of thermal power stations
Manohar Tatwawadi
 
Effect of Coal Quality and Performance of Coal pulverisers / Mills
Effect of Coal Quality and Performance of Coal pulverisers / MillsEffect of Coal Quality and Performance of Coal pulverisers / Mills
Effect of Coal Quality and Performance of Coal pulverisers / Mills
Manohar Tatwawadi
 
Thermal power plant efficiency
Thermal power plant efficiencyThermal power plant efficiency
Thermal power plant efficiency
Manohar Tatwawadi
 
210 mw turbine cycle heat rate
210 mw turbine cycle heat rate210 mw turbine cycle heat rate
210 mw turbine cycle heat rate
Manohar Tatwawadi
 
ENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANT
ENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANTENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANT
ENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANT
Manohar Tatwawadi
 
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATETHERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
Manohar Tatwawadi
 
Biomass Power Plants
Biomass Power PlantsBiomass Power Plants
Biomass Power Plants
Manohar Tatwawadi
 
Swot Analysis
Swot AnalysisSwot Analysis
Swot Analysis
Manohar Tatwawadi
 

More from Manohar Tatwawadi (20)

Power Plant Operations.pdf
Power Plant Operations.pdfPower Plant Operations.pdf
Power Plant Operations.pdf
 
Frequently Asked Questions on TURBINE Part 3
Frequently Asked Questions on TURBINE Part 3Frequently Asked Questions on TURBINE Part 3
Frequently Asked Questions on TURBINE Part 3
 
Green building concepts and good building practices
Green building concepts and good building practicesGreen building concepts and good building practices
Green building concepts and good building practices
 
Auxiliary Consumption and Saving due to Increase in Boiler Efficiency
Auxiliary Consumption and Saving due to Increase in Boiler EfficiencyAuxiliary Consumption and Saving due to Increase in Boiler Efficiency
Auxiliary Consumption and Saving due to Increase in Boiler Efficiency
 
COMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIES
COMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIESCOMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIES
COMPRESSED AIR SYSTEM . ENERGY CONSERVATION OPPORTUNITIES
 
Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1Frequently asked questions on turbines Part 1
Frequently asked questions on turbines Part 1
 
Cooling towers in thermal power plants
Cooling towers in thermal power plantsCooling towers in thermal power plants
Cooling towers in thermal power plants
 
Electrical safety in power stations
Electrical safety in power stationsElectrical safety in power stations
Electrical safety in power stations
 
Cost accounting, cost control and cost reduction in TPS
Cost accounting, cost control and cost reduction in TPSCost accounting, cost control and cost reduction in TPS
Cost accounting, cost control and cost reduction in TPS
 
Environmental and pollution control in Thermal Power Stations
Environmental and pollution control in Thermal Power StationsEnvironmental and pollution control in Thermal Power Stations
Environmental and pollution control in Thermal Power Stations
 
Energy Audit & Energy Conservation Opportunities in Electrical Equipments ...
Energy Audit & Energy  Conservation  Opportunities in  Electrical Equipments ...Energy Audit & Energy  Conservation  Opportunities in  Electrical Equipments ...
Energy Audit & Energy Conservation Opportunities in Electrical Equipments ...
 
Fuels and Combustion Equations
Fuels and Combustion EquationsFuels and Combustion Equations
Fuels and Combustion Equations
 
Basics of thermal power stations
Basics of thermal power stationsBasics of thermal power stations
Basics of thermal power stations
 
Effect of Coal Quality and Performance of Coal pulverisers / Mills
Effect of Coal Quality and Performance of Coal pulverisers / MillsEffect of Coal Quality and Performance of Coal pulverisers / Mills
Effect of Coal Quality and Performance of Coal pulverisers / Mills
 
Thermal power plant efficiency
Thermal power plant efficiencyThermal power plant efficiency
Thermal power plant efficiency
 
210 mw turbine cycle heat rate
210 mw turbine cycle heat rate210 mw turbine cycle heat rate
210 mw turbine cycle heat rate
 
ENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANT
ENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANTENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANT
ENERGY AUDIT METHODOLOGY FOR TURBINE CYCLE IN A POWER PLANT
 
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATETHERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
 
Biomass Power Plants
Biomass Power PlantsBiomass Power Plants
Biomass Power Plants
 
Swot Analysis
Swot AnalysisSwot Analysis
Swot Analysis
 

Recently uploaded

Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 
Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
Intella Parts
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
MuhammadTufail242431
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
Kamal Acharya
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
obonagu
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
abh.arya
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
ssuser9bd3ba
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 

Recently uploaded (20)

Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 
Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 

Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW Boiler

  • 1. STARTING & RECOMMENDED INTERLOCKS FOR AH, ID, FD, PA Fans & BD Valves Manohar Tatwawadi Director total output power solutions
  • 2. Flue gas Path • Dampers Needed to be Opened before AH is started Dampers Open AH Air Motors AH AC Motors
  • 3. Starting of Rotary APH • The lub. Oil pumps of support and guide bearings can be started from control room but preferably from Local for the first time . • Start any one of the pump locally and see that there is no oil leakage. • Check the lub oil pressure . • Stop the pump and start the other pump and see that the flow and pressure is normal, and that there is no oil leakage. Note: All the 8 Nos. pumps shall be started locally and checked before giving clearance for remote operation. The stop push buttons shall be kept in released condition. • Now open the air valve for starting the air motor of APH A or B as the case may be. As the main drives are not in service, the solenoid will supply air to air motor. • Check the operation of APH for any abnormal sound or abnormal seal rubbing. • If the performance is normal, the main drive can be started locally or from remote.
  • 4. Starting of Rotary APH • Check the performance of APH on main drive-the load current and abnormal sound and vibrations are to be watched. • On starting the main drive, the Air motor shall stop. This can be verified in control room by the indication given from the service air pressure switch, provided in the line. • Now stop the main drive from Control room and check that the Air motor comes on Auto. • The air preheater soot blowers are to operated at regular intervals, after lighting up of the boiler. • The DP across Air preheaters has to be watched closely to see that the APHs are free from choking. • The oxygen and carbon dioxide levels in flue gas, before and after APH have to be measured once in a shift to see the performance of the boiler as well as APH. Abnormal drop in carbon dioxide level after APH shall indicate poor performance of the APH seals. Normal Drop: 2%.
  • 5. Rotary Air Heater Interlocks Rotary AHs are the first auxiliary to start Boiler. CONDITIONS BEFORE START UP OF AHS: • Both AHS are off (both AC motors and Air motors are off) • The inlet dampers and the outlet dampers in the gas path, secondary air path, primary air path are in full open condition. STARTING AH ‘A’ (AH ‘B’ IS OFF) OR AH ‘B’ (AH ‘A’ is OFF • AH ‘A’/’B’ AC motor is started. If the temperature of the bearings is less than 70 Deg.C • Whenever AH AC motor trips impulse shall be given for starting Air motor provided the temperature of support/guide bearing of AH ‘A’ is less than 70 Deg. C. • Impulse shall be given for closing of the inlet and outlet dampers of AH which is off.
  • 6. Tripping of Air heaters TRIPPING OF AH ‘A’ (AH ‘B’ IS OFF)/TRIPPING OF AH ‘B’ (AH ‘A’ IS OFF) • AH AC motor/Air motor shall trip manually when the temperature of support/guide bearing of AH is very high (i.e. greater than 70 Deg. C). Under this condition AH Air motor shall be prohibited from starting. • Air motor shall trip automatically when AH AC motor starts. NOTE: Trip signal of AH is to be taken from both AC & Air motors trip
  • 7. Tripping Sequence Of Air Heaters Condition A:- BOTH AHS ARE WORKING WHEN ONE TRIPS AND OTHER AH CONTINUES TO RUN: • The gas inlet damper the secondary air inlet damper and primary air inlet damper of the tripped AH shall automatically closed. The gas outlet damper, the secondary air outlet damper and PA outlet damper of the tripped AH need not be closed. • However, if the operator wants to manually close these outlet dampers they can be closed
  • 8. TRIPPING OF AIR HEATERS Condition B:- ONE AH IS WORKING AND THE OTHER AH IS OFF: • If the working Airheater trips, the operator shall try for restarting the AH. • If the restarting is not within 5 minutes, the boiler shall be tripped. Condition C:- BOTH AHS ARE WORKING AND TRIPPED. • If both AHS ‘A’ and ‘B’ trip the operator may try for restarting the AHs. If any one of the AH is not started within 5 minutes the operator shall manually trip the boiler within 5 minutes.
  • 9. INTERLOCKS FOR LUBE OIL PUMPS OF SUPPORT & GUIDE BEARINGS OF AH A & B 2x100% lube oil pump have been provided for the support bearing. Any of the two lubricating oil pumps can be preselected as main pump and the other as standby. Following interlocks shall be provided for lub oil pumps. • Whenever the temperature of support bearing of air heater A is high (350C), impulse shall be given to start the main oil pump. • The standby oil pump shall start when the main oil pump fails to start or trips. • The main oil pump / stand by oil pump shall trip when the temperature of the support bearing falls below a present value (300C)
  • 10. Flue Gas Cycle.. Starting of ID Fans Dampers Open Dampers Closed
  • 11. ID Fan Pre-checks • Ensure the manholes are closed. • Check the availability of instruments to measure flow, pressure, temperature etc. of the ID fan and drive motor. • Check the closing and the opening of the suction and discharge gates. Keep them closed before starting the ID fan. • Check healthiness of all the protections and interlocks for their functioning. • Ensure the local push button is in the released position. • Check that the discharge dampers of blower motors are open and the modules are kept ON for supply. • Check that the flue gas path is made through – APH inlet flue gas dampers are open . – ESP inlet gates are open . – ESP outlet gates are open . • Check that the seal trough is filled with water and overflow is maintained. • Start the ID fan after ensuring the healthiness of protections whenever the fan is to be started after long shutdown.
  • 12. Starting Permissive for ID Fan Check that the final start permissive is available. The final start permissive will get available if the following conditions are satisfied, • ID fan stopped. • Cooling water to the coolers adequate. • Suction gate closed. • Discharge gate closed. • Ensure VFD for minimum speed. • ID fan tripped indication should not exist. • Ensure 220 V DC control supply for the breaker of other ID fans is available. • Now the first ID fan can be started
  • 13. Post Start Checks of ID Fans • Check the opening of gates on interlock, after 10 secs. • Check the performance of the motor. • Check adequate lub. oil pressure. • Check the starting of both the discharge gate blower motors on interlock. If not , start manually. • Maintain the furnace vacuum at -12 mmWC by suitable loading of the fan.
  • 14. I.D. FAN INTERLOCKS Conditions existing when the unit is shut down and prior to starting of ID fans. • Either or both AHs are running. • I.D. Fan ‘A’ and ID Fan ‘B’ off. • Regulating dampers of fans A&B open. • Inlet gates of Fans A & B open. • Outlet gates of fans A & B open. • The regulating dampers will be on manual control during shut down and impulse from furnace draft control to regulating dampers of ID fans disconnected.
  • 15. Starting ID Fan ‘A’ (ID Fan ‘B’ Off) Interlocks ID Fan ‘A’ shall be prohibited from starting till the following conditions are satisfied. 1. Regulating damper of Fan-A in minimum position. 2. Outlet gate of Fan-A closed. 3. Inlet gate of Fan-A closed. 4. Fan/fan motor bearing temperature not very high. 5. One of the air preheaters running. For starting ID Fan B ( ID Fan A is off) Interlocks similar to those as above shall hold good of this conditions.
  • 16. Starting ID Fan ‘A’ When ID fan ‘A’ is started (ID Fan B is off), impulses shall be give for. 1. Opening the inlet gate and outlet gate of Fan A after the motor reaches the rated speed. 2. Connecting the regulating damper of Fan A to the auto control. 3. Closing the inlet gate and the outlet gate of ID Fan B and bringin the regulating damper to minimum position. 4. Permission to start either FD Fan A or FD Fan B.
  • 17. Tripping of ID Fan A (ID fan B is off) ID Fan ‘A’ shall trip automatically under following conditions. 1. ID Fan A bearing temperature too high (prior to this, ID Fan A bearing temperature high shall be annunciated in UCB). 2. ID Fan A motor bearing temperature too high (prior to this, ID Fan a motor bearing temperature high shall be annunciated in UCB). 3. Post purge fan trip (contact from FSSS) 4. Vibration level of FAN/MOTOR very high. Tripping of ID Fan B (ID Fan A is off): Interlocks similar to those above shall hold good for this condition.
  • 18. Tripping of ID Fan When ID Fan A trips (ID Fan B is off) impulses shall be given for: 1. Opening the outlet gate of ID Fan B. 2. Opening the inlet gate of ID Fan B. 3. Opening the regulating damper of ID Fan B to wide open position. 4. Disconnecting the regulators impulse from acting on regulating damper of ID Fan A. 5. Opening the regulating damper of ID Fan A to wide open position. 6. Tripping the working FD Fans. 7. Boiler tripping. 8. To keep the inlet gate and outlet gate of ID Fan A open.
  • 19. Starting of ID Fan B (ID Fan A is on) ID Fan B shall be prohibited from starting unless the following conditions are satisfied. 1. Outlet gate of Fan B is closed. 2. Inlet gate of Fan B is closed. 3. Regulating damper of Fan Bareing minimum position. 4. Fan/fan motor bearing temperature not very high. Starting of ID Fan A (ID fan B is on) Interlocks similar to above shall hold good for this condition.
  • 20. Both ID Fans Started • When ID Fan B is started, impulses shall be given for. • Opening the inlet gate and outlet gate of Fan B after the motor reaches rated speed. • Connecting the regulating damper of Fan B to auto control. • Permission to start other FD Fan.
  • 21. Tripping of ID Fan B (ID Fan A is on) ID Fan B shall trip automatically under the following conditions. • Fan bearing temperature too high (prior to this fan bearing temperature high shall be annunciated in UCB) • Fan motor bearing temperature too high (Prior to this fan motor bearing temperature high shall be annunciated in UCB) • Vibration level of Fan/motor very high. Tripping ID Fan A (ID fan B is on) Interlocks similar to above shall hold good for this condition.
  • 22. Post Purge Fan Trippings When ID Fan B trips (ID Fan A is on) impulses shall be given for: 1. Disconnecting the regulator from acting on the regulating damper of Fan B. 2. Bringing the regulating damper of Fan B to the minimum position. 3. Closing the inlet gate of Fan B. 4. Closing the outlet gate of Fan B. 5. Tripping the FD Fan B, provided FD Fan A is on. 6. Energisation of partial load relay.
  • 24. FD Fans Starting…. Prechecks • Ensure No Permit is pending. • Ensure the electric supply to the drives and equipment are available. • Ensure the Air Heater flue gas inlet dampers the gas gates before and after ESP are kept open. • Ensure the secondary air dampers of Air Heaters A & B are kept open. At least one pair should be kept open for starting the first FD fan. • Ensure the Secondary air dampers in wind boxes are in open position as per FSSS logic. • Check healthiness of all the protections and interlocks for their functioning. • The suction and discharge dampers of the FD fan should be checked for its operation and kept closed before starting the fan. • Ensure at least one ID fan is in service to start the first FD fan. Both ID fan should be in service to start second FD fan. • Ensure bottom ash hopper seal water trough is filled with water and maintain overflow.
  • 25. FD Fan Start Permissive • Blade pitch control servomotor is in minimum position. • FD fans discharge dampers are in closed position. • ID Fan is running. • Bearing temperature of motor are within permissible limit.
  • 26. FD Fan Start Sequence START SEQUENCE OF THE FAN: a) Tank oil level > 50% b) Tank oil temp > 25 deg C c) Control oil pressure > 20 bar d) Lub oil pressure > 4 bar e) Bearing temp < 95 deg C f) Control blade adjustment : Manual g) Impeller blades position : Close h) Discharge damper/gate : Close i) Fan Motor : ON
  • 27. After Starting FD Fan When any FD fan is started impulses shall be given for: • Opening the outlet damper of the corresponding FD fan after the motor reaches its rated speed. (After 10 secs.) • Connecting the blade pitch control drive of the fan to auto control, if Auto/Manual station is selected on Auto. • Closing the atmospheric suction damper of scanner fan if they are running with suction from the atmosphere
  • 28. FD FAN INTERLOCKS CONDITIONS PRIOR TO STARTING FD FANS. 1. FD Fan A and FD Fan B off. 2. Fan impellers tilted to maximum opening. 3. Outlet dampers are fully open. 4. Fan impeller regulator disconnected. 5. Lube oil pumps of FD Fans off.
  • 29. STARTING FD FAN A (FD FAN B IS OFF) FD Fan A shall be prohibited from starting untill the following conditions are satisfied. 1. ID Fan A or ID Fan B is on. 2. Control oil pressure adequate (8 kg/cm2) (Control oil pressure adequate lamp indication shall be provided on the control desk.) 3. Fan A impeller in the minimum position. 4. Outlet damper of Fan A is closed position. 5. Fan/Motor bearing temperature not “very high”. STARTING FD FAN B (FD FAN A IS OFF) Interlocks similar to above shall hold good for this condition.
  • 30. FD Fan Starting Sequence When FD Fan A is started (FD Fan B off) impulse shall be given for: • Outlet damper of Fan A to open after the motor reaches the rated speed. • The outlet damper of FD Fan B to close & impeller blades of Fan B to be driven to minimum position. • Connecting the impeller of Fan A control drive to auto control.
  • 31. TRIPPING OF FD FAN A (FD FAN B IS OFF) FD Fan A shall trip under the following conditions: 1. FD Fan a bearing temperature too high (Prior to this, FD Fan A bearing temperature high will be annuciated in UCB) • NOTE: Oil pressure low shall be annunciated in UCB 1. FD Fan A motor bearing temperature too high (prior to this, FD Fan A motor bearing temperature high will be annunciated in UCB) 2. Both ID Fans trip. 3. Post purge fan trip (Contact from FSSS) TRIPPING FD FAN B (FD FAN A IS OFF) Interlocks similar to above shall hold good for this condition
  • 32. FD Fan Tripping Sequence 1. When FD Fan A trip (FD Fan B is off) impulses shall be given for: 2. Disconnecting the impeller control drive from the regulator of Fan A. 3. Bringing the impeller of Fan A to the maximum position. 4. Bringing the impeller of FD Fan B to the maximum position. 5. Opening the outlet damper of FD Fan B. 6. To open the emergency scanner air damper. 7. Boiler tripping. 8. The outlet damper of FD fan A shall remain open.
  • 33. STARTING FD FAN B (FD FAN A IS ON) FD Fan B (FD Fan A is on) shall be prohibited from starting until the following conditions are satisfied. 1. Both ID Fans are on. 2. Control oil pressure adequate (8 kg/cm2) (control oil pressure adequate lamp indication shall be provided on the control desk). 3. Impeller of Fan B in the minimum position. 4. Outlet damper of Fan B in the closed position. 5. Fan/Fan motor bearing temperature not very high STARTING FD FAN A (FD FAN B IS ON) Interlocks similar to those at 2.6 shall hold good for this condition.
  • 34. Starting Sequence of FD Fan B 1. When FD Fan B is started (FD Fan A is on), impulses shall be given for: 2. Opening the outlet damper of Fan B after the fan reaches the rated speed. 3. Connecting the impeller control drive of Fan B to auto control.
  • 35. TRIPPING OF FD FAN B (FD FAN A IS ON) FD Fan B shall trip when FD Fan A is on under the following conditions. 1. ID Fan B trips. 2. FD Fan B motor bearing temperature too high (prior to this, FD fan B motor bearing temperature high shall be annunciated in UCB. 3. FD Fan B motor bearing temperature too high (Prior to this, FD Fan B bearing temperature high shall be annunciated in UCB). 4. Vibration level of Fan/Motor very high. NOTE: Oil pressure low shall be annunciated at UCB. TRIPPING OF FD FAN A (FD FAN B IS ON) Interlocks similar to as above shall hold good for this condition
  • 36. Tripping Sequence of FD Fan B When FD Fan B trips (FD Fan A is on), impulses shall be given for: 1. Disconnecting regulator impulse from acting on impeller control drive of Fan B. 2. Bringing impeller of Fan B to the minimum position. 3. Closing the outlet damper of Fan B. 4. Energisation of partial load relay. 5. Tripping mills working more than three through FSSS.
  • 37. ALARM & TRIP VALUES FD Fan DESCRIPTION ALARM TRIP Fan Bearing Temperature >= 95 deg C >= 105 deg C Fan Bearing Vibration (Vel -rms) For Fans erected on Solid Concrete foundation. >= 4.5 mm/s >= 9.0 mm/s Fan Bearing Vibration (Vel - rms) For Fans erected on Spring Isolator >= 7.0 mm/S >= 14 mm/s Differential Pressure across oil filter >= 5 bar **** Lub Oil Pressure low <= 4 bar **** Control Oil Pressure low <=14 bar **** Oil Level In The Tank low < 50 % ****
  • 39. P.A. FANS INTERLOCKS CONDITIONS PRIOR TO START: 1. PA Fan A and PA Fan B off. 2. Outlet dampers of Fan A and Fan B close. 3. Regulating damper of Fan A and Fan B is closed position. 4. Regulating damper regulator disconnected.
  • 40. STARTING PA FAN A (PA FAN B OFF) PA Fan A shall be prohibited from starting until the following conditions are satisfied. 1. Regulating damper of Fan A in the minimum position. 2. Outlet damper of Fan A in closed position. 3. Any one FD Fan is on. 4. Purge complete. (From FSSS) 5. PA Fan/fan motor bearing temperature not very high. 6. PA Fan lubricating oil pressure adequate. NOTE: Signal from PA Fan A start PB shall simultaneously go to start PA Fan A and seal air fan. STARTING PA FAN B (PA FAN A IS OFF) Interlocks similar to as above shall hold good for this condition
  • 41. Starting Sequence of PA Fan A When PA Fan A is started (PA Fan B is off), impulses shall be given for: 1. Opening the outlet damper of Fan A after the motor vehicles the rated speed. 2. Connecting the regulating damper of PA Fan B to the minimum position. 3. Bringing the regulating damper of PA Fan B to the minimum position. 4. Closing the outlet damper of PA Fan B. 5. Permission to start any three mills through FSSS
  • 42. TRIPPING OF PA FAN A (PA FAN B IS OFF) PA Fan A shall trip (PA Fan B is off) under the following condition: 1. PA Fan A bearing temperature too high (prior to this bearing temperature high shall be annunciated in UCB) 2. PA Fan A motor bearing temperature too high. (Prior to this motor bearing temperature high shall be annunciated in UCB) 3. Boiler trips. 4. Vibrator level of Fan/Motor very high. TRIPPING OF PA FAN B (PA FAN A IS OFF): Interlocks similar to those as above shall hold good for this condition
  • 43. Tripping Sequence of PA Fan A (Fan B Off) When PA Fan A trips (PA Fan B is off), impulses shall be given for: 1. Disconnecting the regulating damper of Fan A from the auto control. 2. Bringing the regulating damper of Fan A to minimum position. 3. Closing the outlet damper of PA Fan A. 4. Bringing the regulating damper PA Fan B to minimum position. 5. Closing the outlet damper of PA Fan B. 6. Tripping all the operating mills (done through FSSS)
  • 44. STARTING PA FAN B (PA FAN A IS ON) PA Fan B shall be prohibited from starting unless the following conditions are satisfied. 1. Any one FD Fan is ON. 2. Regulating damper of Fan B in the minimum position. 3. Outlet damper of Fan B in closed position. 4. PA Fan B /Fan motor bearing temperature not very high STARTING OF PA FAN A (PA FAN B IS ON) Interlocks similar to those as above shall hold good for this condition
  • 45. Starting Sequence of PA Fan When PA Fan B is started (PA Fan A is ON) impulses shall be given for: 1. Opening the outlet damper of PA Fan B after the motor reaches the rated speed. 2. Connecting the regulating damper of Fan B to the auto controls. 3. Permission to start three more mills through FSSS.
  • 46. Tripping Of PA Fans P.A. Fan B shall trip (PA Fan A is on) under the following conditions 1. PA Fan B bearing temperature too high (prior to this, fan bearing temperature high shall be annunciated in UCB) 2. PA Fan B motor bearing temperature too high (Prior to this, fan motor bearing temperature high shall be annunciated in UCB) 3. Boiler trip. 4. Vibration level of Fan/Motor very high • TRIPPING OF PA FAN A (PA FAN B IS ON) Interlocks similar to those above shall hold good for this condition • Both the PA Fans shall trip simultaneously when any boiler trip condition is present (impulse from FSSS)
  • 47. Tripping Sequence of PA Fan • When PA Fan B trips (PA Fan A is ON) impulse shall be given for: • Disconnecting the regulating damper of Fan B from the auto control. • Bringing the regulation damper of Fan B to the minimum position. • Closing the outlet damper of fan B. • Energisation of partial load relay. • Bringing the regulating damper of PA Fan A to max. safe position
  • 49. BLOW DOWN VALVES BD8 & BD9 • When drum water level rises to 120 mm above normal water level, an annunciation, Drum Level High shall be given in UCB. • When drum level rises to 25 mm above normal water level, blow down valves B56 and B57 shall open and this condition shall be annunciated. • Blow down valves shall close automatically when the water level falls down to NWL. One de- interlock switch, shall be provided for both the valves for manual operation.