Seminar for eight semester electrical engineering on Conventional and
Un-Conventional Partial Discharge Detection Methods in High Voltage XLPE Cable Accessories
The document discusses various aspects of partial discharge (PD) testing, including definitions, types, and detection methods. It defines PD as localized electrical discharges that only partially bridge insulation between conductors. Four main types are discussed: corona, surface, cavity, and treeing discharges. Detection methods covered include electrical, acoustic, UHF, optical, and chemical (DGA) techniques. The electrical method measures apparent charge, while acoustic localization and UHF detection have advantages of immunity to electromagnetic noise. Optical detection relies on light emission during discharges. A comparison table outlines advantages and disadvantages of each detection method.
Partial discharge is a discharge event that does not bridge the entire insulation system between electrodes. It occurs within cavities in insulation materials under high electric fields. During partial discharge, a plasma channel briefly forms within the cavity, conducting electricity from one side to the other without crossing the entire material. Measurement setups use coupling devices and detectors to monitor the short voltage pulses caused by partial discharge, in order to evaluate insulation condition and detect defects.
This document discusses partial discharge (PD) testing methods for predictive maintenance of medium voltage switchgear. It provides definitions and explanations of partial discharge from standards bodies like IEC and IEEE. It describes the three main types of PD sources as internal, surface, and corona discharge. It then explains various online and offline PD testing methods like ultrasonic, transient earth voltage, high frequency current transformer, and the capacitance voltage divider method. Key aspects of each method like frequency ranges, sensor placement, and background noise measurement are outlined. Causes of partial discharge like cavities, electrical trees, water trees, and corona are described in detail.
The document discusses partial discharge (PD) techniques for measuring the condition of aging high voltage and medium voltage switchgear. It provides 3 key points:
1) PD activity is a major cause of long-term degradation of insulation in switchgear. Measuring PD can detect defects before complete failure and allow targeted maintenance.
2) The latest PD measuring instruments use dual sensors to detect both surface and internal PD non-intrusively. Measurements of PD pulses externally can indicate the insulation condition.
3) Condition-based maintenance using PD measurements can improve safety, reliability and lower costs compared to time-based maintenance. Utilities like SP Powergrid in Singapore have seen significant benefits including reduced outages and savings of
Partial Discharge Detection Products by EA TechnologyRyan McFallo
EA Technology is the global leader in MV Partial Discharge detection. EA’s unique technology allows real time partial discharge detection and monitoring without interrupting service, EA also provides on-site partial discharge surveys.
Would you like to learn more about partial discharge detection and monitoring products/services?
Visit Technical Sales-Northwest at http://www.techsalesnw.com
1) The document discusses online partial discharge (PD) measurement of medium voltage and high voltage power cables to prevent unplanned outages. It describes PD theory, cable structures, sensors used for online PD detection, and case studies demonstrating the technology.
2) Qualitrol offers both portable and permanent online PD monitoring systems using sensors like high frequency current transformers and transient earth voltage sensors to detect PD pulses in energized cables.
3) Case studies demonstrate the system separating noise from PD signals to accurately detect and locate incipient faults in cables in high noise environments like GIS substations and switchgear.
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)AHMED MOHAMED HEGAB
During the life cycle of high voltage (HV) apparatus or systems many tests and measurements are performed to characterize the insulation condition. The results of these tests and
measurements should be compiled in a “life data record”, which supplies information on trends of diagnostic indicator values. The HV on-site test with partial discharge (PD) measurement has an intermediate position between routine tests and in-service monitoring measurements (on-line or offline)
This document summarizes techniques for partial discharge (PD) measurements on transformers. It discusses PD detection systems using electrical, acoustic, and UHF signals. Typical PD patterns are presented that can help identify different types of PD sources. Procedures are provided for PD measurements in laboratories and on-site, including characterizing the transformer, localizing PD sources using different signals, and a recommended multi-step process for solving PD problems. The document concludes that while measurement techniques have improved, unambiguous identification of dangerous PD sources remains an ongoing challenge requiring further research.
The document discusses various aspects of partial discharge (PD) testing, including definitions, types, and detection methods. It defines PD as localized electrical discharges that only partially bridge insulation between conductors. Four main types are discussed: corona, surface, cavity, and treeing discharges. Detection methods covered include electrical, acoustic, UHF, optical, and chemical (DGA) techniques. The electrical method measures apparent charge, while acoustic localization and UHF detection have advantages of immunity to electromagnetic noise. Optical detection relies on light emission during discharges. A comparison table outlines advantages and disadvantages of each detection method.
Partial discharge is a discharge event that does not bridge the entire insulation system between electrodes. It occurs within cavities in insulation materials under high electric fields. During partial discharge, a plasma channel briefly forms within the cavity, conducting electricity from one side to the other without crossing the entire material. Measurement setups use coupling devices and detectors to monitor the short voltage pulses caused by partial discharge, in order to evaluate insulation condition and detect defects.
This document discusses partial discharge (PD) testing methods for predictive maintenance of medium voltage switchgear. It provides definitions and explanations of partial discharge from standards bodies like IEC and IEEE. It describes the three main types of PD sources as internal, surface, and corona discharge. It then explains various online and offline PD testing methods like ultrasonic, transient earth voltage, high frequency current transformer, and the capacitance voltage divider method. Key aspects of each method like frequency ranges, sensor placement, and background noise measurement are outlined. Causes of partial discharge like cavities, electrical trees, water trees, and corona are described in detail.
The document discusses partial discharge (PD) techniques for measuring the condition of aging high voltage and medium voltage switchgear. It provides 3 key points:
1) PD activity is a major cause of long-term degradation of insulation in switchgear. Measuring PD can detect defects before complete failure and allow targeted maintenance.
2) The latest PD measuring instruments use dual sensors to detect both surface and internal PD non-intrusively. Measurements of PD pulses externally can indicate the insulation condition.
3) Condition-based maintenance using PD measurements can improve safety, reliability and lower costs compared to time-based maintenance. Utilities like SP Powergrid in Singapore have seen significant benefits including reduced outages and savings of
Partial Discharge Detection Products by EA TechnologyRyan McFallo
EA Technology is the global leader in MV Partial Discharge detection. EA’s unique technology allows real time partial discharge detection and monitoring without interrupting service, EA also provides on-site partial discharge surveys.
Would you like to learn more about partial discharge detection and monitoring products/services?
Visit Technical Sales-Northwest at http://www.techsalesnw.com
1) The document discusses online partial discharge (PD) measurement of medium voltage and high voltage power cables to prevent unplanned outages. It describes PD theory, cable structures, sensors used for online PD detection, and case studies demonstrating the technology.
2) Qualitrol offers both portable and permanent online PD monitoring systems using sensors like high frequency current transformers and transient earth voltage sensors to detect PD pulses in energized cables.
3) Case studies demonstrate the system separating noise from PD signals to accurately detect and locate incipient faults in cables in high noise environments like GIS substations and switchgear.
High Voltage On-Site Testing with Partial Discharge Measurement (Cigre 502)AHMED MOHAMED HEGAB
During the life cycle of high voltage (HV) apparatus or systems many tests and measurements are performed to characterize the insulation condition. The results of these tests and
measurements should be compiled in a “life data record”, which supplies information on trends of diagnostic indicator values. The HV on-site test with partial discharge (PD) measurement has an intermediate position between routine tests and in-service monitoring measurements (on-line or offline)
This document summarizes techniques for partial discharge (PD) measurements on transformers. It discusses PD detection systems using electrical, acoustic, and UHF signals. Typical PD patterns are presented that can help identify different types of PD sources. Procedures are provided for PD measurements in laboratories and on-site, including characterizing the transformer, localizing PD sources using different signals, and a recommended multi-step process for solving PD problems. The document concludes that while measurement techniques have improved, unambiguous identification of dangerous PD sources remains an ongoing challenge requiring further research.
EE2353 / High Voltage Engineering - Testing of CablesRajesh Ramesh
Cable testing is important to ensure the long life and high efficiency of cables used for high voltage transmission. There are several types of tests conducted on cable samples including mechanical, thermal, impulse withstand voltage, partial discharge, and dielectric power factor tests. Partial discharge tests are particularly important for determining the life of cable insulation by detecting internal discharges under voltage stress. These tests are conducted at various stages of voltage levels on cable samples to certify them for transmission use.
A lightning arrester, also known as a lightning conductor, is a device used to protect electrical power systems and telecommunications systems from damage caused by lightning strikes. It has a high voltage terminal connected to the power line and a ground terminal. When a lightning surge travels along the power line, the arrester diverts the current through itself to ground, usually by means of an arc across an air gap. Common types of lightning arresters include rod arresters, horn gap arresters, multi gap arresters, and various types using silicon carbide or metal oxide components. A horn gap arrester consists of two horn-shaped metal rods separated by a small air gap, connected to the power line through a resistance and choke coil to
1) Streamer theory was proposed in 1940 by Rather, Meek and Loeb to explain phenomena not accounted for by Townsend's theory of gas breakdown, such as dependence on gas pressure and geometry.
2) Streamer theory describes how a single avalanche can develop into a spark discharge through distortion of the electric field by space charge, generating further avalanches cumulatively at the avalanche head.
3) Positive ions are left behind the rapidly advancing avalanche head, enhancing the field in front and reducing it behind, while the field is also enhanced between the tail and cathode. This leads to further space charge increase and field enhancement around the anode, forming a streamer connecting anode to cathode.
EHV (extra high voltage) AC transmission refers to equipment designed for voltages greater than 345 kV. Higher transmission voltages increase efficiency by reducing transmission losses and current, decrease infrastructure costs, and increase transmission capacity. However, they also present safety and interference risks. New technologies like FACTS (flexible AC transmission systems) help maximize the benefits of EHV transmission by enabling voltage control and power flow management. There is growing support for expanding national EHV transmission grids to facilitate large-scale renewable energy integration and inter-regional power sharing.
A presentation explaining how to calculate fault currents for 3-phase or 1-phase faults in power grid. Particularly useful for engineers working in electrical power transmission company.
Principles of Cable Sizing; current carrying capacity, voltage drop, short circuit.
Cables are often the last component considered during system design even if in many situations cables are the true system’s lifeline: if a cable fails, the entire system may stop. Cable reliability is therefore extremely important, then a cable system should be engineered to last the life of the system in the installation environment for the required application. Environments in which cable systems are being used are often challenging, as extreme temperatures, chemicals, abrasion, and extensive flexing. These variables have a direct impact on the materials used for cable insulation and jacketing as well as the construction of the cable. Using a systematic approach will help ensure that designer select the best cable for the required application in the installation environment. This lessons will provide students main guidelines for perform this approach.
Guidelines for Unconventional Partial Discharge Measurement (CIGRE 444)AHMED MOHAMED HEGAB
Several non-conventional PD detection methods based on acoustic and electromagnetic phenomenon have been used for some time for PD detection on power cables, transformers, GIS and generators. Up to now there have not been accepted procedures and guidelines for “non-conventional methods” compared to conventional methods. There are many open questions including: calibration or sensitivity verification procedures, techniques for noise suppression, methods of
fault location, and energy equivalency, among others. The authors of this guide believe that now is the time to prepare guidelines and international recommendations for these non-conventional PD detection methods in order to ensure reproducible and comparative PD measurements on high voltage equipment between users.
The document discusses the main equipment used in 400kV power transmission and distribution substations. It describes some of the key components including transformers, switchgear, isolators, circuit breakers, wave traps, and current transformers. Switchgear is explained in more detail, noting that it is used to control, protect, and isolate electrical equipment by de-energizing circuits for work and clearing faults downstream, improving the reliability of the power supply. The 400kV substation in Bareilly, India is also briefly outlined, including its division into 400kV, 220kV, and 33kV sections served by a common control room.
This document discusses cable sizing calculations and techniques. It explains that proper cable sizing is important to ensure efficient, safe and economic transmission of electrical energy without interruptions or exceeding the cable's limits. The document outlines the common steps for cable sizing: 1) gathering data on the cable, load and installation conditions, 2) determining the minimum size based on current capacity, voltage drop, temperature rise and fault impedance, and 3) selecting the optimally sized cable. Several examples are provided to illustrate implementing the cable selection process. Risks of improper sizing like voltage drops, overheating and shorter lifespan are also summarized.
This document discusses tests performed on transformers and surge arresters, including induced voltage tests, partial discharge tests, impulse tests, and surge arrester tests like spark over tests and residual voltage tests. The tests are used to evaluate the insulation strength and ability to withstand transient overvoltages of transformers and effectiveness of surge arresters in protecting equipment.
This document provides information about a power system protection course, including:
1. The syllabus covers 5 units - introduction to protection schemes, operating principles of relays, apparatus protection, theory of circuit interruption, and circuit breakers.
2. The theory of circuit interruption unit discusses arc phenomena, interruption of DC and AC circuits. It explains the physics behind arc initiation, maintenance and methods of arc extinction.
3. Interruption of capacitive current can produce high transient voltages across the circuit breaker contacts. This occurs when unloaded transmission lines or capacitor banks are switched off.
Breakdown due to Internal Discharges and Surface BreakdownAsim Raza
Electrical breakdown occurs when the voltage applied across an insulator exceeds its breakdown voltage, causing it to become electrically conductive. Breakdown can be caused by internal discharges within voids in solid insulators or at boundaries with electrodes. These internal discharges erode the insulating material over time through carbonization and heating, eventually leading to complete breakdown. Surface breakdown, or flashover, occurs when a conducting path forms on the insulating surface, allowing current flow and sparking that further degrades the insulation. Tracking is the formation of a permanent conducting carbon path, while erosion gradually weakens the material over time.
Safe Operation and Maintenance of Circuit Breakers and SwitchgearLiving Online
Switchgear plays an important role in electricity distribution and its performance significantly affects the overall performance of the system. Failure to efficiently disconnect faults elsewhere in the network or failure in switchgear itself is costly, resulting in additional loss of supply, damage to equipment and possibly fatal injury to personnel. It is therefore critically important that switchgear is operated and maintained correctly, within an overall asset management regime that is both economic and effective in securing a high level of system reliability.
This comprehensive workshop focuses on medium voltage switchgear, which comprises by far the bulk of switchgear on most electricity distribution systems. The emphasis is primarily on oil, air blast, SF6 and vacuum circuit breakers, but other forms of MV switchgear, for example ring main units and auto-reclosers will also be described.
MORE INFORMATION: http://www.idc-online.com/content/safe-operation-and-maintenance-circuit-breakers-and-switchgear-3
1) Tan delta testing uses a very low frequency AC voltage to measure the dissipation factor of insulation to determine its quality and condition. A higher loss angle indicates more contamination.
2) The cable or winding is disconnected and the test voltage is applied and increased in steps while tan delta measurements are taken. A straight trend line indicates healthy insulation while a rising line indicates contamination.
3) Routine maintenance of bushings includes inspecting the porcelain for cracks, metal parts for corrosion, oil levels, and cleaning surface contamination which can cause flashovers. Leaks should be repaired to prevent moisture issues.
EA Technology is a 100% employee-owned company that was originally established in the late 1960s as an R&D center for the UK electricity industry. It provides asset condition assessment, instrumentation, and asset management software and consulting services related to partial discharge detection and diagnosis. Partial discharge refers to a localized breakdown of insulation within an electrical apparatus that does not completely bridge the insulation gap. It can occur due to defects, voids, contamination, or other issues and causes damage over time if left unaddressed. Various online and offline detection techniques exist to identify and locate partial discharge.
Tan delta is the insulation power factor & is equal to the ratio of power dissipated in the insulation in watts to the product of effective voltage & current in volt ampere when tested under sinusoidal voltage.
Power Diagnostix produces versatile instruments for high-voltage diagnostic applications including partial discharge detection. Their ICMseries detectors are used worldwide for evaluating electrical insulation. In addition to partial discharge equipment, they also produce instruments for fiber optic transmission, GIS fault location, and high-voltage test control. The ICMsystem is their flagship partial discharge detector, known for its versatility and ability to evaluate insulation conditions across various frequencies through modular components.
The document discusses the choice of wiring systems and types of cables used for internal building wiring. It outlines several factors to consider when choosing a wiring system, including cost, durability, permanence, accessibility, appearance, mechanical protection, and safety. Common cable types are defined based on conductor material, number of cores, voltage grading, and insulation type. PVC cables are widely used for internal wiring due to their flexibility, insulating qualities, resistance to chemicals, and ability to accommodate more wires in a given conduit size compared to other insulation types.
The document discusses partial discharge (PD) monitoring as a predictive maintenance tool. It explains that PD occurs as small electrical sparks in air-filled cavities within high voltage electrical insulation. PD monitoring can detect insulation issues in rotating equipment like motors and generators, which account for 50% of failures, up to 10 years before catastrophic failure occurs. The document outlines different types of PD that can occur in motors and generators and stresses the importance of early PD detection to prevent unexpected outages and extend equipment life.
This document provides an overview of partial discharge training. It begins by defining what partial discharge is and discussing some of the common causes. It then explains how partial discharge is measured, including through transient earth voltage detection and ultrasonic detection. Various types of partial discharge are described, including internal discharges occurring within insulation cavities and surface discharges at insulation boundaries. Examples of partial discharge findings from switchgear components like cable terminations and circuit breakers are shown. The document also discusses partial discharge instrumentation and the analysis and reporting of partial discharge measurement results.
EE2353 / High Voltage Engineering - Testing of CablesRajesh Ramesh
Cable testing is important to ensure the long life and high efficiency of cables used for high voltage transmission. There are several types of tests conducted on cable samples including mechanical, thermal, impulse withstand voltage, partial discharge, and dielectric power factor tests. Partial discharge tests are particularly important for determining the life of cable insulation by detecting internal discharges under voltage stress. These tests are conducted at various stages of voltage levels on cable samples to certify them for transmission use.
A lightning arrester, also known as a lightning conductor, is a device used to protect electrical power systems and telecommunications systems from damage caused by lightning strikes. It has a high voltage terminal connected to the power line and a ground terminal. When a lightning surge travels along the power line, the arrester diverts the current through itself to ground, usually by means of an arc across an air gap. Common types of lightning arresters include rod arresters, horn gap arresters, multi gap arresters, and various types using silicon carbide or metal oxide components. A horn gap arrester consists of two horn-shaped metal rods separated by a small air gap, connected to the power line through a resistance and choke coil to
1) Streamer theory was proposed in 1940 by Rather, Meek and Loeb to explain phenomena not accounted for by Townsend's theory of gas breakdown, such as dependence on gas pressure and geometry.
2) Streamer theory describes how a single avalanche can develop into a spark discharge through distortion of the electric field by space charge, generating further avalanches cumulatively at the avalanche head.
3) Positive ions are left behind the rapidly advancing avalanche head, enhancing the field in front and reducing it behind, while the field is also enhanced between the tail and cathode. This leads to further space charge increase and field enhancement around the anode, forming a streamer connecting anode to cathode.
EHV (extra high voltage) AC transmission refers to equipment designed for voltages greater than 345 kV. Higher transmission voltages increase efficiency by reducing transmission losses and current, decrease infrastructure costs, and increase transmission capacity. However, they also present safety and interference risks. New technologies like FACTS (flexible AC transmission systems) help maximize the benefits of EHV transmission by enabling voltage control and power flow management. There is growing support for expanding national EHV transmission grids to facilitate large-scale renewable energy integration and inter-regional power sharing.
A presentation explaining how to calculate fault currents for 3-phase or 1-phase faults in power grid. Particularly useful for engineers working in electrical power transmission company.
Principles of Cable Sizing; current carrying capacity, voltage drop, short circuit.
Cables are often the last component considered during system design even if in many situations cables are the true system’s lifeline: if a cable fails, the entire system may stop. Cable reliability is therefore extremely important, then a cable system should be engineered to last the life of the system in the installation environment for the required application. Environments in which cable systems are being used are often challenging, as extreme temperatures, chemicals, abrasion, and extensive flexing. These variables have a direct impact on the materials used for cable insulation and jacketing as well as the construction of the cable. Using a systematic approach will help ensure that designer select the best cable for the required application in the installation environment. This lessons will provide students main guidelines for perform this approach.
Guidelines for Unconventional Partial Discharge Measurement (CIGRE 444)AHMED MOHAMED HEGAB
Several non-conventional PD detection methods based on acoustic and electromagnetic phenomenon have been used for some time for PD detection on power cables, transformers, GIS and generators. Up to now there have not been accepted procedures and guidelines for “non-conventional methods” compared to conventional methods. There are many open questions including: calibration or sensitivity verification procedures, techniques for noise suppression, methods of
fault location, and energy equivalency, among others. The authors of this guide believe that now is the time to prepare guidelines and international recommendations for these non-conventional PD detection methods in order to ensure reproducible and comparative PD measurements on high voltage equipment between users.
The document discusses the main equipment used in 400kV power transmission and distribution substations. It describes some of the key components including transformers, switchgear, isolators, circuit breakers, wave traps, and current transformers. Switchgear is explained in more detail, noting that it is used to control, protect, and isolate electrical equipment by de-energizing circuits for work and clearing faults downstream, improving the reliability of the power supply. The 400kV substation in Bareilly, India is also briefly outlined, including its division into 400kV, 220kV, and 33kV sections served by a common control room.
This document discusses cable sizing calculations and techniques. It explains that proper cable sizing is important to ensure efficient, safe and economic transmission of electrical energy without interruptions or exceeding the cable's limits. The document outlines the common steps for cable sizing: 1) gathering data on the cable, load and installation conditions, 2) determining the minimum size based on current capacity, voltage drop, temperature rise and fault impedance, and 3) selecting the optimally sized cable. Several examples are provided to illustrate implementing the cable selection process. Risks of improper sizing like voltage drops, overheating and shorter lifespan are also summarized.
This document discusses tests performed on transformers and surge arresters, including induced voltage tests, partial discharge tests, impulse tests, and surge arrester tests like spark over tests and residual voltage tests. The tests are used to evaluate the insulation strength and ability to withstand transient overvoltages of transformers and effectiveness of surge arresters in protecting equipment.
This document provides information about a power system protection course, including:
1. The syllabus covers 5 units - introduction to protection schemes, operating principles of relays, apparatus protection, theory of circuit interruption, and circuit breakers.
2. The theory of circuit interruption unit discusses arc phenomena, interruption of DC and AC circuits. It explains the physics behind arc initiation, maintenance and methods of arc extinction.
3. Interruption of capacitive current can produce high transient voltages across the circuit breaker contacts. This occurs when unloaded transmission lines or capacitor banks are switched off.
Breakdown due to Internal Discharges and Surface BreakdownAsim Raza
Electrical breakdown occurs when the voltage applied across an insulator exceeds its breakdown voltage, causing it to become electrically conductive. Breakdown can be caused by internal discharges within voids in solid insulators or at boundaries with electrodes. These internal discharges erode the insulating material over time through carbonization and heating, eventually leading to complete breakdown. Surface breakdown, or flashover, occurs when a conducting path forms on the insulating surface, allowing current flow and sparking that further degrades the insulation. Tracking is the formation of a permanent conducting carbon path, while erosion gradually weakens the material over time.
Safe Operation and Maintenance of Circuit Breakers and SwitchgearLiving Online
Switchgear plays an important role in electricity distribution and its performance significantly affects the overall performance of the system. Failure to efficiently disconnect faults elsewhere in the network or failure in switchgear itself is costly, resulting in additional loss of supply, damage to equipment and possibly fatal injury to personnel. It is therefore critically important that switchgear is operated and maintained correctly, within an overall asset management regime that is both economic and effective in securing a high level of system reliability.
This comprehensive workshop focuses on medium voltage switchgear, which comprises by far the bulk of switchgear on most electricity distribution systems. The emphasis is primarily on oil, air blast, SF6 and vacuum circuit breakers, but other forms of MV switchgear, for example ring main units and auto-reclosers will also be described.
MORE INFORMATION: http://www.idc-online.com/content/safe-operation-and-maintenance-circuit-breakers-and-switchgear-3
1) Tan delta testing uses a very low frequency AC voltage to measure the dissipation factor of insulation to determine its quality and condition. A higher loss angle indicates more contamination.
2) The cable or winding is disconnected and the test voltage is applied and increased in steps while tan delta measurements are taken. A straight trend line indicates healthy insulation while a rising line indicates contamination.
3) Routine maintenance of bushings includes inspecting the porcelain for cracks, metal parts for corrosion, oil levels, and cleaning surface contamination which can cause flashovers. Leaks should be repaired to prevent moisture issues.
EA Technology is a 100% employee-owned company that was originally established in the late 1960s as an R&D center for the UK electricity industry. It provides asset condition assessment, instrumentation, and asset management software and consulting services related to partial discharge detection and diagnosis. Partial discharge refers to a localized breakdown of insulation within an electrical apparatus that does not completely bridge the insulation gap. It can occur due to defects, voids, contamination, or other issues and causes damage over time if left unaddressed. Various online and offline detection techniques exist to identify and locate partial discharge.
Tan delta is the insulation power factor & is equal to the ratio of power dissipated in the insulation in watts to the product of effective voltage & current in volt ampere when tested under sinusoidal voltage.
Power Diagnostix produces versatile instruments for high-voltage diagnostic applications including partial discharge detection. Their ICMseries detectors are used worldwide for evaluating electrical insulation. In addition to partial discharge equipment, they also produce instruments for fiber optic transmission, GIS fault location, and high-voltage test control. The ICMsystem is their flagship partial discharge detector, known for its versatility and ability to evaluate insulation conditions across various frequencies through modular components.
The document discusses the choice of wiring systems and types of cables used for internal building wiring. It outlines several factors to consider when choosing a wiring system, including cost, durability, permanence, accessibility, appearance, mechanical protection, and safety. Common cable types are defined based on conductor material, number of cores, voltage grading, and insulation type. PVC cables are widely used for internal wiring due to their flexibility, insulating qualities, resistance to chemicals, and ability to accommodate more wires in a given conduit size compared to other insulation types.
The document discusses partial discharge (PD) monitoring as a predictive maintenance tool. It explains that PD occurs as small electrical sparks in air-filled cavities within high voltage electrical insulation. PD monitoring can detect insulation issues in rotating equipment like motors and generators, which account for 50% of failures, up to 10 years before catastrophic failure occurs. The document outlines different types of PD that can occur in motors and generators and stresses the importance of early PD detection to prevent unexpected outages and extend equipment life.
This document provides an overview of partial discharge training. It begins by defining what partial discharge is and discussing some of the common causes. It then explains how partial discharge is measured, including through transient earth voltage detection and ultrasonic detection. Various types of partial discharge are described, including internal discharges occurring within insulation cavities and surface discharges at insulation boundaries. Examples of partial discharge findings from switchgear components like cable terminations and circuit breakers are shown. The document also discusses partial discharge instrumentation and the analysis and reporting of partial discharge measurement results.
This document discusses voltage testing and partial discharge measurement techniques for power cable accessories. It provides:
1) An overview of the objective to compare cable testing best practices and determine cable defects using partial discharge methods.
2) A description of an ACRF test system used, including its components like an HV reactor, control unit, and voltage divider.
3) Details on partial discharge measurement methods like using high frequency current transformers and coupling capacitors to detect discharges in cables.
4) The conclusion that resonant testing between 20-300Hz along with partial discharge detection reduces risks from cable systems after installation by locating faults.
VLF Testing of Cables Using IEEE 400.2. Presentation by John Densley that describes the in situ testing of distribution cables using very low frequency (VLF) voltages according to IEEE Standard 400.2. The Standard includes criteria to assess the condition of XLPE, EPR and paper insulated cable circuits. How the criteria were established and their limitations will be discussed, along with Partial Discharge (PD) testing using VLF.
John, the President of ArborLec Solutions Inc. has worked on electrical ageing mechanism and diagnostics techniques in electrical insulation for more than 35 years. He has a sound practical and theoretical knowledge of ageing and failure mechanisms of insulation systems in high voltage equipment such as medium and high voltage cables, transformers and switchgears.
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
1. The document discusses high voltage testing of electrical transformers, including various types of tests like partial discharge testing, impulse testing, turns ratio testing, and insulation resistance testing.
2. These tests help check the insulation quality, detect defects, verify voltage ratios, and ensure transformers can withstand high voltage surges to prevent failures.
3. High voltage testing provides advantages like improved safety, energy efficiency, lower costs, and failure detection; but can also have disadvantages like not removing the root causes of failures.
Precise kilometer calculation by underground cable fault detectorvivekmv716
The document describes an undergraduate student project to locate faults in underground power cables. It presents the project overview, block diagram, components used including a microcontroller, ADC, relays, and LCD. Resistors are used to simulate cable lengths and faults are induced using switches. The voltage drop across resistors is measured and the distance displayed on the LCD based on calculations done by the microcontroller. Relays are used to select cable phases and the system is powered by a 5V regulator.
The document provides recommendations for commissioning testing of medium voltage cables, including sheath testing, withstand testing, and partial discharge (PD) testing. It recommends test voltage levels and durations for different cable types, and evaluates PD measurement results to determine if cables pass or require replacement. The recommendations aim to fulfill safety requirements and quality control by detecting workmanship issues not found during initial testing.
This document provides information on cable testing methods used at Thermo Cables Limited in Hyderabad, India. It discusses the various types of tests conducted on power, control, instrument, signal and other cables to check parameters like high voltage resistance, conductor resistance, insulation resistance, capacitance, inductance, tensile strength, thermal stability, attenuation and more. The tests are conducted according to standards like IS, IEC, ASTM, BS to ensure cable quality meets specifications.
A Frequency-based RF Partial Discharge Detector for Low-power Wireless Sens...Swathi Venugopal
This document describes a low-power wireless detector for monitoring partial discharge (PD) in electrical equipment. The detector uses three frequency bands to capture PD signals from sensors. It was tested in a laboratory setup with different defect types in SF6 gas. The results showed the detector could distinguish between defect types based on variations in the frequency spectra. Multiple defects were also differentiated. The conclusions were that the novel frequency-based approach is capable of PD detection and basic defect classification with low power consumption for wireless applications.
Chopper basically uses a Thyristor for high power applications. The process of turning off a conducting Thyristor is known as commutation. Here Thyristor is turned off by a current pulse that is why it is called a Current Commutated Chopper.
The presentation is delivering the general aspects of transmission of electric energy. At the beginning need of transmission is presented, and then the various aspects of transmission, which affect the choice of scheme of transmission are presented. At the end of presentation, the topic is summarized as comparison among the HVAC and HVDC transmission.
This presentation was given by shivlal mohal, during the final semester of electric engineering.
This document is a thesis submitted by Lakshya Mittal to the Indian Institute of Technology Madras for the award of a Master of Science degree in electrical engineering. The thesis investigates incipient discharge activity in cryogenic insulation structures using UHF techniques. It includes experimental and theoretical studies on corona discharge characterization and electrical tree growth in liquid nitrogen and XLPE cable insulation at low temperatures under AC voltages. Modelling of electrical trees is also presented to understand the electric field distribution during tree initiation and propagation in nano-composite materials.
This document provides an overview of ampacity testing of fire protected raceways conducted by Kent W. Brown of TVA. It describes the test program which was based on IEEE 848 and aimed to determine ampacity derating factors for various cable and raceway configurations protected by fire barriers. The testing covered single and multiple conduits, covered and open trays, and upgrades from 1-hour to 3-hour fire ratings. Final ampacity correction factors are reported for different protected raceway systems based on the test results.
Ultrasonic transducers use ultrasonic waves above 20 kHz to measure parameters. They contain a transmitter that sends ultrasonic waves and a receiver that detects the waves. A timer measures the time difference between transmission and reception, which is calibrated to the parameter being measured, such as the speed of ultrasonic waves through a medium. Piezoelectric crystals are commonly used elements that can both transmit and receive ultrasonic waves when a voltage is applied. Ultrasonic transducers are used to measure fluid flow rates, liquid levels, and object displacement.
The document discusses redesigning LT XLPE cables and HT ABC cables used by a distribution utility to improve reliability. For LT XLPE cables, failures were found to be caused by UV radiation cracking the insulation of red, yellow and blue colored cores. A new design was proposed using black pigment for all cores which is UV retardant. For HT ABC cables, failures were due to sparking between the floating copper screen and messenger wire. A redesign using an aluminum screen that reduces induced voltage was proposed. Technical and economic analysis found both redesigns improved reliability and reduced repair costs. The utility has implemented the LT cable design, filed a patent and proposed changes to product standards.
The document discusses power cable insulation materials and failure mechanisms. The insulation can be paper impregnated with oil or polymers like polyethylene. Contaminants, protrusions, or voids in the insulation can lead to overstress and eventual failure over time by causing discharges. Cable designs are modified to ensure uniform electric stress distribution and avoid issues caused by these defects. Key insulation system types include low density polyethylene, high density polyethylene, cross linked polyethylene, and ethylene propylene rubber. Cable condition is monitored through loss tangent measurements and partial discharge measurements to identify faulty insulation.
Modern underground power cables are sophisticated assemblies of insulators, conductors and protective materials. Within these components are sensors, which enable cable operators to monitor conditions along the cable in real time.
The condition of the cable insulation is usually monitored through the following two main methods:
Loss tangent measurements
Partial discharge (PD) measurements
EE-55 Power Cables Testing & Fault LocationRina Florentes
Dr. Adel Al-Faraskoury will teach a course on power cable testing and fault location from December 27-31, 2015 in Dubai, UAE. The course will cover topics such as partial discharge techniques, very low frequency testing, cable fault location methods, and cable failures and their analysis. It is aimed at engineers and technicians from electrical utilities and will help participants better understand cable testing and maintenance. Registration must be completed and paid for 25 days prior to the course date to receive an early bird discount.
1. The document provides a specific method statement for HV cable testing.
2. It outlines the preliminary steps such as qualifications, PPE, site induction and inspections.
3. The main stages include setting up the testing zone, confirming switchgear status, issuing isolation certificates, conducting phasing tests, and performing pre-insulation resistance tests between phases and from phases to earth.
Brugg Kabel AG uses silicone insulation for high voltage cable accessories up to 400kV. Routine partial discharge (PD) testing is done on prefabricated joints to ensure quality and detect defects. On-site PD measurements after installation can accurately detect PD above 5pC and localize faults. Directional coupler sensors allow sensitive PD detection and localization in unscreened environments. PD testing is important for ensuring reliability of joints and avoiding premature failures during operation.
This document discusses using artificial neural networks (ANNs) and statistical techniques to classify partial discharge (PD) defects within cross-linked polyethylene (XLPE) medium voltage cables. PD measurements were taken from six cables with different defects and voltages. Statistical features were extracted from the 3D PD patterns to form the input for various ANNs for classification. 72 different ANN structures were analyzed to determine the most effective and optimal classification technique, based on metrics like mean square error and accuracy. The proposed approach achieved high recognition rates for identifying different types of PD defects within XLPE cables.
Results of 10 years after installation tests with partial discharge detection...HighVoltageDUT
In 2004 Alliander decided to add partial discharge (PD) measurements in their after installation test policy. Over the last years, dozens of accessories and a few cable parts were taken out of the tested cables, based on PD activity, measured during after installation test. In many cases severe abnormalities were found, threatening the reliability of the cable system, but also cases were found where the reason for PD was not clear. It is also discovered that cable systems can contain PD’s in accessories but still survive the after installation test.
Cyclic voltammetry readout circuitry for DNA biosensor applicationjournalBEEI
Cyclic voltammetry electrochemical biosensors reported a wide usage and applications for its fast response, able to be miniaturized and its sensitivity. However, the bulky, expensive and laboratory-based readout circuitry made it impossible to be used in the field-based environment. A miniaturized and portable readout circuitry for the DNA detection using hybridization technique had been design and developed in this work. It embedded with fabricated FR4 based sensor and produced respective current when the applied voltage was within the range of 0 to 0.5 V. The readout circuitry had been verified with five analysis environments. Bare Au with distilled water (dH2O), bare Au with ferricyanide reagent solution, DNA immobilization, DNA non-hybridization and DNA hybridization. All the results performed produced peak cathodic current when the applied input voltage is within 0.5 V to 3 V and hence proved that the miniaturized and portable readout circuitry is suitable to be implemented for cyclic voltammetry electrochemical biosensor.
Comparison of Different Voltage Waveforms for Cable PD Testing.pdfAliNaderian2
The document summarizes a study that compares different voltage waveforms for partial discharge (PD) measurement in medium voltage cables and accessories. Laboratory tests were conducted on cable samples containing various defects when subjected to sinusoidal AC at 60 Hz, sinusoidal very low frequency at 0.1 Hz, and damped alternating current. The results found that sinusoidal AC was the most sensitive in detecting PD, followed by very low frequency, while damped alternating current required higher voltages and was the least sensitive. Continuous AC waveforms like sinusoidal AC and very low frequency were preferred for cable commissioning and maintenance testing based on the study.
This document describes a study that compares the sensitivity of a single mode fiber optic sensor (FOS) to a conventional capacitive sensor (CS) for detecting partial discharge (PD) in transformer oil. PD occurs due to electrical breakdown in the oil and degrades the transformer insulation over time. Both sensors were immersed in an oil tank with high voltage electrodes to generate PD. The FOS detected acoustic emission from the PD, which modulated light in the fiber from a laser source. The CS detected electric fields from the PD. Analysis of the sensor signals in time and frequency domains found the FOS had a higher resolution (~9 dB) than the CS (~15 dB) for voltages over 15 kV, demonstrating it is a more
This document describes research on simulating partial discharges (PDs) at variable frequencies between 0.01-50 Hz in a disc-shaped cavity. PD phase, magnitude, and number of discharges per cycle varied with frequency. A charge-consistent model was developed to dynamically simulate PD sequences. Simulated results showed cavity surface properties and emission were affected by the applied frequency magnitude due to conductivity effects. The paper illustrates how applied voltage amplitude and cavity size influence the frequency dependence of PD activity.
IRJET - A Review of an Investigation of Partial Discharge Sources and Loc...IRJET Journal
This document reviews methods for detecting partial discharge (PD) sources and locations along high voltage transformer windings. PD occurs due to dielectric breakdown within cracks or voids in insulating materials under high voltage stress, degrading insulation over time. The document discusses several PD detection methods including conventional electrical measurements of apparent charge, ultra-high frequency measurements of electromagnetic emissions from PD, and ultrasonic acoustic measurements to locate PD sources based on differences in signal arrival times at sensors. It provides details on the principles, advantages, and limitations of each method for both offline and online PD monitoring and diagnosis in transformers.
1. The document describes an underground cable fault distance locator project that uses a microcontroller to determine the distance of faults in underground power cables.
2. The project uses a bank of resistors to represent an underground cable carrying power. When a fault occurs, the voltage drop across the cable varies depending on the fault location, allowing the distance to be calculated.
3. The microcontroller measures the voltage drop, performs calculations, and displays the fault distance on an LCD screen. It can also send the fault information via GSM to notify relevant parties.
Underground Transmission Cable Monitoring – Lessons Learned at AEPPower System Operation
As part of its system and asset health monitoring initiative, American Electric Power (AEP) has deployed several new online health monitoring systems on its cross-linked polyethylene power cables. Two different types of monitoring systems have been deployed, including partial discharge monitoring and distributed temperature sensing monitoring on a total of 4 different 138kV power cable circuits and 1 69kV power cable circuit. These continuous health monitors provide multiple indicators about the power cable assisting in the health assessment of an otherwise invisible asset. The first of these installations was completed in 2016, with the latest installation being completed in 2019. The nature of the monitoring systems, the possible benefits, as well as some of AEP’s lessons learned from these pilot installations will be discussed in the following paper.
This document summarizes techniques for locating faults in underground power cables. It discusses using a microcontroller to determine the distance of a fault from the base station in kilometers by applying a low DC voltage through resistors representing the cable and detecting voltage drops. Tracer and terminal methods for fault location are described. Using fiber optic distributed temperature sensors and neural networks for fault identification are also summarized. The document provides block diagrams of the proposed underground cable fault distance system conveyed over GSM and its components including the power supply, microcontroller, rectifier, voltage regulator, and relay.
This document provides guidelines for designing and laying out a printed circuit board for a switch mode power supply to be compatible with EMC/EMI standards. It begins with an overview of some international and European EMC standards. It then outlines key techniques for minimizing conducted and radiated emissions from the power supply, such as reducing the magnetic loops on the PCB, filtering noise at the source, adapting the operating frequency, and using decoupling capacitors. The document provides checklists of design practices and considerations for EMC compliance.
This paper proposes fault location model for underground power cable using microcontroller. The aim of this project is to determine the di stance of underground cable fault from base station in kilometers. This project uses the simple c oncept of ohm�s law.When any fault like short circuit occurs,voltage drop will vary depending on the length of fault in cable,since the current varies. A set of resistors are ther efore used to represen t the cable and a dc vol tage is fed at one end and the fault is detected by detecting the change in voltage using a analog to voltage converter and a microcontroller is used to make the necessary calculations so that the fault distance is displayed on the LCD display.
This document provides an overview of infrared thermography and its applications for electrical systems. It discusses what infrared thermography is, how it works, common test instruments used, electrical components that can be inspected, typical faults detected, condition monitoring benefits, electrical applications, and case studies. Infrared thermography allows non-contact surface temperature measurements and visualization of thermal issues. It can be used to detect problems in transformers, distribution panels, motors, and more. Periodic inspections provide predictive maintenance benefits like reduced downtime and safety improvements.
Underground Cable Fault Detection Using ArduinoIRJET Journal
This document describes a project to detect faults in underground cables using an Arduino. It contains the following key points:
1. The project uses a circuit of resistors connected to an Arduino to represent the length of an underground cable. Switches placed at 1 km intervals can induce faults manually.
2. When a fault occurs, the Arduino and its ADC convert the analog current readings to digital data to determine the precise location of the fault in kilometers.
3. The document reviews related work on cable fault detection and discusses cable types, common fault types like earth faults and short circuits, and methods like Time Domain Reflectometry that have been used.
Online condition moniroing of power system, branched cablesMuhammad Shafiq
Partial discharge (PD) detection and localization in medium voltage (MV) cables connected in branched network configurations, is difficult by using the conventional methods. In this presentation, Comparison of the polarity of PD pulses captured at different cable branches identifies the faulty section of the cable network.
An Ethernet Cable Discharge Event (CDE) Test and Measurement SystemESDEMC Technology LLC
This document describes a test system for measuring Cable Discharge Events (CDEs) on Ethernet cables. CDEs occur when charged Ethernet cables are connected to devices and can damage electronics if not properly handled. The proposed test system aims to reproduce real-world CDE scenarios in the lab by controlling cable charge levels, cable types, contact sequences and timings, and electrical characteristics of the discharge path. This will allow engineers to test designs under repeatable CDE conditions and improve immunity. Key parts of the system include a controller to set test parameters, a charge module representing different cable types, and monitors to check for failures.
ESDEMC_PB2014.08 An Ethernet Cable Discharge Event (CDE) Test and Measurement...ESDEMC Technology LLC
This document describes a test and measurement system for cable discharge events (CDEs) on Ethernet cables. A CDE occurs when a charged Ethernet cable discharges to a connector. The system aims to reproduce real-world CDE conditions in the lab to test hardware immunity. It consists of a controller to set cable charge levels and control discharges, charge modules representing different cable types, and a failure test monitor. The controller controls each cable wire separately and measures discharge currents. Calibration with defined loads validated the system's functionality and output parameters.
Underground Cable Fault Detection Using IOTIRJET Journal
This document discusses a system to detect faults in underground cable lines using IoT. It proposes using a microprocessor, LCD display, fault sensing circuit module, LoRa module, and power supply to detect the location and type of fault (single line to ground, double line to ground, or three phase faults). The system measures voltage changes across series resistors when a short circuit occurs to determine the fault location. It can display the fault location and phase on the LCD and transmit the data over WiFi. The document reviews literature on condition monitoring of underground cables, current transformer saturation effects, and comparing optical and magnetic current transformers.
Partial Discharge Analysis in High Voltage Current TransformersIRJESJOURNAL
ABSTRACT: In High Voltage (HV) electrical power systems, variety of materials (solid, liquid and gaseous) is used for insulation purpose to protect the incipient failure in Current Transformers. Most of insulating materials are not perfect in all respect and contains always some impurities. The presence of air bubble is one of such impurities in insulating materials and highly undesirable for such type of insulation which causes a local weak zone inside the insulator. Due to the high voltage stress the weak zone inside the insulator causes the partial discharge (PD) and finally the insulation properties of such materials is enormously degrades its quality. In this work, the simulation of PD activity due to presence of a small cylindrical void inside the solid insulation material of high voltage power equipment is analyzed with the MATLAB Simulink platform.
Similar to Seminar on Partial Discharge detection methods (20)
ACEP Magazine edition 4th launched on 05.06.2024Rahul
This document provides information about the third edition of the magazine "Sthapatya" published by the Association of Civil Engineers (Practicing) Aurangabad. It includes messages from current and past presidents of ACEP, memories and photos from past ACEP events, information on life time achievement awards given by ACEP, and a technical article on concrete maintenance, repairs and strengthening. The document highlights activities of ACEP and provides a technical educational article for members.
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMSIJNSA Journal
The smart irrigation system represents an innovative approach to optimize water usage in agricultural and landscaping practices. The integration of cutting-edge technologies, including sensors, actuators, and data analysis, empowers this system to provide accurate monitoring and control of irrigation processes by leveraging real-time environmental conditions. The main objective of a smart irrigation system is to optimize water efficiency, minimize expenses, and foster the adoption of sustainable water management methods. This paper conducts a systematic risk assessment by exploring the key components/assets and their functionalities in the smart irrigation system. The crucial role of sensors in gathering data on soil moisture, weather patterns, and plant well-being is emphasized in this system. These sensors enable intelligent decision-making in irrigation scheduling and water distribution, leading to enhanced water efficiency and sustainable water management practices. Actuators enable automated control of irrigation devices, ensuring precise and targeted water delivery to plants. Additionally, the paper addresses the potential threat and vulnerabilities associated with smart irrigation systems. It discusses limitations of the system, such as power constraints and computational capabilities, and calculates the potential security risks. The paper suggests possible risk treatment methods for effective secure system operation. In conclusion, the paper emphasizes the significant benefits of implementing smart irrigation systems, including improved water conservation, increased crop yield, and reduced environmental impact. Additionally, based on the security analysis conducted, the paper recommends the implementation of countermeasures and security approaches to address vulnerabilities and ensure the integrity and reliability of the system. By incorporating these measures, smart irrigation technology can revolutionize water management practices in agriculture, promoting sustainability, resource efficiency, and safeguarding against potential security threats.
Advanced control scheme of doubly fed induction generator for wind turbine us...IJECEIAES
This paper describes a speed control device for generating electrical energy on an electricity network based on the doubly fed induction generator (DFIG) used for wind power conversion systems. At first, a double-fed induction generator model was constructed. A control law is formulated to govern the flow of energy between the stator of a DFIG and the energy network using three types of controllers: proportional integral (PI), sliding mode controller (SMC) and second order sliding mode controller (SOSMC). Their different results in terms of power reference tracking, reaction to unexpected speed fluctuations, sensitivity to perturbations, and resilience against machine parameter alterations are compared. MATLAB/Simulink was used to conduct the simulations for the preceding study. Multiple simulations have shown very satisfying results, and the investigations demonstrate the efficacy and power-enhancing capabilities of the suggested control system.
Redefining brain tumor segmentation: a cutting-edge convolutional neural netw...IJECEIAES
Medical image analysis has witnessed significant advancements with deep learning techniques. In the domain of brain tumor segmentation, the ability to
precisely delineate tumor boundaries from magnetic resonance imaging (MRI)
scans holds profound implications for diagnosis. This study presents an ensemble convolutional neural network (CNN) with transfer learning, integrating
the state-of-the-art Deeplabv3+ architecture with the ResNet18 backbone. The
model is rigorously trained and evaluated, exhibiting remarkable performance
metrics, including an impressive global accuracy of 99.286%, a high-class accuracy of 82.191%, a mean intersection over union (IoU) of 79.900%, a weighted
IoU of 98.620%, and a Boundary F1 (BF) score of 83.303%. Notably, a detailed comparative analysis with existing methods showcases the superiority of
our proposed model. These findings underscore the model’s competence in precise brain tumor localization, underscoring its potential to revolutionize medical
image analysis and enhance healthcare outcomes. This research paves the way
for future exploration and optimization of advanced CNN models in medical
imaging, emphasizing addressing false positives and resource efficiency.
A review on techniques and modelling methodologies used for checking electrom...nooriasukmaningtyas
The proper function of the integrated circuit (IC) in an inhibiting electromagnetic environment has always been a serious concern throughout the decades of revolution in the world of electronics, from disjunct devices to today’s integrated circuit technology, where billions of transistors are combined on a single chip. The automotive industry and smart vehicles in particular, are confronting design issues such as being prone to electromagnetic interference (EMI). Electronic control devices calculate incorrect outputs because of EMI and sensors give misleading values which can prove fatal in case of automotives. In this paper, the authors have non exhaustively tried to review research work concerned with the investigation of EMI in ICs and prediction of this EMI using various modelling methodologies and measurement setups.
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024Sinan KOZAK
Sinan from the Delivery Hero mobile infrastructure engineering team shares a deep dive into performance acceleration with Gradle build cache optimizations. Sinan shares their journey into solving complex build-cache problems that affect Gradle builds. By understanding the challenges and solutions found in our journey, we aim to demonstrate the possibilities for faster builds. The case study reveals how overlapping outputs and cache misconfigurations led to significant increases in build times, especially as the project scaled up with numerous modules using Paparazzi tests. The journey from diagnosing to defeating cache issues offers invaluable lessons on maintaining cache integrity without sacrificing functionality.
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTjpsjournal1
The rivalry between prominent international actors for dominance over Central Asia's hydrocarbon
reserves and the ancient silk trade route, along with China's diplomatic endeavours in the area, has been
referred to as the "New Great Game." This research centres on the power struggle, considering
geopolitical, geostrategic, and geoeconomic variables. Topics including trade, political hegemony, oil
politics, and conventional and nontraditional security are all explored and explained by the researcher.
Using Mackinder's Heartland, Spykman Rimland, and Hegemonic Stability theories, examines China's role
in Central Asia. This study adheres to the empirical epistemological method and has taken care of
objectivity. This study analyze primary and secondary research documents critically to elaborate role of
china’s geo economic outreach in central Asian countries and its future prospect. China is thriving in trade,
pipeline politics, and winning states, according to this study, thanks to important instruments like the
Shanghai Cooperation Organisation and the Belt and Road Economic Initiative. According to this study,
China is seeing significant success in commerce, pipeline politics, and gaining influence on other
governments. This success may be attributed to the effective utilisation of key tools such as the Shanghai
Cooperation Organisation and the Belt and Road Economic Initiative.
Batteries -Introduction – Types of Batteries – discharging and charging of battery - characteristics of battery –battery rating- various tests on battery- – Primary battery: silver button cell- Secondary battery :Ni-Cd battery-modern battery: lithium ion battery-maintenance of batteries-choices of batteries for electric vehicle applications.
Fuel Cells: Introduction- importance and classification of fuel cells - description, principle, components, applications of fuel cells: H2-O2 fuel cell, alkaline fuel cell, molten carbonate fuel cell and direct methanol fuel cells.
Comparative analysis between traditional aquaponics and reconstructed aquapon...bijceesjournal
The aquaponic system of planting is a method that does not require soil usage. It is a method that only needs water, fish, lava rocks (a substitute for soil), and plants. Aquaponic systems are sustainable and environmentally friendly. Its use not only helps to plant in small spaces but also helps reduce artificial chemical use and minimizes excess water use, as aquaponics consumes 90% less water than soil-based gardening. The study applied a descriptive and experimental design to assess and compare conventional and reconstructed aquaponic methods for reproducing tomatoes. The researchers created an observation checklist to determine the significant factors of the study. The study aims to determine the significant difference between traditional aquaponics and reconstructed aquaponics systems propagating tomatoes in terms of height, weight, girth, and number of fruits. The reconstructed aquaponics system’s higher growth yield results in a much more nourished crop than the traditional aquaponics system. It is superior in its number of fruits, height, weight, and girth measurement. Moreover, the reconstructed aquaponics system is proven to eliminate all the hindrances present in the traditional aquaponics system, which are overcrowding of fish, algae growth, pest problems, contaminated water, and dead fish.
1. 1
Conventional and
Un-Conventional Partial Discharge
Detection Methods in High Voltage
XLPE Cable Accessories
Presented By:
Harshit Bhandari
8th
Sem Electrical
Guided by:
Prof. Harish Khyani
2. CONTENTS
2
What Is XLPE ?
Problem with XLPE cables
Detection of Faults
Partial discharge
What causes partial discharge ?
Partial discharge detection methods
Classification
Conventional Method
Conclusion
3. 3
What is XLPE ?
XLPE stands for Cross-linked Polyethylene cables .
These are most extensively used power cables for
transmission of High voltages
They are frequently used for both overhead and
underground high voltage transmission system
5. 5
Power cable system basically consists of cables
themselves and their accessories.
Cable accessories consist of joint and termination.
As the extensive application of Cross-linked
Polyethylene (XLPE) cable in power grid, power
accidents caused by insulation faults in cable
equipments are increasing constantly.
6. 6
Insulation faults occur more often in cable accessories and
the existence of insulation faults, can lead internal partial
discharge (PD) to occur.
The cable laying method is mainly concerned with
underground, which brings. problems on state testing and
fault localization in cable systems
Therefore, how to judge the cable insulation
situation effectively and locate the fault site accurately is of
great practical significance
7. Partial Discharge
Partial discharges are in general a consequence of local
electrical stress concentrations in the insulation or on the
surface of the insulation.
Generally, such discharges appear as pulses having a
duration of
much less than 1 ps.
More continuous forms can, however, occur, such as the so-
called pulse-less discharges in
gaseous dielectrics.
For eg:- Corona Discharge
7
9. What causes Partial Discharge?
After installation or long time use, the insulation of cable or
accessories may include small voids and cavities, conductive
or insulating contaminants, or conductive protrusions in
different interfaces.
The installation may also cause other defects like mechanical
cuts.
During the service the temperature variation and other
environmental stresses as well as electric filed and heating
due to load current may enlarge these defects, and partial
discharges may be incepted.
9
10. These effects may also introduce cavities in originally sound cable
insulation or enlarge original micro voids.
Partial discharge measurement methods are most important and
preferred and they have received much attention in recent years.
Cont…
10
11. 11
Partial discharge (PD) measurement methods are most
important and preferred in testing of underground high voltage
cables and they have received much attention in recent years.
Apparent charge, partial discharge inception voltage as well
as number and distribution of PD pulses are most important
quantities for the determination of the insulation quality.
Identification with certain PD patterns and localization of PD
are most important aspects.
13. Conventional Method
Conventional PD detection is a standardized method for PD
measurement as described in IEC 60270.
This method based on measurement of apparent charge
displacement q in the leads of the sample. This charge is usually
expressed in Pico-Coulombs (pC)
Unconventional Method
Un-conventional PD measurement is based on detection of
high frequency PD activities.
14. Conventional Method
Partial discharges that occur in the test object will produce
current or voltage pulses.
Output PD pulse magnitude is more or less a measure of the
PD current amplitude and not for the apparent charge
This method based on measurement of the charge
displacement q, expressed in (pC), from the pulses which
generated from partial discharge
14
15. The tests are carried out in the Extra High Voltage Research
Centre (EHVRC) PD Lab. In these PD measurements, 50Hz
continuous AC voltage is used as an energizing method.
Using this PD detector several important parameters of PD
occurrence can be obtained such as:
• PD inception voltage (PDIV)
• PD magnitude in pC at PDIV
• PD magnitude as a function of voltage applied
• PD pattern
The PD measurements have been carried out according to IEC
for the XLPE cable sample 220 kV -1600 mm2
with two different
type of joint and termination as shown in figure
15
16. PD measurement is carried out in 2 minutes for each test
voltage. During this period three quantities are recorded:
The number of PD pulses,
The maximum value of PD magnitudes and
The average value of PD magnitudes
.
These three quantities are plotted as a function of phase
angle of sinusoidal AC voltage. 1 and the PD measurements
results as shown in next Figure
16
20. Unconventional Method
Un-conventional PD detection is used to provide result with
suppressed noise or high signal to noise ratio.
Basically there are two main methods,
High Frequency/Very High Frequency/ Ultra High Frequency (HF/
VHF/ UHF)
Acoustic method.
20
22. This methods use HFCT (High Frequency Current Transformer).
Using ultrasonic detector acoustic waves due to partial discharge are
detected .
This method does not requires any testing lab or heavy equipments
On-site detection of faults can be done easily with a semi skilled
person
22
Unconventional Method
CB Link with mounted three
HFCT (PD Sensor)