SlideShare a Scribd company logo
Seminar guide Seminar coordinator
Ms. Aanchal Baranwal Mr. Alok pandey
(Assistant professor) (Assistant professor)
Department of Electrical Department of Electrical
Engineering Engineering
A
Seminar
on
High voltage testing of
Electrical Transformer
PRESENTED BY
Hari Shankar Singh:-1308220902
CONTENTS
 Introduction of transformer and HV transformer
 Types of testing of transformer and explain with
detail
 Advantages of HV testing of transformer
 Disadvantages of HV testing of transformer
 Conclusion
 References
What is Transformer ?
• Transformer is an electrostatic device which
transfer electrical energy one circuit to another
circuit by magnetic flux without change of
frequency . Transformer has based on principle
of electromagnetic induction(EMI).
• Formula used as measured a value,
Vs / V p = Ns / N p = I p / Is
HIGH VOLTAGE
TRANSFORMER
• High voltage transformers convert voltages from
one level or phase configuration to another,
usually from higher to lower.
• They can include features for electrical isolation,
power distribution, and control and
instrumentation applications.
• High voltage transformers usually depend on
the principle of magnetic induction between
coils to convert voltage and current levels .
TYPES OF HV TESTING OF
ELECTRICAL TRANSFORMER
1. Partial discharge test
2. Impulse transformer test
3. Transformer turns ratio test
4. Insulation resistance test
5. Routine test
6. Temperature rise of oil testing of transformer
PARTIAL DISCHARGE TEST
• Partial discharge is a small localised dielectric
breakdown of an electrical insulation system
under high voltage stress.
• Each discrete partial discharge is the result of an
electrical breakdown of an air pocket within the
insulation.
• These discharges erode insulation and
eventually result in insulation failure.
• Acoustic techniques are used by manufacturers
to locate discharges that occur during HV testing
factory.
• PD occurs if the electric field strength applied to
a dielectric exceeds the dielectric withstand
strength of an insulation system locally.
• This may be caused by either increased field
strengths , e.g. due to design problems, sharp
edges on electrodes, small clearances , ageing ,
manufacture defect , insulation failure , damage
etc.
PDT TEST CIRCUIT
DIAGRAM
Fig.1
CAUSES OF FAILURE IN
PDT
Fig.2
FAILURE LOCATION OF
PDT
Fig.3
FUTURE APPLIANCES FROM
PDT
• Cables and Power transformers and bushings.
• Switchgear.
• Motors and generators
• Conclusion PDT testing prevents failure,
1. Off-line testing is a critical pre-commissioning
check.
2. On- line testing is an extremely powerful non-
instructive condition monitoring tool.
IMPULSE TRANSFORMER
TEST
• This test is made to prove that the transformer
insulation will withstand voltage surges which
may be caused by lightning or switching.
• This includes insulation to ground, insulation
between turns and windings, and the flashover
value of the associated bushings.
• A high-voltage wave of standard values, and
approximating a lightning surge, is imposed on
the unit to be tested.
• By a lightning pulse method used as measured
for impulse transformer testing followed as full
wave, half wave and front of wave show in Fig.4.
Fig.4:- Graph between ultra frequency and time
CONNECTION DIAGRAM OF
IMPULSE TRANSFORMER
TEST
Fig.5:-Connection of Impulse transformer test
TRANSFORMER TURN’S
RATIO TEST
• The Transformer Turns Ratio test is used to
make sure that the Turns Ratio between the
winding of the transformer is correct.
• With this information, you can decide what the
output voltage of the transformer will be. The
ratio is calculated under no-load conditions using
formula given below,
V pri /V sec = Z pri/ Z sec = (N pri /N sec )2
INSULATION RESISTANCE
TEST
(IR VALUE TEST)
• Insulation ages and deteriorates because of
moisture, dust and electrostatic stress. Insulation
should be monitored continually to avoid sudden
failure of the equipment.
• An insulation resistance test detects insulation
quality within the transformer.
• The conductive impurities or mechanical flows in
the dielectric can be analysis based on this test.
CONNECTION OF IR VALUE
TESTING DIAGRAM
Fig.6:- IR Value testing connection diagram
• Normally, MEGGERS have a test voltage of
500V , 2500V , or 5000V .
• IR between HV and LV as well as windings to
earth.
• Minimum IR value for Tap changer is 1000 ohm
per volt service voltage
FACTORS AFFECTING ON IR
VALUE OF TRANSFORMER
• The IR value of transformers are influenced by
Surface condition of the terminal bushing.
• Quality of oil.
• Quality of winding insulation.
• Temperature of oil.
• Duration of application and value of test voltage.
IR VALUE TESTING
FORMULAS
• 1 Phase Transformer
IR Value (MΩ) = C X E / (√KVA)
• 3 Phase Transformer (Star)
IR Value (MΩ) = C X E (P-n) / (√KVA)
• 3 Phase Transformer(Delta)
IR Value (MΩ) = C X E (P-P) / (√KVA)
Where C= 1.5 for Oil filled T/C with Oil Tank,
30 for Oil filled T/C without Oil Tank or Dry Type T/C.
ROUTINE TEST FOR
TRANSFORMER
A Routine test of transformer is mainly for confirming
operational performance of individual unit in a
production lot. Routine tests are carried out on every
unit manufactured.
All transformers are subjected to the following
Routine tests:
• Insulation resistance Test.
• Winding resistance Test.
• Turns Ratio / Voltage ratio Test
• Polarity / Vector group Test
• Open circuit and short circuit Test.
• Continuity Test.
• High Voltage Test.
• Partial discharge Test.
• Separate source AC voltage.
• Induced overvoltage.
• Lightning impulse Tests.
• On -load tap changers Test.
TEMPERATURE OIL
TESTING OF TRANSFORMER
• Temperature rise test of oil of Transformer is
included in type test of transformer.
• In this test we check whether the temperature
rising limit of transformer winding and oil as per
specification or not.
• Faults detects at above 75˚C by the help of
Buchholz relay and work as ALARM and TRIP
circuit.
BUCHHOLZ RELAY,
EXPAIL BY THE THIS
VIDEO
ADVANTAGES OF HV
TESTING TRANSFORMER
• Pure conductivity by IR Value test.
• Controlling of HV surges by Impulse test.
• Removing of discrete waveform by the help of
Partial Discharge test.
• Terminals has used connected correctly by
Transformer Turn’s Ratio test.
• Units measured a correctly and manufacturing
defect check by Routine test.
DISADVANTAGES OF HV
TESTING OF TRANSFORMER
• After failure, transformer is removed and
replaced with new/repaired one without removing
the cause of failure which results in immediate or
short time failure.
• Insufficient Oil level.
• Faulty operation of tap changer switch.
• Lack of installation checks.
• Prolonged Over loading.
CONCLUSION
• Knowledge of the construction of high voltage test
transformers, their design and use in high voltage
testing system gives the solution of the most
adjustment transformer in respect of parameters
and prices.
• HV testing are main advantages of safety ,
higher efficiency , lower cost ,savings of energy ,
avoiding of failures ,trouble shooting for failure
detection , accurate detection , quality assurance.
REFERENCES
• R.S. Jha, “High Voltage Engineering”, Dhanpat
Rai & Sons, Second Edition in 1996.
• C. L. Wadhwa, “High Voltage Engineering”, Wiley
Eastern Ltd. Third Edition in 2012.
• E.Kuffel and W.S. Zaengl, “High Voltage
Engineering” , Pergamon Press, First Edition
in1984.
444444444

More Related Content

What's hot

Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
Kabilesh K
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
jibinjoy1988
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
CS V
 
Substations
SubstationsSubstations
Substations
itfakash
 
Electric substation
Electric substation Electric substation
Electric substation
ANNU KUMAR
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, India
RajuMondal18
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
kaushal boghani
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
Md Irshad Ahmad
 
Transformer testing on sight and off sight
Transformer testing on sight and off sightTransformer testing on sight and off sight
Transformer testing on sight and off sight
DHAVALKUMAR JULASANA
 
Insulation Resistance Test
Insulation Resistance TestInsulation Resistance Test
Insulation Resistance Test
Shanid Pazhamkavil
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester ppt
IrinElsa
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
kishore kish
 
Sub station training ppt
Sub station training pptSub station training ppt
Sub station training ppt
sitesh95074
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission line
md muzahidul haque
 
Report on industrial summer training on 220 kv substation
Report  on industrial summer training on 220 kv substationReport  on industrial summer training on 220 kv substation
Report on industrial summer training on 220 kv substation
Ashutosh Srivastava
 
Transformer
TransformerTransformer
Transformer
Sandeep Kumar
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
Ang Sovann
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformer
Santu Mondal
 

What's hot (20)

Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Substations
SubstationsSubstations
Substations
 
Electric substation
Electric substation Electric substation
Electric substation
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, India
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Transformer testing on sight and off sight
Transformer testing on sight and off sightTransformer testing on sight and off sight
Transformer testing on sight and off sight
 
Insulation Resistance Test
Insulation Resistance TestInsulation Resistance Test
Insulation Resistance Test
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester ppt
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Sub station training ppt
Sub station training pptSub station training ppt
Sub station training ppt
 
Presentation topic is transmission line
Presentation topic is transmission linePresentation topic is transmission line
Presentation topic is transmission line
 
Report on industrial summer training on 220 kv substation
Report  on industrial summer training on 220 kv substationReport  on industrial summer training on 220 kv substation
Report on industrial summer training on 220 kv substation
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Transformer
TransformerTransformer
Transformer
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Stability test of transformer
Stability test of transformerStability test of transformer
Stability test of transformer
 

Viewers also liked

transformer ppt
transformer ppttransformer ppt
transformer ppt
Sharukh Ansari
 
Transformer construction,types and working
Transformer construction,types and workingTransformer construction,types and working
Transformer construction,types and working
maharshi dayanand university rohtak
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-enSuresh Patil
 
Transformer Maintenance and Testing
Transformer Maintenance and TestingTransformer Maintenance and Testing
Transformer Maintenance and TestingGPTraining
 
132kv Substation
132kv Substation132kv Substation
132kv Substationguestecdd58
 
digital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerdigital testing of high voltage circuit breaker
digital testing of high voltage circuit breaker
Renuka Verma
 
Partial discharge switchgear ea tech
Partial discharge switchgear ea techPartial discharge switchgear ea tech
Partial discharge switchgear ea tech
Mauritz Roni Gabe Manurung
 
Tansformer @dheeraj upadhyay
Tansformer @dheeraj upadhyayTansformer @dheeraj upadhyay
Tansformer @dheeraj upadhyay
Dheeraj Upadhyay
 
HV testing of insulator
HV testing of insulatorHV testing of insulator
HV testing of insulator
Jawad Ali
 
open circuit and short circuit test on transformer
open circuit and short circuit test on transformeropen circuit and short circuit test on transformer
open circuit and short circuit test on transformer
MILAN MANAVAR
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
Jimit Dhruv
 
Partial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyPartial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA Technology
Ryan McFallo
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
Living Online
 
Impulse test for power transformers
Impulse test for power transformersImpulse test for power transformers
Impulse test for power transformers
jibinjoy1988
 
Why dehydration of transformer oil is important?
Why dehydration of transformer oil is important?Why dehydration of transformer oil is important?
Why dehydration of transformer oil is important?
Transfo Tech. Engineering
 
Grid Voltage Regulation
Grid Voltage RegulationGrid Voltage Regulation
Grid Voltage Regulation
Aditya Nehwal
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGE
Jamil Abdullah
 
Transformer(Class 12 Investigatory Project)
Transformer(Class 12 Investigatory Project)Transformer(Class 12 Investigatory Project)
Transformer(Class 12 Investigatory Project)
अयशकांत मिश्र
 

Viewers also liked (20)

transformer ppt
transformer ppttransformer ppt
transformer ppt
 
Transformer construction,types and working
Transformer construction,types and workingTransformer construction,types and working
Transformer construction,types and working
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
 
Transformer Maintenance and Testing
Transformer Maintenance and TestingTransformer Maintenance and Testing
Transformer Maintenance and Testing
 
132kv Substation
132kv Substation132kv Substation
132kv Substation
 
digital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerdigital testing of high voltage circuit breaker
digital testing of high voltage circuit breaker
 
Transformer
TransformerTransformer
Transformer
 
Partial discharge switchgear ea tech
Partial discharge switchgear ea techPartial discharge switchgear ea tech
Partial discharge switchgear ea tech
 
Tansformer @dheeraj upadhyay
Tansformer @dheeraj upadhyayTansformer @dheeraj upadhyay
Tansformer @dheeraj upadhyay
 
HV testing of insulator
HV testing of insulatorHV testing of insulator
HV testing of insulator
 
open circuit and short circuit test on transformer
open circuit and short circuit test on transformeropen circuit and short circuit test on transformer
open circuit and short circuit test on transformer
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
 
Partial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA TechnologyPartial Discharge Detection Products by EA Technology
Partial Discharge Detection Products by EA Technology
 
final yr project-1
final yr project-1final yr project-1
final yr project-1
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 
Impulse test for power transformers
Impulse test for power transformersImpulse test for power transformers
Impulse test for power transformers
 
Why dehydration of transformer oil is important?
Why dehydration of transformer oil is important?Why dehydration of transformer oil is important?
Why dehydration of transformer oil is important?
 
Grid Voltage Regulation
Grid Voltage RegulationGrid Voltage Regulation
Grid Voltage Regulation
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGE
 
Transformer(Class 12 Investigatory Project)
Transformer(Class 12 Investigatory Project)Transformer(Class 12 Investigatory Project)
Transformer(Class 12 Investigatory Project)
 

Similar to HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH

TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
ChristinaBoyd12
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
santubanga333
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
ssuser1f60f6
 
Chapter 5 mukesh gurjar
Chapter 5 mukesh gurjarChapter 5 mukesh gurjar
Chapter 5 mukesh gurjar
Mukesh gurjar
 
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptxET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ChristianAceSolidum1
 
tcee-161003100321.pptx
tcee-161003100321.pptxtcee-161003100321.pptx
tcee-161003100321.pptx
Satish Pydimarla
 
Transformers pptxx.ppt
Transformers pptxx.pptTransformers pptxx.ppt
Transformers pptxx.ppt
jaajasnjkja
 
Unit 1-2-b
Unit 1-2-bUnit 1-2-b
Unit 1-2-b
srichakra kripa
 
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuitsModule 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Asha Anu Kurian
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier ppt
vikas kumar
 
High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Pune
bizproto26
 
switchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptxswitchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptx
DrNiveditaSingh3
 
Frequency response analysis (FRA) of transformer
Frequency response analysis (FRA) of transformerFrequency response analysis (FRA) of transformer
Frequency response analysis (FRA) of transformer
Raveendranath Macherla
 
Transformer cont
Transformer contTransformer cont
Transformer cont
MuhammadJunaidAwan5
 
ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
hiiarindam
 
Mod5part1
Mod5part1Mod5part1
Mod5part1
Asha Anu Kurian
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
Nadir Baloch
 
Surge diverter
Surge diverterSurge diverter
Surge diverter
sarunkutti
 
Lightning impulse test in precise
Lightning impulse test in  preciseLightning impulse test in  precise
Lightning impulse test in precise
Muthar Hussain
 

Similar to HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH (20)

TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
Chapter 5 mukesh gurjar
Chapter 5 mukesh gurjarChapter 5 mukesh gurjar
Chapter 5 mukesh gurjar
 
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptxET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptx
 
tcee-161003100321.pptx
tcee-161003100321.pptxtcee-161003100321.pptx
tcee-161003100321.pptx
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
Transformers pptxx.ppt
Transformers pptxx.pptTransformers pptxx.ppt
Transformers pptxx.ppt
 
Unit 1-2-b
Unit 1-2-bUnit 1-2-b
Unit 1-2-b
 
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuitsModule 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
Module 2 ee369 KTU syllabus-high voltage ac generation,resonant circuits
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier ppt
 
High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Pune
 
switchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptxswitchgearpresentation-151030171028-lva1-app6892.pptx
switchgearpresentation-151030171028-lva1-app6892.pptx
 
Frequency response analysis (FRA) of transformer
Frequency response analysis (FRA) of transformerFrequency response analysis (FRA) of transformer
Frequency response analysis (FRA) of transformer
 
Transformer cont
Transformer contTransformer cont
Transformer cont
 
ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
 
Mod5part1
Mod5part1Mod5part1
Mod5part1
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Surge diverter
Surge diverterSurge diverter
Surge diverter
 
Lightning impulse test in precise
Lightning impulse test in  preciseLightning impulse test in  precise
Lightning impulse test in precise
 

HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH

  • 1. Seminar guide Seminar coordinator Ms. Aanchal Baranwal Mr. Alok pandey (Assistant professor) (Assistant professor) Department of Electrical Department of Electrical Engineering Engineering A Seminar on High voltage testing of Electrical Transformer PRESENTED BY Hari Shankar Singh:-1308220902
  • 2. CONTENTS  Introduction of transformer and HV transformer  Types of testing of transformer and explain with detail  Advantages of HV testing of transformer  Disadvantages of HV testing of transformer  Conclusion  References
  • 3. What is Transformer ? • Transformer is an electrostatic device which transfer electrical energy one circuit to another circuit by magnetic flux without change of frequency . Transformer has based on principle of electromagnetic induction(EMI). • Formula used as measured a value, Vs / V p = Ns / N p = I p / Is
  • 4. HIGH VOLTAGE TRANSFORMER • High voltage transformers convert voltages from one level or phase configuration to another, usually from higher to lower. • They can include features for electrical isolation, power distribution, and control and instrumentation applications. • High voltage transformers usually depend on the principle of magnetic induction between coils to convert voltage and current levels .
  • 5. TYPES OF HV TESTING OF ELECTRICAL TRANSFORMER 1. Partial discharge test 2. Impulse transformer test 3. Transformer turns ratio test 4. Insulation resistance test 5. Routine test 6. Temperature rise of oil testing of transformer
  • 6. PARTIAL DISCHARGE TEST • Partial discharge is a small localised dielectric breakdown of an electrical insulation system under high voltage stress. • Each discrete partial discharge is the result of an electrical breakdown of an air pocket within the insulation. • These discharges erode insulation and eventually result in insulation failure.
  • 7. • Acoustic techniques are used by manufacturers to locate discharges that occur during HV testing factory. • PD occurs if the electric field strength applied to a dielectric exceeds the dielectric withstand strength of an insulation system locally. • This may be caused by either increased field strengths , e.g. due to design problems, sharp edges on electrodes, small clearances , ageing , manufacture defect , insulation failure , damage etc.
  • 9. CAUSES OF FAILURE IN PDT Fig.2
  • 11. FUTURE APPLIANCES FROM PDT • Cables and Power transformers and bushings. • Switchgear. • Motors and generators • Conclusion PDT testing prevents failure, 1. Off-line testing is a critical pre-commissioning check. 2. On- line testing is an extremely powerful non- instructive condition monitoring tool.
  • 12. IMPULSE TRANSFORMER TEST • This test is made to prove that the transformer insulation will withstand voltage surges which may be caused by lightning or switching. • This includes insulation to ground, insulation between turns and windings, and the flashover value of the associated bushings. • A high-voltage wave of standard values, and approximating a lightning surge, is imposed on the unit to be tested.
  • 13. • By a lightning pulse method used as measured for impulse transformer testing followed as full wave, half wave and front of wave show in Fig.4. Fig.4:- Graph between ultra frequency and time
  • 14. CONNECTION DIAGRAM OF IMPULSE TRANSFORMER TEST Fig.5:-Connection of Impulse transformer test
  • 15. TRANSFORMER TURN’S RATIO TEST • The Transformer Turns Ratio test is used to make sure that the Turns Ratio between the winding of the transformer is correct. • With this information, you can decide what the output voltage of the transformer will be. The ratio is calculated under no-load conditions using formula given below, V pri /V sec = Z pri/ Z sec = (N pri /N sec )2
  • 16. INSULATION RESISTANCE TEST (IR VALUE TEST) • Insulation ages and deteriorates because of moisture, dust and electrostatic stress. Insulation should be monitored continually to avoid sudden failure of the equipment. • An insulation resistance test detects insulation quality within the transformer. • The conductive impurities or mechanical flows in the dielectric can be analysis based on this test.
  • 17. CONNECTION OF IR VALUE TESTING DIAGRAM Fig.6:- IR Value testing connection diagram
  • 18. • Normally, MEGGERS have a test voltage of 500V , 2500V , or 5000V . • IR between HV and LV as well as windings to earth. • Minimum IR value for Tap changer is 1000 ohm per volt service voltage
  • 19. FACTORS AFFECTING ON IR VALUE OF TRANSFORMER • The IR value of transformers are influenced by Surface condition of the terminal bushing. • Quality of oil. • Quality of winding insulation. • Temperature of oil. • Duration of application and value of test voltage.
  • 20. IR VALUE TESTING FORMULAS • 1 Phase Transformer IR Value (MΩ) = C X E / (√KVA) • 3 Phase Transformer (Star) IR Value (MΩ) = C X E (P-n) / (√KVA) • 3 Phase Transformer(Delta) IR Value (MΩ) = C X E (P-P) / (√KVA) Where C= 1.5 for Oil filled T/C with Oil Tank, 30 for Oil filled T/C without Oil Tank or Dry Type T/C.
  • 21. ROUTINE TEST FOR TRANSFORMER A Routine test of transformer is mainly for confirming operational performance of individual unit in a production lot. Routine tests are carried out on every unit manufactured. All transformers are subjected to the following Routine tests: • Insulation resistance Test. • Winding resistance Test. • Turns Ratio / Voltage ratio Test
  • 22. • Polarity / Vector group Test • Open circuit and short circuit Test. • Continuity Test. • High Voltage Test. • Partial discharge Test. • Separate source AC voltage. • Induced overvoltage. • Lightning impulse Tests. • On -load tap changers Test.
  • 23. TEMPERATURE OIL TESTING OF TRANSFORMER • Temperature rise test of oil of Transformer is included in type test of transformer. • In this test we check whether the temperature rising limit of transformer winding and oil as per specification or not. • Faults detects at above 75˚C by the help of Buchholz relay and work as ALARM and TRIP circuit.
  • 24. BUCHHOLZ RELAY, EXPAIL BY THE THIS VIDEO
  • 25. ADVANTAGES OF HV TESTING TRANSFORMER • Pure conductivity by IR Value test. • Controlling of HV surges by Impulse test. • Removing of discrete waveform by the help of Partial Discharge test. • Terminals has used connected correctly by Transformer Turn’s Ratio test. • Units measured a correctly and manufacturing defect check by Routine test.
  • 26. DISADVANTAGES OF HV TESTING OF TRANSFORMER • After failure, transformer is removed and replaced with new/repaired one without removing the cause of failure which results in immediate or short time failure. • Insufficient Oil level. • Faulty operation of tap changer switch. • Lack of installation checks. • Prolonged Over loading.
  • 27. CONCLUSION • Knowledge of the construction of high voltage test transformers, their design and use in high voltage testing system gives the solution of the most adjustment transformer in respect of parameters and prices. • HV testing are main advantages of safety , higher efficiency , lower cost ,savings of energy , avoiding of failures ,trouble shooting for failure detection , accurate detection , quality assurance.
  • 28. REFERENCES • R.S. Jha, “High Voltage Engineering”, Dhanpat Rai & Sons, Second Edition in 1996. • C. L. Wadhwa, “High Voltage Engineering”, Wiley Eastern Ltd. Third Edition in 2012. • E.Kuffel and W.S. Zaengl, “High Voltage Engineering” , Pergamon Press, First Edition in1984.
  • 29.