PROTECTION OF POWER SYSTEMPREPARED BY                       TRAINEE ENGINEER MUDDASIR MASOOD
WHAT DOES PROTECTION MEANSEVERY THING IN THIS WORLD NEEDS PROTECTION AGAINST THREATS SO DOES ELECTRICAL EQUIPMENTSINTERNAL THREATSEXTERNAL THREATSDAMAGEDPOWER SYSTEMCRITICAL ELECTRICAL EQUIPMENT
TYPES OF ELECTRICAL THREATS/FAULTSPHASE TO PHASE SHORT CIRCUITPHASE TO GROUND FAULTSHUNT FAULTSSERIES FAULTOPEN CIRCUIT
TASK OF THE PROTECTION SYSTEMPROTECT THE ELECTRICAL EQUIPMENT AGAINST UNESISSARY DAMAGEPROTECT THE PERSONAL IN THE VICINITYOF THE ELECTRICAL FAULTENABLE CONTINUED SERVICE IN THE UNTROUBLED AREA OF THE NETWORK
PHILOSPHY OF THE PROTECTION SYSTEMABNORMAL BUT SECURE OPERATIONNORMAL NETWORK OPERATIONFAULT CONDITIONABNORMAL NETWORK OPERATION
REQUIREMENT OF THE PROTECTION SYSTEMSPEEDYSELECTIVITYSENSITIVITYRELIABILITYSIMPLICITY
PROTECTION SCHEME FOR THE POWER SYSTEMPROTECTION SYSTEM IS DIVIDED INTO ZONESPROTECTION ZONES ARE DECIDED BY THE LOCATION OF CTPRIMARY PROTECTIONBACKUP PROTECTIONEARTH FAULT PROTECTIONDIFFERENTIAL PROTECTIONGT-1CIRCUIT BREAKERPOWER TRANSFORMERGENERATORCURRENT TRANSFORMER132KV BUSBAR
TYPICAL PROTECTION SCHEMETRIP COIL-1	TRIPPING MECHANISMTRIP COIL-2DC SUPPLYTRIP CIRCUITPROTECTION RELAY-1DC SUPPLYTRIPING MATRIXPROTECTION RELAY-2
BREAKER FAILURE SCHEMEINTEGRATED POWER SYSTEMGPROTECTIVE RELAYTRIP ALL PARALLEL CBMBREAKER FAILURETIME DELAY
TYPE OF EARTHING SYSTEMLITTLE FAULT CURRENTEXTREME OVERVOLTAGEUNEARTHED NEUTRALLARGE FAULT CURRENTNO OVERVOLTAGEDIRECTLY EARTHEDLESS FAULT CURRENTLESS OVERVOLTAGEINDUCTOR/ TRANSFORMER GROUNDING
GENERATOR PROTECTIONVOLTAGE RISE PROTECTIONROTOR EARTH FAULT PROTECTIONDIFFERENTIAL PROTECTIONIMPEDENCE PROTECTIONGUNDEREXCITATION PROTECTIONREVERSE POWER PROTECTIONNEGATIVE PHASE SEQUENCE PROTECTION80% STATOR EARTH FAULTR100% STATOR EARTH FAULT
UNIT STEPUP TRANSFORMER PROTECTIONUNIT TRANSFORMER BUCHHOLZ TRIPPRESSURE RELIEF OLTC TRIPYOIL TEMPERATURE TRIPYBAT∆∆TRANSFORMER EARTH FAULT PROTECTIONWINDING TEMPERATURE TRIPGENERATORTRANSFORMER DIFFERENTIAL PROTECTIONPOWER TRANSFORMER OTHER PROTECTIONS∆GYBBTYYR
PROTECTION LOGIC ADOPTED AT BLOCK-1TWO INDEPENDANT TRIP COILSTRIP SUPERVISORY CKT220 OR 24 VOLTPOWER SUPPLYTRIPPING MATRIX+24PROTECTION RELAYTRIP CIRCUITTRIP RELAYOPENING MECHANISM OF CBTRIP CIRCUIT SUPERVISIONTRIP ANNUNCIATIONTRIP COMMAND REGISTER
TRIPPING MATRIXOVERCURRENT TIME PROTECTION EXCT. TRAFOUNDER EXCITATION PROTECTION WITH 2 STEPUNIT AUXILIARY  TRANSFORMER DIFFERENTIAL PROTECTIONLOSS OF EXCITATION PROTECTIONUNIT TRANSFORMER BUCHOLZ OVERTEMP.100% EARTH FAULT PROTECTIONUNDEREXCITATION PROTECTIONUNBALANCED LOAD PROTECTIONREVERSE POWER PROTECTION WITH TIME DELAYEXCITATION TRANSFORMER BUCHOLZ TRIPFREQUENCY DROP PROTECTIONSS TRANSFORMER BUCHOLZ OVERTEMP.OVERFLUXING PROTECTIONIMPEDENCE PROTECTION T1 IMPEDENCE PROTECTION TE UNIT TRANSFORMER DIFFERENTIAL PROTECTIONTRANSFORMER EARTH FAULT PROTECTIONSS TRAFO OVERCURRENTTIME PROTECTIONROTOR EARTH FAULT PROTECTION80% EARTH FAULT PROTECTIONFREQUENCY RISEGENERATORDIFFERENTIALPROTECTIONSFC EARTH FAULTREVERSE POWER PROTECTIONVOLTAGE RISE PROTECTIONSFC FAILURESYNC BREAKER-1SYNC BREAKER-2ST SERVICE SUPPLY BREAKEREMERGENCY TRIPDE-EXCITATIONSFC BREAKEREXCIT. BREAKERUNIT AUXILIARY CHANGEOVERLOCAL INDICATIONREMOTE SIGNALRESET
POWER SUPPLY CIRCUIT BREAKERTRIP COILSL+220VL-
GENERATOR DIFFERENTIAL PROTECTION 7TD43GIS=I1=I2IA=0NO TRIPPING I1 RACTIFIERIA TRIPPING TRANSFORMERRACTIFIERIS I2 STABILIZING TRANSFORMERTMSYNCH BREAKER-1DE-EXCITATION BREAKERSFC BREAKERUNIT AUX CHANGOVERST SERVICE SUPPLY BREAKEREMERGENCY TRIPSYNCH BREAKER-2
GENERATOR DIFFERENTIAL PROTECTIONPROTECTION AGAINST PHASE TO PHASE FAULTPROTECTION AGAINST PHASE TO EARTH FAULTPROTECTION ZONE DEFINED BY THE LOCATION OF CTSINSENSITIVE TO INTERTURN FAULTSINOPERATIVE TO EXTERNAL FAULTSEARTH FAULT SENSITIVITY DEPEND UPON GROUNDING SYSTEM
GENERATOR DIFFERENTIAL PROTECTIONBLOCKUs/UnTRIPUa/UnPICKUP CHARACTERISTIC FOR THE SINGLE INFEED FAULT
100% EARTH FAULT PROTECTION 7ue21 20 HZ FREQUENCY GENERATORCTSYNCH BREAKERTRIP MATRIXDE-EXCITATIONRACTIFIERSERVICE STATIONTRIPEMERGENCY TRIPMEASURING CURRENT Im COMPARATORCOMPENSATING CURRENTIc SFCLIMIT VALUE SETTERAUXILLARY CHANGEOVERIC>Im TIMMERTRIP SIGNAL
100% EARTH FAULT PROTECTIONEARTH FAUTL DUE TO INSULATION DAMAGESHORT CIRCUIT DUE TO THE PHASE WITH THE CORE EARTH FAULT PROTECTIONHIGHLY SENSITIVEDETECTION OF THE EARTH FAULT AT ANY LOCATION
80% EARTH FAULT PROTECTIONVOLTAGE INPUT MODULE 7TM36VOLTAGE TRIGGER MODULE 7TU12PICKUPTIMMER 7TT10TRIP
ROTOR EARTH FAULT PROTECTION 7UR20UNGROUNDED FIELD WINDINGSINGLE EARTH FAULT CAUSE LITTLE CURRENTDOUBLE EARTH FAULT/ MAGNETIC UNBALANCEHIGH CURRENT AT THE FAULT LOCATIONELECTRICAL STRESS INCREASESEXCITATION SYSTEMIE 
ROTOR EARTH FAULT CONT.DETECT BEFORE IT EFFECTSCOUPLING RESISTER RvSET VALUEReRcLOW PASS FILTERWAIT FOR THE STEADY STATELIMIT VALUE GENERATORSQUARE WAVERmUM ALARM<80KΩTRIPPING<5KΩSYNCH BREAKER-1 AND 2DE-EXCITATION BREAKERSERVICE STATION BREAKEREMERGENCY TRIPSFCAUXILLIARY CHANGEOVERTRIPPING SIGNALTRIPPING MATRIX
UNDEREXCITATION PROTECTIONCAUSEHIGHLY CAPACITIVE LOADTOO LOW EXCITATION/FIELD CIRCUIT FAULTEFFECTROTOR OVERHEATINGASYNCHRONOUS OPERATIONSTEADY STATE STABILITY OF THE GENERATOR
UNDER-EXCITATION PROTECTION
UNDER-EXCITATION PROTECTIONCURRENT INPUT 7TM16TRANSDUCER 7TL41T3ANGLE TRIGGER(A)TRIPT2TRIPANGLE TRIGGER (C)VOLTAGE INPUT 7TM36AC VOLTAGE MONITOR 7TU127TU14 EXCITER VOLTAGE MONITORT1TRIPANGLE TRIGGER (B)SYNCH BREAKER-1SYNCH BREAKER-2DE-EXCITATIONEMERGENCY TRIPSERIVCE STATIONAUXILLIARY CHANGEOVER
NEGATIVE PHASE SEQUENCE PROTECTIONCAUSEaZERO SEQUENCEbcUNEVEN LOADSERIES FAULTSHUNT FAULT POSITIVE SEQUENCEEFFECTROTOR OVERHEATINGROTOR DISTORTIONNEGATIVE SEQUENCEHEAVY VIBRATION
NEGATIVE PHASE SEQUENCE PROTECTIONPOWER SUPPLY 15V2-17.5%8-70%2*(0.1-6.4)CURRENT INPUT MODULE 7TM16LIMIT VALUE TRIGGER 7TP12SEQUENCE FILTER 7TF20TIMER 7TT11TRIPTHERMAL REPLICA/ INVERSE TIME CHARACTERISTICTRIPUNBALANCE LOAD MONITORINGTRIPTRIPPING MATRIXSYNCH BREAKER-1 AND 2
REVERSE POWER PROTECTIONCAUSEFAILURE OF DRIVING TURBINEMOTORING OF GENERATOREFFFECTCOMPRESSOR LOADSYSTEM OVERLOADEDSTEAM TURBINE BLADE OVERHEATING
REVERSE POWER PROTECTION/ DIRECTIONAL POWER RELAYCURRENT INPUT MODULE 7TM17VOLTAGE INPUT MODULE 7TM37POWER TRIGGER 7TM28TRIPCOUPLING MODULE 7TR20TIMER 7TT11TRIPTRIPPING MATRIXSYNCH BREAKER 1-2TRIP T1SERVICE STATION BREAKERDE-EXCITATIONTRIP WITH LONG TIMEUNIT AUXILLIARY CHANGEOVER
Frequency protectionCAUSEOVER LOAD SYSTEM (UNDER FREQUENCY)LOAD SHEDDING (OVER FREQUENCY)FAULTY FREQUENCY RAGULATOREFFECTGENERATOR/TRANSFORMER OVERHEATING
BUSBAR PROTECTION SCHEMEIT IS IMPORTANT AT FIRST TO HAVE A KNOW HOW OF BUSBAR ARRANGMENT
BUSBAR PROTECTIONHERE ARE SOME OF THE PROTECTION ADOPTED AT OUR SWITCHYARDTIME OVERCURRENT AND EARTH FAULT PROTECTION (IKT943)STATIC BUSBAR PROTECTION (INX5)STATIC DISTANCE RELAY (LZ92)FOR THE PROTECTION OF STEPUP TRANSFORMER, STARTUP TRANSFORMER AND AUTO TRANSFORMERELECTROMECHANICAL DISTANCE RELAY (LH1)OVERCURRENT/UNDERVOLTAGE (IUX159)DIRECTIONAL EARTH FAULT (RE91-10)
PROTECTION LAYOUT OF THE FEEDERSIDEFEEDERDISTANCE PROTECTION(LZ92)DISTANCE RELAY(LH1)BUSBAR PROTECTION(INX5)DIRECTIONAL EARTH FAULT(RE91-10)MEASUREMENTOVERCURRENT/UNDERVOLTAGE(IUX159)BUSBAR BBUSBAR A
DISTANCE PROTECTION(LZ92)CAUSEOVERHEAD LINES SERIES/SHUNT FAULTEXTERNAL THREAT TO THE POWER UNITEFFECTSUSEPTEBLE TO HIGH SHORT CIRCUIT CURRENTOUT OF STABILITYIMPLEMENTATIONMEASURE THE IMPEDENCE OF THE FEEDING ENDZONE DEFINED
TRANSMISSION LINELINE IMPEDENCELOADDISTANCE RELAY(Zl)GSOURCE IMPEDENCE ZsFAULT IMPEDENCE ZfUrefSELECTION CIRCUITCONSTANT TIME CURVEVTRIPANDRESISTANCEUfIREACTANCEIfI>/Z<TIMER
LINE CB TRIP COIL 1-2AUTO RECLOSUREDISTANCE RELAY F11TRIP SUPERVISION 1-2CONSTANT CURRENT CHARACTERISTIC
THE ENDGOD BLESS U ALL

Power System Protection

  • 1.
    PROTECTION OF POWERSYSTEMPREPARED BY TRAINEE ENGINEER MUDDASIR MASOOD
  • 2.
    WHAT DOES PROTECTIONMEANSEVERY THING IN THIS WORLD NEEDS PROTECTION AGAINST THREATS SO DOES ELECTRICAL EQUIPMENTSINTERNAL THREATSEXTERNAL THREATSDAMAGEDPOWER SYSTEMCRITICAL ELECTRICAL EQUIPMENT
  • 3.
    TYPES OF ELECTRICALTHREATS/FAULTSPHASE TO PHASE SHORT CIRCUITPHASE TO GROUND FAULTSHUNT FAULTSSERIES FAULTOPEN CIRCUIT
  • 4.
    TASK OF THEPROTECTION SYSTEMPROTECT THE ELECTRICAL EQUIPMENT AGAINST UNESISSARY DAMAGEPROTECT THE PERSONAL IN THE VICINITYOF THE ELECTRICAL FAULTENABLE CONTINUED SERVICE IN THE UNTROUBLED AREA OF THE NETWORK
  • 5.
    PHILOSPHY OF THEPROTECTION SYSTEMABNORMAL BUT SECURE OPERATIONNORMAL NETWORK OPERATIONFAULT CONDITIONABNORMAL NETWORK OPERATION
  • 6.
    REQUIREMENT OF THEPROTECTION SYSTEMSPEEDYSELECTIVITYSENSITIVITYRELIABILITYSIMPLICITY
  • 7.
    PROTECTION SCHEME FORTHE POWER SYSTEMPROTECTION SYSTEM IS DIVIDED INTO ZONESPROTECTION ZONES ARE DECIDED BY THE LOCATION OF CTPRIMARY PROTECTIONBACKUP PROTECTIONEARTH FAULT PROTECTIONDIFFERENTIAL PROTECTIONGT-1CIRCUIT BREAKERPOWER TRANSFORMERGENERATORCURRENT TRANSFORMER132KV BUSBAR
  • 8.
    TYPICAL PROTECTION SCHEMETRIPCOIL-1 TRIPPING MECHANISMTRIP COIL-2DC SUPPLYTRIP CIRCUITPROTECTION RELAY-1DC SUPPLYTRIPING MATRIXPROTECTION RELAY-2
  • 9.
    BREAKER FAILURE SCHEMEINTEGRATEDPOWER SYSTEMGPROTECTIVE RELAYTRIP ALL PARALLEL CBMBREAKER FAILURETIME DELAY
  • 10.
    TYPE OF EARTHINGSYSTEMLITTLE FAULT CURRENTEXTREME OVERVOLTAGEUNEARTHED NEUTRALLARGE FAULT CURRENTNO OVERVOLTAGEDIRECTLY EARTHEDLESS FAULT CURRENTLESS OVERVOLTAGEINDUCTOR/ TRANSFORMER GROUNDING
  • 11.
    GENERATOR PROTECTIONVOLTAGE RISEPROTECTIONROTOR EARTH FAULT PROTECTIONDIFFERENTIAL PROTECTIONIMPEDENCE PROTECTIONGUNDEREXCITATION PROTECTIONREVERSE POWER PROTECTIONNEGATIVE PHASE SEQUENCE PROTECTION80% STATOR EARTH FAULTR100% STATOR EARTH FAULT
  • 12.
    UNIT STEPUP TRANSFORMERPROTECTIONUNIT TRANSFORMER BUCHHOLZ TRIPPRESSURE RELIEF OLTC TRIPYOIL TEMPERATURE TRIPYBAT∆∆TRANSFORMER EARTH FAULT PROTECTIONWINDING TEMPERATURE TRIPGENERATORTRANSFORMER DIFFERENTIAL PROTECTIONPOWER TRANSFORMER OTHER PROTECTIONS∆GYBBTYYR
  • 13.
    PROTECTION LOGIC ADOPTEDAT BLOCK-1TWO INDEPENDANT TRIP COILSTRIP SUPERVISORY CKT220 OR 24 VOLTPOWER SUPPLYTRIPPING MATRIX+24PROTECTION RELAYTRIP CIRCUITTRIP RELAYOPENING MECHANISM OF CBTRIP CIRCUIT SUPERVISIONTRIP ANNUNCIATIONTRIP COMMAND REGISTER
  • 14.
    TRIPPING MATRIXOVERCURRENT TIMEPROTECTION EXCT. TRAFOUNDER EXCITATION PROTECTION WITH 2 STEPUNIT AUXILIARY TRANSFORMER DIFFERENTIAL PROTECTIONLOSS OF EXCITATION PROTECTIONUNIT TRANSFORMER BUCHOLZ OVERTEMP.100% EARTH FAULT PROTECTIONUNDEREXCITATION PROTECTIONUNBALANCED LOAD PROTECTIONREVERSE POWER PROTECTION WITH TIME DELAYEXCITATION TRANSFORMER BUCHOLZ TRIPFREQUENCY DROP PROTECTIONSS TRANSFORMER BUCHOLZ OVERTEMP.OVERFLUXING PROTECTIONIMPEDENCE PROTECTION T1 IMPEDENCE PROTECTION TE UNIT TRANSFORMER DIFFERENTIAL PROTECTIONTRANSFORMER EARTH FAULT PROTECTIONSS TRAFO OVERCURRENTTIME PROTECTIONROTOR EARTH FAULT PROTECTION80% EARTH FAULT PROTECTIONFREQUENCY RISEGENERATORDIFFERENTIALPROTECTIONSFC EARTH FAULTREVERSE POWER PROTECTIONVOLTAGE RISE PROTECTIONSFC FAILURESYNC BREAKER-1SYNC BREAKER-2ST SERVICE SUPPLY BREAKEREMERGENCY TRIPDE-EXCITATIONSFC BREAKEREXCIT. BREAKERUNIT AUXILIARY CHANGEOVERLOCAL INDICATIONREMOTE SIGNALRESET
  • 15.
    POWER SUPPLY CIRCUITBREAKERTRIP COILSL+220VL-
  • 16.
    GENERATOR DIFFERENTIAL PROTECTION7TD43GIS=I1=I2IA=0NO TRIPPING I1 RACTIFIERIA TRIPPING TRANSFORMERRACTIFIERIS I2 STABILIZING TRANSFORMERTMSYNCH BREAKER-1DE-EXCITATION BREAKERSFC BREAKERUNIT AUX CHANGOVERST SERVICE SUPPLY BREAKEREMERGENCY TRIPSYNCH BREAKER-2
  • 17.
    GENERATOR DIFFERENTIAL PROTECTIONPROTECTIONAGAINST PHASE TO PHASE FAULTPROTECTION AGAINST PHASE TO EARTH FAULTPROTECTION ZONE DEFINED BY THE LOCATION OF CTSINSENSITIVE TO INTERTURN FAULTSINOPERATIVE TO EXTERNAL FAULTSEARTH FAULT SENSITIVITY DEPEND UPON GROUNDING SYSTEM
  • 18.
    GENERATOR DIFFERENTIAL PROTECTIONBLOCKUs/UnTRIPUa/UnPICKUPCHARACTERISTIC FOR THE SINGLE INFEED FAULT
  • 19.
    100% EARTH FAULTPROTECTION 7ue21 20 HZ FREQUENCY GENERATORCTSYNCH BREAKERTRIP MATRIXDE-EXCITATIONRACTIFIERSERVICE STATIONTRIPEMERGENCY TRIPMEASURING CURRENT Im COMPARATORCOMPENSATING CURRENTIc SFCLIMIT VALUE SETTERAUXILLARY CHANGEOVERIC>Im TIMMERTRIP SIGNAL
  • 20.
    100% EARTH FAULTPROTECTIONEARTH FAUTL DUE TO INSULATION DAMAGESHORT CIRCUIT DUE TO THE PHASE WITH THE CORE EARTH FAULT PROTECTIONHIGHLY SENSITIVEDETECTION OF THE EARTH FAULT AT ANY LOCATION
  • 21.
    80% EARTH FAULTPROTECTIONVOLTAGE INPUT MODULE 7TM36VOLTAGE TRIGGER MODULE 7TU12PICKUPTIMMER 7TT10TRIP
  • 22.
    ROTOR EARTH FAULTPROTECTION 7UR20UNGROUNDED FIELD WINDINGSINGLE EARTH FAULT CAUSE LITTLE CURRENTDOUBLE EARTH FAULT/ MAGNETIC UNBALANCEHIGH CURRENT AT THE FAULT LOCATIONELECTRICAL STRESS INCREASESEXCITATION SYSTEMIE 
  • 23.
    ROTOR EARTH FAULTCONT.DETECT BEFORE IT EFFECTSCOUPLING RESISTER RvSET VALUEReRcLOW PASS FILTERWAIT FOR THE STEADY STATELIMIT VALUE GENERATORSQUARE WAVERmUM ALARM<80KΩTRIPPING<5KΩSYNCH BREAKER-1 AND 2DE-EXCITATION BREAKERSERVICE STATION BREAKEREMERGENCY TRIPSFCAUXILLIARY CHANGEOVERTRIPPING SIGNALTRIPPING MATRIX
  • 24.
    UNDEREXCITATION PROTECTIONCAUSEHIGHLY CAPACITIVELOADTOO LOW EXCITATION/FIELD CIRCUIT FAULTEFFECTROTOR OVERHEATINGASYNCHRONOUS OPERATIONSTEADY STATE STABILITY OF THE GENERATOR
  • 25.
  • 26.
    UNDER-EXCITATION PROTECTIONCURRENT INPUT7TM16TRANSDUCER 7TL41T3ANGLE TRIGGER(A)TRIPT2TRIPANGLE TRIGGER (C)VOLTAGE INPUT 7TM36AC VOLTAGE MONITOR 7TU127TU14 EXCITER VOLTAGE MONITORT1TRIPANGLE TRIGGER (B)SYNCH BREAKER-1SYNCH BREAKER-2DE-EXCITATIONEMERGENCY TRIPSERIVCE STATIONAUXILLIARY CHANGEOVER
  • 27.
    NEGATIVE PHASE SEQUENCEPROTECTIONCAUSEaZERO SEQUENCEbcUNEVEN LOADSERIES FAULTSHUNT FAULT POSITIVE SEQUENCEEFFECTROTOR OVERHEATINGROTOR DISTORTIONNEGATIVE SEQUENCEHEAVY VIBRATION
  • 28.
    NEGATIVE PHASE SEQUENCEPROTECTIONPOWER SUPPLY 15V2-17.5%8-70%2*(0.1-6.4)CURRENT INPUT MODULE 7TM16LIMIT VALUE TRIGGER 7TP12SEQUENCE FILTER 7TF20TIMER 7TT11TRIPTHERMAL REPLICA/ INVERSE TIME CHARACTERISTICTRIPUNBALANCE LOAD MONITORINGTRIPTRIPPING MATRIXSYNCH BREAKER-1 AND 2
  • 29.
    REVERSE POWER PROTECTIONCAUSEFAILUREOF DRIVING TURBINEMOTORING OF GENERATOREFFFECTCOMPRESSOR LOADSYSTEM OVERLOADEDSTEAM TURBINE BLADE OVERHEATING
  • 30.
    REVERSE POWER PROTECTION/DIRECTIONAL POWER RELAYCURRENT INPUT MODULE 7TM17VOLTAGE INPUT MODULE 7TM37POWER TRIGGER 7TM28TRIPCOUPLING MODULE 7TR20TIMER 7TT11TRIPTRIPPING MATRIXSYNCH BREAKER 1-2TRIP T1SERVICE STATION BREAKERDE-EXCITATIONTRIP WITH LONG TIMEUNIT AUXILLIARY CHANGEOVER
  • 31.
    Frequency protectionCAUSEOVER LOADSYSTEM (UNDER FREQUENCY)LOAD SHEDDING (OVER FREQUENCY)FAULTY FREQUENCY RAGULATOREFFECTGENERATOR/TRANSFORMER OVERHEATING
  • 32.
    BUSBAR PROTECTION SCHEMEITIS IMPORTANT AT FIRST TO HAVE A KNOW HOW OF BUSBAR ARRANGMENT
  • 33.
    BUSBAR PROTECTIONHERE ARESOME OF THE PROTECTION ADOPTED AT OUR SWITCHYARDTIME OVERCURRENT AND EARTH FAULT PROTECTION (IKT943)STATIC BUSBAR PROTECTION (INX5)STATIC DISTANCE RELAY (LZ92)FOR THE PROTECTION OF STEPUP TRANSFORMER, STARTUP TRANSFORMER AND AUTO TRANSFORMERELECTROMECHANICAL DISTANCE RELAY (LH1)OVERCURRENT/UNDERVOLTAGE (IUX159)DIRECTIONAL EARTH FAULT (RE91-10)
  • 34.
    PROTECTION LAYOUT OFTHE FEEDERSIDEFEEDERDISTANCE PROTECTION(LZ92)DISTANCE RELAY(LH1)BUSBAR PROTECTION(INX5)DIRECTIONAL EARTH FAULT(RE91-10)MEASUREMENTOVERCURRENT/UNDERVOLTAGE(IUX159)BUSBAR BBUSBAR A
  • 35.
    DISTANCE PROTECTION(LZ92)CAUSEOVERHEAD LINESSERIES/SHUNT FAULTEXTERNAL THREAT TO THE POWER UNITEFFECTSUSEPTEBLE TO HIGH SHORT CIRCUIT CURRENTOUT OF STABILITYIMPLEMENTATIONMEASURE THE IMPEDENCE OF THE FEEDING ENDZONE DEFINED
  • 36.
    TRANSMISSION LINELINE IMPEDENCELOADDISTANCERELAY(Zl)GSOURCE IMPEDENCE ZsFAULT IMPEDENCE ZfUrefSELECTION CIRCUITCONSTANT TIME CURVEVTRIPANDRESISTANCEUfIREACTANCEIfI>/Z<TIMER
  • 37.
    LINE CB TRIPCOIL 1-2AUTO RECLOSUREDISTANCE RELAY F11TRIP SUPERVISION 1-2CONSTANT CURRENT CHARACTERISTIC
  • 38.