Introduction & Background
- Testing and Measurement Program
- Measured Ventilation Rates (PFT testing)
- Cause of Ventilation Rates
- Extension of Study Findings
- Conclusions & Recommendations
Airflow in Mid to High-rise Multi-Unit Residential BuildingsRDH Building Science
Agenda
1. Understand typical ventilation practices for multi-unit residential buildings including corridor pressurization systems.
2. Understand performance issues associated with the ventilation of high-rise multi-unit residential buildings including the impacts of stack effect, wind, and airtightness.
3. Learn about how the theory of airflow relates well to what is
measured in-service, but that the well understood theory is not always taken into account in design.
This document summarizes a study of the performance of a corridor pressurization ventilation system in a 13-story residential building in Vancouver. Measurements found significant variations in ventilation rates between suites, with most under or over-ventilated. The study found that only 8% of intended ventilation air actually reaches the suites, with significant leakage along the ventilation path. Stack effects and wind pressures were also found to influence ventilation rates and overwhelm the mechanical pressures at times. The document recommends direct ventilation of suites and improved compartmentalization of spaces to limit natural pressures and better control ventilation.
Challenges Related to Measuring and Reporting Temperature-Dependent Apparent ...RDH Building Science
In North America, the apparent thermal conductivity (and R-value) of building insulation materials is commonly reported at a mean temperature of 24°C (75°F) and practitioners typically assume thermal properties remain constant over the range of temperatures that are experienced in building applications. Researchers have long known and acknowledged the fact that the thermal properties of most building insulation materials change with temperature. There has been little more than academic reason to measure and report this effect. However, interest in temperature-dependent thermal performance has grown with the introduction of new materials, increasing concerns regarding energy performance, and the development of tools transient energy, thermal, and hygrothermal simulation software packages (e.g. Energy Plus, HEAT2, WUFI etc.) that have capacity to account for temperature-dependence. Continue reading by clicking the Download link to the left.
Presented at the 15th Canadian Conference on Building Science and Technology.
Ventilation in Multi-Family Buildings - Summer Camp 2015Lorne Ricketts
This document summarizes a case study on ventilation in a 13-story multi-family building in Vancouver, Canada. Testing found significant variations in ventilation rates between suites, with most under or over-ventilated. It also found higher CO2 levels in lower suites. The study determined the main causes were: duct and corridor leakage reducing airflow to suites by over 90%, and stack effect pressures competing with the mechanical system. The findings suggest natural pressures like stack effect can overwhelm mechanical ventilation in multi-family buildings, particularly in more extreme climates or taller buildings.
Improvements in building efficiency can significantly reduce carbon emissions and are an intrinsic component in greenhouse gas reduction targets. The Passive House concept provides a framework for high-performance building that is growing in popularity in Canada, and particularly in the Pacific Northwest. The Passive House standard requires its buildings to achieve specific performance values for heating energy use intensity, total energy use intensity, spatial temperature variation, heat recovery ventilation performance and air leakage rate. The promised co-benefits of Passive Houses include superior thermal comfort and indoor air quality.
Passive House design is not prescriptive and can incorporate many different design aspects. The wall assembly is no exception. This paper evaluates the hygrothermal performance of a deep-stud wall assembly of a Passive House in Victoria, BC, with regards to moisture durability. The concern with deep or doublestud wall assemblies is the combined effects of reduced drying with wall configurations that place moisture sensitive materials in riskier locations. Consequently, enclosure monitoring was undertaken in an occupied six-plex over the period of one year.
The enclosure monitoring sensor packages were installed in strategic locations in the wall assembly to monitor the conditions of the assembly. The assemblies were evaluated based on the results of an empirical mold risk index. The wall assembly appears to perform acceptably, with minor concerns of mold growth on the North wall. Air leakage is a significant concern for cavity insulated walls, but the airtightness requirements of Passive house minimize this risk.
Presented at the 15th Canadian Conference on Building Science and Technology.
This document summarizes a case study evaluating the energy savings from a deep energy retrofit of a multi-unit residential building in Vancouver, BC. It found that upgrading the building enclosure through exterior wall insulation, triple-glazed windows, and air sealing reduced the building's energy use intensity by 19% from 226 to 183 kWh/m2/yr, matching the 20% savings predicted by energy modeling. Measured savings included a 33% reduction in suite electricity use and a 63% drop in electric baseboard heating. Further energy and cost savings may be possible by upgrading the building's mechanical ventilation system. The study demonstrates that deep energy retrofits can significantly cut energy consumption in existing multi-unit residential buildings.
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...RDH Building Science
Control of the indoor humidity in a marine climate is a challenge, especially under operating conditions where high indoor humidity is a norm. Outdated mechanical equipment, inefficient ventilation design, and occupants’ life styles are some of the contributing factors to high indoor humidity. In this field experimental study, the moisture buffering potential of unfinished drywall in reducing daily indoor humidity peaks, coupled with various ventilation strategies are investigated. Two identical test buildings exposed to real climatic conditions in Burnaby, BC are monitored under varying ventilation rates and schemes.
The interior of the test building is clad with unfinished drywall, while the control building is covered with polyethylene, which has negligible moisture buffering. In this way, the moisture buffering potential of drywall under four test cases is isolated. Under the test cases, the indoor air quality in terms of CO2 concentration, and ventilation heat loss of the two buildings are also evaluated.
The results show that the moisture buffering potential of drywall effectively regulates indoor humidity peaks, and maintains relative humidity levels within acceptable thresholds, when coupled with adequate ventilation as recommended by ASHRAE. When coupled with time-controlled and demand-controlled ventilation schemes, the moisture buffering effect of drywall shows competing benefits.
Presented at the 15th Canadian Conference on Building Science and Technology
Conventional Roofing Assemblies: Measuring the Thermal Benefits of Light to D...RDH Building Science
Presentation Overview:
• Conventional Roofing Designs
and Current Issues
• Conventional Roofing Field
Monitoring and Research
Program
• Measured Insulation Performance
• Selecting Roofing Membrane
Color and Insulation Strategy for
Optimum Energy Efficiency
• Case Studies
Airflow in Mid to High-rise Multi-Unit Residential BuildingsRDH Building Science
Agenda
1. Understand typical ventilation practices for multi-unit residential buildings including corridor pressurization systems.
2. Understand performance issues associated with the ventilation of high-rise multi-unit residential buildings including the impacts of stack effect, wind, and airtightness.
3. Learn about how the theory of airflow relates well to what is
measured in-service, but that the well understood theory is not always taken into account in design.
This document summarizes a study of the performance of a corridor pressurization ventilation system in a 13-story residential building in Vancouver. Measurements found significant variations in ventilation rates between suites, with most under or over-ventilated. The study found that only 8% of intended ventilation air actually reaches the suites, with significant leakage along the ventilation path. Stack effects and wind pressures were also found to influence ventilation rates and overwhelm the mechanical pressures at times. The document recommends direct ventilation of suites and improved compartmentalization of spaces to limit natural pressures and better control ventilation.
Challenges Related to Measuring and Reporting Temperature-Dependent Apparent ...RDH Building Science
In North America, the apparent thermal conductivity (and R-value) of building insulation materials is commonly reported at a mean temperature of 24°C (75°F) and practitioners typically assume thermal properties remain constant over the range of temperatures that are experienced in building applications. Researchers have long known and acknowledged the fact that the thermal properties of most building insulation materials change with temperature. There has been little more than academic reason to measure and report this effect. However, interest in temperature-dependent thermal performance has grown with the introduction of new materials, increasing concerns regarding energy performance, and the development of tools transient energy, thermal, and hygrothermal simulation software packages (e.g. Energy Plus, HEAT2, WUFI etc.) that have capacity to account for temperature-dependence. Continue reading by clicking the Download link to the left.
Presented at the 15th Canadian Conference on Building Science and Technology.
Ventilation in Multi-Family Buildings - Summer Camp 2015Lorne Ricketts
This document summarizes a case study on ventilation in a 13-story multi-family building in Vancouver, Canada. Testing found significant variations in ventilation rates between suites, with most under or over-ventilated. It also found higher CO2 levels in lower suites. The study determined the main causes were: duct and corridor leakage reducing airflow to suites by over 90%, and stack effect pressures competing with the mechanical system. The findings suggest natural pressures like stack effect can overwhelm mechanical ventilation in multi-family buildings, particularly in more extreme climates or taller buildings.
Improvements in building efficiency can significantly reduce carbon emissions and are an intrinsic component in greenhouse gas reduction targets. The Passive House concept provides a framework for high-performance building that is growing in popularity in Canada, and particularly in the Pacific Northwest. The Passive House standard requires its buildings to achieve specific performance values for heating energy use intensity, total energy use intensity, spatial temperature variation, heat recovery ventilation performance and air leakage rate. The promised co-benefits of Passive Houses include superior thermal comfort and indoor air quality.
Passive House design is not prescriptive and can incorporate many different design aspects. The wall assembly is no exception. This paper evaluates the hygrothermal performance of a deep-stud wall assembly of a Passive House in Victoria, BC, with regards to moisture durability. The concern with deep or doublestud wall assemblies is the combined effects of reduced drying with wall configurations that place moisture sensitive materials in riskier locations. Consequently, enclosure monitoring was undertaken in an occupied six-plex over the period of one year.
The enclosure monitoring sensor packages were installed in strategic locations in the wall assembly to monitor the conditions of the assembly. The assemblies were evaluated based on the results of an empirical mold risk index. The wall assembly appears to perform acceptably, with minor concerns of mold growth on the North wall. Air leakage is a significant concern for cavity insulated walls, but the airtightness requirements of Passive house minimize this risk.
Presented at the 15th Canadian Conference on Building Science and Technology.
This document summarizes a case study evaluating the energy savings from a deep energy retrofit of a multi-unit residential building in Vancouver, BC. It found that upgrading the building enclosure through exterior wall insulation, triple-glazed windows, and air sealing reduced the building's energy use intensity by 19% from 226 to 183 kWh/m2/yr, matching the 20% savings predicted by energy modeling. Measured savings included a 33% reduction in suite electricity use and a 63% drop in electric baseboard heating. Further energy and cost savings may be possible by upgrading the building's mechanical ventilation system. The study demonstrates that deep energy retrofits can significantly cut energy consumption in existing multi-unit residential buildings.
Moisture Buffering and Ventilation Strategies to Control Indoor Humidity in a...RDH Building Science
Control of the indoor humidity in a marine climate is a challenge, especially under operating conditions where high indoor humidity is a norm. Outdated mechanical equipment, inefficient ventilation design, and occupants’ life styles are some of the contributing factors to high indoor humidity. In this field experimental study, the moisture buffering potential of unfinished drywall in reducing daily indoor humidity peaks, coupled with various ventilation strategies are investigated. Two identical test buildings exposed to real climatic conditions in Burnaby, BC are monitored under varying ventilation rates and schemes.
The interior of the test building is clad with unfinished drywall, while the control building is covered with polyethylene, which has negligible moisture buffering. In this way, the moisture buffering potential of drywall under four test cases is isolated. Under the test cases, the indoor air quality in terms of CO2 concentration, and ventilation heat loss of the two buildings are also evaluated.
The results show that the moisture buffering potential of drywall effectively regulates indoor humidity peaks, and maintains relative humidity levels within acceptable thresholds, when coupled with adequate ventilation as recommended by ASHRAE. When coupled with time-controlled and demand-controlled ventilation schemes, the moisture buffering effect of drywall shows competing benefits.
Presented at the 15th Canadian Conference on Building Science and Technology
Conventional Roofing Assemblies: Measuring the Thermal Benefits of Light to D...RDH Building Science
Presentation Overview:
• Conventional Roofing Designs
and Current Issues
• Conventional Roofing Field
Monitoring and Research
Program
• Measured Insulation Performance
• Selecting Roofing Membrane
Color and Insulation Strategy for
Optimum Energy Efficiency
• Case Studies
Thermal bridges in concrete construction solutions to address energy code co...RDH Building Science
This document discusses the significant thermal impact that uninsulated concrete slab edges and balconies can have on the effective R-value and energy performance of building walls. While balconies make up a small percentage of total wall area, their low R-value of around R-1 can reduce the overall wall R-value by 40-60%. This negatively impacts energy code compliance and increases heating and cooling loads. The document evaluates different solutions for insulating slab edges and balconies, such as structural cut-outs, insulation wraps, and manufactured thermal breaks. Thermal breaks in particular are shown to improve the overall wall R-value and help meet increasing energy code requirements.
This document summarizes key differences between window rating standards in North America (NFRC) and Europe (ISO, Passive House). There are differences in boundary conditions, window geometries, calculation methodologies, and treatment of sloped glazing that can lead to different U-value and SHGC ratings for the same window. Simulation results showed centre of glass U-values can vary by up to 23% depending on the standard used, and frame U-values vary by 11-16%. The differences are most pronounced for larger glazing cavities and affect optimal cavity sizes. Understanding these differences is important for high performance window selection.
NBEC 2014 - Flow Exponent Values and Implications for Air Leakage TestingRDH Building Science
- Introduction to air leakage testing
- Relationship between flow and pressure
- Case study building
- Abnormal flow exponents
- Data extrapolation to operating pressures
- Conclusions/Implications
- Further study
Current Issues with Ventilated Attics
Case Study of Repairs
Attic Roof Hut Research & Monitoring Study – Key Findings
Performance of Potential Solutions
Ongoing Research & Field Trials
State of the Art of Multi-Unit Residential Building Airtightness: Test Procedures, Performance, and Industry Involvement
Outline:
- Airtightness Test Procedures & Equipment
- Worldwide Regulatory Requirements & Targets for Airtightness
- Airtightness of Multi-Unit Residential Buildings
- Air Barrier Systems
- Industry Preparedness for Airtightness Testing
State of the Art Review of Unvented Sloped Wood-Framed Roofs in Cold ClimatesRDH Building Science
Typical residential house construction in North America has long had vented attics above living space with the insulation and air control layer at the ceiling plane of the living space. Except for documented wintertime condensation issues in cold climates, such vented attics generally perform quite well, provided that they are ventilated adequately and air leakage from the interior is prevented. However, architects and designers are moving away from empty attics by using the attic space as conditioned storage or bonus rooms, or by designing larger interior volumes with cathedral ceilings. The practical challenges of ventilating cathedralized attics and cathedral ceilings have been significant, both because of increased geometrical complexity and because of the number of penetrations typically required for services.
Spray foam has been used successfully in tens of thousands of unvented roof assemblies throughout North America but some concerns remain in the building industry that these assemblies are inferior to ventilated roof assemblies. The National Building Code of Canada, in particular, makes it difficult for designers to use unvented roof assemblies, even using designs that are approved in similar building codes in the United States and have been proven to be durable, high-performing options. Over the past decade, the authors have been directly involved with studies of both 0.5 pcf (8 kg/m3) open cell spray foam, and 2.0 pcf (32 kg/m3) closed cell spray foam in unvented roof assemblies in various climates with continuous monitoring of temperature and moisture conditions. This paper provides a literature review of research that has been conducted on wood-framed sloped unvented roof assemblies, but will focus on results from a field monitoring study of sloped unvented wood roofs in partnership with the University of Waterloo, as well as a field survey that opened roofs and removed samples from aged unvented roof assemblies.
Presented at the 15th Canadian Conference on Building Science and Technology.
Vapour Permeable Air Barriers: Real World Evaluation - What Works, What Doesn...Lorne Ricketts
As insulation and airtightness requirements increase, vapour permeable liquid and self-adhesive air barrier membrane products are rapidly gaining traction in the North American marketplace. This presentation looks at real world testing of various types of these membranes and identifies potential strengths and weakness of these types of products.
Ventilated attics are prone to moisture problems in the Coastal Pacific Northwest climate. This presentation discusses recent research investigating the causes of these issues, and presents cutting edge findings regarding potential solutions.
Overview:
- Background
- Net Zero Building Enclosure Targets & Potential Savings
- Interior and Exterior Building Enclosure Retrofit Strategies
- Hygrothermal Considerations & Risk Assessment Evaluation Methodology
- Economics of Net Zero Building Enclosure Retrofits
Presentation Outline:
- What are "Super-Insulated" buildings and what are the drivers?
- Thermal bridging- problems and solutions
- Designing of highly insulated walls - insulation placement & durability considerations
- Super-Insulated wood-frame building enclosure design guide
Achieving the Passive House criteria on a high-rise, concrete-framed building located in Vancouver, BC.
Presented at the 2017 NAPHN Conference and Expo by Eric Catania, M.Eng., BEMP, CPHD, LEED AP BD+C, PHI Accredited Passive House Certifier.
Energy Consumption in Low-Rise Wood Frame Multi-Unit Residential BuildingsRDH Building Science
A study was performed to understand the energy consumption in low-rise wood-frame multi-unit residential buildings (MURBs) and townhouse buildings in south-west British Columbia. Low-rise MURBs are an important building type as they make up a growing proportion of housing stock in cities across North
America.
Through this study, energy data was collected from electricity and gas utilities for 20 low-rise buildings (four storeys and less) and three townhouse complexes. This data was calendarized and weather normalized to determine average annual and monthly energy consumption for analysis and comparison. Two buildings were chosen from the data set for detailed analysis, one low-rise (four-storey) and one townhouse complex. The buildings were selected based on characteristics typical of low-rise MURBs in south-west BC. The purpose of the detailed analysis was to assess opportunities to improve the energy efficiency and reduce carbon emissions in existing low-rise MURBs using whole building energy modelling.
This paper details the energy consumption trends observed through the data analysis, and the energy modelling results of the buildings chosen for detailed study. These results are also compared to results from a similar study which evaluated the energy use in mid- to high-rise non-combustible MURBs. The work presented here will improve our understanding of energy consumption in low-rise MURBs, and characterize opportunities for energy savings in these buildings.
Presented by Elyse Henderson at the 15th Canadian Conference on Building Science and Technology
Building Enclosures of the Future - Building Tomorrow's Buildings TodayRDH Building Science
- Trends and Drivers for Improved Building Enclosures & Whole Building Energy Efficiency
- New BCBC & VBBL Building & Energy Code Updates
- Effective R-values & Insulation Behaviour
- Highly Insulated Walls – Alternate Assemblies & New Cladding Attachment Strategies
- Highly Insulated Low-Slope Roofs – Insulation Strategies & New Research into Conventional Roofs
Presentation on Building Enclosure Airtightness Testing in Washington StateRDH Building Science
This document discusses building airtightness testing that was conducted in Washington State on 31 buildings. It provides an overview of airtightness testing procedures and requirements under the 2009 and 2012 energy codes. Test results showed that while an airtightness of 0.4 cfm/ft2 is attainable, achieving it requires repetitive simple details, experienced teams, and coordination between designers, contractors and trades to minimize air leakage.
Christy Love, EIT LEED AP BD+C, is a Senior Project Engineer at RDH Building Science. This presentation was given at the 2016 Passive House Northwest Conference.
The North Park Passive House, a 6-unit strata project located in Victoria BC, was occupied in September 2015. It is the first market strata-title certified Passive House development in Canada.
While well-established elsewhere, the potential benefits of Passive House and other low energy design approaches are not as well understood in Canada, and there are limited data on the actual performance of low energy residential buildings in various Canadian climates.
To address this gap, RDH, in partnership with the Canadian Mortgage and Housing Corporation, the Homeowner Protection Office of BC Housing, and FP Innovations, is undertaking detailed quantitative and qualitative performance measurement of the North Park Passive House. The intent of this research is to develop a comprehensive case study for a Passive House project in the coastal BC climate.
Learning Objectives:
- Understand the scope of the research and what we hope to learn from it.
- Understand preliminary results about how the building is performing in terms of comfort, air quality, and energy use, via measured data collected within select suites and qualitative interviews with occupants.
- Understand and interpret preliminary results of how the building enclosure is performing.
- Learn tips and share lessons learned about undertaking this type of research.
Developing an Open Source Hourly Building Energy Modelling Software ToolRDH Building Science
Energy modelling is an important tool in the design of low energy buildings. It helps evaluate energy savings of various energy efficiency measures and can predict total building energy consumption.
Participants will:
1. Learn about approaches to identifying, quantifying, and investigating IGU performance problems and how results needed can inform the investigation tools/processes used.
2. Learn about the unique design challenges with replacing structurally glazed IGUs and how those challenges were overcome.
3. Learn how quality assurance procedures can be used to deliver innovative products that meet performance expectations.
4. Learn about how building enclosure repair implementation can be as challenging as figuring out how to repair the damaged building enclosure component.
Energy Efficient Building Enclosure Design Guidelines for Wood-Frame BuildingsRDH Building Science
The document summarizes a new guide for designing energy efficient building enclosures for wood-frame buildings. It provides an overview of the guide's contents, which include chapters on building and energy codes, moisture and thermal control strategies, recommendations for highly insulated wall and roof assemblies, and construction detailing. The guide aims to help designers meet current and upcoming energy code requirements with wood-frame construction and provides guidance on enclosure designs for different climate zones in North America.
NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...RDH Building Science
This study examined the impacts of insulation strategy and membrane colour on conventional roof performance in Canada. It monitored 9 roof sections with different colour membranes (white, grey, black) and insulation types (stone wool, polyiso, hybrid). Field monitoring found that darker membranes experienced much higher temperatures than lighter ones. Insulation type also impacted temperatures, with stone wool and hybrid strategies showing less peak heating and cooling than polyiso alone. Energy modeling further showed that lighter membranes and stone wool or hybrid insulation led to lower energy use. The study aims to continue monitoring insulation movement, moisture, and aging effects over the long term.
Presented at the BCBEC Building Smart with Safe and Durable Wall Assemblies Symposium Feb 2, 2017, by Lorne Ricketts.
Ever increasing thermal performance requirements for wood-frame walls have had a dramatic impact on how we build walls. To meet these targets, exterior insulation is becoming more and more common, and methods to support the cladding are required that are strong and rigid, yet do not create significant thermal bridging through the insulation. This presentation discusses the results of recent structural testing of various different arrangements on long fasteners through exterior insulation as a method of supporting cladding while limiting thermal bridging.
A deterioration model for establishing an optimal mix of time-based maintenance (TbM) and Condition-Based Maintenance (CbM) for the Enclosure System.
Participants will:
1. Learn the two types of asset deterioration models
2. Explore the correlations when the two deterioration models are overlaid
3. Identify six different phases in the maintenance of an asset
4. Identify further model development needs
Thermal bridges in concrete construction solutions to address energy code co...RDH Building Science
This document discusses the significant thermal impact that uninsulated concrete slab edges and balconies can have on the effective R-value and energy performance of building walls. While balconies make up a small percentage of total wall area, their low R-value of around R-1 can reduce the overall wall R-value by 40-60%. This negatively impacts energy code compliance and increases heating and cooling loads. The document evaluates different solutions for insulating slab edges and balconies, such as structural cut-outs, insulation wraps, and manufactured thermal breaks. Thermal breaks in particular are shown to improve the overall wall R-value and help meet increasing energy code requirements.
This document summarizes key differences between window rating standards in North America (NFRC) and Europe (ISO, Passive House). There are differences in boundary conditions, window geometries, calculation methodologies, and treatment of sloped glazing that can lead to different U-value and SHGC ratings for the same window. Simulation results showed centre of glass U-values can vary by up to 23% depending on the standard used, and frame U-values vary by 11-16%. The differences are most pronounced for larger glazing cavities and affect optimal cavity sizes. Understanding these differences is important for high performance window selection.
NBEC 2014 - Flow Exponent Values and Implications for Air Leakage TestingRDH Building Science
- Introduction to air leakage testing
- Relationship between flow and pressure
- Case study building
- Abnormal flow exponents
- Data extrapolation to operating pressures
- Conclusions/Implications
- Further study
Current Issues with Ventilated Attics
Case Study of Repairs
Attic Roof Hut Research & Monitoring Study – Key Findings
Performance of Potential Solutions
Ongoing Research & Field Trials
State of the Art of Multi-Unit Residential Building Airtightness: Test Procedures, Performance, and Industry Involvement
Outline:
- Airtightness Test Procedures & Equipment
- Worldwide Regulatory Requirements & Targets for Airtightness
- Airtightness of Multi-Unit Residential Buildings
- Air Barrier Systems
- Industry Preparedness for Airtightness Testing
State of the Art Review of Unvented Sloped Wood-Framed Roofs in Cold ClimatesRDH Building Science
Typical residential house construction in North America has long had vented attics above living space with the insulation and air control layer at the ceiling plane of the living space. Except for documented wintertime condensation issues in cold climates, such vented attics generally perform quite well, provided that they are ventilated adequately and air leakage from the interior is prevented. However, architects and designers are moving away from empty attics by using the attic space as conditioned storage or bonus rooms, or by designing larger interior volumes with cathedral ceilings. The practical challenges of ventilating cathedralized attics and cathedral ceilings have been significant, both because of increased geometrical complexity and because of the number of penetrations typically required for services.
Spray foam has been used successfully in tens of thousands of unvented roof assemblies throughout North America but some concerns remain in the building industry that these assemblies are inferior to ventilated roof assemblies. The National Building Code of Canada, in particular, makes it difficult for designers to use unvented roof assemblies, even using designs that are approved in similar building codes in the United States and have been proven to be durable, high-performing options. Over the past decade, the authors have been directly involved with studies of both 0.5 pcf (8 kg/m3) open cell spray foam, and 2.0 pcf (32 kg/m3) closed cell spray foam in unvented roof assemblies in various climates with continuous monitoring of temperature and moisture conditions. This paper provides a literature review of research that has been conducted on wood-framed sloped unvented roof assemblies, but will focus on results from a field monitoring study of sloped unvented wood roofs in partnership with the University of Waterloo, as well as a field survey that opened roofs and removed samples from aged unvented roof assemblies.
Presented at the 15th Canadian Conference on Building Science and Technology.
Vapour Permeable Air Barriers: Real World Evaluation - What Works, What Doesn...Lorne Ricketts
As insulation and airtightness requirements increase, vapour permeable liquid and self-adhesive air barrier membrane products are rapidly gaining traction in the North American marketplace. This presentation looks at real world testing of various types of these membranes and identifies potential strengths and weakness of these types of products.
Ventilated attics are prone to moisture problems in the Coastal Pacific Northwest climate. This presentation discusses recent research investigating the causes of these issues, and presents cutting edge findings regarding potential solutions.
Overview:
- Background
- Net Zero Building Enclosure Targets & Potential Savings
- Interior and Exterior Building Enclosure Retrofit Strategies
- Hygrothermal Considerations & Risk Assessment Evaluation Methodology
- Economics of Net Zero Building Enclosure Retrofits
Presentation Outline:
- What are "Super-Insulated" buildings and what are the drivers?
- Thermal bridging- problems and solutions
- Designing of highly insulated walls - insulation placement & durability considerations
- Super-Insulated wood-frame building enclosure design guide
Achieving the Passive House criteria on a high-rise, concrete-framed building located in Vancouver, BC.
Presented at the 2017 NAPHN Conference and Expo by Eric Catania, M.Eng., BEMP, CPHD, LEED AP BD+C, PHI Accredited Passive House Certifier.
Energy Consumption in Low-Rise Wood Frame Multi-Unit Residential BuildingsRDH Building Science
A study was performed to understand the energy consumption in low-rise wood-frame multi-unit residential buildings (MURBs) and townhouse buildings in south-west British Columbia. Low-rise MURBs are an important building type as they make up a growing proportion of housing stock in cities across North
America.
Through this study, energy data was collected from electricity and gas utilities for 20 low-rise buildings (four storeys and less) and three townhouse complexes. This data was calendarized and weather normalized to determine average annual and monthly energy consumption for analysis and comparison. Two buildings were chosen from the data set for detailed analysis, one low-rise (four-storey) and one townhouse complex. The buildings were selected based on characteristics typical of low-rise MURBs in south-west BC. The purpose of the detailed analysis was to assess opportunities to improve the energy efficiency and reduce carbon emissions in existing low-rise MURBs using whole building energy modelling.
This paper details the energy consumption trends observed through the data analysis, and the energy modelling results of the buildings chosen for detailed study. These results are also compared to results from a similar study which evaluated the energy use in mid- to high-rise non-combustible MURBs. The work presented here will improve our understanding of energy consumption in low-rise MURBs, and characterize opportunities for energy savings in these buildings.
Presented by Elyse Henderson at the 15th Canadian Conference on Building Science and Technology
Building Enclosures of the Future - Building Tomorrow's Buildings TodayRDH Building Science
- Trends and Drivers for Improved Building Enclosures & Whole Building Energy Efficiency
- New BCBC & VBBL Building & Energy Code Updates
- Effective R-values & Insulation Behaviour
- Highly Insulated Walls – Alternate Assemblies & New Cladding Attachment Strategies
- Highly Insulated Low-Slope Roofs – Insulation Strategies & New Research into Conventional Roofs
Presentation on Building Enclosure Airtightness Testing in Washington StateRDH Building Science
This document discusses building airtightness testing that was conducted in Washington State on 31 buildings. It provides an overview of airtightness testing procedures and requirements under the 2009 and 2012 energy codes. Test results showed that while an airtightness of 0.4 cfm/ft2 is attainable, achieving it requires repetitive simple details, experienced teams, and coordination between designers, contractors and trades to minimize air leakage.
Christy Love, EIT LEED AP BD+C, is a Senior Project Engineer at RDH Building Science. This presentation was given at the 2016 Passive House Northwest Conference.
The North Park Passive House, a 6-unit strata project located in Victoria BC, was occupied in September 2015. It is the first market strata-title certified Passive House development in Canada.
While well-established elsewhere, the potential benefits of Passive House and other low energy design approaches are not as well understood in Canada, and there are limited data on the actual performance of low energy residential buildings in various Canadian climates.
To address this gap, RDH, in partnership with the Canadian Mortgage and Housing Corporation, the Homeowner Protection Office of BC Housing, and FP Innovations, is undertaking detailed quantitative and qualitative performance measurement of the North Park Passive House. The intent of this research is to develop a comprehensive case study for a Passive House project in the coastal BC climate.
Learning Objectives:
- Understand the scope of the research and what we hope to learn from it.
- Understand preliminary results about how the building is performing in terms of comfort, air quality, and energy use, via measured data collected within select suites and qualitative interviews with occupants.
- Understand and interpret preliminary results of how the building enclosure is performing.
- Learn tips and share lessons learned about undertaking this type of research.
Developing an Open Source Hourly Building Energy Modelling Software ToolRDH Building Science
Energy modelling is an important tool in the design of low energy buildings. It helps evaluate energy savings of various energy efficiency measures and can predict total building energy consumption.
Participants will:
1. Learn about approaches to identifying, quantifying, and investigating IGU performance problems and how results needed can inform the investigation tools/processes used.
2. Learn about the unique design challenges with replacing structurally glazed IGUs and how those challenges were overcome.
3. Learn how quality assurance procedures can be used to deliver innovative products that meet performance expectations.
4. Learn about how building enclosure repair implementation can be as challenging as figuring out how to repair the damaged building enclosure component.
Energy Efficient Building Enclosure Design Guidelines for Wood-Frame BuildingsRDH Building Science
The document summarizes a new guide for designing energy efficient building enclosures for wood-frame buildings. It provides an overview of the guide's contents, which include chapters on building and energy codes, moisture and thermal control strategies, recommendations for highly insulated wall and roof assemblies, and construction detailing. The guide aims to help designers meet current and upcoming energy code requirements with wood-frame construction and provides guidance on enclosure designs for different climate zones in North America.
NBEC 2014 - Conventional Roofs: Measuring Impacts of Insulation Strategy and ...RDH Building Science
This study examined the impacts of insulation strategy and membrane colour on conventional roof performance in Canada. It monitored 9 roof sections with different colour membranes (white, grey, black) and insulation types (stone wool, polyiso, hybrid). Field monitoring found that darker membranes experienced much higher temperatures than lighter ones. Insulation type also impacted temperatures, with stone wool and hybrid strategies showing less peak heating and cooling than polyiso alone. Energy modeling further showed that lighter membranes and stone wool or hybrid insulation led to lower energy use. The study aims to continue monitoring insulation movement, moisture, and aging effects over the long term.
Presented at the BCBEC Building Smart with Safe and Durable Wall Assemblies Symposium Feb 2, 2017, by Lorne Ricketts.
Ever increasing thermal performance requirements for wood-frame walls have had a dramatic impact on how we build walls. To meet these targets, exterior insulation is becoming more and more common, and methods to support the cladding are required that are strong and rigid, yet do not create significant thermal bridging through the insulation. This presentation discusses the results of recent structural testing of various different arrangements on long fasteners through exterior insulation as a method of supporting cladding while limiting thermal bridging.
A deterioration model for establishing an optimal mix of time-based maintenance (TbM) and Condition-Based Maintenance (CbM) for the Enclosure System.
Participants will:
1. Learn the two types of asset deterioration models
2. Explore the correlations when the two deterioration models are overlaid
3. Identify six different phases in the maintenance of an asset
4. Identify further model development needs
This document discusses a case study of a deep energy retrofit of a 13-story multifamily residential building in Vancouver, BC. It describes the existing building's poor energy performance and enclosure issues. A comprehensive building enclosure renewal was performed, including exterior wall insulation, new triple-glazed windows, roof and air sealing upgrades. This improved the overall enclosure R-value from R-2.8 to R-9.1. Measured energy savings from the retrofit were 19% total energy, 33% electricity, and reductions in electric baseboard heating and gas fireplace usage. Benchmarking showed the building's energy use intensity decreased from 71 to 56 kBTU/sqft per year, improving its performance significantly.
Window Standards Compared: NFRC, ISO and Passive House RatingsRDH Building Science
This slide deck was presented by Brittany Hanham at Passive House North Conference 2013.
Outline:
- North American and Passive House window rating systems
- Example simulation results
- What this means and things to be aware of
Presentation Outline:
- Gravity support systems
- Design criteria and thermal performance requirements
- Canadian energy codes
- Nominal vs. Effective R-Values
- Thermal modeling and effective
- R-values
- Conclusions
Energy Consumption in Mid to High-rise Residential Buildings both Before and ...RDH Building Science
This document analyzes energy consumption data from six mid- to high-rise residential buildings before and after enclosure rehabilitation. It found that while enclosure retrofits improved building enclosures, they did not necessarily reduce total energy use, as service systems had a greater influence on energy consumption. On average, the buildings saw a 4.8% reduction in total energy use after rehabilitation, but results varied, with savings of up to 16.8% in one building and increased usage of 13.8% in another. The study concluded that energy improvements require coordinated efforts between enclosure and service system engineers.
Thermal Bridging of Masonry Veneer Claddings and Energy Code ComplianceRDH Building Science
The document discusses thermal bridging through masonry veneer ties and its impact on effective wall R-values under energy codes. Three-dimensional modeling was used to analyze different tie materials and configurations over concrete, steel stud, and wood framed walls with varying insulation depths. Results showed ties reduced R-values by 5-30% depending in factors like material and holes. Stainless steel ties performed best with under half the reduction of galvanized ties. Shelf angle supports saw reductions of 45-55% without modifications. When configured properly, masonry veneer can provide one of the most thermally efficient cladding attachment strategies.
Energy Simulation of High-Rise Residential Buildings: Lessons LearnedRDH Building Science
This presentation covers lessons learned from an energy study of over 60 architecturally representative mid to high rise multi-unit residential buildings (MURBS) in BC.
Airtightness of Large Buildings - Where We're At and Where We're GoingLorne Ricketts
This document discusses airtightness testing of large buildings. It begins by outlining the impacts of air leakage on building energy consumption, indoor air quality, durability, comfort and more. Despite this, building energy codes provide little guidance on air barriers or verification of performance. The document then reviews differences between testing houses versus high-rises, common test methods and standards, and examples of performance requirements in different jurisdictions. It presents data on airtightness test results and the impact of requirements. It also discusses trends in air barrier materials, impacts of testing, and clarifies the difference between airtightness and actual air leakage.
- Why care about concrete balconies and exposed slab edges?
- Impacts of uninsulated slab edges and balconies
- Comparison of alternate solutions
- Benefit of balcony thermal breaks
Air sealing and ventilation improvements were tested in six multifamily buildings to reduce odor transfer between units. General approaches included ventilating odor sources, reducing air leakage between units through sealing, and increasing ventilation of receiving units. Air sealing focused on leaks between units and reduced shared leakage by an average of 23%. Ventilation was increased by installing new fans, converting intermittent exhaust to continuous, and balancing air flows, raising average rates by 60%. Tracer gas tests found reduced odor transfer in 65% of units, with 80% of tenants reporting less frequent and severe secondhand smoke drift. The study demonstrated practical, low-cost air sealing and ventilation treatments can effectively improve indoor air quality in multifamily housing.
Improvement of ventilation system in a mining sitesaadamatola
The document discusses improving the ventilation system at the Blue Reef Gold Mine in Tanzania. It is experiencing production stoppages twice a week due to insufficient ventilation. The objectives are to calculate airflow needs, design the primary ventilation system, and identify hindering factors. Data on the mine dimensions, worker numbers, gas levels, temperatures, dust levels and airflow rates at stations is collected and analyzed. The primary ventilation circuit is analyzed using Kirchoff's law to calculate airflow quantities at junctions. Improving the system is expected to enhance worker safety, health and productivity to meet production goals.
An overview of diagnostic tools used in RESNET testingBill Spohn
Learn about the variety of tools and test instruments that apply in RESNET standards 310 (pending) and 380. We'll cover the proper procedures as well as pros and cons of various devices.
The document discusses duct design for air conditioning systems. It covers topics such as:
- The purpose of ductwork is to deliver conditioned air from fans to diffusers in rooms.
- Air flows through ducts due to pressure differences created by fans. Proper duct sizing minimizes pressure drops while keeping costs low.
- Factors like velocity, static pressure, and friction affect pressure in ducts. Methods for calculating and minimizing these pressures are presented.
- Guidelines for maximum duct velocities based on application type are provided to control noise generation.
- Approximate ductwork material and construction costs are given based on duct size.
This document discusses HVAC air duct leakage. It begins by defining different types of leakage, including duct leakage, equipment leakage, and system leakage. It explains that duct leakage testing alone does not determine overall system leakage. The document discusses recommendations from codes and standards to test 25% of high-pressure duct. It also addresses questions around how much ductwork should be tested, including low-pressure duct, and why percentage of fan flow is not a suitable metric. The document notes misconceptions around duct leakage testing and provides guidance on good practices for specifications and testing. New tools like SMACNA's duct leakage calculator app are introduced.
The document summarizes research on air sealing commercial buildings to reduce energy use. It discusses methods for measuring air leakage, findings from whole-building air leakage tests of 387 commercial buildings in the US, and a study on air sealing 7 Minnesota buildings. On average, US buildings leak 0.72 cfm/ft2 but tighter construction (<0.25 cfm/ft2) can reduce infiltration by 70% and energy use by 5-20%. The Minnesota study found sealing reduced leakage in all 7 buildings to below the standard of 0.25 cfm/ft2.
This document provides information on designing high velocity ductwork systems using round ducts. It discusses the fundamentals of static regain duct design, key advantages over rectangular ducts which include lower installation costs and heat gain. Real world examples show savings of 37% on average using round ducts. Proper design techniques are outlined as well as common misconceptions.
This document discusses mechanical systems design considerations for tall buildings in Toronto and Dubai. It covers plumbing systems, life safety systems, heating systems, and ventilation. Some key differences between the cities include water supply reliability, regulatory frameworks, and climate influences on system design. Pressure regulation is needed for plumbing systems every 30 stories. Life safety systems require fire pumps and smoke control systems. Heating is primarily via hot water systems, while ventilation requires filtering, cooling and dehumidification in Dubai due to climate.
The energy required to heat and cool outdoor air and infiltration air is a significant fraction of thermal loads. This project has developed diagnostic procedures to identify air leaks and methods to calculate the savings from air sealing large commercial and institutional buildings. Envelope air sealing could significantly reduce large building energy consumption, but no systematic research has identified the most cost-effective strategies for Minnesota buildings.
The document provides information on designing and operating a water treatment plant, including:
1) Key components and processes include rapid mixing, flocculation, sedimentation, and filters. Chemicals like alum are used to treat water.
2) Safety guidelines, project expectations, teamwork strategies, and plant goals are outlined. Turbidity standards and potential penalties are defined.
3) Capital and operation costs are estimated. Calculations are described to determine the cost of water production based on a plant's design.
4) Troubleshooting methods like identifying problems, developing hypotheses, and testing components are discussed. A modular design approach is recommended.
This document provides an overview of cleanrooms, including their purpose of controlling airborne particle concentrations, classifications based on particle levels, sources of contamination, and design considerations. Cleanrooms aim to maintain cleanliness levels through isolation of contamination sources, filtration of air supplies, and regulating air flow, temperature, and humidity. Particle testing and certification ensure cleanrooms meet standards like ISO 14644-1.
This document discusses duct design for HVAC systems. It defines different types of ducts including supply, return, fresh air, and exhaust ducts. It also covers duct classification based on velocity and pressure, duct shapes, sizing methods like equal friction and static regain, and standard duct sizes for different air flows. Design considerations include aspect ratio, static versus dynamic pressure, and pressure losses from friction and changes in air flow.
False air or excess air in sealed systems like boiler flue gas paths or ACC vacuum systems can cause issues like heat loss, fan inefficiency, and increased downtime. It is important to identify sources of false air, measure levels periodically, and implement remedial actions like sealing leaks. Key steps include dedicating teams to identify leak areas, take measurements, and make repairs during outages in a timely manner, as well as implementing design and fabrication best practices, online monitoring instruments, and preventative maintenance programs.
This document provides an introduction and overview of acoustics and noise control for mechanical systems. It defines basic acoustical terms like amplitude, frequency, and quality of sound. It discusses indoor noise criteria curves and recommendations for limiting noise from air handling systems, roof-top units, terminal boxes, chillers, and pumps through strategies like isolation, attenuation, duct lining, and space planning.
Air tightness refers to preventing unintentional air movement through a building. Building regulations now require new dwellings to pass air permeability testing to ensure high standards of energy efficiency. The blower door test is used to measure air tightness by pressurizing the building and measuring air flow rates. Common air leakage paths include poorly fitted windows/doors, gaps around pipes/vents, and junctions between walls/floors. Improving air tightness reduces energy consumption for heating by preventing warm air from escaping, lowering bills and improving a home's BER rating.
Air tightness refers to preventing unintentional air movement through a building. Building regulations now require new dwellings to pass air permeability testing to ensure high standards of energy efficiency. The blower door test is used to measure air tightness by pressurizing the building and measuring air flow rates. Common air leakage paths include windows, doors, attic hatches, pipes and poor sealing around fixtures. Achieving good air tightness reduces energy consumption and improves a home's BER rating.
The document summarizes principles of air distribution systems and duct design. It discusses:
- Components of air distribution systems including diffusers, grilles, fans, ductwork and accessories.
- Design considerations for room air distribution including temperature and velocity ranges.
- Methods for duct design including velocity method and equal friction method. Both methods aim to size ducts and select fans to distribute air as required while minimizing pressure losses.
This document provides information about the Fall 2008 EE 410/510 course on Microfabrication and Semiconductor Processes at the University of Alabama in Huntsville. The instructor is John D. Williams and the class will cover topics such as basic vacuum science, vacuum pumps, vacuum gauges, thin film deposition techniques including thermal evaporation, e-beam evaporation and sputtering, and thermal oxidation. Formulas for evaporation rate, deposition rate, diffusion, and oxide growth are also presented.
The document discusses testing done to evaluate whether liquid membrane flashings are suitable for use as window sill pan flashings. It describes tests done to assess the long-term water ponding resistance, drying potential, and gap bridging ability of different liquid and self-adhered membrane products. The results showed that while some liquid membrane chemistries were acceptable, thicker applications were needed for proper gap bridging. Overall, permeable and impermeable self-adhered membranes performed better than liquid membranes as sill flashings. No discernible drying benefit was found for liquid membranes over impermeable self-adhered options. New test standards may be needed to better evaluate liquid membrane flashing performance.
Impact of Heating and Cooling of Expanded Polystyrene and Wool Insulations on...RDH Building Science
The thermal expansion and contraction of insulation products within conventional roof assemblies has been identified as a potential performance concern in the roofing industry. This movement can create gaps between insulation boards, which can short-circuit the insulation with respect to heat flow, and in conventional roof assemblies where the insulation also provides the substrate for the roofing membrane, insulation movement can also adversely affect the durability and integrity of the membrane and roofing system. Problems with creasing and ridging of membranes have been observed in the field, along with stress concentrations and holes around fixed penetrations. In particular, field observations have indicated that shrinkage of expanded polystyrene (EPS) insulation products may put undue stress on the roof membranes and could potentially affect the durability of styrene-butadiene-styrene (SBS) roof membranes.
To investigate these industry concerns regarding the potential effect of dimensional movement of EPS insulation on the performance of SBS membranes, laboratory testing was performed on conventional roof specimens in a purpose-built climate chamber. The roof assemblies were cooled and heated to evaluate the amount of insulation movement, and to then observe the impact of these temperature cycles on the roof assembly. This portion of the investigation in to this issue focused on recreation of the observed field condition (e.g., wrinkled membrane), and direct comparison of the relative performance of different insulation types as a first step towards determining the cause of the observed in-service wrinkling.
Presented at the 15th Canadian Conference on Building Science and Technology.
Guideline for the Two-Dimensional Simulation of Spandrel Panel Thermal Perfor...RDH Building Science
While the approach to thermal simulation of vision glazing areas is well documented by groups such as the National Fenestration Rating Council (NFRC), the approach to simulate opaque spandrel panels is not similarly documented. Furthermore, spandrel assemblies are substantially different from conventional
opaque wall assemblies (i.e., concrete, steel stud, wood stud, etc.). To address this industry need, RDH in partnership with the Fenestration Association of BC (FENBC) and funding from BC Housing has developed a procedure to determine spandrel panel U-factors using common industry tools and familiar methods. The methodology includes consideration of various spandrel panel arrangements and builds off the existing NFRC 100 simulation methodology. The objective of this procedure is to document a reasonably accurate and practical approach to determine opaque spandrel area U-values with higher precision and uniformity. This allows for both the accurate representation of these systems with regards to code compliance and
energy modelling, as well as the fair comparison of competing products.
Presented at the 15th Canadian Conference on Building Science and Technology.
Solutions to Address Osmosis and the Blistering of Liquid-Applied Waterproofi...RDH Building Science
Waterproofing membranes are widely used in the building industry as a barrier for water entry into a building enclosure. Over the past two decades, waterproofing system failure due to osmotic blistering has occurred in some protected membrane/inverted roofing assemblies. Not all waterproofing membrane assemblies are at risk for this process and the authors have developed a test protocol to establish the relative risk level of waterproofing membranes to osmosis. Using this protocol, the osmotic flow rate of SBS, hot rubberized asphalt, PMMA, EPDM, TPO, HDPE, polyurea, asphalt emulsion, asphalt-modified polyurethane, and various other 2-component cold applied membranes was measured to determine a threshold osmotic flow rate for low risk waterproofing membrane systems.
In this research, a wide range of osmotic flow rates were obtained for the various membrane types. Most asphalt-modified polyurethane membranes consistently exhibit osmotic flow rates significantly higher than the low-risk threshold of ~0.0 g/m²/day (typically 1.4 to over 20 g/m²/day) after data corrections, which results in osmotic blistering and premature membrane failures. Some polyurea and asphalt emulsion membranes have flow rates above 2.0 g/m²/day with unknown long-term performance, while most other membranes that were tested have flow rates around 0.0 g/m²/day after data corrections from control samples. To reduce the potential for osmotic blistering over concrete, it is recommended that waterproofing membranes used in inverted roofing assemblies should have an osmotic flow rate near 0.0 g/m²/day when tested using the methodology herein, an inverted wet cup vapour permeance less than that of the substrate (i.e. <0.1 US Perms on a concrete substrate), and minimal long-term water absorption.
Presented at the 15th Canadian Conference on Building Science and Technology.
1. Structural testing was conducted on screws installed through thick exterior insulation for wall assemblies. Different screw types, insulation thicknesses, fastener arrangements, and cladding weights were tested.
2. The testing showed that screws installed through insulation from 3-12 inches thick can structurally support most cladding weights, with deflections generally under 1/8 inches. Longer screws had higher load capacities.
3. Additional guidance is needed for designers on allowable loads, fastener types and spacing, and installation methods when using screws through thick exterior insulation.
Interest in taller wood buildings utilizing cross laminated timber (CLT), nail laminated timber (NLT), and structural glued laminated timber (glulam) is growing rapidly in Canada and the United States. On the west coast, recently completed projects including the 97 foot tall, 6-story Wood Innovation and Design Center (WIDC) in Prince George, BC, the 180 foot tall, 18-story UBC Brock Commons Tallwood House in Vancouver, BC, and the upcoming 12-story Framework project in Portland, OR, have captured the attention of the international construction industry. Several other taller wood buildings are on the horizon and feasibility studies are currently being performed for mass timber buildings over 30 stories in height. Tall wood buildings have been a reality in Europe longer than North America, and there is much to learn from the European experience. However, conditions unique to the North American construction industry create many challenges for the design team in demonstrating the safety, durability, and economics of these buildings, all while forming public perception of wood at taller heights.
Presented at the 15th Canadian Conference on Building Science and Technology.
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...RDH Building Science
Heating, ventilating and air-conditioning (HVAC) typically accounts for 30% to 50% of commercial building energy use. Small commercial buildings often use oversized and inefficient rooftop air handling units (RTUs) to provide both air conditioning and ventilation. A conversion strategy to reduce energy
consumption is the installation of a very high efficiency dedicated outdoor air system (DOAS) to provide ventilation with a separate heat pump system to provide heating and cooling. Decoupling the heating and cooling from ventilation allows for improved energy efficiency and control of space conditions. Upgrades to mechanical systems can also improve the indoor air quality (IAQ) and comfort through control of carbon dioxide (CO2) concentrations, dry bulb temperature, and relative humidity (RH).
A pilot study of eight buildings was conducted to investigate the potential benefits of replacing existing RTUs with high efficiency heat recovery ventilators (HRVs) and air source heat pumps in the Pacific Northwest. This report contains results for a subset of seven buildings for which data is available. The
building energy use before and after the conversion was determined using utility data, energy modeling and monitoring. Indoor environmental conditions were measured at hourly intervals for up to one year postconversion using CO2, temperature, and RH sensors. The data was analyzed to determine changes in energy use and IAQ before and after the conversion.
This paper presents the pilot building results pre- and post-conversion. While several factors need to be in place to ensure optimal performance and cost effectiveness, the pilot shows that replacing RTUs with DOAS systems in existing commercial buildings can both reduce energy use as well as improve indoor environmental conditions. This conversion type is viable for a wide variety of building types and scale-up of the retrofits has the potential to significantly improve a previously underserved segment of the building stock.
Presented by James Montgomery at the 15th Canadian Conference on Building Science and Technology.
Moisture Uptake Testing for CLT Floor Panels in a Tall Wood Building in Vanco...RDH Building Science
This document summarizes research on controlling construction moisture in cross-laminated timber (CLT) used in tall wood buildings. Small-scale and full-scale CLT samples were exposed to moisture and different protective coatings were tested. Hygrothermal modeling was calibrated and used to project moisture levels over time under different coatings. Coatings like polyurethane and silicone sealers were found to reduce moisture levels compared to uncoated CLT. Left unprotected, CLT can absorb over 25% moisture content which can lead to mold or structural damage over time. Recommendations include protecting CLT from moisture during construction and using moisture management strategies like sealants and non-moisture producing heaters.
Digital Twins Computer Networking Paper Presentation.pptxaryanpankaj78
A Digital Twin in computer networking is a virtual representation of a physical network, used to simulate, analyze, and optimize network performance and reliability. It leverages real-time data to enhance network management, predict issues, and improve decision-making processes.
Applications of artificial Intelligence in Mechanical Engineering.pdfAtif Razi
Historically, mechanical engineering has relied heavily on human expertise and empirical methods to solve complex problems. With the introduction of computer-aided design (CAD) and finite element analysis (FEA), the field took its first steps towards digitization. These tools allowed engineers to simulate and analyze mechanical systems with greater accuracy and efficiency. However, the sheer volume of data generated by modern engineering systems and the increasing complexity of these systems have necessitated more advanced analytical tools, paving the way for AI.
AI offers the capability to process vast amounts of data, identify patterns, and make predictions with a level of speed and accuracy unattainable by traditional methods. This has profound implications for mechanical engineering, enabling more efficient design processes, predictive maintenance strategies, and optimized manufacturing operations. AI-driven tools can learn from historical data, adapt to new information, and continuously improve their performance, making them invaluable in tackling the multifaceted challenges of modern mechanical engineering.
Road construction is not as easy as it seems to be, it includes various steps and it starts with its designing and
structure including the traffic volume consideration. Then base layer is done by bulldozers and levelers and after
base surface coating has to be done. For giving road a smooth surface with flexibility, Asphalt concrete is used.
Asphalt requires an aggregate sub base material layer, and then a base layer to be put into first place. Asphalt road
construction is formulated to support the heavy traffic load and climatic conditions. It is 100% recyclable and
saving non renewable natural resources.
With the advancement of technology, Asphalt technology gives assurance about the good drainage system and with
skid resistance it can be used where safety is necessary such as outsidethe schools.
The largest use of Asphalt is for making asphalt concrete for road surfaces. It is widely used in airports around the
world due to the sturdiness and ability to be repaired quickly, it is widely used for runways dedicated to aircraft
landing and taking off. Asphalt is normally stored and transported at 150’C or 300’F temperature
Null Bangalore | Pentesters Approach to AWS IAMDivyanshu
#Abstract:
- Learn more about the real-world methods for auditing AWS IAM (Identity and Access Management) as a pentester. So let us proceed with a brief discussion of IAM as well as some typical misconfigurations and their potential exploits in order to reinforce the understanding of IAM security best practices.
- Gain actionable insights into AWS IAM policies and roles, using hands on approach.
#Prerequisites:
- Basic understanding of AWS services and architecture
- Familiarity with cloud security concepts
- Experience using the AWS Management Console or AWS CLI.
- For hands on lab create account on [killercoda.com](https://killercoda.com/cloudsecurity-scenario/)
# Scenario Covered:
- Basics of IAM in AWS
- Implementing IAM Policies with Least Privilege to Manage S3 Bucket
- Objective: Create an S3 bucket with least privilege IAM policy and validate access.
- Steps:
- Create S3 bucket.
- Attach least privilege policy to IAM user.
- Validate access.
- Exploiting IAM PassRole Misconfiguration
-Allows a user to pass a specific IAM role to an AWS service (ec2), typically used for service access delegation. Then exploit PassRole Misconfiguration granting unauthorized access to sensitive resources.
- Objective: Demonstrate how a PassRole misconfiguration can grant unauthorized access.
- Steps:
- Allow user to pass IAM role to EC2.
- Exploit misconfiguration for unauthorized access.
- Access sensitive resources.
- Exploiting IAM AssumeRole Misconfiguration with Overly Permissive Role
- An overly permissive IAM role configuration can lead to privilege escalation by creating a role with administrative privileges and allow a user to assume this role.
- Objective: Show how overly permissive IAM roles can lead to privilege escalation.
- Steps:
- Create role with administrative privileges.
- Allow user to assume the role.
- Perform administrative actions.
- Differentiation between PassRole vs AssumeRole
Try at [killercoda.com](https://killercoda.com/cloudsecurity-scenario/)
Prediction of Electrical Energy Efficiency Using Information on Consumer's Ac...PriyankaKilaniya
Energy efficiency has been important since the latter part of the last century. The main object of this survey is to determine the energy efficiency knowledge among consumers. Two separate districts in Bangladesh are selected to conduct the survey on households and showrooms about the energy and seller also. The survey uses the data to find some regression equations from which it is easy to predict energy efficiency knowledge. The data is analyzed and calculated based on five important criteria. The initial target was to find some factors that help predict a person's energy efficiency knowledge. From the survey, it is found that the energy efficiency awareness among the people of our country is very low. Relationships between household energy use behaviors are estimated using a unique dataset of about 40 households and 20 showrooms in Bangladesh's Chapainawabganj and Bagerhat districts. Knowledge of energy consumption and energy efficiency technology options is found to be associated with household use of energy conservation practices. Household characteristics also influence household energy use behavior. Younger household cohorts are more likely to adopt energy-efficient technologies and energy conservation practices and place primary importance on energy saving for environmental reasons. Education also influences attitudes toward energy conservation in Bangladesh. Low-education households indicate they primarily save electricity for the environment while high-education households indicate they are motivated by environmental concerns.
This study Examines the Effectiveness of Talent Procurement through the Imple...DharmaBanothu
In the world with high technology and fast
forward mindset recruiters are walking/showing interest
towards E-Recruitment. Present most of the HRs of
many companies are choosing E-Recruitment as the best
choice for recruitment. E-Recruitment is being done
through many online platforms like Linkedin, Naukri,
Instagram , Facebook etc. Now with high technology E-
Recruitment has gone through next level by using
Artificial Intelligence too.
Key Words : Talent Management, Talent Acquisition , E-
Recruitment , Artificial Intelligence Introduction
Effectiveness of Talent Acquisition through E-
Recruitment in this topic we will discuss about 4important
and interlinked topics which are
smart pill dispenser is designed to improve medication adherence and safety f...
NBEC 2014 - Airflow in Mid to High-rise Multi-Unit Residential Buildings
1. Airflow in Mid to High-rise
Multi-Unit Residential Buildings
LORNE RICKETTS, MASC
RDH BUILDING ENGINEERING LTD. VANCOUVER, BC
CO-AUTHOR: DR. JOHN STRAUBE, PHD, P.ENG.
2. Outline
à Introduction & Background
à Testing and Measurement Program
à Measured Ventilation Rates (PFT testing)
à Cause of Ventilation Rates
à Extension of Study Findings
à Conclusions & Recommendations
3. Introduction & Background
à Most apartments/condos (multi-unit residential buildings) are
ventilated using pressurized corridor systems
à Decades of research and experience indicates that this
system likely does not work very well
à Still most common system
à Few physical measurements
à Particularly relevant now, as newer more airtight building
have less tolerance for poorly performing ventilation
systems
à Less infiltration and exfiltration to supplement ventilation
4. Pressurized Corridor Ventilation System
à DESIGN INTENT
à Provide ventilation air to all zones
à Control flow of air contaminates
between zones
à HOW
à Provides air to corridors directly
via a vertical shaft which
pressurizes the corridor
à Corridor pressurization forces air
into suites via intentional gaps
under the entrance doors
Introduction & Background
5. Case Study Building
à 13-storey multi-unit residential
building in Vancouver, Canada with
37 residential suites
à Constructed 1986
à Enclosure renewal 2012
à Below grade parking garage located
under the building
à Ventilated using pressurized
corridor system by a single make-
up air unit (MAU) on the roof
Introduction & Background
Overall, is typical of high-rise multi-unit residential buildings
6. Perfluorocarbon (PFT) Testing
Two component system:
à PFT Sources (7 distinct types)
à Capillary absorption tube
samplers (CATS)
à Sources release distinct PFT
tracer gasses in different
zones and use CATS to sample
the concentrations
Measured Ventilation Rates
Sources
CATS
7. à Order of magnitude variation in the ventilation rates
à Significantly higher rates for upper suites than lower suites
à Most suites under-ventilated or over-ventilated
Measured Ventilation Rates
ASHRAE
62.1-‐2010
≈
40
L/s
per
suite
Waste
of
Energy
Indoor
Air
Quality
Issues
8. PMCP
Released
in
MAU
Measured Ventilation Rates
PDCB
Released
in
Parking
Garage
9. à Carbon dioxide concentration were monitored as an
indicator of indoor air quality (IAQ)
à Significantly higher concentration in the lower suites
Measured Ventilation Rates
10. à Summary:
à Over ventilation and under ventilation of most suites
à Higher ventilation rates in upper suites than lower suites
à Better indoor air quality in upper suites than lower suites
Why is this happening?
Measured Ventilation Rates
11. Maybe the MAU isn’t working correctly?
à Custom powered flow hood used to measure intake flow rate of the make-up air unit
à MAU airflow approximately the same as design flow rate of 1,560 L/s (3,300 cfm)
Cause of Ventilation Rates
12. Maybe the ventilation air isn’t reaching the corridors?
à Only 40% of intake flow reaches the corridors directly
Cause of Ventilation Rates
0
2
4
6
8
10
12
14
0 25 50 75 100 125 150
Floor
Number
Flow
Rate
[L/s]
MAU
Supply
to
Corridors
Pre-‐Retrofit
(21°C) Post-‐Retrofit
(6°C) Post-‐Retrofit
(16°C)
Pre-‐Retrofit (21°C)
Total
=
593
L/s
Post-‐Retrofit
(6°C)
Total
=
559
L/s
Post-‐Retrofit
(16°C)
Total
=
580
L/s
Fire
Damper
noted
to
be
closed
on
Floors
4,
8,
&
12.
1
L/s
≈
2
cfm
13. Maybe the air isn’t reaching the suites from the corridors?
à Airtightness tested corridors and found significant flow paths other than to
the suites through the suite entrance doors. Only 20% to the suites
Cause of Ventilation Rates
1
L/s
≈
2
cfm
14. à Theoretically, only 8% of intended ventilation actually
goes where it is supposed to! Waste of ventilation air,
and the energy needed to move and condition it.
Cause of Ventilation Rates
à If only 40% of the flow rate reaches the corridors
And, only 20% of that air reaches the suites…
Leakage of air along ventilation flow
path is a major issue.
𝟒𝟎%×𝟐𝟎%=𝟖%
15. à Pressure differences were
monitored with a focus on an
upper floor and a lower floor
(Floors 11 & 3)
à Assessed relationship between
exterior temperature (stack
effect) and wind events using a
weather station on the roof
Maybe pressure differences
are an important factor?
Cause of Ventilation Rates
16. à Mechanical ventilation system creates pressure of 5 to 10 Pa
Cause of Ventilation Rates
-‐20
-‐15
-‐10
-‐5
0
5
10
15
20
Feb
8
6:00 Feb
8
8:00 Feb
8
10:00 Feb
8
12:00 Feb
8
14:00 Feb
8
16:00 Feb
8
18:00
Pressure
Difference
[Pa]
Average
Corridor
to
Suite
Pressure
by
Floor
when
MAU
Off
Floor
02 Floor
03 Floor
04 Floor
10 Floor
11 Floor
12
Measurement with
MAU
Off
Measurement with
MAU
Recently
Turned
On
Corridor-‐to-‐Suite
Pressure
Difference
[Pa]
≈10 Pa
≈5 Pa
Corridor-to-Suite Pressure Difference
17. -‐5
0
5
10
15
20
25
-‐10
-‐5
0
5
10
15
20
Exterior
Temperature
[°C]
Corridor-‐to-‐Suite
Pressure
Difference
[Pa]
Average
Suite
to
Corridor
Pressures
by
Floor
and
Exterior
Temperature
-‐ 24
Hour
Moving
Average
Floor
02 Floor
03 Floor
04
Floor
10 Floor
11 Floor
12
Exterior
Temperature
[°C]
-‐5
0
5
10
15
20
25
-‐10
-‐5
0
5
10
15
20
Exterior
Temperature
[°C]
Corridor-‐to-‐Suite
Pressure
Difference
[Pa]
Average
Suite
to
Corridor
Pressures
by
Floor
and
Exterior
Temperature
-‐ 24
Hour
Moving
Average
Floor
02 Floor
03 Floor
04
Floor
10 Floor
11 Floor
12
Exterior
Temperature
[°C]
-‐5
0
5
10
15
20
25
-‐10
-‐5
0
5
10
15
20
Exterior
Temperature
[°C]
Corridor-‐to-‐Suite
Pressure
Difference
[Pa]
Average
Suite
to
Corridor
Pressures
by
Floor
and
Exterior
Temperature
-‐ 24
Hour
Moving
Average
Floor
02 Floor
03 Floor
04
Floor
10 Floor
11 Floor
12
Exterior
Temperature
[°C]
à Pressures created by stack effect found to be of similar
magnitude (10 to 15 Pa) as mechanical pressures
Cause of Ventilation Rates
Corridor-to-Suite Pressure Difference
10 – 15 Pa
18. à Stack effect pressures found to distribute 69% across the corridor to
suite boundary and 9% across exterior enclosure
à Stack effect pressure acts primarily in the same location as mechanical
pressures intended to provide ventilation and control contaminate flow
Cause of Ventilation Rates
19. à Vancouver is a relatively
moderate climate
à Should consider
other climates
à Case study building is
13 storeys
à Should consider different
building heights
Extension of Study Findings
20. 0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
40
m
Tall
Building
in
Miami
40m Tall Building in Miami
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
40
m
Tall
Building
in
Vancouver
40m Tall Building in Vancouver40m Tall Building in Toronto
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
40
m
Tall
Building
in
Toronto
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
40
m
Tall
Building
in
Fairbanks
40m Tall Building in Fairbanks
Extension of Study Findings
Wind Stack Effect Mechanical
(10 Pa)
à Climate
21. 0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
20
m
Tall
Building
in
Toronto
20m Tall Building in Toronto
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
40
m
Tall
Building
in
Toronto
40m Tall Building in Toronto
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
60
m
Tall
Building
in
Toronto
60m Tall Building in Toronto80m Tall Building in Toronto
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Percentage
of
Driving
Force
Pressure
Daily
Average
Distribution
of
Pressure
Difference
due
to
Driving
Forces
for
a
80
m
Tall
Building
in
Toronto
Extension of Study Findings
Wind Stack Effect Mechanical
(10 Pa)
à Building Height
22. Extension of Study Findings
à Stack effect is more significant in taller buildings
à Proportion of wind pressures remains relatively the same
à Relative magnitude of mechanical pressures decreases as
height increases
0%
10%
20%
30%
40%
50%
60%
70%
Stack
Effect Wind Mechanical
(10
Pa)
Percentage
of
Driving
Force
Pressure
Average
Proportions
of
Driving
Force
Pressure
Differences
-‐ Vancouver
20
m
40
m
60
m
80
m
100
m
Building
Height
23. Extension of Study Findings
à Stack effect more significant in cold climates
à Wind highly variable, but typically more significant in
warm climates
0%
10%
20%
30%
40%
50%
60%
70%
Stack
Effect Wind Mechanical
(10
Pa)
Percentage
of
Driving
Force
Pressure
Average
Proportions
of
Driving
Force
Pressure
Differnces
-‐ 40m
Tall
Building
Miami
Houston
Los
Angeles
New
York
Vancouver
Toronto
Calgary
Fairbanks
24. Comparison of Driving Forces
à Since all of the pressure differences created by the driving forces
(stack effect, wind, & mechanical systems) are of similar
magnitude, it is possible that any one could dominate
à This is exaggerated for buildings located in more extreme
climates than Vancouver
Ventilation system can not practically overwhelm nature.
25. Conclusion
à Corridor pressurization does not provide intended
ventilation rates to a large number of suites
à Some significantly over ventilated while others significantly
under ventilated
à Significant leakage along the ventilation air flow path
from the duct and the corridor (wasted ventilation)
à Uncontrolled airflow wastes energy and provides poor
ventilation
à Stack effect and wind pressures are often similar or
greater than mechanically-induced pressures
à Ventilation system can not practically overwhelm nature
26. Recommendations for Ventilation System Design
à Ventilation air should be directly supplied to suites to
limit the potential of loss along the flow path and of the
system being overwhelmed by stack effect and wind
à The exterior enclosure should be airtight, and suites
and vertical shafts should be compartmentalized
(airtight) to limit the impact of wind and stack effect on
ventilation