Submit Search
Upload
Lineprotection basics june2008
•
8 likes
•
3,541 views
L
lankeshdb
Follow
line protection basic
Read less
Read more
Engineering
Report
Share
Report
Share
1 of 98
Download now
Download to read offline
Recommended
DOCUMENT FOR SOTF PROTECTION FINAL
DOCUMENT FOR SOTF PROTECTION FINAL
EKANANDHAN G
basics of busbar and lbb protection
basics of busbar and lbb protection
Salim Palayi
Pilot protection
Pilot protection
Suraj Shandilya
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
Basic protection and relaying
Basic protection and relaying
Biswajit Pratihari
Reactors
Reactors
Molla Morshad
substation protection basics.ppt
substation protection basics.ppt
Salim Palayi
Ipsa mv relay co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adam
Shaik Abdullah Adam
Recommended
DOCUMENT FOR SOTF PROTECTION FINAL
DOCUMENT FOR SOTF PROTECTION FINAL
EKANANDHAN G
basics of busbar and lbb protection
basics of busbar and lbb protection
Salim Palayi
Pilot protection
Pilot protection
Suraj Shandilya
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
Basic protection and relaying
Basic protection and relaying
Biswajit Pratihari
Reactors
Reactors
Molla Morshad
substation protection basics.ppt
substation protection basics.ppt
Salim Palayi
Ipsa mv relay co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adam
Shaik Abdullah Adam
Switchgear and protection 3
Switchgear and protection 3
Md Irshad Ahmad
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Muhd Hafizi Idris
Power system protection topic 1
Power system protection topic 1
Siswoyo Edo
Excitation System & capability curve of synchronous generator
Excitation System & capability curve of synchronous generator
MANOJ KUMAR MAHARANA
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Md Sarowar Alam
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
jbpatel7290
Transformer design and protection
Transformer design and protection
ashwin fcc
ETAP - Coordination and protecion 2
ETAP - Coordination and protecion 2
Himmelstern
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
moiz89
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over Current Protection
SARAVANAN A
Directional over current relay
Directional over current relay
CS V
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
UtthejNani1
Factors to be considered while selecting CT
Factors to be considered while selecting CT
Parth Patel
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
ABHISHEK RAI
Power system protection
Power system protection
Anu Priya
Substation Neutral Earthing
Substation Neutral Earthing
Power System Operation
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
Living Online
Power System Protection basics
Power System Protection basics
Rajan Singh Tanwar
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Power System Operation
ETAP - Curso protecciones con el etap
ETAP - Curso protecciones con el etap
Himmelstern
transmission line
transmission line
singh1515
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
Rohini Haridas
More Related Content
What's hot
Switchgear and protection 3
Switchgear and protection 3
Md Irshad Ahmad
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Muhd Hafizi Idris
Power system protection topic 1
Power system protection topic 1
Siswoyo Edo
Excitation System & capability curve of synchronous generator
Excitation System & capability curve of synchronous generator
MANOJ KUMAR MAHARANA
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Md Sarowar Alam
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
jbpatel7290
Transformer design and protection
Transformer design and protection
ashwin fcc
ETAP - Coordination and protecion 2
ETAP - Coordination and protecion 2
Himmelstern
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
moiz89
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over Current Protection
SARAVANAN A
Directional over current relay
Directional over current relay
CS V
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
UtthejNani1
Factors to be considered while selecting CT
Factors to be considered while selecting CT
Parth Patel
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
ABHISHEK RAI
Power system protection
Power system protection
Anu Priya
Substation Neutral Earthing
Substation Neutral Earthing
Power System Operation
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
Living Online
Power System Protection basics
Power System Protection basics
Rajan Singh Tanwar
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Power System Operation
ETAP - Curso protecciones con el etap
ETAP - Curso protecciones con el etap
Himmelstern
What's hot
(20)
Switchgear and protection 3
Switchgear and protection 3
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Power system protection topic 1
Power system protection topic 1
Excitation System & capability curve of synchronous generator
Excitation System & capability curve of synchronous generator
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Power system-protection-presentation-dated-03-10-2013-integrated-protection-c...
Transformer design and protection
Transformer design and protection
ETAP - Coordination and protecion 2
ETAP - Coordination and protecion 2
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over Current Protection
Directional over current relay
Directional over current relay
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
Factors to be considered while selecting CT
Factors to be considered while selecting CT
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
Power system protection
Power system protection
Substation Neutral Earthing
Substation Neutral Earthing
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
Power System Protection basics
Power System Protection basics
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
ETAP - Curso protecciones con el etap
ETAP - Curso protecciones con el etap
Viewers also liked
transmission line
transmission line
singh1515
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
Rohini Haridas
Transmission Line Automation
Transmission Line Automation
Kundan Kumar
Smart grid networks and security architecture: Threat analysis, threat scenar...
Smart grid networks and security architecture: Threat analysis, threat scenar...
John-André Bjørkhaug
Short circuit monitoring by using PLC & SCADA
Short circuit monitoring by using PLC & SCADA
RAGUL BHAWAN
K.Sravanthi.
K.Sravanthi.
SRAVANTHI KUPPA
Gps in protection scheme
Gps in protection scheme
shanthan balaji reddy
Practical Medium and High voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High voltage Testing of Electrical Equipment for Enginee...
Living Online
Brief Literature Review on Phasor Based Transmission Line Fault Location Algo...
Brief Literature Review on Phasor Based Transmission Line Fault Location Algo...
sarasijdas
Effective two terminal single line to ground fault location algorithm
Effective two terminal single line to ground fault location algorithm
Muhd Hafizi Idris
Power Cables Operation, Maintenance, Location and Fault Detection
Power Cables Operation, Maintenance, Location and Fault Detection
Living Online
Distance Protection
Distance Protection
ncct
Power Cable Fault Location - Medium & High Voltage Cables
Power Cable Fault Location - Medium & High Voltage Cables
Thorne & Derrick International
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
siddiqui arshad hussain
Protection of transmission lines (distance)
Protection of transmission lines (distance)
Rohini Haridas
Relay testing procedure
Relay testing procedure
sambit mohapatra
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
Politeknik Negeri Ujung Pandang
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
J. FR
A mini project on the transmission tower
A mini project on the transmission tower
naqeeb04
HVDC vs HVAC ppt
HVDC vs HVAC ppt
Sameer Gupta
Viewers also liked
(20)
transmission line
transmission line
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
Transmission Line Automation
Transmission Line Automation
Smart grid networks and security architecture: Threat analysis, threat scenar...
Smart grid networks and security architecture: Threat analysis, threat scenar...
Short circuit monitoring by using PLC & SCADA
Short circuit monitoring by using PLC & SCADA
K.Sravanthi.
K.Sravanthi.
Gps in protection scheme
Gps in protection scheme
Practical Medium and High voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High voltage Testing of Electrical Equipment for Enginee...
Brief Literature Review on Phasor Based Transmission Line Fault Location Algo...
Brief Literature Review on Phasor Based Transmission Line Fault Location Algo...
Effective two terminal single line to ground fault location algorithm
Effective two terminal single line to ground fault location algorithm
Power Cables Operation, Maintenance, Location and Fault Detection
Power Cables Operation, Maintenance, Location and Fault Detection
Distance Protection
Distance Protection
Power Cable Fault Location - Medium & High Voltage Cables
Power Cable Fault Location - Medium & High Voltage Cables
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
Protection of transmission lines (distance)
Protection of transmission lines (distance)
Relay testing procedure
Relay testing procedure
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
FAULT DETECTION AND CLASSIFICATION ON SINGLE CIRCUIT TRANSMISSION LINE USING ...
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
A mini project on the transmission tower
A mini project on the transmission tower
HVDC vs HVAC ppt
HVDC vs HVAC ppt
Similar to Lineprotection basics june2008
Protection & switchgear
Protection & switchgear
johny renoald
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
Bhushan Kumbhalkar
Bus Bar protection
Bus Bar protection
srini09
K046016266
K046016266
IJERA Editor
Mv system neutral grounding
Mv system neutral grounding
SEKHAR BHATTACHARYA
transmission-line-protection.ppt
transmission-line-protection.ppt
ssuser0132001
Relay operation principles
Relay operation principles
Ammar Al Hakeim
Generator protection LEC 2
Generator protection LEC 2
Rahaf Waheep
Schneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
Eduardo Higino
ABB Lightning & Overvoltage Protection For Water Treatment Plants
ABB Lightning & Overvoltage Protection For Water Treatment Plants
Thorne & Derrick International
03_Prot.transmission_Line.pdf
03_Prot.transmission_Line.pdf
MohammedAAli10
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
Thien Phan Bản
FAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
Armstrong Okai Ababio
Fy3610821086
Fy3610821086
IJERA Editor
Busbar protection LEC 2.pptx
Busbar protection LEC 2.pptx
Rahaf Waheep
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf
Thien Phan Bản
class on Protection.pptx
class on Protection.pptx
SubhroSen9
Transformers Protection
Transformers Protection
Power System Operation
Distance Protection.ppt
Distance Protection.ppt
RaviKumar400685
Generator Transformer Protections.
Generator Transformer Protections.
Nischal Popat
Similar to Lineprotection basics june2008
(20)
Protection & switchgear
Protection & switchgear
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
Bus Bar protection
Bus Bar protection
K046016266
K046016266
Mv system neutral grounding
Mv system neutral grounding
transmission-line-protection.ppt
transmission-line-protection.ppt
Relay operation principles
Relay operation principles
Generator protection LEC 2
Generator protection LEC 2
Schneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
ABB Lightning & Overvoltage Protection For Water Treatment Plants
ABB Lightning & Overvoltage Protection For Water Treatment Plants
03_Prot.transmission_Line.pdf
03_Prot.transmission_Line.pdf
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
os-exe3-23-may2011-sr-i-776s21tr-lineprotection-120425095503-phpapp02 (2).ppt
FAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
Fy3610821086
Fy3610821086
Busbar protection LEC 2.pptx
Busbar protection LEC 2.pptx
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf
class on Protection.pptx
class on Protection.pptx
Transformers Protection
Transformers Protection
Distance Protection.ppt
Distance Protection.ppt
Generator Transformer Protections.
Generator Transformer Protections.
Recently uploaded
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
ranjana rawat
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
upamatechverse
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Suman Mia
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
RajkumarAkumalla
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
9953056974 Low Rate Call Girls In Saket, Delhi NCR
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
KurinjimalarL3
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
null - The Open Security Community
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Dr.Costas Sachpazis
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
Soham Mondal
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Dr.Costas Sachpazis
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
humanexperienceaaa
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
ranjana rawat
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur High Profile
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
wendy cai
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
soniya singh
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
Suhani Kapoor
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
ranjana rawat
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
Tsuyoshi Horigome
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
ranjana rawat
Recently uploaded
(20)
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
Lineprotection basics june2008
1.
©ABBGroup-1- 19-Mar-08 Line Protection
2.
©ABBGroup-2- 19-Mar-08 Line Protection Electrical faults
in the power system Transmission lines 85% Busbar 12% Transformer/ Generator 3% 100%
3.
©ABBGroup-3- 19-Mar-08 Line Protection Fault types Transient
faults are common on transmission lines, approximately 80-85% lightning are the most common reason can also be caused by birds, falling trees, swinging lines etc. will disappear after a short dead interval Persistent faults can be caused by a broken conductor fallen down can be a tree falling on a line must be located and repaired before normal service
4.
©ABBGroup-4- 19-Mar-08 Line Protection Fault types
on double circuit lines Simultaneous and Interline faults On parallel line applications a problem can occur with simultaneous faults. A full scheme relay is superior when the protection is measuring two different fault types at the same time. L1 L3 L3 L1 L2 L2 ~~ Z < L2- N L1- N
5.
©ABBGroup-5- 19-Mar-08 Line Protection Main requirements
on line protection are: • SPEED • SENSITIVITY • SELECTIVITY • DEPENDABILITY • SECURITY
6.
©ABBGroup-6- 19-Mar-08 Line Protection Measuring principles Over
current protection Differential protection Phase comparison Distance protection Directional- wave protection
7.
©ABBGroup-7- 19-Mar-08 Line Protection Over current
protection Are normally used in radial networks with system voltage below 70 kV where relatively long operating time is acceptable. On transmission lines directional or non-directional over current relays are used as back-up protections. I > I > I > I > block
8.
©ABBGroup-8- 19-Mar-08 Line Protection Dependent Time
Overcurrent Relays CHARACTERISTICS OF DEPENDENT TIME OVERCURRENT RELAYS 0.1 1.0 10.0 100.0 1 10 100 Current (multiple of setting) OperateTime[s] Long Time Inverse Extremely Inverse Normal Inverse Very Inverse
9.
©ABBGroup-9- 19-Mar-08 Line Protection Two or
Three Phase Over current Relays Two phase over current relays and one residual over current relay give complete protection on power lines and cables A third phase relay provides back-up protection In case of a D/Y-connected transformer, the fault current in one phase may be twice that in the other two phases and it may be necessary to provide three phase over current relays
10.
©ABBGroup-10- 19-Mar-08 Line Protection Directional Over
current Relays Relays on radial lines do not need directional element Directional elements are useful on parallel lines, on looped lines, and in meshed networks
11.
©ABBGroup-11- 19-Mar-08 Line Protection Directional Residual
Overcurrent Relays Reverse operation Forward operation Upol -3U03I0D 0.6 3I0Dx 3I0 > φφφφ = the characteristic angle of zero sequence source impedance φ=65φ=65φ=65φ=65
12.
©ABBGroup-12- 19-Mar-08 Line Protection Directional Residual
Overcurrent Relays Residual voltage polarization requires a sensitive directional element Third harmonics in voltage must not cause incorrect operation of the directional element
13.
©ABBGroup-13- 19-Mar-08 Line Protection Pilot wire
differential protection Pilot wires can be in soil or on towers. The resistance in the wires will limit the use on longer lines. The use is mostly restricted to distances up to 10 km. High sensitivity Can be used on short lines Very useful on series compensated lines Insensitive to power swing Weak source no problem Why differential protection?
14.
©ABBGroup-14- 19-Mar-08 Line Protection Idiff =
Delta Current = 0 Differential protection - operating principle Idiff = Delta Current > 0
15.
©ABBGroup-15- 19-Mar-08 Line Protection Digital differential
communication Digital communication with optical fibers or by multiplexed channels L1 L2 L3 DL1 DL2 DL3 DL1 DL2 DL3
16.
©ABBGroup-16- 19-Mar-08 Line Protection Phase comparison Phase
comparison relays compare the angle difference between the two currents at both ends of the line. The measured time for zero crossing is transmitted to the other end. Normally a start criteria is added to the phase angle requirement. I1 I2 e 1 e 2 e 2 e1 - φφφφ > φφφφ > I1 I2 load I2 I2 I1func- tion αααα αααα φφφφ φφφφ
17.
©ABBGroup-17- 19-Mar-08 Line Protection Directional wave
protection The basic principle of directional wave protection is to observe the polarities of the instantaneous change in voltage and current. Here by one can determine the direction of a fault with respect to the location of the measurement. Tripping is achieved when both protections detects a fault in forward direction. ~ ~ A B F I U + + - - - + + - Trip 0 0 1 1
18.
©ABBGroup-18- 19-Mar-08 Line Protection Why: Local current
and voltage: No need for communication Fault on protected line: Reach independent of fault current level Impedance characteristics can be chosen with different reach for different impedance phase angles. Enables remote back-up protection Application of distance protection
19.
©ABBGroup-19- 19-Mar-08 Line Protection The principle
of distance protection ZK=Uk/ Ik Uk=0Uk IkZ< A B metallic faultZk The impedance is proportional to the distance!
20.
©ABBGroup-20- 19-Mar-08 Line Protection The principle
of distance protection • Power lines have impedances of 0,3- 0,4 ohm/ km and normal angles of 80 - 85 degrees in a 50Hz systems. • The line impedance may have to be converted to secondary values with the formula: A Z< B Z< ZL=R+jX Zsec= VTsec VTprim CTsec CTprim Zprimx x
21.
©ABBGroup-21- 19-Mar-08 Line Protection Fault resistance multi-phase
faults consists only of arc resistance earth faults consists of arc and tower footing resistance L1 L3 L3 L1 L2 L2 Footing resistance Rarc = 28707 x L 1.4 I Warrington´s formula L= length of arc in meters I= the actual fault current in A
22.
©ABBGroup-22- 19-Mar-08 Line Protection Application of
distance protection A Z< B Z< C t1 t2 t3 Distance protection has different functional zones with different impedance reaches With a combination of distance reach setting and functional delay for each zone selectivity is relatively easy to achieve.
23.
©ABBGroup-23- 19-Mar-08 Line Protection A B
C t1 t2 t3 t1 t2 t3 Z< Z< Z< Z< Application of distance protection
24.
©ABBGroup-24- 19-Mar-08 Line Protection A B
C f1 f2 t1 t2 t3 t1 t2 t3 Z< Z< Application of distance protection
25.
©ABBGroup-25- 19-Mar-08 Line Protection A B
C f3 t1 t2 t3 t1 t2 t3 Z< Z< Z< Z< Application of distance protection
26.
©ABBGroup-26- 19-Mar-08 Line Protection Design of
distance protection Switched scheme consists of a start relay which detects the type of fault and select (switch) the measuring loop to the single measuring relay. The relevant loop voltages and currents are switched to the measuring unit. Full scheme has a measuring element for each measuring loop and for each zone ~~ Z< L2-N L1-N
27.
©ABBGroup-27- 19-Mar-08 Line Protection Requirements on
Distance relay Zones Zone-1 Must not overreach Zone-2 Must overreach Must co-ordinate with next section Provides back-up for the next busbar Provides back-up for the first part of next line Zone-3 Can provide back-up for next line Can provide back-up for next busbar In feed of fault current at the remote busbar affects the effective reach of the overreaching zones
28.
©ABBGroup-28- 19-Mar-08 Line Protection Measuring loop
for earth faults The distance protection relays are always set based on the phase impedance to the fault Zs RL XL RN XN The measured Impedance is a function of positive and zero sequence impedance IL1 UL1 IN
29.
©ABBGroup-29- 19-Mar-08 Line Protection Measuring loop
for two- phase faults The distance protection relays are always set based on the phase impedance to the fault Zs RL XL UL1-L2 IL1 IL2 The measured impedance is equal to the positive sequence impedance up to the fault location
30.
©ABBGroup-30- 19-Mar-08 Line Protection Measuring loop
for three- phase faults • The distance protection relays are always set based on the phase impedance to the fault Zs RL XL UL1 IL1 IL2 The measured impedance is equal to the positive sequence impedance up to the fault location IL3UL2 UL3
31.
©ABBGroup-31- 19-Mar-08 Line Protection The earth
fault measurement U= I1Z1+I0Z0+I2Z2 Z1=Z2 U= Z1( I1+I2+I0 ) +I0Z0 -I0Z1 I= I1+I2+I0 U=I Z1+I0 ( Z0 - Z1 ) 3I0=IN U=IZ1+IN( Z0 - Z1 3 )U=I Z1+ IN 3 ( Z0 - Z1 )
32.
©ABBGroup-32- 19-Mar-08 Line Protection The earth
fault measurement The current used is thus the phase current plus the residual current times a factor KN = (Z0-Z1) / 3Z1, the zero sequence compensation factor. The factor KN is a transmission line constant and Z0/ Z1 is presumed to be identical throughout the whole line length. (1+KN) Z1 gives the total loop impedance for the earth fault loop for single end infeed.
33.
©ABBGroup-33- 19-Mar-08 Line Protection Measurement Loops Fault
Voltage Current R-Earth VR IR +Kn⋅3I0 S-Earth VS IS +Kn⋅3I0 T-Earth VT IT +Kn⋅3I0 R- S VR - VS IR - IS S- T VS - VT IS - IT T- R VT - VR IT - IR R- S- T Anyphase-earthvoltage anyphase-phasevoltage Correspondingphasecurrent Correspondingphase-phasecurrent R- S- T- Earth Anyphase-earthvoltage anyphase-phasevoltage Correspondingphasecurrent Correspondingphase-phasecurrent
34.
©ABBGroup-34- 19-Mar-08 Line Protection Directional measurement When
a fault occurs close to the relay location the voltage can drop to a value where the directional measurement can not be performed. Modern distance protection relays will instead use the healthy voltage e.g. for L1- fault the voltage UL2-L3, shifted 90 degrees compared to UL1. This cross polarisation is used in different proportions between healthy and faulty phases in different products. At three- phase fault close to the station all phase voltages are low and cross polarisation is not of any use. Instead a memory voltage is used to secure correct measurement.
35.
©ABBGroup-35- 19-Mar-08 Line Protection Distance protection
on short lines Distance protection with mho characteristic can not see an average fault resistance RF XF jX R
36.
©ABBGroup-36- 19-Mar-08 Line Protection Distance protection
on short lines Quadrilateral characteristic improves sensitivity for higher RF/XF ratio It still has some limitations: the value of set RF/XF ratio is limited to 5 jX RXF RF
37.
©ABBGroup-37- 19-Mar-08 Line Protection Distance protection
on short lines Overreaching permissive schemes increase the sensitivity Weak infeed logic for very high fault resistance Independent underreaching zone 1 gives additional advantage jX R RF XF
38.
©ABBGroup-38- 19-Mar-08 Line Protection Distance protection
on long lines Load impedance limits the reach in resistive direction High value of RF/XF ratio is generally not necessary Circular (mho) characteristic Has no strictly defined reach in resistive direction Needs limitations in resistive direction (blinder) R jX
39.
©ABBGroup-39- 19-Mar-08 Line Protection Double end
infeed I1 I2 UF RF UF = RF ( I1 + I2 ) RF ( I1 + I2 ) RF1= I1 U1 U2 I Load
40.
©ABBGroup-40- 19-Mar-08 Line Protection Resistive fault,
double end fed ZSCA ZSCBk ZL (1-k) ZL Rf + EA - + EB - IA IB VA f A BA L A A A R I II Zk I V Z ⋅ + +⋅==( ) fBAALA RIIIZkV ⋅++⋅⋅= The fault has more or less fault resistance. If the fault is an arcing fault the fault resistance is normally very small. The influence of the fault resistance depends on the fault current infeed from the remote line end.
41.
©ABBGroup-41- 19-Mar-08 Line Protection Resistive fault,
double end fed f A BA LA R I II ZkZ ⋅ + +⋅= The fault resistance seen by the distance protection can be increased compared to its real value. fR f A BA R I II ⋅ + LZk⋅ UNDERREACH!
42.
©ABBGroup-42- 19-Mar-08 Line Protection Resistive fault,
double end fed f A BA LA R I II ZkZ ⋅ + +⋅= There is a risk that zone 1 will trip for faults outside its border. fR f A BA R I II ⋅ + LZk⋅ OVERREACH! The apparent fault resistance can also get a phase shift, depending on the load conditions before the load.
43.
©ABBGroup-43- 19-Mar-08 Line Protection Compensation of
overreach in Zone1 due to load ph - E R X Fault resistance reach influence Zone 1 of the REL 5XX/REL 670 terminal has a compensation of the characteristic due to the overreach caused by the load current. In case of active power out from the station the characteristic is automatically tilted. This is valid only for Ph-E loops.
44.
©ABBGroup-44- 19-Mar-08 Line Protection Remote faults Due
to current contribution If2 and If3 in substation B, the distance protection in station A will measure a higher impedance than the "true" impedance to the fault. The relay will thus underreach and this means in practice it can be diffcult to get a remote back-up. Z< If 1 If 2 If 3 If=If1+If2+If3 ZL ZF A B Um Um= If1 x ZL+ (If1+If2+If3) x ZF
45.
©ABBGroup-45- 19-Mar-08 Line Protection Zero- sequence
mutual coupling on parallel lines ZA< overreaching ZB< underreaching ~ ZOM ZL ZL ~ ZA< ZB< ~ ~
46.
©ABBGroup-46- 19-Mar-08 Line Protection Parallel line
out of service and earthed at both ends ∆∆∼ ∼ ∆Z = - ZL KOM • ZOM / ZOL 1 + KO • = - 0.23 ZL
47.
©ABBGroup-47- 19-Mar-08 Line Protection Parallel line
in Service ∆Z = ∼ ∆ D KOM 1 + KO • ZL = 0.38 ZL
48.
©ABBGroup-48- 19-Mar-08 Line Protection Distance relay
settings for parallel lines The influence of zero sequence coupling can be compensated in two different ways Different K factor for different Zones within same group setting parameters Different groups of setting parameters for different operating conditions
49.
©ABBGroup-49- 19-Mar-08 Line Protection Communication equipment Power
line carrier (PLC) equipment is based on a capacitive connection of signals with frequency in range 50- 500 kHz on the power line. Radio link is a good and reliable communication equiment, but is rarely used due to the high cost. Optical fibres have the advantage to be insensitive to noise and can transmit a huge amount of information.
50.
©ABBGroup-50- 19-Mar-08 Line Protection Permissive schemes. PermissivePermissive UnderreachUnderreach OverreachOverreach permission
to trip instantaneously to an overreaching zone. The permission is sent by an Under reaching zone The permission is sent by an Overreaching zone
51.
©ABBGroup-51- 19-Mar-08 Line Protection Permissive underreaching
scheme CS = ZM1 Trip = ZM1 + ZM2 *(T2 + CR) +ZM3 * T3 ZM2, T2 ZM1, T1 A B ZM2, T2 ZM1, T1 Permission is sent by an Underreaching zone (ZM1) Permission to trip instantaneously to an overreaching zone (ZM2). If B has a weak source, it could not see the fault and fail to send the carrier to A.
52.
©ABBGroup-52- 19-Mar-08 Line Protection Permissive communication
schemes Communication signal carrier send (CS) is sent to remote end when the fault is detected in forward direction. Tripping is achieved when the commmunication signal carrier receive (CR) is received and the local relay has detected a forward fault. In a permissive underreaching scheme the communication signal is sent from a zone that underreaches the remote end. In a permissive overreaching scheme the communication signal is sent from a zone that overreaches the remote end. A Z< Z< B Carrier send CS = Z< forward, under or overreach Trip = ZM1 + ZM2 (t2 + CR) + ZM3 x t3
53.
©ABBGroup-53- 19-Mar-08 Line Protection Permissive Underreach
Distance Protection
54.
©ABBGroup-54- 19-Mar-08 Line Protection Permissive overreaching
scheme CS = ZM2 Trip = ZM1 + ZM2 *(T2 + CR) +ZM3 * T3 A B Permission is sent by an Overreaching zone (ZM 2) Permission to trip instantaneously to an overreaching zone (ZM2). The carrier is sent by both relays for faults on the whole line. ZM2, T2 ZM1, T3 ZM3, T3 ZM2, T2 ZM1, T1 ZM3, T3 Good for weak-end infeed. Echo carrier signal is sent back from B if a carrier has been received but no fault detected in ZM1, ZM2 and ZM3.
55.
©ABBGroup-55- 19-Mar-08 Line Protection Permissive Overreach
Distance Protection
56.
©ABBGroup-56- 19-Mar-08 Line Protection Permissive overreaching
schemes are adopted for short lines( Also called directional comparison schemes) Advantages are • Better performance for high resistance faults. • Superior to pilot wire as digital decisions are exchanged and not analogue • Superior to phase comparison which requires faithful transmission of phase information. Permissive Overreach Distance Protection
57.
©ABBGroup-57- 19-Mar-08 Line Protection Blocking communication
schemes Communication signal (CS) is sent to remote end when the fault is detected in the reverse direction. Tripping is achieved when this blocking signal is not received within a time T0 (20-40 ms) and the local relay has detected a fault in the forward direction. A Z< Z< B Carrier send CS = Z< reverse zone Trip = ZM1 + ZM2 (t2 + CR x T0) + ZM3 x t3
58.
©ABBGroup-58- 19-Mar-08 Line Protection Blocking overreaching
scheme ZM2, T2 ZM1, T1 A B Block signal is sent by the reverse zone (Zone 3) Overreaching inst. zone to be Blocked by a block signal). • Carrier is sent when the line is healthy • Good for short lines, where it is impossible to set 80-90% of the line length. • Series compensated lines ZM3, T3 CS = ZM3 Trip = ZM1 + ZM2 * TCR* CR+ (ZM3 * T3 + ZM2 * T2) ZM2, T2 ZM1, T1 ZM3, T3 Waiting time for the block signal (tCoord) Block signal.
59.
©ABBGroup-59- 19-Mar-08 Line Protection Blocking Overreach
Distance Protection
60.
©ABBGroup-60- 19-Mar-08 Line Protection This function
is based on condition 3Uo > 20 % of Un / √√√√ 3 and 3Io < 20 % of In It can be selected to block protection and give alarm or just to give alarm. Fuse fail supervision is blocked for 200ms following Line energisation in order not to operate for unequal pole closing and also during auto-reclosing. MCB can also be used. FUSE FAIL SUPERVISION
61.
©ABBGroup-61- 19-Mar-08 Line Protection Switch On
To Fault (SOTF) When energizing a power line onto a forgotten earthing, no measuring voltage will be available and the directional measuring can thus not operate correctly. A special SOTF function is thus provided. Different principles can be used, from one phase current to non-directional impedance measuring. Z< U=0 V SOTF condition can either be taken from the manual closing signal activating the (BC) input or it can be detected internally by a logic.
62.
©ABBGroup-62- 19-Mar-08 Line Protection A power
swing can start by sudden load change or due to a fault somewhere in the network. Close to the centre of the power swing, low voltage and thus low impedance will occur. A distance protection relay must then be blocked during the power swing. This can be done by measuring the transit time of the impedance locus passing two dedicated impedance zones. Normally the time used is 35-40 ms. Power Swing Blocking function
63.
©ABBGroup-63- 19-Mar-08 Line Protection Power Swing
Blocking function ∆∆∆∆t ∆∆∆∆t = 40 ms X R Power swing locus
64.
©ABBGroup-64- 19-Mar-08 Line Protection • When
power swing detection unit operates any impedence zone can be selected to be blocked or not as required. • Operation of power swing detection unit is inhibited when zero sequence current is detected. This feature is included to ensure tripping of high resistance earth faults where fault resistance can decrease slowly. • The residual current inhibit condition ensure PSD will not block due to unbalanced load or residual current experienced with un-transposed transmission lines. Power Swing Blocking function
65.
©ABBGroup-65- 19-Mar-08 Line Protection Stub protection
function It is not possible for the distance protection relay to measure impedance when the line disconnector is open. Not to risk incorrect operation the distance protection must be blocked and a Stub protection is released. The Stub protection is a simple current relay. line disc open I STUB > & trip 25ms Bus A Bus B > Z+
66.
©ABBGroup-66- 19-Mar-08 Line Protection Current reversal
logic ~~ A: 1 B: 1 A: 2 B: 2 ~~ A: 1 B: 1 A: 2 B: 2 Permissive overreaching schemes can trip healthy line without C.R.L 1 Fault occurs on line 1 Fault detection by protection A:1 B:1 and A:2 2 Relay B:1 trips CB and sends carrier to A:1 Relay A:2 sees fault in forward direction and sends carrier to B:2 3 Fault cleared at B:1, current direction changed on line 2 4 Carrier from A:2 and forward looking measuring element in relay A:2 does not reset before relay B:2 detects the fault in forward direction and trips, also relay A:1 will trip when receiving carrier from B:1 C.R.L allows slowly resetting communication equipment without risking to tripping the healthy line.
67.
©ABBGroup-67- 19-Mar-08 Line Protection Simultaneous faults
68.
©ABBGroup-68- 19-Mar-08 Line Protection On parallel
line applications a problem can occur with simultaneous faults. A full scheme relay is superior when the protection is measuring two different fault types at the same time. Simultaneous faults
69.
©ABBGroup-69- 19-Mar-08 Line Protection Weak end
infeed Weak end infeed is a condition which can occur on a transmission line, either when the circuit breaker is open, so there is no current infeed from that line end, or when the current infeed is low due to weak generation behind the protection. lt1 t2 t3 CS = ZM2 TRIP = ZM1 + ZM2(CR + t2) CS (echo)=CR x low voltage x no start forward or reverse Z< Z<CS CS (echo) CR CR
70.
©ABBGroup-70- 19-Mar-08 Line Protection ∼∼∼∼∼∼∼∼ ∼∼∼∼ - + L F A B IA I F I B ZA
ZB RF pZL ( I - p )ZL pZL ( 1- p ) ZL ZA ZB Fault Locator Measuring Principle UA=IA X P ZL + IFA X RF DA DA = (I-P) ZL +ZB ZA+ZL +ZB
71.
©ABBGroup-71- 19-Mar-08 Line Protection Series compensated
system • Correct direction discrimination at voltage reversal (negative fault reactance) • variation in resulted line impedance Consideration for line distance protections BA F1 X =70%C X =100%l R jX A B B´ 70% 100% gap not flashed gap flashed
72.
©ABBGroup-72- 19-Mar-08 Line Protection
73.
©ABBGroup-73- 19-Mar-08 Line Protection (i) Zone-I:
to be set to cover 80-85% of protected line length (ii) Zone II: to be set to cover minimum 120% of length of principle line section. However, in case of D/C lines 150% coverage must be provided to take care of, under reaching due to mutual coupling effect but, care is to be taken that it does not reach into next lower voltage level. 3.0 SETTING CRITERIA3.0 SETTING CRITERIA 3.1 Reach settings of distance protection3.1 Reach settings of distance protection
74.
©ABBGroup-74- 19-Mar-08 Line Protection (iii) Zone-III: For
400kV lines Zone-III to be set to cover 120% of principle section plus adjacent longest section subject to a reach restriction so that it does not reach into next lower voltage level. For 220 kV lines, Zone-III reach may be provided to cover adjacent longest section if there is no provision of LBB or all protection are connected to single DC source at remote end substation. (iv) Resistive reach should be set to give maximum coverage subject to check of possibility against load point encroachment considering minimum expected voltage and maximum load. Attention has to be given to any limitations indicated by manufacturer in respect of resistive setting vis-a-vis reactance setting.
75.
©ABBGroup-75- 19-Mar-08 Line Protection • A
Zone-II timing of 0.3 second is recommended. If a long line is follow- ed by a short line, then a higher setting may be adopted on long line to avoid indiscriminate tripping through Zone-II operation on both lines. • Zone-III timer should be set so as to provide discrimination with the operating time of relays provided in subsequent sections with which Zone- III reach of relay being set overlaps. 3.2 Time setting of distance protection3.2 Time setting of distance protection
76.
©ABBGroup-76- 19-Mar-08 Line Protection 3.3.1 • Low
set voltage may be set at 110% with a typical time delay of 5 seconds. • A time grading of 1 second may be provided between relays of different lines at a station. • Longest time delay should be checked with expected operating time of overfluxing relay of the transformer to ensure disconnection of line before tripping of transformer. 3.3.2 • High set stage may be set at 150% with a time delay of 100 m second. 3.3 O / V Protection3.3 O / V Protection
77.
©ABBGroup-77- 19-Mar-08 Line Protection • Decisions
pertaining to allowing which Zone to trip and which to block should be taken based on system studies on case to case basis. 3.4 Power Swing Blocking Function Associated with Distance Relays3.4 Power Swing Blocking Function Associated with Distance Relays
78.
©ABBGroup-78- 19-Mar-08 Setting of Protections (distance
relays)
79.
©ABBGroup-79- 19-Mar-08 Line Protection Zone-1 Offers instantaneous
circuit-local back-up protection for nearby faults, but not for the entire transmission circuit from both terminals. Set to under reach protected circuit to ensure external security In case of parallel circuit may be necessary to increase degree of under reach For multi circuit lines reach reduces further due to in feeds
80.
©ABBGroup-80- 19-Mar-08 Line Protection Zone-2 Reach
Setting Criteria Should overreach all terminals of the protected circuit by an acceptable margin (typically 20% of highest impedance seen) for all fault conditions and for all intended modes of system operation. As far as possible, should be less than Zone-1 coverage of all adjacent lines, to minimize the required Zone-2 time delay setting.
81.
©ABBGroup-81- 19-Mar-08 Line Protection Zone-2 reach
setting
82.
©ABBGroup-82- 19-Mar-08 Line Protection Zone-2 Zone-2 time
Setting Criteria Must be set to coordinate with clearance of adjacent circuit faults, within reach, by the intended main protection or by breaker fail protection tZ2 = Required Zone-2 time delay tMA = Operating time of slowest adjacent circuit main protection or Circuit Local back-up for faults within Zone-2 reach tCB = Associated adjacent circuit breaker clearance time tZ2reset= Resetting time of Zone-2 impedance element with load current Present tS = Safety margin for tolerance (e.g. 100ms) sresetzCBMAz ttttt +++> 22
83.
©ABBGroup-83- 19-Mar-08 Line Protection Zone-2 Effect of
parallel lines Where common impedance settings exist for phase and ground fault impedance elements, or where independent residual compensation settings are not available for each zone of protection the phase fault Zone-2 reach will unavoidably be extended in order to satisfy ground fault reach requirements. This can create Zone-2 back-up co-ordination difficulties, particularly where adjacent sections or transmission circuit are of unequal length
84.
©ABBGroup-84- 19-Mar-08 Line Protection Zone-2 Multi terminal
circuits The primary Zone-2 setting criterion must be met with allowance for the highest apparent impedance seen for a fault at any remote circuit terminal. The Zone-2 reach setting may reach very high percentage of the circuit impedance between the closest terminals. The reach may need to be further enhanced to address under reach for ground faults when protecting parallel multi-terminal circuits.
85.
©ABBGroup-85- 19-Mar-08 Line Protection Zone-2 in
multi-terminal lines
86.
©ABBGroup-86- 19-Mar-08 Line Protection Zone-2 Load encroachment One
problem with mho impedance elements is that the fault resistance coverage varies with the forward reach setting. When applying Zone-1 elements to short lines, fault resistance coverage may be insufficient. It can also be disadvantage for Zone–2 elements to be set with unusually high forward reach setting in relation to the minimum load impedance. It may be possible for the minimum load impedance to encroach upon the Zone-2 operating region.
87.
©ABBGroup-87- 19-Mar-08 Line Protection Zone-2 load
encroachment
88.
©ABBGroup-88- 19-Mar-08 Line Protection Zone-3 Remote
back-up General Usually set to provide remote back-up protection for adjacent sections of a transmission circuit. May have independently adjustable forward and reverse reach setting Usually forward reach provides remote back-up protection. With duplicate main protection, there may be a case for not applying Zone-3 remote back-up protection at all. In case of long 400kV lines it may be desirable either to reduce the reach or to block 3rd zone of distance relay for reasons of security.
89.
©ABBGroup-89- 19-Mar-08 Line Protection Zone-3 remote
back-up Reach setting Zone –3 should overreach the remote terminal of the longest adjacent line by an acceptable margin (typically 20% of highest impedance seen) for all fault conditions and in feed conditions associated with all intended modes of system operation Zone-3 reach should be less than the Zone-2 protection coverage of the shortest adjacent transmission circuit and it should not see through power transformers into distribution systems, in order to minimize the required zone-3 time delay setting.
90.
©ABBGroup-90- 19-Mar-08 Line Protection Zone-3 remote
back-up Time setting Must be set to co-ordinate with clearance of faults by adjacent circuit-local back-up protection. Zone-2 distance protection or time delayed over current protection The following formula would be the basis for determining the minimum acceptable Zone-3 time setting: Where: tZ3 = Required Zone-3 time delay tMA = Operating time of slowest adjacent circuit local back-up protection tCB = Associated adjacent circuit breaker clearance time tZ3reset = Resetting time of Zone-3 impedance element with load current present tS = Safety margin for tolerance (e.g. 100ms) sresetzCBMAz ttttt +++> 33
91.
©ABBGroup-91- 19-Mar-08 Line Protection Zone-3 remote
back-up Consideration of mutual coupling As for Zone-2 protection the under reaching effect of zero sequence mutual coupling for remote ground faults must also be considered. Such consideration is quite complex, since there may well be differences in the levels of mutual coupling for the protected circuit and any number of adjacent circuits. In addition, some circuit sections may be multi- circuit while other sections may not be.
92.
©ABBGroup-92- 19-Mar-08 Line Protection Zone-3 remote
back-up Considerations for intervening fault currents The under reaching effects are encountered in relation to adjacent circuit impedance, when applying Zone-3 remote back-up protection. These under-reaching effects are particularly difficult to address, since they are variable according to the type of fault. Ground faults can invoke additional zero sequence current in feed from transformers with grounded star- connected primary windings and other delta-connected windings.
93.
©ABBGroup-93- 19-Mar-08 Line Protection Zone-3 remote
back-up Zone-3 load impedance encroachment Encroachment due to the minimum load impedance under expected modes of system operation and the minimum impedance that might be sustained for seconds or minutes during abnormal or emergency system situations. Use of blinders in case of Mho type of elements or by use of polygon type impedance elements. In case of long 400kV transmission lines it may be desirable to limit the reach of Zone-3 for reasons of security. In such cases, if the adjacent station has bus bar protection and breaker failure protection, Zone-3 can be dispensed with. ESKOM (South Africa) have a practice of not using third zone impedance protection in long line applications . They use enhanced local breaker back-up .
94.
©ABBGroup-94- 19-Mar-08 Line Protection Effect of
in feeds on Zone-3
95.
©ABBGroup-95- 19-Mar-08 Line Protection Zone-3 load
encroachment
96.
©ABBGroup-96- 19-Mar-08 Line Protection Zone-3 coordination
97.
©ABBGroup-97- 19-Mar-08 Line Protection Zone- 4
substation local back-up An additional zone of reverse-looking protection (e.g. Zone-4) to offer substation-local back-up protection. The Zone-4 reverse reach must adequately cover expected levels of apparent bus bar fault resistance, when allowing for multiple in feeds from other circuits. Sometimes when separate reverse looking element is not available the above is achieved by offset reach of Zone-3 of distance relay.
98.
©ABBGroup-98- 19-Mar-08 Line Protection
Download now