Introduction of LVAC Auto Change Over Scheme in DEWA
Transmission System
Owen Raymond Glynn, Jayasingh Balakrishnan, Amod Madhukar Khirwadkar, Muthusamy
Veerabahu, Pownrajan Chinnadurai, Raghavendra Upadhya Heggodlu-
Transmission Protection Department, Dubai Electricity & Water Authority.
---------------------------------------------------------------------------***---------------------------------------------------------------------------
Abstract- Dubai’s transmission power system plays a vital
role in delivering optimum reliability and uninterrupted
power. We therefore need to maintain the highest levels of
technology, operational and best design practices for all
digital systems.
This paper aims to provide the conceptual design overview
and benefits of the innovative design of LVAC Auto
Changeover Scheme in DEWA Transmission Substations
(132kV).
The existing design of LVAC switchboards (400V AC supply
for substation equipment’s) used in 132/11 KV substations
under DEWA transmission network have three buses
powered through three earthing transformers and has two
bus sections. During normal operation, all three buses in
LVAC switchboard are independently supplied by each
earthing transformer (incomer) respectively and bus sections
are in open condition. To maintain uninterruptable LVAC
supply to substation equipment’s, a PLC is used and
programmed to execute automatic switching operation of
concerned bus section / incomer breakers in case of any of
the incomer supply fails. LVAC switchboard has an Auto/
Manual switch and PLC is operational if the switch is on Auto
mode. The existing scheme has mainly two issues as below:
A) In case of outage required on any of the IDT’s, operator
intervention is required to execute switching by shifting
Auto/ Manual switch in Manual mode. Manual switching
results in loss of LVAC supply as well as generation of
several alarms through SCMS.
B) In case of switching off any IDT during LVAC in Auto
mode, switching through PLC will affect only with a time
delay results in momentary interruptions to downstream
LV circuits which generates large number of undesired
alarms in SCMS.
With an objective to eliminate momentary supply
interruptions and unwanted alarms due to that, the team has
developed new logic diagrams to facilitate high speed
Automatic changeover of LVAC supplies with minimum
allowable paralleling time for the IDT’s after study on the
risks involved during momentary paralleling. In place of PLC,
Bay Control Units (BCU) from approved OEM’s are utilized
which are in use at higher voltage levels in DEWA system.
BCU’s are having major advantages over PLC in terms of ease
and flexibility in logic buildings, programming of the device
and speed of operation.
This paper aims to provide the conceptual overview and
benefits of LVAC High speed Auto Change Over scheme
developed in house by DEWA specialists in conjunction with
specialists from the original equipment manufacturers. The
new scheme involves use of Bay Control Units in place of
PLC’s in LVAC switchgear design. The BCU’s and overall
scheme is engineered, configured and extensively laboratory
tested to ensure perfect functionality of High-Speed Auto
Change Overs in LVAC board. Utilizing the capabilities of
modern IED’s to build large numbers of user defined logic
and implementing these in innovative new ways has
produced new unique LVAC changeover scheme that enhance
functionality and reliability by eliminating discreet
components and circuitry whilst maximizing overall
efficiency by reducing supply interruptions and unwarranted
alarms during supply changeover.
This innovative initiative will ensure that DEWA will have
arguably the most advanced LVAC switchboards in its
transmission systems both regionally and globally by
introducing the latest digital technologies, optimized designs
in line with the industry leading best practices.
I. INTRODUCTION
Dubai Electricity & Water Authority (DEWA) was
established in 1992 by His Excellency Sheikh Maktoum bin
Rashid Al Maktoum with the objective to provide reliable
power to residents of the Emirate of Dubai. Since its
inception, DEWA has continuously invested in maintaining
and upgrading the power delivery infrastructure to meet
the increasing demands of the growing Emirate of Dubai.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 968
Dubai Electricity & Water Authority (DEWA) Power System
includes Generation, Transmission and Distribution
networks. The transmission network operates at 400kV and
132kV voltage levels with over 350 transmission
substations consisting of 400/132kV, 132/33kV and
132/11kV sites. LVAC switchgears are installed in all types
of transmission substations and are used to supply station
loads (station auxiliaries, air conditioning, heating, and
lighting etc.). LVAC supplies to various equipment’s and
related systems are continuously monitored by connecting
the alarms through SCMS to DEWA control center. As per
existing design, during supply changeover in LVAC, many
unwanted alarms are received. Moreover, if the LVAC
operational switch is kept in manual mode, manual
intervention is required to execute supply changeovers.
In order to overcome the above-mentioned constraints,
DEWA team has developed a high speed LVAC auto
changeover scheme which allows momentary paralleling of
transformers without any side effect thus to avoid supply
interruption. The innovative LVAC scheme under
discussions is approved for implementation in DEWA’s all
future 132/11 KV substations.
The major concerns while finalizing the scheme were as
follows:
1) 1) During any one of the IDT Switching, paralleling of
secondary side may involve circulating currents. In
order to overcome the same it is ensured that the
primary of the concerned IDT’s are already parallel and
maximum paralleling time is set as 500 msec and to
eliminate any adverse effect such as IDT circulating
currents. Moreover the LVAC busbar fault levels are
within the limits for paralleling the two LVAC incomers
(LVAC fault levels are shown in figure 1).
Figure-1: LVAC Fault Levels
2) The complications of switching LVAC breakers from
control center would have been challenging with
existing PLC, however use of Bay Control Units having
IEC 61850 communication facility found as a suitable
solution to achieve remote switching.
3) High speed changeover in case of tripping of any one
IDT was considered as a risk to other healthy IDT’s for
momentary paralleling. Hence a hybrid solution was
adapted. High speed paralleling was configured for
planned switching and low speed LVAC changeover
with 10 sec time delay was maintained for IDT
protection tripping scenarios without paralleling the
IDT’s.
II.PROBLEMS WITH EXISTING LVAC SCHEME
Existing LVAC Single Line Diagram
The salient features specified for the existing LVAC scheme
related to supply changeover scheme are as below:
1) The substation shall be provided with three auxiliary
supplies derived from the three earthing transformers
2) Normally three sections (Bus 1, 2, 3) of the main LVAC
switchboard shall be supplied via the associated main
incoming circuit breakers with both the bus section
breakers in open condition.
3) Electrical interlock shall be provided such that it shall not
be possible to parallel any two transformers both on
Auto and Manual mode of operations.
4) Only one Auto/Manual switch common to all 5 ACBs
shall be provided, and operation logic shall be submitted
for DEWA approval.
5) If a fault occurs on a section of the busbars the relevant
circuit breaker shall open to isolate the faulty section and
any auto-changeover on to a faulty section shall be
inhibited.
6) When selected on manual mode no automatic
changeover shall occur.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 969
7) SCADA alarms are hardwired since the existing PLC
devices are not capable to send alarms directly to SCMS
system.
It is evident from the above-mentioned specification clauses
that paralleling of transformers was not permitted and
manual operations are required for supply changeover
during planned outages on any one of the IDT’s.
Moreover, momentary supply interruption will results in
several unwanted alarms from associated LVAC circuits to
SCMS.
III. High Speed Auto Changeover Scheme
The high-speed auto changeover (ACO) scheme is
implemented by redesigning the LVAC control system as
follows:
1. Auto Changeover (ACO) can be enabled or disabled
using the existing auto/ manual switch.
2. The ACO is completely autonomous requiring no action
from TCC or HMI.
3. Detection of IDT1 switching out: (the same is applicable
for IDT2 & IDT3)
a) Detect IDT1 132kV CB Open command (switching
out IDT1).
b) Initiate auto changeover of LVAC Bus 1.
c) Close BS1 and Open Incomer 1 (Aux contact of BS1
Opens IC1 to achieve coordinated high speed
switching).
4. Detection of IDT1 switching back into service:
a) 132kV CB Closed and LVAC supply healthy for 5
seconds.
b) Initiates restore of LVAC Bus 1 to normal supply.
c) Close Incomer 1 and then open BS1 (Aux contact of
IC1 opens BS1 to achieve coordinated high-speed
switching).
5. Duration of paralleling is kept to minimum
(milliseconds) therefore no overload concerns.
IDT1 Switching – ACO Scenario is shown in Figure-2.
Figure-2: IDT1 Switching
A. ACO Logic
Sample logic – LVAC Incomer CB close
Sample logic – LVAC Incomer CB Open
B. Methodology: The steps undertaken for
implementing the LVAC changeover scheme are as
explained below:
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 970
1) Existing LVAC logic and schematic diagrams are
thoroughly studied by the team and based on it,
new logics are prepared to incorporate hybrid
changeover scheme. One high speed logic for
routing switching of IDT’s and other slow logic
for IDT tripping cases.
2) PLC was proposed to be replaced with modern
and sophisticated BCU’s.
3) The proposal was presented to DEWA
Transmission Power Technical Committee and
approval was received.
4) BCU input /output requirements were finalized
and accordingly, Generic wiring diagrams were
prepared.
5) DEWA approved OEM’s (SEL, Hitachi, GE and
Siemens) were approached to finalize suitable
BCU device.
6) M/s Hitachi REC 670 and SEL451 BCU’s found
most suitable for this application.
7) Extensive laboratory testing was performed on
these BCU’s considering all network conditions
in presence of DEWA stakeholder departments
and BCU settings and configurations were
finalized.
8) Based on successful evaluation of the BCU’s,
tender documents were updated to include High
Speed Automatic changeover.
C. Advantages of the High-Speed Auto Changeover
Scheme
The new innovative LVAC design provides significant benefits
to DEWA as a utility. The new design for 132/11kV
substations includes the following advantages:
 Eliminate momentary interruption of LVAC supply
during IDT outage or switching
 The Scheme is completely autonomous.
 Fast switching avoids exposure to circulating
currents.
 It is a cost-effective design improvement due to less
number of components and wiring.
 Eliminate unwanted alarms during IDT outage.
 Increased digitization due to elimination of hard
wiring (BCU option). BCU is directly connected to
SCADA system and all LVAC related alarms are send
to SCADA via IEC61850 protocol.
 BCU’s are having major advantages over PLC in terms
of ease and flexibility in logic buildings, programming
of the device and speed of operation.
IV. CONCLUSION
Implementing a high-speed auto changeover (ACO) will
avoid interruption of LVAC supply in the event of switching
IDT’s in and out of service. This will in turn avoid
unnecessary supply interruption, associated alarms and
improve reliability of equipment.
The high speed ACO avoids the need for operator
intervention and avoids exposure to overload since
paralleling is extremely short in duration.
The proposed ACO scheme was configured and tested with
different OEM BCU. All the test scenario was simulated and
passed. Hence the same concept can be implemented
wherever applicable.
BCU is the preferred option rather than the PLC.
V. REFERENCES
[1] Aster A. Roy, Gesa F. Newton & Aondoakaa I. Solomon:
“Design and Implementation of a 3-Phase Automatic Power
Change-Over Switch” published in American Journal of
Engineering Research (AJER) Vol-3, Issue-9, pp-07-14
[2] Scott Manson and Saurabh Shah “Automated Power
Management Systems for Power Consumers with On-site
Generation” Available on SEL website, SEL Inc. Pullman
[3] Scott M. Manson, Ashish Upreti and Michael Thompson
Available on SEL website, SEL Inc. Pullman
[4] Stefan Meier, Thomas Werner, “Performance
considerations in digital substation applications” white
paper presented at PAC World UK 2015.
[5] Greg Rzepka, Scott Wenke, Sarah Walling, “Choose
Simplicity for a Better Digital Substation Design”, 70th
Annual Conference for Protective Relay Engineers, Texas,
April-2017.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072

More Related Content

Similar to Introduction of LVAC Auto Change Over Scheme in DEWA Transmission System

The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...Power System Operation
 
switching substation, plcc and scada
switching substation, plcc and scadaswitching substation, plcc and scada
switching substation, plcc and scadaHemendra Kumar Rajput
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsEnergyTech2015
 
TRANSFORMER HEALTH MONITORING SYSTEM
TRANSFORMER HEALTH MONITORING SYSTEMTRANSFORMER HEALTH MONITORING SYSTEM
TRANSFORMER HEALTH MONITORING SYSTEMIRJET Journal
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4AxelDijksman
 
A review on hvdc circuit breakers
A review on hvdc circuit breakersA review on hvdc circuit breakers
A review on hvdc circuit breakersJuly Carranza
 
POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...
POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...
POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...IRJET Journal
 
Doc a.7-tlc report
Doc a.7-tlc reportDoc a.7-tlc report
Doc a.7-tlc report9951081577
 
IRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta Converter
IRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta ConverterIRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta Converter
IRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta ConverterIRJET Journal
 
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...IJMREMJournal
 
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...IJMREMJournal
 
Ppt power grid design
Ppt power grid designPpt power grid design
Ppt power grid designsusanta das
 
Making Interconnection in the Gulf a Reality
Making Interconnection in the Gulf a RealityMaking Interconnection in the Gulf a Reality
Making Interconnection in the Gulf a RealityPower System Operation
 
IRJET- Hybrid Feed Forward Control for Power Factor Correction Rectifier
IRJET-  	  Hybrid Feed Forward Control for Power Factor Correction RectifierIRJET-  	  Hybrid Feed Forward Control for Power Factor Correction Rectifier
IRJET- Hybrid Feed Forward Control for Power Factor Correction RectifierIRJET Journal
 
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...Power System Operation
 
SEMINAR-2015 (abhishek)
SEMINAR-2015 (abhishek)SEMINAR-2015 (abhishek)
SEMINAR-2015 (abhishek)Abhishek Karan
 
Low cost automatic water level control for domestic or industrial applicat...
Low cost  automatic water level control for domestic  or industrial  applicat...Low cost  automatic water level control for domestic  or industrial  applicat...
Low cost automatic water level control for domestic or industrial applicat...Ahasan Ullah Hasan
 

Similar to Introduction of LVAC Auto Change Over Scheme in DEWA Transmission System (20)

The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
 
switching substation, plcc and scada
switching substation, plcc and scadaswitching substation, plcc and scada
switching substation, plcc and scada
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
 
TRANSFORMER HEALTH MONITORING SYSTEM
TRANSFORMER HEALTH MONITORING SYSTEMTRANSFORMER HEALTH MONITORING SYSTEM
TRANSFORMER HEALTH MONITORING SYSTEM
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4
 
I012455457
I012455457I012455457
I012455457
 
A review on hvdc circuit breakers
A review on hvdc circuit breakersA review on hvdc circuit breakers
A review on hvdc circuit breakers
 
Multi_Vdd_IEEE_Paper
Multi_Vdd_IEEE_PaperMulti_Vdd_IEEE_Paper
Multi_Vdd_IEEE_Paper
 
POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...
POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...
POWER QUALITY IMPROVEMENT OF DISTRIBUTION GRID USING ULTRA CAPACITOR INTEGRAT...
 
Doc a.7-tlc report
Doc a.7-tlc reportDoc a.7-tlc report
Doc a.7-tlc report
 
IRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta Converter
IRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta ConverterIRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta Converter
IRJET- IoT Enabled BLDC Motor Driven Water Pump Employing Zeta Converter
 
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
 
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
Design and Simulation Analysis of Sliding Mode Controller for DC-DC Cuk Conve...
 
Home automation
Home automationHome automation
Home automation
 
Ppt power grid design
Ppt power grid designPpt power grid design
Ppt power grid design
 
Making Interconnection in the Gulf a Reality
Making Interconnection in the Gulf a RealityMaking Interconnection in the Gulf a Reality
Making Interconnection in the Gulf a Reality
 
IRJET- Hybrid Feed Forward Control for Power Factor Correction Rectifier
IRJET-  	  Hybrid Feed Forward Control for Power Factor Correction RectifierIRJET-  	  Hybrid Feed Forward Control for Power Factor Correction Rectifier
IRJET- Hybrid Feed Forward Control for Power Factor Correction Rectifier
 
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
The Operation of the GCCIA HVDC Project and Its Potential Impacts on the Elec...
 
SEMINAR-2015 (abhishek)
SEMINAR-2015 (abhishek)SEMINAR-2015 (abhishek)
SEMINAR-2015 (abhishek)
 
Low cost automatic water level control for domestic or industrial applicat...
Low cost  automatic water level control for domestic  or industrial  applicat...Low cost  automatic water level control for domestic  or industrial  applicat...
Low cost automatic water level control for domestic or industrial applicat...
 

More from IRJET Journal

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...IRJET Journal
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTUREIRJET Journal
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...IRJET Journal
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsIRJET Journal
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...IRJET Journal
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...IRJET Journal
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...IRJET Journal
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...IRJET Journal
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASIRJET Journal
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...IRJET Journal
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProIRJET Journal
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...IRJET Journal
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemIRJET Journal
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesIRJET Journal
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web applicationIRJET Journal
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...IRJET Journal
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.IRJET Journal
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...IRJET Journal
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignIRJET Journal
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...IRJET Journal
 

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 

Recently uploaded (20)

CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 

Introduction of LVAC Auto Change Over Scheme in DEWA Transmission System

  • 1. © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 967 Introduction of LVAC Auto Change Over Scheme in DEWA Transmission System Owen Raymond Glynn, Jayasingh Balakrishnan, Amod Madhukar Khirwadkar, Muthusamy Veerabahu, Pownrajan Chinnadurai, Raghavendra Upadhya Heggodlu- Transmission Protection Department, Dubai Electricity & Water Authority. ---------------------------------------------------------------------------***--------------------------------------------------------------------------- Abstract- Dubai’s transmission power system plays a vital role in delivering optimum reliability and uninterrupted power. We therefore need to maintain the highest levels of technology, operational and best design practices for all digital systems. This paper aims to provide the conceptual design overview and benefits of the innovative design of LVAC Auto Changeover Scheme in DEWA Transmission Substations (132kV). The existing design of LVAC switchboards (400V AC supply for substation equipment’s) used in 132/11 KV substations under DEWA transmission network have three buses powered through three earthing transformers and has two bus sections. During normal operation, all three buses in LVAC switchboard are independently supplied by each earthing transformer (incomer) respectively and bus sections are in open condition. To maintain uninterruptable LVAC supply to substation equipment’s, a PLC is used and programmed to execute automatic switching operation of concerned bus section / incomer breakers in case of any of the incomer supply fails. LVAC switchboard has an Auto/ Manual switch and PLC is operational if the switch is on Auto mode. The existing scheme has mainly two issues as below: A) In case of outage required on any of the IDT’s, operator intervention is required to execute switching by shifting Auto/ Manual switch in Manual mode. Manual switching results in loss of LVAC supply as well as generation of several alarms through SCMS. B) In case of switching off any IDT during LVAC in Auto mode, switching through PLC will affect only with a time delay results in momentary interruptions to downstream LV circuits which generates large number of undesired alarms in SCMS. With an objective to eliminate momentary supply interruptions and unwanted alarms due to that, the team has developed new logic diagrams to facilitate high speed Automatic changeover of LVAC supplies with minimum allowable paralleling time for the IDT’s after study on the risks involved during momentary paralleling. In place of PLC, Bay Control Units (BCU) from approved OEM’s are utilized which are in use at higher voltage levels in DEWA system. BCU’s are having major advantages over PLC in terms of ease and flexibility in logic buildings, programming of the device and speed of operation. This paper aims to provide the conceptual overview and benefits of LVAC High speed Auto Change Over scheme developed in house by DEWA specialists in conjunction with specialists from the original equipment manufacturers. The new scheme involves use of Bay Control Units in place of PLC’s in LVAC switchgear design. The BCU’s and overall scheme is engineered, configured and extensively laboratory tested to ensure perfect functionality of High-Speed Auto Change Overs in LVAC board. Utilizing the capabilities of modern IED’s to build large numbers of user defined logic and implementing these in innovative new ways has produced new unique LVAC changeover scheme that enhance functionality and reliability by eliminating discreet components and circuitry whilst maximizing overall efficiency by reducing supply interruptions and unwarranted alarms during supply changeover. This innovative initiative will ensure that DEWA will have arguably the most advanced LVAC switchboards in its transmission systems both regionally and globally by introducing the latest digital technologies, optimized designs in line with the industry leading best practices. I. INTRODUCTION Dubai Electricity & Water Authority (DEWA) was established in 1992 by His Excellency Sheikh Maktoum bin Rashid Al Maktoum with the objective to provide reliable power to residents of the Emirate of Dubai. Since its inception, DEWA has continuously invested in maintaining and upgrading the power delivery infrastructure to meet the increasing demands of the growing Emirate of Dubai. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072
  • 2. © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 968 Dubai Electricity & Water Authority (DEWA) Power System includes Generation, Transmission and Distribution networks. The transmission network operates at 400kV and 132kV voltage levels with over 350 transmission substations consisting of 400/132kV, 132/33kV and 132/11kV sites. LVAC switchgears are installed in all types of transmission substations and are used to supply station loads (station auxiliaries, air conditioning, heating, and lighting etc.). LVAC supplies to various equipment’s and related systems are continuously monitored by connecting the alarms through SCMS to DEWA control center. As per existing design, during supply changeover in LVAC, many unwanted alarms are received. Moreover, if the LVAC operational switch is kept in manual mode, manual intervention is required to execute supply changeovers. In order to overcome the above-mentioned constraints, DEWA team has developed a high speed LVAC auto changeover scheme which allows momentary paralleling of transformers without any side effect thus to avoid supply interruption. The innovative LVAC scheme under discussions is approved for implementation in DEWA’s all future 132/11 KV substations. The major concerns while finalizing the scheme were as follows: 1) 1) During any one of the IDT Switching, paralleling of secondary side may involve circulating currents. In order to overcome the same it is ensured that the primary of the concerned IDT’s are already parallel and maximum paralleling time is set as 500 msec and to eliminate any adverse effect such as IDT circulating currents. Moreover the LVAC busbar fault levels are within the limits for paralleling the two LVAC incomers (LVAC fault levels are shown in figure 1). Figure-1: LVAC Fault Levels 2) The complications of switching LVAC breakers from control center would have been challenging with existing PLC, however use of Bay Control Units having IEC 61850 communication facility found as a suitable solution to achieve remote switching. 3) High speed changeover in case of tripping of any one IDT was considered as a risk to other healthy IDT’s for momentary paralleling. Hence a hybrid solution was adapted. High speed paralleling was configured for planned switching and low speed LVAC changeover with 10 sec time delay was maintained for IDT protection tripping scenarios without paralleling the IDT’s. II.PROBLEMS WITH EXISTING LVAC SCHEME Existing LVAC Single Line Diagram The salient features specified for the existing LVAC scheme related to supply changeover scheme are as below: 1) The substation shall be provided with three auxiliary supplies derived from the three earthing transformers 2) Normally three sections (Bus 1, 2, 3) of the main LVAC switchboard shall be supplied via the associated main incoming circuit breakers with both the bus section breakers in open condition. 3) Electrical interlock shall be provided such that it shall not be possible to parallel any two transformers both on Auto and Manual mode of operations. 4) Only one Auto/Manual switch common to all 5 ACBs shall be provided, and operation logic shall be submitted for DEWA approval. 5) If a fault occurs on a section of the busbars the relevant circuit breaker shall open to isolate the faulty section and any auto-changeover on to a faulty section shall be inhibited. 6) When selected on manual mode no automatic changeover shall occur. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072
  • 3. © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 969 7) SCADA alarms are hardwired since the existing PLC devices are not capable to send alarms directly to SCMS system. It is evident from the above-mentioned specification clauses that paralleling of transformers was not permitted and manual operations are required for supply changeover during planned outages on any one of the IDT’s. Moreover, momentary supply interruption will results in several unwanted alarms from associated LVAC circuits to SCMS. III. High Speed Auto Changeover Scheme The high-speed auto changeover (ACO) scheme is implemented by redesigning the LVAC control system as follows: 1. Auto Changeover (ACO) can be enabled or disabled using the existing auto/ manual switch. 2. The ACO is completely autonomous requiring no action from TCC or HMI. 3. Detection of IDT1 switching out: (the same is applicable for IDT2 & IDT3) a) Detect IDT1 132kV CB Open command (switching out IDT1). b) Initiate auto changeover of LVAC Bus 1. c) Close BS1 and Open Incomer 1 (Aux contact of BS1 Opens IC1 to achieve coordinated high speed switching). 4. Detection of IDT1 switching back into service: a) 132kV CB Closed and LVAC supply healthy for 5 seconds. b) Initiates restore of LVAC Bus 1 to normal supply. c) Close Incomer 1 and then open BS1 (Aux contact of IC1 opens BS1 to achieve coordinated high-speed switching). 5. Duration of paralleling is kept to minimum (milliseconds) therefore no overload concerns. IDT1 Switching – ACO Scenario is shown in Figure-2. Figure-2: IDT1 Switching A. ACO Logic Sample logic – LVAC Incomer CB close Sample logic – LVAC Incomer CB Open B. Methodology: The steps undertaken for implementing the LVAC changeover scheme are as explained below: International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072
  • 4. © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 970 1) Existing LVAC logic and schematic diagrams are thoroughly studied by the team and based on it, new logics are prepared to incorporate hybrid changeover scheme. One high speed logic for routing switching of IDT’s and other slow logic for IDT tripping cases. 2) PLC was proposed to be replaced with modern and sophisticated BCU’s. 3) The proposal was presented to DEWA Transmission Power Technical Committee and approval was received. 4) BCU input /output requirements were finalized and accordingly, Generic wiring diagrams were prepared. 5) DEWA approved OEM’s (SEL, Hitachi, GE and Siemens) were approached to finalize suitable BCU device. 6) M/s Hitachi REC 670 and SEL451 BCU’s found most suitable for this application. 7) Extensive laboratory testing was performed on these BCU’s considering all network conditions in presence of DEWA stakeholder departments and BCU settings and configurations were finalized. 8) Based on successful evaluation of the BCU’s, tender documents were updated to include High Speed Automatic changeover. C. Advantages of the High-Speed Auto Changeover Scheme The new innovative LVAC design provides significant benefits to DEWA as a utility. The new design for 132/11kV substations includes the following advantages:  Eliminate momentary interruption of LVAC supply during IDT outage or switching  The Scheme is completely autonomous.  Fast switching avoids exposure to circulating currents.  It is a cost-effective design improvement due to less number of components and wiring.  Eliminate unwanted alarms during IDT outage.  Increased digitization due to elimination of hard wiring (BCU option). BCU is directly connected to SCADA system and all LVAC related alarms are send to SCADA via IEC61850 protocol.  BCU’s are having major advantages over PLC in terms of ease and flexibility in logic buildings, programming of the device and speed of operation. IV. CONCLUSION Implementing a high-speed auto changeover (ACO) will avoid interruption of LVAC supply in the event of switching IDT’s in and out of service. This will in turn avoid unnecessary supply interruption, associated alarms and improve reliability of equipment. The high speed ACO avoids the need for operator intervention and avoids exposure to overload since paralleling is extremely short in duration. The proposed ACO scheme was configured and tested with different OEM BCU. All the test scenario was simulated and passed. Hence the same concept can be implemented wherever applicable. BCU is the preferred option rather than the PLC. V. REFERENCES [1] Aster A. Roy, Gesa F. Newton & Aondoakaa I. Solomon: “Design and Implementation of a 3-Phase Automatic Power Change-Over Switch” published in American Journal of Engineering Research (AJER) Vol-3, Issue-9, pp-07-14 [2] Scott Manson and Saurabh Shah “Automated Power Management Systems for Power Consumers with On-site Generation” Available on SEL website, SEL Inc. Pullman [3] Scott M. Manson, Ashish Upreti and Michael Thompson Available on SEL website, SEL Inc. Pullman [4] Stefan Meier, Thomas Werner, “Performance considerations in digital substation applications” white paper presented at PAC World UK 2015. [5] Greg Rzepka, Scott Wenke, Sarah Walling, “Choose Simplicity for a Better Digital Substation Design”, 70th Annual Conference for Protective Relay Engineers, Texas, April-2017. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 12 | Dec 2023 www.irjet.net p-ISSN: 2395-0072