SlideShare a Scribd company logo
ECNG 3013
           Electrical Transmission and
              Distribution Systems




Course Instructor: Prof. Chandrabhan Sharma
Email:    chandrabhan.sharma@sta.uwi.edu
Phone:    Ext. 3141
Office:   Rm. 221                             B
Approximate Models for Analysis
Assumption: Balanced 3Φ transposed system.
1.Voltage Drop:




                (ZI)
    VS = VL + (R + jX)I
       = VL + RI + jXI … (1)
Figure below gives the phasor representation




The voltage drop down the line is defined as the difference
between the magnitudes of VS and VL
∴drop = |VS| - |VL| ... (2)
   V
Since δ is small for a distribution line.
 V ≈ Re(ZI)            … (3)
     drop
Equation (3) would be used as a definition for voltage drop.
Example: For the feeder given before, the impedance of the first line segment is:




Also I12 = 43.0093 ∠-25.8419 A
      Z12 = (0.2841 + j0.5682) Ω

      VN1 = 2400 ∠0 V

      V2 = 2400 ∠0 – (0.2841 + j0.5682)(43.0093 ∠-25.8419)
The exact voltage at N2 is:

                           ∠-0.4015
∴V = 2378.40982378.4098 V 21.5902 V
    drop (exact) = 2400 –           =

    Vdrop = Re[(0.2841 + j0.5682)(43.0093 ∠-25.8419)]
Computing Vdrop according to Eq. 3

∴           = 21.64926 V
   Error = (21.5902 -21.6426) 100
                      21.5902
            = -0.27%      (small)
Line Impedance → Approximate Model

Assumption → Line fully transposed → +ve
  sequence only needs to be determined.
                Given: the equation for +ve Sequence

                Z1 = r + j0.12134ln(Deq/GMR) Ω/mile …(4)
                where r = conductor resistance/ mile
                                          3
                Deq = equivalent spacing = Dab.Dbc.Dca (ft)
                GMR = conductor geometric mean radius
                (from tables)
A 3Φ line segment has a T configuration as given before. The spacings between
the conductors are:
Dab = 2.5ft ; Dbc = 4.5 ft and Dca = 7.0 ft
The conductors are ACSR with r = 0.306Ω/ mile and GMR = 0.0244ft (obtained
from tables)
Find the Z1 for the line.

Solution:
Equivalent Spacing = (2.5)(4.5)(7) = 4.2868 ft
                      3


From equation (4)
Z1 = 0.306 + j0.12134ln(4.2863/0.0244) Ω/mile
   = 0.306 + j0.6272 Ω/mile

‘K’ Factors
Another method of obtaining voltage drop is by use of a ‘k’ factor. There are two
types of k factors:
         (a) one for voltage drop and
         (b) another for voltage rise calculations.
Kdrop Factor ∆ % Phase Voltage drop/ kVA.mile …(5)
                                         (km)
This gives the % voltage drop per mile (km) of conductor with a 1kVA load. A
p.f. of 0.9 is assumed!

Example:
For the T line given before, calculate the K drop factor assuming p.f. = 0.9lag
and nominal LL voltage is 12.47kV.

Solution:
Previously Z = (0.306 + j0.6272) Ω/mile

I = 1kVA/ (√3.kVLL) ∠–cos-1 0.9
For load 1kVA at 0.9 pf.

  = 1/ (√3 x 12.47) ∠-25.84 = 0.046299 ∠-25.84 A
∴ = Re[ZI] = Re{[0.306 + j0.6272][0.046299 ∠-25.84]}
   Vdrop
                    = 0.025408 V
                VLN = 12.47/ √3 = 7199.6 V
        Kdrop factor = (0.025408/7199.6)100
                                          (km)
                Kdrop = 0.00035291 % / kVA.mile
Most utilities have standard conductors, spacings and voltages.
Therefore a simple spreadsheet would be developed to
compute the Kdrop factors for the utility.

How do we use Kdrop?

Assume for the configuration given before it is required to find
the voltage drop if a load of 7500kVA is fed 1.5 miles away?
   Vdrop = Kdrop. kVA. Mile
         = (0.00035291)(7500)(1.5) = 3.9702%

Suppose the utility’s standard for voltage drop is 3% max. Then
the max. load which can be fed is given by:
   kVAload = 3.0%/(0.00035291 x 1.5) = 5667.2 kVA
Given Kdrop = 0.00035291. Determine the percentage voltage drop from N0 to
N3.

Solution: Total kVA flowing in segment N0 to N1:
kVA01 = (300 + 750 + 500) = 1550 kVA
    % voltage drop from N0 to N1 = (0.0003591)(1550)(1.5) = 0.8205%
∴ 12 = 750 + 500 = 1250 kVA
kVA
   Voltage drop from N1 to N2:
∴ Vdrop12 = (0.00035291)(1250)(0.75) = 0.3308%
         Vdrop23 = (0.00035291)(500)(0.5) = 0.0882%
   Total % voltage drop from N0 to N3
∴ Vdroptotal = (0.8205 + 0.3308 + 0.0882) = 1.2396%
                          (approximate value)
Krise Factor

            In this case the load is a shunt capacitor.
N .B.   |   When a leading current flows through an inductive reactance (Z line) there
            is a voltage rise across the reactance NOT a drop!
                                                                                         |
            Observe the phasor diagram below:




        ∴ rise = |Re(ZIcap)| = X|Icap|
         V                               … (6)
        ∴Krise = Voltage rise %           … (7)
                    kVAr . mile
            where the load is a 1 kVAr capacitor
For the example before:
(1)Calculate the Krise factor
(2) Determine the rating of a 3Φ capacitor bank to limit the voltage drop to
2.5% in the last example.

Solution:
Z/mile = (0.306 + j0.6272)Ω

Icap = 1kVAr ∠90
The current taken by a 1kVAr bank:


                         ∠90 = 0.046299 ∠90
       √3 kVLL
          =     1
       √3 x 12.47
∴Voltage rise per kVAr mile is:

        = |Re(0.306 + j0.6272)(0.046299 ∠90 )| = 0.029037 V
 Vrise = Re|Z.Icap|

          But VLN = 7199.6V
∴
 Krise factor = (0.029037/7199.6)100 = 4.0331 x 10 -4 % rise/ kVAr.mile
From the last example the % voltage drop for a 7500kVA load at
1.5 mile was 3.9702%.
To limit this to 2.5%, the required voltage rise need is
Vrise = 3.9702 – 2.5 = 1.4702%

∴Required rating of shunt capacitor is
kVAr =   Vrise        =              1.4702

       Krise . mile       (4.0331x10-4)(1.5)
     = 2430.18 kVAr
Uniformly Distributed Loads
Distribution laterals with transformers of the
  same rating can be assessed as a uniformly
  distributed load.




     Generalized Line with n uniformly distributed loads.
Voltage Drop

Given n uniformly spaced loads dx apart.

The loads are treated as constant current loads di.

Let L = length of feeder
    Z = r + jx = impedance of line in Ω / mile
    dx = length of each section
    di = load at each node
    n = # of nodes & no. of line sections
    IT = total current into the feeder
∴ Load currents are given by: di = IT /n … (8)



 Voltage drop of first line segment is given by:

       Vdrop1 = Re[ Z.dx.(n.di)]    … (9)


 Similarly,
       Vdrop2 = Re[ Z.dx.{(n-1).di}] etc … (10)
∴ Voltage drop is given by:
 Total

Vdroptotal = Vdrop1 + Vdrop2 + … + Vdropn

           = Re { Z.dx.di.[n + (n-1) + (n-2) + … + 1] } … (11)

Equation (11) can be reduced by using the expansion:
      n
  [ ∑ m]
   m =1    1 + 2 + 3 + … + n = n(n+1)/2      … (12)

Sub into (11)
→ Vdroptotal = Re{ Z.dx.di [ n(n+1)/2] }     … (13)

But        dx = L/ n                         … (14)

and        di = IT/ n                        … (15)

Sub (14) and (15) into (13) yields
VdropT    = Re[ Z. L/n. IT /n (n(n+1)/2) ]

     = Re{ Z. L. IT. ½. (n+1)/n}

VdropT    = Re{ ½ . Z. IT (1 + 1/n)} … (16)

where Z T = Z.L

This is the general equation for an evenly
distributed load.
As n→∞ then
      Vdrop total = Re[ ½ . Z T . IT]    …
The load (distributed) can be represented using either of the two models:


                                                         Model # 1
                                                         Load at
                                                         midpoint


OR
                                                        Model # 2
                                                        ½ load at last
                                                        node



 where Vdrop total = Re [ ½ ZT. IT]
Power Loss
Using the line model shown previously:
  Model # 1 gives the 3Φ Power Loss as:
     Ploss = 3.|IT|2 R/2 = 3/2|IT|2.R … (18)
  where R = total resistance of line
  Model # 2 gives the 3Φ Power Loss as:
    Ploss = 3.|IT/2|2.R = ¾.|IT|2.R … (19)


      Which one is correct? → Neither!
Correct Model
Recall before:
                                       L




Power loss to node 1 => Ploss1 = 3 (r.dx).|n.di|2                  … (20)
          Similarly            Ploss2 = 3 (r.dx).[|(n-1).di|]2     … (21)
          Etc.
∴P
    loss Total = 3(r.dx). |di| [n + (n-1) + (n-3) + … + 1 ]        … (22)
                              2    2         2        2        2

where n2 + (n-1)2 + (n-2)2 + …+ 12 = n (n+1) (2n+1)                … (23)
                                                    6
∴ loss Total = 3 ( r . L/n )(|IT/n|)2 [ n (n+1) (2n+1) ]
  P                                                                … (24)
                                                  6
Simplifying (24)
Ploss Tot = 3. R. |IT|2 [ (n+1) (2n+1) ]
                               6n2
Ploss Tot = 3R|IT|2 [ 2n2 + 3n + 1 ]
                             6n2
Ploss Tot = 3R|IT|2 [ 1 + 1 + 1 ]                     … (25)
                        3 2n 6n2
where R = r . L = total resistance / phase
As n → ∞ → Ploss total = 3R|IT|2[ 1/3 ]
                            = 3. R/3 |IT|2   … (26)

                                                               Model # 1
                                                               for Power
                                                               Loss/ phase


                                                               Model # 2
                                                               for Power
                                                               Loss/ phase
The Exact Lumped Load Model




Need to Find ‘k’ and ‘c’
Vdrop Total = Re[ kZIT + (1-k).Z.c.IT]                     … (27)
where Z = Total line impedance in ohms
             k = as given above
             c = fraction of current at end of line s.t.
                       IT = IX + cIT
But (from before) Vdrop Total = Re[ ½. Z. IT ]             … (28)

Equating (27) and (28)
        Re [ ½ ZIT ] = Re [ kZIT + (1 –k)ZcIT ]            … (29)
Or       ½ ZIT = kZIT + (1-k) ZcIT                         … (30)
Dividing across by ZIT gives
              ½ = k + c( 1-k )                … (31)
Solving for k:
                     0. 5 − c               … (32)
                 k =          
                      1− c 
Applying the procedure to the power loss model yields:
Ploss Total = 3[ kR|IT|2 + (1-k)R(c.|IT|)2 ]… (33)
But before Ploss Total = 3[ 1/3 R |IT|2 ]          … (34)

Equating (33) and (34)
        3[ 1/3R|IT|2] = 3[kR|IT|2 + (1-k)R (c|IT|2) ]
        1/3 = [ k (1-c2) + c2 ]               … (35)

Solving equation (32) and (35) for k and c
Sub. for k from (32) into (35)
        0.5 − c 
                
        1− c 
1/3 = [       ( 1 – c 2 ) + c2 ]              … (36)
Solving for c → c = 1/3                       … (37)
Sub into (32) → k = ¼                         … (38)
The exact model for the distribution line is:

More Related Content

What's hot

Single and 3 phase transformer
Single and 3 phase transformerSingle and 3 phase transformer
Single and 3 phase transformeravocado1111
 
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...Pradeep Avanigadda
 
Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Asha Anu Kurian
 
Exp 5 (1)5. Newton Raphson load flow analysis Matlab Software
Exp 5 (1)5.	Newton Raphson load flow analysis Matlab SoftwareExp 5 (1)5.	Newton Raphson load flow analysis Matlab Software
Exp 5 (1)5. Newton Raphson load flow analysis Matlab SoftwareShweta Yadav
 
Per unit calculation
Per unit calculationPer unit calculation
Per unit calculationobaidurbd
 
Presentation on Z- Source Converter
Presentation on Z- Source ConverterPresentation on Z- Source Converter
Presentation on Z- Source Converternibeditamishra
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protectionSy Thinhbk
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission linepamu17
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerSMDDTech
 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power systemEklavya Sharma
 
dc to dc-converter
dc to dc-converterdc to dc-converter
dc to dc-converterStudent
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
 
Hydrothermal scheduling
Hydrothermal schedulingHydrothermal scheduling
Hydrothermal schedulingASHIRBAD BARIK
 
Lv genset protection
Lv genset protectionLv genset protection
Lv genset protectionrkdheepan
 
Open circuit and Short circuit test on transformer
Open circuit and Short circuit test on transformerOpen circuit and Short circuit test on transformer
Open circuit and Short circuit test on transformerHarshit Khandelwal
 

What's hot (20)

Gauss seidel method
Gauss seidel methodGauss seidel method
Gauss seidel method
 
Single and 3 phase transformer
Single and 3 phase transformerSingle and 3 phase transformer
Single and 3 phase transformer
 
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
DETECTING POWER GRID SYNCHRONISATION FAILURE ON SENSING BAD VOLTAGE OR FREQUE...
 
Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)
 
Load flow studies 19
Load flow studies 19Load flow studies 19
Load flow studies 19
 
Economic Dispatch
Economic DispatchEconomic Dispatch
Economic Dispatch
 
Exp 5 (1)5. Newton Raphson load flow analysis Matlab Software
Exp 5 (1)5.	Newton Raphson load flow analysis Matlab SoftwareExp 5 (1)5.	Newton Raphson load flow analysis Matlab Software
Exp 5 (1)5. Newton Raphson load flow analysis Matlab Software
 
Balanced faults
Balanced faultsBalanced faults
Balanced faults
 
Per unit calculation
Per unit calculationPer unit calculation
Per unit calculation
 
Presentation on Z- Source Converter
Presentation on Z- Source ConverterPresentation on Z- Source Converter
Presentation on Z- Source Converter
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
 
AC TRANSMISSION by Dr. Kundur
AC TRANSMISSION by Dr. Kundur AC TRANSMISSION by Dr. Kundur
AC TRANSMISSION by Dr. Kundur
 
Presentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformerPresentation Design of Computer aided design of power transformer
Presentation Design of Computer aided design of power transformer
 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power system
 
dc to dc-converter
dc to dc-converterdc to dc-converter
dc to dc-converter
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Hydrothermal scheduling
Hydrothermal schedulingHydrothermal scheduling
Hydrothermal scheduling
 
Lv genset protection
Lv genset protectionLv genset protection
Lv genset protection
 
Open circuit and Short circuit test on transformer
Open circuit and Short circuit test on transformerOpen circuit and Short circuit test on transformer
Open circuit and Short circuit test on transformer
 

Viewers also liked

Viewers also liked (10)

ECNH 3015 Examples of PU system
ECNH 3015  Examples of PU systemECNH 3015  Examples of PU system
ECNH 3015 Examples of PU system
 
ECNG 6509 Transformer Technology
ECNG 6509  Transformer TechnologyECNG 6509  Transformer Technology
ECNG 6509 Transformer Technology
 
ECNG 6509 Switchgear Technology
ECNG 6509    Switchgear TechnologyECNG 6509    Switchgear Technology
ECNG 6509 Switchgear Technology
 
ECNG 3015 chapter 2 - pu system
ECNG 3015  chapter 2 - pu systemECNG 3015  chapter 2 - pu system
ECNG 3015 chapter 2 - pu system
 
ECNG 3013 C
ECNG 3013 CECNG 3013 C
ECNG 3013 C
 
ECNG 3013 E
ECNG 3013 EECNG 3013 E
ECNG 3013 E
 
ECNG 3015 Industrial and Commercial Electrical Systems
ECNG 3015   Industrial and Commercial Electrical SystemsECNG 3015   Industrial and Commercial Electrical Systems
ECNG 3015 Industrial and Commercial Electrical Systems
 
Circuit breaker arc phenomena
Circuit breaker arc phenomenaCircuit breaker arc phenomena
Circuit breaker arc phenomena
 
ECNG 3015- System Earthing
ECNG 3015- System EarthingECNG 3015- System Earthing
ECNG 3015- System Earthing
 
ECNG 3015 chapter 1 - Basics
ECNG 3015  chapter 1 - BasicsECNG 3015  chapter 1 - Basics
ECNG 3015 chapter 1 - Basics
 

Similar to ECNG 3013 B

16th July 2015 Road lighting_modified
16th July 2015 Road  lighting_modified16th July 2015 Road  lighting_modified
16th July 2015 Road lighting_modifiedPrateek Singh
 
Physics Formula list (4)
Physics Formula list (4)Physics Formula list (4)
Physics Formula list (4)WAYNE FERNANDES
 
Transmission line By Lipun
Transmission line By LipunTransmission line By Lipun
Transmission line By LipunNanigopal Jena
 
IC Design of Power Management Circuits (II)
IC Design of Power Management Circuits (II)IC Design of Power Management Circuits (II)
IC Design of Power Management Circuits (II)Claudia Sin
 
Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )
Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )
Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )MohitRaghav19
 
Transmission and distribution line design final
Transmission and distribution line design finalTransmission and distribution line design final
Transmission and distribution line design finalBhanu Poudyal
 
Chapter 05
Chapter 05Chapter 05
Chapter 05Tha Mike
 
chapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptxchapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptxLiewChiaPing
 
Microwave Engineering Lecture Notes
Microwave Engineering Lecture NotesMicrowave Engineering Lecture Notes
Microwave Engineering Lecture NotesFellowBuddy.com
 
IC Design of Power Management Circuits (III)
IC Design of Power Management Circuits (III)IC Design of Power Management Circuits (III)
IC Design of Power Management Circuits (III)Claudia Sin
 

Similar to ECNG 3013 B (20)

Report_AKbar_PDF
Report_AKbar_PDFReport_AKbar_PDF
Report_AKbar_PDF
 
16th July 2015 Road lighting_modified
16th July 2015 Road  lighting_modified16th July 2015 Road  lighting_modified
16th July 2015 Road lighting_modified
 
TL_Theory.pdf
TL_Theory.pdfTL_Theory.pdf
TL_Theory.pdf
 
Modern2426
Modern2426Modern2426
Modern2426
 
Chap2 s11b
Chap2 s11bChap2 s11b
Chap2 s11b
 
Physics Formula list (4)
Physics Formula list (4)Physics Formula list (4)
Physics Formula list (4)
 
Physics formulas
Physics formulasPhysics formulas
Physics formulas
 
Physics Working Formulas
Physics Working FormulasPhysics Working Formulas
Physics Working Formulas
 
Transmission line By Lipun
Transmission line By LipunTransmission line By Lipun
Transmission line By Lipun
 
Smith Chart Problems
Smith Chart ProblemsSmith Chart Problems
Smith Chart Problems
 
IC Design of Power Management Circuits (II)
IC Design of Power Management Circuits (II)IC Design of Power Management Circuits (II)
IC Design of Power Management Circuits (II)
 
Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )
Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )
Presentation of Electrical Engineering ( Analysis of AC circuit: RC circuit )
 
Lecture 7
Lecture 7Lecture 7
Lecture 7
 
Dc Distributed Load
Dc Distributed LoadDc Distributed Load
Dc Distributed Load
 
Transmission and distribution line design final
Transmission and distribution line design finalTransmission and distribution line design final
Transmission and distribution line design final
 
Chapter 05
Chapter 05Chapter 05
Chapter 05
 
chapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptxchapter_2 AC to DC Converter.pptx
chapter_2 AC to DC Converter.pptx
 
Microwave Engineering Lecture Notes
Microwave Engineering Lecture NotesMicrowave Engineering Lecture Notes
Microwave Engineering Lecture Notes
 
IC Design of Power Management Circuits (III)
IC Design of Power Management Circuits (III)IC Design of Power Management Circuits (III)
IC Design of Power Management Circuits (III)
 
Transmissionline
TransmissionlineTransmissionline
Transmissionline
 

More from Chandrabhan Sharma

More from Chandrabhan Sharma (9)

ECNG 3015 chapter 6 - switchgear technology
ECNG 3015  chapter 6 - switchgear technologyECNG 3015  chapter 6 - switchgear technology
ECNG 3015 chapter 6 - switchgear technology
 
Ices chapter 8 - illumination engineering
Ices   chapter 8 - illumination engineeringIces   chapter 8 - illumination engineering
Ices chapter 8 - illumination engineering
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent Protection
 
ECNG 3015 Power System Protection
ECNG 3015    Power System ProtectionECNG 3015    Power System Protection
ECNG 3015 Power System Protection
 
ECNG 6503 #4
ECNG 6503 #4ECNG 6503 #4
ECNG 6503 #4
 
ECNG 6503 # 3
ECNG 6503 # 3ECNG 6503 # 3
ECNG 6503 # 3
 
ECNG 6503 #2
ECNG 6503  #2ECNG 6503  #2
ECNG 6503 #2
 
ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation ECNG 3015 - PU system and 3Phase Fault calculation
ECNG 3015 - PU system and 3Phase Fault calculation
 
ECNG 6503 #1
ECNG 6503 #1 ECNG 6503 #1
ECNG 6503 #1
 

ECNG 3013 B

  • 1. ECNG 3013 Electrical Transmission and Distribution Systems Course Instructor: Prof. Chandrabhan Sharma Email: chandrabhan.sharma@sta.uwi.edu Phone: Ext. 3141 Office: Rm. 221 B
  • 2. Approximate Models for Analysis Assumption: Balanced 3Φ transposed system. 1.Voltage Drop: (ZI) VS = VL + (R + jX)I = VL + RI + jXI … (1)
  • 3. Figure below gives the phasor representation The voltage drop down the line is defined as the difference between the magnitudes of VS and VL ∴drop = |VS| - |VL| ... (2) V Since δ is small for a distribution line.  V ≈ Re(ZI) … (3) drop Equation (3) would be used as a definition for voltage drop.
  • 4. Example: For the feeder given before, the impedance of the first line segment is: Also I12 = 43.0093 ∠-25.8419 A Z12 = (0.2841 + j0.5682) Ω VN1 = 2400 ∠0 V V2 = 2400 ∠0 – (0.2841 + j0.5682)(43.0093 ∠-25.8419) The exact voltage at N2 is: ∠-0.4015 ∴V = 2378.40982378.4098 V 21.5902 V drop (exact) = 2400 – = Vdrop = Re[(0.2841 + j0.5682)(43.0093 ∠-25.8419)] Computing Vdrop according to Eq. 3 ∴ = 21.64926 V Error = (21.5902 -21.6426) 100 21.5902 = -0.27% (small)
  • 5. Line Impedance → Approximate Model Assumption → Line fully transposed → +ve sequence only needs to be determined. Given: the equation for +ve Sequence Z1 = r + j0.12134ln(Deq/GMR) Ω/mile …(4) where r = conductor resistance/ mile 3 Deq = equivalent spacing = Dab.Dbc.Dca (ft) GMR = conductor geometric mean radius (from tables)
  • 6. A 3Φ line segment has a T configuration as given before. The spacings between the conductors are: Dab = 2.5ft ; Dbc = 4.5 ft and Dca = 7.0 ft The conductors are ACSR with r = 0.306Ω/ mile and GMR = 0.0244ft (obtained from tables) Find the Z1 for the line. Solution: Equivalent Spacing = (2.5)(4.5)(7) = 4.2868 ft 3 From equation (4) Z1 = 0.306 + j0.12134ln(4.2863/0.0244) Ω/mile = 0.306 + j0.6272 Ω/mile ‘K’ Factors Another method of obtaining voltage drop is by use of a ‘k’ factor. There are two types of k factors: (a) one for voltage drop and (b) another for voltage rise calculations.
  • 7. Kdrop Factor ∆ % Phase Voltage drop/ kVA.mile …(5) (km) This gives the % voltage drop per mile (km) of conductor with a 1kVA load. A p.f. of 0.9 is assumed! Example: For the T line given before, calculate the K drop factor assuming p.f. = 0.9lag and nominal LL voltage is 12.47kV. Solution: Previously Z = (0.306 + j0.6272) Ω/mile I = 1kVA/ (√3.kVLL) ∠–cos-1 0.9 For load 1kVA at 0.9 pf. = 1/ (√3 x 12.47) ∠-25.84 = 0.046299 ∠-25.84 A ∴ = Re[ZI] = Re{[0.306 + j0.6272][0.046299 ∠-25.84]} Vdrop = 0.025408 V VLN = 12.47/ √3 = 7199.6 V Kdrop factor = (0.025408/7199.6)100 (km) Kdrop = 0.00035291 % / kVA.mile
  • 8. Most utilities have standard conductors, spacings and voltages. Therefore a simple spreadsheet would be developed to compute the Kdrop factors for the utility. How do we use Kdrop? Assume for the configuration given before it is required to find the voltage drop if a load of 7500kVA is fed 1.5 miles away? Vdrop = Kdrop. kVA. Mile = (0.00035291)(7500)(1.5) = 3.9702% Suppose the utility’s standard for voltage drop is 3% max. Then the max. load which can be fed is given by: kVAload = 3.0%/(0.00035291 x 1.5) = 5667.2 kVA
  • 9. Given Kdrop = 0.00035291. Determine the percentage voltage drop from N0 to N3. Solution: Total kVA flowing in segment N0 to N1: kVA01 = (300 + 750 + 500) = 1550 kVA % voltage drop from N0 to N1 = (0.0003591)(1550)(1.5) = 0.8205% ∴ 12 = 750 + 500 = 1250 kVA kVA Voltage drop from N1 to N2: ∴ Vdrop12 = (0.00035291)(1250)(0.75) = 0.3308% Vdrop23 = (0.00035291)(500)(0.5) = 0.0882% Total % voltage drop from N0 to N3 ∴ Vdroptotal = (0.8205 + 0.3308 + 0.0882) = 1.2396% (approximate value)
  • 10. Krise Factor In this case the load is a shunt capacitor. N .B. | When a leading current flows through an inductive reactance (Z line) there is a voltage rise across the reactance NOT a drop! | Observe the phasor diagram below: ∴ rise = |Re(ZIcap)| = X|Icap| V … (6) ∴Krise = Voltage rise % … (7) kVAr . mile where the load is a 1 kVAr capacitor
  • 11. For the example before: (1)Calculate the Krise factor (2) Determine the rating of a 3Φ capacitor bank to limit the voltage drop to 2.5% in the last example. Solution: Z/mile = (0.306 + j0.6272)Ω Icap = 1kVAr ∠90 The current taken by a 1kVAr bank: ∠90 = 0.046299 ∠90 √3 kVLL = 1 √3 x 12.47 ∴Voltage rise per kVAr mile is: = |Re(0.306 + j0.6272)(0.046299 ∠90 )| = 0.029037 V Vrise = Re|Z.Icap| But VLN = 7199.6V ∴ Krise factor = (0.029037/7199.6)100 = 4.0331 x 10 -4 % rise/ kVAr.mile
  • 12. From the last example the % voltage drop for a 7500kVA load at 1.5 mile was 3.9702%. To limit this to 2.5%, the required voltage rise need is Vrise = 3.9702 – 2.5 = 1.4702% ∴Required rating of shunt capacitor is kVAr = Vrise = 1.4702 Krise . mile (4.0331x10-4)(1.5) = 2430.18 kVAr
  • 13. Uniformly Distributed Loads Distribution laterals with transformers of the same rating can be assessed as a uniformly distributed load. Generalized Line with n uniformly distributed loads.
  • 14. Voltage Drop Given n uniformly spaced loads dx apart. The loads are treated as constant current loads di. Let L = length of feeder Z = r + jx = impedance of line in Ω / mile dx = length of each section di = load at each node n = # of nodes & no. of line sections IT = total current into the feeder
  • 15. ∴ Load currents are given by: di = IT /n … (8) Voltage drop of first line segment is given by: Vdrop1 = Re[ Z.dx.(n.di)] … (9) Similarly, Vdrop2 = Re[ Z.dx.{(n-1).di}] etc … (10)
  • 16. ∴ Voltage drop is given by: Total Vdroptotal = Vdrop1 + Vdrop2 + … + Vdropn = Re { Z.dx.di.[n + (n-1) + (n-2) + … + 1] } … (11) Equation (11) can be reduced by using the expansion: n [ ∑ m] m =1 1 + 2 + 3 + … + n = n(n+1)/2 … (12) Sub into (11) → Vdroptotal = Re{ Z.dx.di [ n(n+1)/2] } … (13) But dx = L/ n … (14) and di = IT/ n … (15) Sub (14) and (15) into (13) yields
  • 17. VdropT = Re[ Z. L/n. IT /n (n(n+1)/2) ] = Re{ Z. L. IT. ½. (n+1)/n} VdropT = Re{ ½ . Z. IT (1 + 1/n)} … (16) where Z T = Z.L This is the general equation for an evenly distributed load. As n→∞ then Vdrop total = Re[ ½ . Z T . IT] …
  • 18. The load (distributed) can be represented using either of the two models: Model # 1 Load at midpoint OR Model # 2 ½ load at last node where Vdrop total = Re [ ½ ZT. IT]
  • 19. Power Loss Using the line model shown previously: Model # 1 gives the 3Φ Power Loss as: Ploss = 3.|IT|2 R/2 = 3/2|IT|2.R … (18) where R = total resistance of line Model # 2 gives the 3Φ Power Loss as: Ploss = 3.|IT/2|2.R = ¾.|IT|2.R … (19) Which one is correct? → Neither!
  • 20. Correct Model Recall before: L Power loss to node 1 => Ploss1 = 3 (r.dx).|n.di|2 … (20) Similarly Ploss2 = 3 (r.dx).[|(n-1).di|]2 … (21) Etc. ∴P loss Total = 3(r.dx). |di| [n + (n-1) + (n-3) + … + 1 ] … (22) 2 2 2 2 2 where n2 + (n-1)2 + (n-2)2 + …+ 12 = n (n+1) (2n+1) … (23) 6 ∴ loss Total = 3 ( r . L/n )(|IT/n|)2 [ n (n+1) (2n+1) ] P … (24) 6
  • 21. Simplifying (24) Ploss Tot = 3. R. |IT|2 [ (n+1) (2n+1) ] 6n2 Ploss Tot = 3R|IT|2 [ 2n2 + 3n + 1 ] 6n2 Ploss Tot = 3R|IT|2 [ 1 + 1 + 1 ] … (25) 3 2n 6n2 where R = r . L = total resistance / phase As n → ∞ → Ploss total = 3R|IT|2[ 1/3 ] = 3. R/3 |IT|2 … (26) Model # 1 for Power Loss/ phase Model # 2 for Power Loss/ phase
  • 22. The Exact Lumped Load Model Need to Find ‘k’ and ‘c’ Vdrop Total = Re[ kZIT + (1-k).Z.c.IT] … (27) where Z = Total line impedance in ohms k = as given above c = fraction of current at end of line s.t. IT = IX + cIT But (from before) Vdrop Total = Re[ ½. Z. IT ] … (28) Equating (27) and (28) Re [ ½ ZIT ] = Re [ kZIT + (1 –k)ZcIT ] … (29) Or ½ ZIT = kZIT + (1-k) ZcIT … (30)
  • 23. Dividing across by ZIT gives ½ = k + c( 1-k ) … (31) Solving for k:  0. 5 − c  … (32) k =   1− c  Applying the procedure to the power loss model yields: Ploss Total = 3[ kR|IT|2 + (1-k)R(c.|IT|)2 ]… (33) But before Ploss Total = 3[ 1/3 R |IT|2 ] … (34) Equating (33) and (34) 3[ 1/3R|IT|2] = 3[kR|IT|2 + (1-k)R (c|IT|2) ] 1/3 = [ k (1-c2) + c2 ] … (35) Solving equation (32) and (35) for k and c Sub. for k from (32) into (35)  0.5 − c     1− c  1/3 = [ ( 1 – c 2 ) + c2 ] … (36) Solving for c → c = 1/3 … (37) Sub into (32) → k = ¼ … (38)
  • 24. The exact model for the distribution line is: