Summary
High-Voltage Direct Current (HVDC) technology
transports bulk electrical power over long distances
efficiently and economically, and also allows the
interconnectionofasynchronouspowergrids.InaHVDC
converter station, a converter transformer provides the
appropriate voltage for converter commutation and also
ensures galvanic isolation between the AC system and
the DC link. The provision of adequate protection for a
converter transformer is crucial; it must limit the damage
to the transformer and adjacent plant when an internal
short-circuit fault occurs.
Differential protection is widely applied to converter
transformers, owing to its simple operating principle,
high sensitivity on internal faults, and excellent security
on external faults. Nevertheless, a challenge is to prevent
mal-operation during transformer energization (i.e.
magnetizing inrush). Numerous techniques have been
used to discriminate between inrush conditions and
internal faults, but harmonic blocking is the simplest
and the most widely used solution. Harmonic blocking
assumes the second harmonic component dominates
the inrush current, but is an insignificant component of
the internal fault current. However, this approach is less
effective in modern transformers that use cores made by
low-loss amorphous materials; these materials produce
lower harmonics in the inrush currents. The challenges
are even more complex for a converter transformer,
which operates in a complicated environment affected by
AC and DC stresses.This suggests significant second and
fifth harmonic components can occur in the internal fault
current, and the fault current may behave like an inrush
current. As a result, a harmonic blocking element may
wronglyinhibittheoperationofthedifferentialprotection,
and the converter transformer may be subjected to fault
currents for an extended period, leading to severe damage
or even the rupture of the transformer tank.
Differential protection must detect all possible short-
circuit faults within a converter transformer, but few
studies have considered how harmonic blocking
performs when an internal fault occurs in a converter
transformer. This paper investigates whether harmonic
blocking is suitable for identifying inrush conditions in a
convertertransformer.Toachievethis,theCIGREHVDC
benchmark test system available in PSCAD/EMTDC
is utilized, and an appropriate differential protection
scheme is designed for the converter transformers.
Asymmetrical internal faults are simulated to assess
the operating behaviour of the differential protection
with harmonic blocking. The test results demonstrate
the differential protection is unable to initiate a trip
signal when an internal phase to ground fault is applied
on the DC side of a converter transformer. The fault
analysis implies the fault current contains a heavy DC
component which flows towards the fault point via
the windings of the converter transformer. This heavy
DC component induces a DC bias flux, which leads to
significant converter transformer half-cycle saturation,
and results in an increase in the second harmonic in
the differential current. As a result, the ratio of second
harmonic to fundamental in the differential current is
beyond the pre-set blocking threshold, restraining the
differential protection. The results analysed in this paper
demonstrate a harmonic blocking inrush identification
approach may adversely block the operation of the
Unwanted blocking of differential
protection during converter transformer
internal faults
Y. ZHAO*, P. CROSSLEY
The University of Manchester United Kingdom
KEYWORDS
HVDC, converter transformer, differential protection, half-cycle saturation, harmonic blocking
* yucong.zhao@postgrad.manchester.ac.uk
฀ ฀ ฀ ฀ ฀ ฀ ฀
54
the negative sequence components in the AC system
could introduce second harmonics into the thyristor
valves due to the interaction between the AC and DC
systems, causing unnecessary blocking of differential
protection. More tests, however, need to be conducted to
further verify these points. Paper [6] analysed the failure
of differential protection operation during converter
transformer internal faults. It was demonstrated that the
waveform of the differential current was high in the first
halfcycle of the fault current, but small in the next half-
cycle; this characteristic was similar to an inrush current
and consequently, the additional harmonics caused the
differential protection to be wrongly blocked. However,
the explanation about this result was based on the wave-
shape characteristics of the differential current, and the
reason for this unusual characteristic and the increase in
harmonics remain uncertain.
This paper thoroughly investigates the reasons
differential protection may fail to trip during a converter
transformer internal fault. To achieve this, the CIGRE
HVDC benchmark test system was simulated, and an
appropriate differential protection was applied to the
converter transformers. Multiple types of internal faults
were used to assess the dependability of differential
protection with harmonic blocking. Fault analysis
demonstrates an internal asymmetrical fault on the DC
side of the converter transformer results in a heavy DC
component that dominates the fault current and flows
to the fault point through the windings of the converter
transformer. This causes the converter transformer to
experience significant half-cycle saturation, which
results in the generation of excessive second harmonic
components. Eventually, the ratio of second harmonic
to fundamental in the differential current goes beyond
the blocking threshold, and this wrongly activates the
harmonic blocking.
2. Operating behaviour of
differential protection with
harmonic blocking during
converter transformer internal
faults
2.1. Modelling
To thoroughly demonstrate the operating behaviour of
differential protection during an internal fault on a
converter transformer.
1. Introduction
High-Voltage Direct Current (HVDC) is an effective
technique for delivering bulk electrical power over long
distances and for interconnecting asynchronous grids.
In a HVDC system, a converter transformer isolates the
AC grid from the DC link, and provides the appropriate
commutation voltages required by the valves. To limit
the damage to a converter transformer during short
circuits, differential protection is usually employed as
themainprotectionschemeowingtoitssimpleoperating
principle, high sensitivity on internal faults, and good
security against mal-operation on external faults and
non-fault events [1].
Nevertheless, conventional differential protection
encounters a critical challenge, i.e. distinguishing
between magnetizing inrush and internal faults.
Numerous methods have been proposed to prevent
differential protection mal-operation in the event of
transformer energization, and the most widely applied
approach is harmonic blocking. This approach assumes
the second harmonic component dominates an inrush
current but is significantly lower in a fault current.
Although the effectiveness of harmonic blocking has
beenconfirmedinmanyapplications,thisapproachhasa
limitation; it can be difficult to determine an appropriate
blocking threshold which can be guaranteed to not affect
the operating performance during an internal fault. This
is because the second harmonic component seen in the
internal fault current, may in some cases be as high as
that observed in an inrush current, and as a result, the
operationofdifferentialprotectionwouldbedesensitized
or delayed [2],[3].
Time-delayed fault clearance is unacceptable for
converter transformers, but few studies have considered
the operating behaviour of harmonic blocking during
converter transformer internal faults. Paper [4]
considered the harmonics produced by converters might
lead to the harmonic blocking element misjudging
the current caused by an internal fault to be an inrush
current, which means the operation of the differential
relay would be wrongly blocked. Paper [5] suggested,
in the case of converter transformer internal faults,
฀ ฀ ฀ ฀ ฀ ฀ ฀
55
where and arethephasecurrentsobtainedfromthe
protectionCTsattheACandDCsidesofT1respectively.
The operating characteristics of the protection were set
in accordance with conventional criteria, i.e. the tripping
threshold was 0.3 p.u., the breakpoint was 2 p.u., the
lower slope 1 was 30%, and the high slope 2 was 60%.
According to the surveys conducted by CIGRE WG
C2/B4.28 [9], the majority of transformer failures were
related to connections and terminals, because these
components are usually subjected to the superimposed
AC and DC stresses. In this regard, different types of
fault, single-phase to ground, phase-to-phase to ground,
and three-phase faults were applied on the terminal at
the DC side of T1 respectively, and each fault lasted for
0.5seconds.Thefollowingsubsectionsdescribeselected
results, where the differential protection failed to operate
on an internal fault.
2.3. Scenario 1: Single-phase to ground fault
Initially, a single-phase to ground (A-G) fault occurred
on the DC side T1 terminal at t = 1.005 s. The response
of differential protection is demonstrated in Fig. 2. In
this figure, Diff denotes the waveform of differential
current;Funddenotesthemagnitudeofthefundamental
component of differential current; and 2nd Ratio
denotes the ratio of second harmonic to fundamental
components in the differential current. The grey shaded
region shows when the harmonic blocking element was
activated.
As illustrated by the A-Diff in Fig. 2, the asymmetrical
A-G fault leads to an increase in differential current,
and the corresponding magnitude (A-Fund) is beyond
the operating threshold. In the meantime, the content
of the second harmonic in the A-phase differential
current increases, and the harmonic blocking element
is activated for a very short time (less than 10 ms).
This is caused by the sudden transient onset of the fault
which produces second harmonics in the differential
current, and this will occur for all faults [10]. The
A-2nd Ratio in Fig. 2 demonstrates a brief gap between
the shaded areas, suggesting the harmonic blocking
element is deactivated for 2 ms. In practice, the
differential protection is unable to operate during this
differential protection with harmonic blocking during
converter transformer internal faults, the CIGRE HVDC
benchmark test system available in PSCAD/EMTDC was
utilised, see Fig. 1. This is a standard reference model for
the study of an HVDC system in terms of control strategy
and recovery performance. This system is a monopolar
HVDC link designed to operate at 500 kV and 1000 MW.
The AC/DC converters are represented by two six-pulse
thyristor-based valves in series connection (i.e. forming
12-pulse converters) and are installed at both the rectifier
andinvertersides.Ineachconverterstation,twoconverter
transformers with winding connections of grounded
and provide a 30° phase shift to achieve the 12-pulse
rectification. More information about the primary system
can be found in [7] and [8].
In this paper, the protection of the converter transformer
T1 installed on the rectifier side is primarily studied.
The default parameters of T1 in this benchmark system
are 603.73 MVA and 345/213.4557 kV. The positive
sequence leakage reactance and copper loss are 0.18 p.u.
and 0.02 p.u. respectively, and the air-gap reactance is
0.2 p.u.; the knee point is 1.25 p.u. and the magnetizing
current is 1%. The protection currents are measured
from the CTs installed on both sides of the converter
transformer T1. To simplify the investigation, the
protection CTs are over-dimensioned, i.e. they do not
saturate during transient conditions. Therefore, the turns
ratio of the CTs on the AC and DC sides are 1500/5 and
2000/5 respectively, and each is connected to a burden
2.2. Transient study
In this study, the converter transformer T1 was
implemented with conventional percentage differential
protection with harmonic blocking. The differential
current and the bias current were derived using the
following equations:
(1)
(2)
Fig. 1. Single-line diagram of CIGRE benchmark HVDC system
฀ ฀ ฀ ฀ ฀ ฀ ฀
56
differential relay should initiate a trip signal. However,
the second harmonic ratios, A-2nd Ratio and B-2nd Ratio,
in the A and B phase differential currents are greater
than 15% for the entire duration of the fault occurrence.
Consequently, the differential protection is incorrectly
blocked, and this fault cannot be cleared in a reasonable
time.
3. Fault analysis
The previous two examples demonstrate incorrect
blocking of differential protection during converter
transformer internal faults. However, to determine
exactly why the protection failed to operate, Scenario 1
is now thoroughly analysed.
As illustrated in the A-Diff in Fig. 2, the waveform of
differential current sharply increases after the fault
initiation and then decreases demonstrating spikes.
This waveshape characteristic suggests the converter
time, i.e. differential protection cannot reliably detect
this internal fault and trip the T1 circuit breaker.
ThisA-Gfaultalsoresultsinasecondharmonicincrement
in the B-phase differential current. As illustrated by the
B-2nd Ratio in Fig. 2, the ratio of second harmonic to
fundamental is beyond the inhibiting threshold for the
entire transient period. Therefore, if the cross-blocking
function of the relay is activated, this A-G fault would
not be cleared within an appropriate time, as the relay is
incorrectly blocked by the harmonic blocking associated
with the B-phase differential element.
2.4. Scenario 2: Two-phase to ground fault
In this scenario, a double-phase to ground (A-B-G)
fault occurred on the DC side of T1 at t = 1.00 s. Fig.
3 describes the response of the differential protection
during this transient condition. It can be seen the
magnitudeofthedifferentialcurrents,A-DiffandB-Diff,
are above the tripping threshold, and consequently, the
Fig. 2. Failure to trip of differential protection duringA-G internal fault
฀ ฀ ฀ ฀ ฀ ฀ ฀
57
D61) of the valve group G1 are grounded, as shown in
Fig. 5. After the fault occurs, the DC currents on the
transmission line significantly decreases; the control
system at the rectifier side then provides fast response
to this current reduction and reduces the firing angle
from the nominal level ( ) to the minimum
limit ( ) to maintain the current level, as shown
in Fig. 6. This suggests the firing pulse is persistently
initiated to trigger the thyristors, i.e. the lower-arm
thyristors of G1 and the thyristors of G2 are capable of
conducting and commutating during the fault condition.
Consequently, after the fault occurs, DC currents are
converted by the valve group G2 and then delivered by
the lower-arm thyristors of G1. Because of the potential
difference between the fault point and the converter
ground electrode, these DC currents then return to the
ground electrode of G2 via the ground. As a result, a
new loop for DC currents is formed, i.e. valve group G2
– lowerarm of G1 – windings of converter transformer
transformerishalf-cyclesaturatedduringthefaultperiod.
Normally, the asymmetrical saturation of a transformer
is due to the superimposed AC flux and DC bias flux,
where the latter results from the DC components in
the fault current. To determine the DC components
experienced by T1 during the transient period, the Fast
Fourier Transform (FFT) module is used to extract the
DC components in the terminal currents of T1 and they
are displayed in Fig. 4. Note the reference direction of
theterminalcurrentistowardsthetransformer;hencethe
negative magnitude denotes the DC components flow
out of T1. Fig. 5 illustrates, during the transient period,
the flow path of these DC components produced by the
thyristors, based on the bridge-conducting sequence.
Note that the commutation overlap period is neglected.
The A-G fault on the DC side ofT1 can be treated as
a short-circuit across the valves [6],[11], i.e. the anode
of the upper-arm thyristors (D11, D31, and ) and
the cathode of the lower-arm thyristors (D21, D41, and
Fig. 3. Failure to trip of differential protection duringA-B-G internal fault
฀ ฀ ฀ ฀ ฀ ฀ ฀
58
in Fig. 5 (a)); the DC components in D61 and D21 flow
through the “short” by passing through the a-b and c-a
windings of the converter transformer T1 respectively
(see the red and yellow arrows in Fig. 5 (b) and (c));
afterwards, these DC components are superimposed on
the faulted phase currents and flow through the “short”.
The DC components displayed in the lower plot of Fig.
4 confirms this phenomenon, i.e. they flow into the
convertertransformerT1viathephaseBandCterminals
and out of T1 via the phaseA terminal.
– ground fault point – the ground – ground electrode of
G2.
Hence, during the transient period, the lower-arm
thyristors of G1 experience a “threephase short-circuit”,
and the fault currents deviate from the zero axis as they
contain significant DC offsets [12],[13]. Based on the
newly formed DC current loop, the fault currents flow
through the “short”. Hence the DC component in D41
flows into the faulted phase directly (see the pink arrow
Fig. 4. DC components in the terminal currents of T1
Fig. 5. Path loop of DC components experienced by T1
Fig. 6. Firing angle of the rectifier
฀ ฀ ฀ ฀ ฀ ฀ ฀
59
4. Conclusion
The operating behaviour of differential protection with
harmonic blocking in the event of converter transformer
internal faults was evaluated in this paper. A differential
protection scheme was designed and implemented on
the converter transformer used in the CIGRE HVDC
benchmark test system. The investigation shows that
differential protection is unnecessarily blocked when
an internal asymmetrical fault occurs on the DC side
of the converter transformer. Based on fault analysis,
it was demonstrated the DC components dominate the
fault current and they flow to the fault point via the
windings of the converter transformer. As a result, the
converter transformer is significantly saturated, due to
the additional DC bias flux, and this produces second
harmonics in the differential current. Consequently,
the ratio of second harmonic to fundamental in the
differential current exceeds the pre-set blocking
threshold, and the differential protection is incorrectly
blocked. The presented results demonstrate a harmonic
blocking based inrush identification method may
adversely affect the operation of differential protection
during converter transformer internal faults.
5. Bibliography
[1] K. Sharifabadi, L. Harnefors, H.-P. Nee, S. Norrga, and R.
Teodorescu, Design, Control and Application of Modular
Multilevel Converters for HVDC Transmission Systems.
Chichester, UK: John Wiley & Sons, Ltd, 2016.
[2] D. Bejmert, W. Rebizant, and L. Schiel, “Transformer differential
protection with fuzzy logic based inrush stabilization,” Int. J.
Electr. Power Energy Syst., vol. 63, pp. 51–63, Dec. 2014.
[3] E. Ali, A. Helal, H. Desouki, K. Shebl, S. Abdelkader, and O. P.
Malik, “Power transformer differential protection using current
and voltage ratios,” Electr. Power Syst. Res., vol. 154, pp. 140–
150, Jan. 2018.
[4] Y. Xiao, J. Wen, Y. Yuan, and W. Liu, “Protection of converter
transformer in HVDC,” Autom. Electr Power Syst, vol. 30, no. 9,
pp. 91–94, May 2006.
[5] J. Shi, “Discussion on relay protection and interrelated
equipment for converter station,” Hubei Electr Power, vol. 22,
no. 4, pp. 35–40, Dec. 1998.
[6] X. Lin et al., “Abnormal operation behavior analysis and
When the converter transformer T1 experiences these
DC components, it initially remains in the linear region
of its hysteresis loop, and a portion of the DC currents
are transiently induced on the AC side of the converter
transformer, as shown in the upper plot of Fig. 4. These
DC components generate DC excitation voltages across
the winding and the core. Because flux linkage is the
integraloftheexcitationvoltagebytime,thefluxlinkage
oftheconvertertransformercorerampsupaftert=1.005
s, as indicated by Fig. 7. When the flux increases, the
magnetic operating point of the core is gradually shifted
up, above the knee point, and the core enters saturation.
This suggests the non-linear inductance of the core
significantly reduces and eventually can be considered
as zero. Therefore, the voltage drop across the winding
falls to zero and the induced DC components in the
primary windings diminish. Ultimately, the converter
transformer enters into a severe half-cycle saturated
condition because of the DC components in the fault
current. Spikes are presented in the differential current,
and evenorder harmonics are produced; as a result,
the ratio of second harmonic to fundamental in the
differential current is beyond the inhibiting threshold
which leads to the incorrect blocking of the differential
protection.
The primary reason differential protection fails to trip
during converter transformer internal faults is half-
cycle saturation of the transformer core. This saturation
stems from the significant DC components in the
asymmetrical fault current. As a result, high levels of
the second harmonic component are measured by the
differential protection and this causes the activation of
a second harmonic blocking element. The likelihood of
unnecessary blocking is higher when the cross-blocking
functionisactivated.Consequently,aharmonicblocking
based inrush identification method is not suitable for
differential protection applied to converter transformers,
i.e. it is unable to differentiate inrush conditions from
internal faults.
Fig. 7 Converter transformer’s flux linkage increment due to extra DC bias flux
฀ ฀ ฀ ฀ ฀ ฀ ฀
60
Saturation on Transformer Differential Protection,” IEEE Trans.
Power Deliv., vol. 30, no. 3, pp. 1278–1287, Jun. 2015.
[11] X. Lin, J. Ma, Q. Tian, and H. Weng, Electromagnetic Transient
Analysis and Novel Protective Relaying Techniques for Power
Transformers. Singapore: John Wiley & Sons Singapore Pte. Ltd,
2014.
[12] J. Cheng and Z. Xu, “Analysis of AC Faults in Converter
Station and Characteristics of Its Relay Protection,” Proceeding
CSEE, vol. 31, no. 22, pp. 88–95, Aug. 2011.
[13] G. Li, J. Liang, F. Ma, C. E. Ugalde-Loo, and H. Liang, “Analysis
of Single-Phaseto-Ground Faults at the Valve-Side of HB-MMCs
in HVDC Systems,” IEEE Trans. Ind. Electron., vol. 66, no. 3, pp.
2444–2453, Mar. 2019.
countermeasures on the differential protection of converter
transformer,” Int. J. Electr. Power Energy Syst., vol. 64, pp. 516–
525, Jan. 2015.
[7] M. Szechtman, T. Wess, and C. V. Thio, “A Benchmark model for
HVDC system studies,” in International Conference on AC and
DC Power Transmission, 1991, 1991, pp. 1–5.
[8] M. Faruque, Y. Zhang, and V. Dinavahi, “Detailed Modeling of
CIGRÉ HVDC Benchmark System Using PSCAD/EMTDC and
PSB/SIMULINK,” IEEE Trans. Power Deliv., vol. 21, no. 1, pp.
378–387, Jan. 2006.
[9] CIGRE Joint Working Group A2/B4.28, “HVDC Converter
Transformers Design Review, Test Procedures, Ageing Evaluation
and Reliability in Service,” 2010.
[10] M. Stanbury and Z. Djekic, “The Impact of Current-Transformer

More Related Content

What's hot

Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
Hybrid HVDC Circuit Breaker Definitions
Hybrid HVDC Circuit Breaker  DefinitionsHybrid HVDC Circuit Breaker  Definitions
Hybrid HVDC Circuit Breaker DefinitionsAli Sepehri
 
Voltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit BreakersVoltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit BreakersAli Sepehri
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...IAEME Publication
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detailSlides Hub
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit iivenki249
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONDr. Rohit Babu
 
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Low
 
Transformer asset management
Transformer asset managementTransformer asset management
Transformer asset managementMuthar Hussain
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisHamedPasha1
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Dipen Kantariya
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]moiz89
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYRaviraj solanki
 
Circuit interruption
Circuit interruptionCircuit interruption
Circuit interruptionjawaharramaya
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its typesSlides Hub
 

What's hot (20)

Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
Hybrid HVDC Circuit Breaker Definitions
Hybrid HVDC Circuit Breaker  DefinitionsHybrid HVDC Circuit Breaker  Definitions
Hybrid HVDC Circuit Breaker Definitions
 
Voltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit BreakersVoltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit Breakers
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit ii
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015Edwin Newsletter on transformer failures on 13 October 2015
Edwin Newsletter on transformer failures on 13 October 2015
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
Transformer asset management
Transformer asset managementTransformer asset management
Transformer asset management
 
Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...
Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...
Efficient Approach to LVRT Capability of DFIG-Based Wind Turbines under Symme...
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response Analysis
 
Cz36611614
Cz36611614Cz36611614
Cz36611614
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
C231924
C231924C231924
C231924
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
Circuit interruption
Circuit interruptionCircuit interruption
Circuit interruption
 
Fuse and its types
Fuse and its typesFuse and its types
Fuse and its types
 

Similar to Unwanted blocking of diffrential protection during converter transformer internal faults

8 fault-analysis-and-electrical
8 fault-analysis-and-electrical8 fault-analysis-and-electrical
8 fault-analysis-and-electricalSenghuo LY
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdfThien Phan Bản
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLCSageer Ali Khan
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerIRJET Journal
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substationijtsrd
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.pptThien Phan Bản
 
Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Aditya Kumar Tripathy
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfSultanAlSaiari1
 
Alternator protection
Alternator protectionAlternator protection
Alternator protectionjawaharramaya
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...IOSR Journals
 
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdfvikip35
 
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...IRJET Journal
 

Similar to Unwanted blocking of diffrential protection during converter transformer internal faults (20)

8 fault-analysis-and-electrical
8 fault-analysis-and-electrical8 fault-analysis-and-electrical
8 fault-analysis-and-electrical
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLC
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power Transformer
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems
 
L44086268
L44086268L44086268
L44086268
 
circuit breaker
circuit breakercircuit breaker
circuit breaker
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
Dp35648654
Dp35648654Dp35648654
Dp35648654
 
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...
 

More from Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

Basics of Relay for Engineering Students
Basics of Relay for Engineering StudentsBasics of Relay for Engineering Students
Basics of Relay for Engineering Studentskannan348865
 
15-Minute City: A Completely New Horizon
15-Minute City: A Completely New Horizon15-Minute City: A Completely New Horizon
15-Minute City: A Completely New HorizonMorshed Ahmed Rahath
 
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfInvolute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfJNTUA
 
electrical installation and maintenance.
electrical installation and maintenance.electrical installation and maintenance.
electrical installation and maintenance.benjamincojr
 
Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...IJECEIAES
 
Dynamo Scripts for Task IDs and Space Naming.pptx
Dynamo Scripts for Task IDs and Space Naming.pptxDynamo Scripts for Task IDs and Space Naming.pptx
Dynamo Scripts for Task IDs and Space Naming.pptxMustafa Ahmed
 
The Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxThe Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxMANASINANDKISHORDEOR
 
Filters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsFilters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsMathias Magdowski
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...drjose256
 
Intro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniIntro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniR. Sosa
 
History of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationHistory of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationEmaan Sharma
 
NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...
NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...
NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...Amil baba
 
Passive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptPassive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptamrabdallah9
 
Software Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdfSoftware Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdfssuser5c9d4b1
 
Diploma Engineering Drawing Qp-2024 Ece .pdf
Diploma Engineering Drawing Qp-2024 Ece .pdfDiploma Engineering Drawing Qp-2024 Ece .pdf
Diploma Engineering Drawing Qp-2024 Ece .pdfJNTUA
 
5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...archanaece3
 
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdflitvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdfAlexander Litvinenko
 
What is Coordinate Measuring Machine? CMM Types, Features, Functions
What is Coordinate Measuring Machine? CMM Types, Features, FunctionsWhat is Coordinate Measuring Machine? CMM Types, Features, Functions
What is Coordinate Measuring Machine? CMM Types, Features, FunctionsVIEW
 
Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1T.D. Shashikala
 
Maximizing Incident Investigation Efficacy in Oil & Gas: Techniques and Tools
Maximizing Incident Investigation Efficacy in Oil & Gas: Techniques and ToolsMaximizing Incident Investigation Efficacy in Oil & Gas: Techniques and Tools
Maximizing Incident Investigation Efficacy in Oil & Gas: Techniques and Toolssoginsider
 

Recently uploaded (20)

Basics of Relay for Engineering Students
Basics of Relay for Engineering StudentsBasics of Relay for Engineering Students
Basics of Relay for Engineering Students
 
15-Minute City: A Completely New Horizon
15-Minute City: A Completely New Horizon15-Minute City: A Completely New Horizon
15-Minute City: A Completely New Horizon
 
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfInvolute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
 
electrical installation and maintenance.
electrical installation and maintenance.electrical installation and maintenance.
electrical installation and maintenance.
 
Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...
 
Dynamo Scripts for Task IDs and Space Naming.pptx
Dynamo Scripts for Task IDs and Space Naming.pptxDynamo Scripts for Task IDs and Space Naming.pptx
Dynamo Scripts for Task IDs and Space Naming.pptx
 
The Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxThe Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptx
 
Filters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsFilters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility Applications
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
 
Intro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniIntro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney Uni
 
History of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationHistory of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & Modernization
 
NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...
NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...
NO1 Best Powerful Vashikaran Specialist Baba Vashikaran Specialist For Love V...
 
Passive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptPassive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.ppt
 
Software Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdfSoftware Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdf
 
Diploma Engineering Drawing Qp-2024 Ece .pdf
Diploma Engineering Drawing Qp-2024 Ece .pdfDiploma Engineering Drawing Qp-2024 Ece .pdf
Diploma Engineering Drawing Qp-2024 Ece .pdf
 
5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...
 
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdflitvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
 
What is Coordinate Measuring Machine? CMM Types, Features, Functions
What is Coordinate Measuring Machine? CMM Types, Features, FunctionsWhat is Coordinate Measuring Machine? CMM Types, Features, Functions
What is Coordinate Measuring Machine? CMM Types, Features, Functions
 
Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1
 
Maximizing Incident Investigation Efficacy in Oil & Gas: Techniques and Tools
Maximizing Incident Investigation Efficacy in Oil & Gas: Techniques and ToolsMaximizing Incident Investigation Efficacy in Oil & Gas: Techniques and Tools
Maximizing Incident Investigation Efficacy in Oil & Gas: Techniques and Tools
 

Unwanted blocking of diffrential protection during converter transformer internal faults

  • 1. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 53 Summary High-Voltage Direct Current (HVDC) technology transports bulk electrical power over long distances efficiently and economically, and also allows the interconnectionofasynchronouspowergrids.InaHVDC converter station, a converter transformer provides the appropriate voltage for converter commutation and also ensures galvanic isolation between the AC system and the DC link. The provision of adequate protection for a converter transformer is crucial; it must limit the damage to the transformer and adjacent plant when an internal short-circuit fault occurs. Differential protection is widely applied to converter transformers, owing to its simple operating principle, high sensitivity on internal faults, and excellent security on external faults. Nevertheless, a challenge is to prevent mal-operation during transformer energization (i.e. magnetizing inrush). Numerous techniques have been used to discriminate between inrush conditions and internal faults, but harmonic blocking is the simplest and the most widely used solution. Harmonic blocking assumes the second harmonic component dominates the inrush current, but is an insignificant component of the internal fault current. However, this approach is less effective in modern transformers that use cores made by low-loss amorphous materials; these materials produce lower harmonics in the inrush currents. The challenges are even more complex for a converter transformer, which operates in a complicated environment affected by AC and DC stresses.This suggests significant second and fifth harmonic components can occur in the internal fault current, and the fault current may behave like an inrush current. As a result, a harmonic blocking element may wronglyinhibittheoperationofthedifferentialprotection, and the converter transformer may be subjected to fault currents for an extended period, leading to severe damage or even the rupture of the transformer tank. Differential protection must detect all possible short- circuit faults within a converter transformer, but few studies have considered how harmonic blocking performs when an internal fault occurs in a converter transformer. This paper investigates whether harmonic blocking is suitable for identifying inrush conditions in a convertertransformer.Toachievethis,theCIGREHVDC benchmark test system available in PSCAD/EMTDC is utilized, and an appropriate differential protection scheme is designed for the converter transformers. Asymmetrical internal faults are simulated to assess the operating behaviour of the differential protection with harmonic blocking. The test results demonstrate the differential protection is unable to initiate a trip signal when an internal phase to ground fault is applied on the DC side of a converter transformer. The fault analysis implies the fault current contains a heavy DC component which flows towards the fault point via the windings of the converter transformer. This heavy DC component induces a DC bias flux, which leads to significant converter transformer half-cycle saturation, and results in an increase in the second harmonic in the differential current. As a result, the ratio of second harmonic to fundamental in the differential current is beyond the pre-set blocking threshold, restraining the differential protection. The results analysed in this paper demonstrate a harmonic blocking inrush identification approach may adversely block the operation of the Unwanted blocking of differential protection during converter transformer internal faults Y. ZHAO*, P. CROSSLEY The University of Manchester United Kingdom KEYWORDS HVDC, converter transformer, differential protection, half-cycle saturation, harmonic blocking * yucong.zhao@postgrad.manchester.ac.uk
  • 2. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 54 the negative sequence components in the AC system could introduce second harmonics into the thyristor valves due to the interaction between the AC and DC systems, causing unnecessary blocking of differential protection. More tests, however, need to be conducted to further verify these points. Paper [6] analysed the failure of differential protection operation during converter transformer internal faults. It was demonstrated that the waveform of the differential current was high in the first halfcycle of the fault current, but small in the next half- cycle; this characteristic was similar to an inrush current and consequently, the additional harmonics caused the differential protection to be wrongly blocked. However, the explanation about this result was based on the wave- shape characteristics of the differential current, and the reason for this unusual characteristic and the increase in harmonics remain uncertain. This paper thoroughly investigates the reasons differential protection may fail to trip during a converter transformer internal fault. To achieve this, the CIGRE HVDC benchmark test system was simulated, and an appropriate differential protection was applied to the converter transformers. Multiple types of internal faults were used to assess the dependability of differential protection with harmonic blocking. Fault analysis demonstrates an internal asymmetrical fault on the DC side of the converter transformer results in a heavy DC component that dominates the fault current and flows to the fault point through the windings of the converter transformer. This causes the converter transformer to experience significant half-cycle saturation, which results in the generation of excessive second harmonic components. Eventually, the ratio of second harmonic to fundamental in the differential current goes beyond the blocking threshold, and this wrongly activates the harmonic blocking. 2. Operating behaviour of differential protection with harmonic blocking during converter transformer internal faults 2.1. Modelling To thoroughly demonstrate the operating behaviour of differential protection during an internal fault on a converter transformer. 1. Introduction High-Voltage Direct Current (HVDC) is an effective technique for delivering bulk electrical power over long distances and for interconnecting asynchronous grids. In a HVDC system, a converter transformer isolates the AC grid from the DC link, and provides the appropriate commutation voltages required by the valves. To limit the damage to a converter transformer during short circuits, differential protection is usually employed as themainprotectionschemeowingtoitssimpleoperating principle, high sensitivity on internal faults, and good security against mal-operation on external faults and non-fault events [1]. Nevertheless, conventional differential protection encounters a critical challenge, i.e. distinguishing between magnetizing inrush and internal faults. Numerous methods have been proposed to prevent differential protection mal-operation in the event of transformer energization, and the most widely applied approach is harmonic blocking. This approach assumes the second harmonic component dominates an inrush current but is significantly lower in a fault current. Although the effectiveness of harmonic blocking has beenconfirmedinmanyapplications,thisapproachhasa limitation; it can be difficult to determine an appropriate blocking threshold which can be guaranteed to not affect the operating performance during an internal fault. This is because the second harmonic component seen in the internal fault current, may in some cases be as high as that observed in an inrush current, and as a result, the operationofdifferentialprotectionwouldbedesensitized or delayed [2],[3]. Time-delayed fault clearance is unacceptable for converter transformers, but few studies have considered the operating behaviour of harmonic blocking during converter transformer internal faults. Paper [4] considered the harmonics produced by converters might lead to the harmonic blocking element misjudging the current caused by an internal fault to be an inrush current, which means the operation of the differential relay would be wrongly blocked. Paper [5] suggested, in the case of converter transformer internal faults,
  • 3. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 55 where and arethephasecurrentsobtainedfromthe protectionCTsattheACandDCsidesofT1respectively. The operating characteristics of the protection were set in accordance with conventional criteria, i.e. the tripping threshold was 0.3 p.u., the breakpoint was 2 p.u., the lower slope 1 was 30%, and the high slope 2 was 60%. According to the surveys conducted by CIGRE WG C2/B4.28 [9], the majority of transformer failures were related to connections and terminals, because these components are usually subjected to the superimposed AC and DC stresses. In this regard, different types of fault, single-phase to ground, phase-to-phase to ground, and three-phase faults were applied on the terminal at the DC side of T1 respectively, and each fault lasted for 0.5seconds.Thefollowingsubsectionsdescribeselected results, where the differential protection failed to operate on an internal fault. 2.3. Scenario 1: Single-phase to ground fault Initially, a single-phase to ground (A-G) fault occurred on the DC side T1 terminal at t = 1.005 s. The response of differential protection is demonstrated in Fig. 2. In this figure, Diff denotes the waveform of differential current;Funddenotesthemagnitudeofthefundamental component of differential current; and 2nd Ratio denotes the ratio of second harmonic to fundamental components in the differential current. The grey shaded region shows when the harmonic blocking element was activated. As illustrated by the A-Diff in Fig. 2, the asymmetrical A-G fault leads to an increase in differential current, and the corresponding magnitude (A-Fund) is beyond the operating threshold. In the meantime, the content of the second harmonic in the A-phase differential current increases, and the harmonic blocking element is activated for a very short time (less than 10 ms). This is caused by the sudden transient onset of the fault which produces second harmonics in the differential current, and this will occur for all faults [10]. The A-2nd Ratio in Fig. 2 demonstrates a brief gap between the shaded areas, suggesting the harmonic blocking element is deactivated for 2 ms. In practice, the differential protection is unable to operate during this differential protection with harmonic blocking during converter transformer internal faults, the CIGRE HVDC benchmark test system available in PSCAD/EMTDC was utilised, see Fig. 1. This is a standard reference model for the study of an HVDC system in terms of control strategy and recovery performance. This system is a monopolar HVDC link designed to operate at 500 kV and 1000 MW. The AC/DC converters are represented by two six-pulse thyristor-based valves in series connection (i.e. forming 12-pulse converters) and are installed at both the rectifier andinvertersides.Ineachconverterstation,twoconverter transformers with winding connections of grounded and provide a 30° phase shift to achieve the 12-pulse rectification. More information about the primary system can be found in [7] and [8]. In this paper, the protection of the converter transformer T1 installed on the rectifier side is primarily studied. The default parameters of T1 in this benchmark system are 603.73 MVA and 345/213.4557 kV. The positive sequence leakage reactance and copper loss are 0.18 p.u. and 0.02 p.u. respectively, and the air-gap reactance is 0.2 p.u.; the knee point is 1.25 p.u. and the magnetizing current is 1%. The protection currents are measured from the CTs installed on both sides of the converter transformer T1. To simplify the investigation, the protection CTs are over-dimensioned, i.e. they do not saturate during transient conditions. Therefore, the turns ratio of the CTs on the AC and DC sides are 1500/5 and 2000/5 respectively, and each is connected to a burden 2.2. Transient study In this study, the converter transformer T1 was implemented with conventional percentage differential protection with harmonic blocking. The differential current and the bias current were derived using the following equations: (1) (2) Fig. 1. Single-line diagram of CIGRE benchmark HVDC system
  • 4. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 56 differential relay should initiate a trip signal. However, the second harmonic ratios, A-2nd Ratio and B-2nd Ratio, in the A and B phase differential currents are greater than 15% for the entire duration of the fault occurrence. Consequently, the differential protection is incorrectly blocked, and this fault cannot be cleared in a reasonable time. 3. Fault analysis The previous two examples demonstrate incorrect blocking of differential protection during converter transformer internal faults. However, to determine exactly why the protection failed to operate, Scenario 1 is now thoroughly analysed. As illustrated in the A-Diff in Fig. 2, the waveform of differential current sharply increases after the fault initiation and then decreases demonstrating spikes. This waveshape characteristic suggests the converter time, i.e. differential protection cannot reliably detect this internal fault and trip the T1 circuit breaker. ThisA-Gfaultalsoresultsinasecondharmonicincrement in the B-phase differential current. As illustrated by the B-2nd Ratio in Fig. 2, the ratio of second harmonic to fundamental is beyond the inhibiting threshold for the entire transient period. Therefore, if the cross-blocking function of the relay is activated, this A-G fault would not be cleared within an appropriate time, as the relay is incorrectly blocked by the harmonic blocking associated with the B-phase differential element. 2.4. Scenario 2: Two-phase to ground fault In this scenario, a double-phase to ground (A-B-G) fault occurred on the DC side of T1 at t = 1.00 s. Fig. 3 describes the response of the differential protection during this transient condition. It can be seen the magnitudeofthedifferentialcurrents,A-DiffandB-Diff, are above the tripping threshold, and consequently, the Fig. 2. Failure to trip of differential protection duringA-G internal fault
  • 5. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 57 D61) of the valve group G1 are grounded, as shown in Fig. 5. After the fault occurs, the DC currents on the transmission line significantly decreases; the control system at the rectifier side then provides fast response to this current reduction and reduces the firing angle from the nominal level ( ) to the minimum limit ( ) to maintain the current level, as shown in Fig. 6. This suggests the firing pulse is persistently initiated to trigger the thyristors, i.e. the lower-arm thyristors of G1 and the thyristors of G2 are capable of conducting and commutating during the fault condition. Consequently, after the fault occurs, DC currents are converted by the valve group G2 and then delivered by the lower-arm thyristors of G1. Because of the potential difference between the fault point and the converter ground electrode, these DC currents then return to the ground electrode of G2 via the ground. As a result, a new loop for DC currents is formed, i.e. valve group G2 – lowerarm of G1 – windings of converter transformer transformerishalf-cyclesaturatedduringthefaultperiod. Normally, the asymmetrical saturation of a transformer is due to the superimposed AC flux and DC bias flux, where the latter results from the DC components in the fault current. To determine the DC components experienced by T1 during the transient period, the Fast Fourier Transform (FFT) module is used to extract the DC components in the terminal currents of T1 and they are displayed in Fig. 4. Note the reference direction of theterminalcurrentistowardsthetransformer;hencethe negative magnitude denotes the DC components flow out of T1. Fig. 5 illustrates, during the transient period, the flow path of these DC components produced by the thyristors, based on the bridge-conducting sequence. Note that the commutation overlap period is neglected. The A-G fault on the DC side ofT1 can be treated as a short-circuit across the valves [6],[11], i.e. the anode of the upper-arm thyristors (D11, D31, and ) and the cathode of the lower-arm thyristors (D21, D41, and Fig. 3. Failure to trip of differential protection duringA-B-G internal fault
  • 6. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 58 in Fig. 5 (a)); the DC components in D61 and D21 flow through the “short” by passing through the a-b and c-a windings of the converter transformer T1 respectively (see the red and yellow arrows in Fig. 5 (b) and (c)); afterwards, these DC components are superimposed on the faulted phase currents and flow through the “short”. The DC components displayed in the lower plot of Fig. 4 confirms this phenomenon, i.e. they flow into the convertertransformerT1viathephaseBandCterminals and out of T1 via the phaseA terminal. – ground fault point – the ground – ground electrode of G2. Hence, during the transient period, the lower-arm thyristors of G1 experience a “threephase short-circuit”, and the fault currents deviate from the zero axis as they contain significant DC offsets [12],[13]. Based on the newly formed DC current loop, the fault currents flow through the “short”. Hence the DC component in D41 flows into the faulted phase directly (see the pink arrow Fig. 4. DC components in the terminal currents of T1 Fig. 5. Path loop of DC components experienced by T1 Fig. 6. Firing angle of the rectifier
  • 7. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 59 4. Conclusion The operating behaviour of differential protection with harmonic blocking in the event of converter transformer internal faults was evaluated in this paper. A differential protection scheme was designed and implemented on the converter transformer used in the CIGRE HVDC benchmark test system. The investigation shows that differential protection is unnecessarily blocked when an internal asymmetrical fault occurs on the DC side of the converter transformer. Based on fault analysis, it was demonstrated the DC components dominate the fault current and they flow to the fault point via the windings of the converter transformer. As a result, the converter transformer is significantly saturated, due to the additional DC bias flux, and this produces second harmonics in the differential current. Consequently, the ratio of second harmonic to fundamental in the differential current exceeds the pre-set blocking threshold, and the differential protection is incorrectly blocked. The presented results demonstrate a harmonic blocking based inrush identification method may adversely affect the operation of differential protection during converter transformer internal faults. 5. Bibliography [1] K. Sharifabadi, L. Harnefors, H.-P. Nee, S. Norrga, and R. Teodorescu, Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems. Chichester, UK: John Wiley & Sons, Ltd, 2016. [2] D. Bejmert, W. Rebizant, and L. Schiel, “Transformer differential protection with fuzzy logic based inrush stabilization,” Int. J. Electr. Power Energy Syst., vol. 63, pp. 51–63, Dec. 2014. [3] E. Ali, A. Helal, H. Desouki, K. Shebl, S. Abdelkader, and O. P. Malik, “Power transformer differential protection using current and voltage ratios,” Electr. Power Syst. Res., vol. 154, pp. 140– 150, Jan. 2018. [4] Y. Xiao, J. Wen, Y. Yuan, and W. Liu, “Protection of converter transformer in HVDC,” Autom. Electr Power Syst, vol. 30, no. 9, pp. 91–94, May 2006. [5] J. Shi, “Discussion on relay protection and interrelated equipment for converter station,” Hubei Electr Power, vol. 22, no. 4, pp. 35–40, Dec. 1998. [6] X. Lin et al., “Abnormal operation behavior analysis and When the converter transformer T1 experiences these DC components, it initially remains in the linear region of its hysteresis loop, and a portion of the DC currents are transiently induced on the AC side of the converter transformer, as shown in the upper plot of Fig. 4. These DC components generate DC excitation voltages across the winding and the core. Because flux linkage is the integraloftheexcitationvoltagebytime,thefluxlinkage oftheconvertertransformercorerampsupaftert=1.005 s, as indicated by Fig. 7. When the flux increases, the magnetic operating point of the core is gradually shifted up, above the knee point, and the core enters saturation. This suggests the non-linear inductance of the core significantly reduces and eventually can be considered as zero. Therefore, the voltage drop across the winding falls to zero and the induced DC components in the primary windings diminish. Ultimately, the converter transformer enters into a severe half-cycle saturated condition because of the DC components in the fault current. Spikes are presented in the differential current, and evenorder harmonics are produced; as a result, the ratio of second harmonic to fundamental in the differential current is beyond the inhibiting threshold which leads to the incorrect blocking of the differential protection. The primary reason differential protection fails to trip during converter transformer internal faults is half- cycle saturation of the transformer core. This saturation stems from the significant DC components in the asymmetrical fault current. As a result, high levels of the second harmonic component are measured by the differential protection and this causes the activation of a second harmonic blocking element. The likelihood of unnecessary blocking is higher when the cross-blocking functionisactivated.Consequently,aharmonicblocking based inrush identification method is not suitable for differential protection applied to converter transformers, i.e. it is unable to differentiate inrush conditions from internal faults. Fig. 7 Converter transformer’s flux linkage increment due to extra DC bias flux
  • 8. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 60 Saturation on Transformer Differential Protection,” IEEE Trans. Power Deliv., vol. 30, no. 3, pp. 1278–1287, Jun. 2015. [11] X. Lin, J. Ma, Q. Tian, and H. Weng, Electromagnetic Transient Analysis and Novel Protective Relaying Techniques for Power Transformers. Singapore: John Wiley & Sons Singapore Pte. Ltd, 2014. [12] J. Cheng and Z. Xu, “Analysis of AC Faults in Converter Station and Characteristics of Its Relay Protection,” Proceeding CSEE, vol. 31, no. 22, pp. 88–95, Aug. 2011. [13] G. Li, J. Liang, F. Ma, C. E. Ugalde-Loo, and H. Liang, “Analysis of Single-Phaseto-Ground Faults at the Valve-Side of HB-MMCs in HVDC Systems,” IEEE Trans. Ind. Electron., vol. 66, no. 3, pp. 2444–2453, Mar. 2019. countermeasures on the differential protection of converter transformer,” Int. J. Electr. Power Energy Syst., vol. 64, pp. 516– 525, Jan. 2015. [7] M. Szechtman, T. Wess, and C. V. Thio, “A Benchmark model for HVDC system studies,” in International Conference on AC and DC Power Transmission, 1991, 1991, pp. 1–5. [8] M. Faruque, Y. Zhang, and V. Dinavahi, “Detailed Modeling of CIGRÉ HVDC Benchmark System Using PSCAD/EMTDC and PSB/SIMULINK,” IEEE Trans. Power Deliv., vol. 21, no. 1, pp. 378–387, Jan. 2006. [9] CIGRE Joint Working Group A2/B4.28, “HVDC Converter Transformers Design Review, Test Procedures, Ageing Evaluation and Reliability in Service,” 2010. [10] M. Stanbury and Z. Djekic, “The Impact of Current-Transformer