Fault Analysis and Electrical Protection of Distribution
Transformers
By Md Asaduzzaman Nur, Mehdi Hasan Sourov, M. S. Muhit
& Md Khaled Hossain
American International University, Bangladesh
Abstract- The demand on the electric power for the household, commercial and industrial loads is on the
increase. Also, the management of electric distribution system is becoming more complex. Lack of
information at the base station regarding status of the distribution network has been identified as the
major bottleneck to its effective monitoring and control. The work described is a development of
Microcontroller-based Protection of Electric Distribution system for the purpose of effective monitoring
and control of distribution system. A powerful GSM networking is designed to send data from Distribution
side to the Sub-station and a Matlab GUI system has been develop to show the data. In general, the
proposed design is developed for the user to easily recognize the distribution transformer is safe or
unsafe and the distribution line that is suffered by fault. The ultimate objective is to monitor the distribution
line status continuously and hence to guard the fault of distribution line due to the constraints such as
overvoltage, under voltage, SLG, DLG faults. If any of these does occurs then a message will be sent to
the designed controlling unit or substation.
Keywords: microcontroller, transformer protection, GSM module, GUI, bridge rectifier, wireless
monitoring & control.
GJRE-F Classification : FOR Code: 290901p
FaultAnalysisandElectricalProtectionofDistributionTransformers
Strictly as per the compliance and regulations of :
Fault Analysis and Electrical Protection of
Distribution Transformers
Md Asaduzzaman Nur α
, Mehdi Hasan Sourov σ
, M. S. Muhit ρ
& Md Khaled Hossain Ѡ
Abstract- The demand on the electric power for the household,
commercial and industrial loads is on the increase. Also, the
management of electric distribution system is becoming more
complex. Lack of information at the base station regarding
status of the distribution network has been identified as the
major bottleneck to its effective monitoring and control. The
work described is a development of Microcontroller-based
Protection of Electric Distribution system for the purpose of
effective monitoring and control of distribution system. A
powerful GSM networking is designed to send data from
Distribution side to the Sub-station and a Matlab GUI system
has been develop to show the data. In general, the proposed
design is developed for the user to easily recognize the
distribution transformer is safe or unsafe and the distribution
line that is suffered by fault. The ultimate objective is to monitor
the distribution line status continuously and hence to guard the
fault of distribution line due to the constraints such as
overvoltage, under voltage, SLG, DLG faults. If any of these
does occurs then a message will be sent to the designed
controlling unit or substation.
Keywords: microcontroller, transformer protection, GSM
module, GUI, bridge rectifier, wireless monitoring &
control.
I. INTRODUCTION
rotection system’s main function is to clear faults
from the power system at high speed to ensure
safety, minimize equipment damage and maintain
power system stability[2]. Protection of power systems
requires an understanding of system faults, their
detection, and safe isolation of the faulted device. By
taking an inventory of all the essential electrical loads
and doing a basic electrical load evaluation [2], an idea
regarding how much power our system needs to
produce has been obtained. We are also aware about
the power fluctuation situations also that means what
voltage minimum / maximum we are getting from the
A.C supply mains. In doing this project we would be
using concepts of microcontrollers, GSM network and
GUI of MATLAB.
II. Fault Types and Protection
a) Single-Line-to-Ground Fault
A short circuit between one line and ground,
very often caused by physical contact, for example due
Author α σ Ѡ: Student, Electrical and Electronic engineering
department, AIUB, Dhaka, Bangladesh 1.
e-mail: nur.aiub@yahoo.com
Author ρ: Faculty, Electrical and Electronic engineering department,
AIUB, Dhaka, Bangladesh 3.
to lightning or other common means. The single line to
ground fault can occur in any of the three phases [1].
However, it is sufficient to analyze only one of the cases.
Figure 1 : Single Line to Ground fault
b) Line-to-Line Fault
A short circuit between lines, caused by
ionization of air, or when lines come into physical
contact[1], for example due to a broken insulator. For a
Line-to-line fault, the currents will be high, because the
fault current is only limited by the inherent (natural)
series impedance of the power system up to the point of
faulty (refer Ohms law).
Figure 2 : Line to line fault
P
GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI
61
Year2014
© 2014 Global Journals Inc. (US)
c) Double-Line-to Ground Fault
Two lines come into contact with the ground
(and each other), also commonly due to stormy weather
or some other means [1].
Figure 3 : Double line to Ground Fault
d) Transformer Protection
Transformers are a critical and expensive
component of the power system. Due to the long lead
time for repair of and replacement of transformers, a
major goal of transformer protection will restrict the
damage to a faulted transformer & also protect it from
thieves to avoid long term area blackouts. The
comprehensive transformer protection provided by
multiple function protective relays is appropriate for
critical transformers of all applications [2]. Organized
theft of electric transformers from live transmission lines
is widespread throughout the country making power
distribution agencies and consumers counting losses in
several millions of BDT and great sufferings. In the last
10 years, electric transformers worth BDT 2000 Million
had been stolen. So, for an improved power system
stability and efficiently innovative technology, a micro
controller based protection system should be achieved
to protect transformers.
e) Lower Voltage
Low voltage is a relative term, the definition
varying by context. Different definitions are used in
transmission and distribution line, and in the electronics
industry. Electrical safety codes define "low voltage"
circuits that are exempt from the protection required at
higher voltages. These definitions vary by country and
specific code. Lower voltage is defined as incoming line
voltage at the point of use which is smaller than the
Public Service Commission’s mandated legal limits;
and/or smaller than the voltage ratings of the connected
equipment. Lower voltage is considered a safety hazard
by all industry standards and can cause premature
failure of connected equipment. Devices could be
damaged by lower line voltage.
f) Over Voltage
Overvoltage is defined as incoming line voltage
at the point of use which is greater than the Public
Service Commission’s mandated legal limits; and/or
greater than the voltage ratings of the connected
equipment. Overvoltage is considered a safety hazard
by all industry standards, and can cause premature
failure of connected equipment. Overvoltage has been a
widely known industry problem for many years, but it is
not generally understood by many who have to deal with
it. Power companies have been unable to control it
adequately. Overvoltage occurs most often during
severe cold winter weather for the following reasons: (1)
Inadequate size of power distribution systems; (2) slow
reaction time for power company’s distribution systems
to regulate voltage during extreme load variations; and
(3) abrupt reductions of loads
III. Block Diagram Arrangement
In figure 4, the basic arrangement of the
implemented project can be found.
Figure 4 : Block diagram arrangement of the project
Among the major components required to
establish the project, few of them are the power
transformers (step down), microcontroller ATMEGA 16
and GSM module, Bridge rectifier.
a) Transformer
Transformer is an electrical device used to step
up and down the AC voltages. There are two types of
transformers: Step up and step down transformer. Step
up transformer increases the magnitude of voltage while
step down transformer decrease the magnitude of
voltage. Depending on the ratio of the number of turns
in the primary & secondary winding a transformer is
characterized as step up or step down. For this project
purpose, considering 1Ф voltage to be around 220 V, 3
step down power transformer of rating 220/12 has been
used to represent a realistic representation of the 3 Ф
system.
GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI
62
Year2014
© 2014 Global Journals Inc. (US)
Fault Analysis and Electrical Protection of Distribution Transformers
Figure 5 : 220v/12v transformer
b) Microcontroller ATMEGA 16
Brain of this project is Atmega16 micro-
controller. It is a 8 bit Micro controller with RISC
architecture. Its speed is up to 16MIPS throughput at
16MHz. It has 16K bytes of flash and 512 bytes
EEPROM. Operating voltage 2.7v -5.5v, in active mode it
consumes only 1.1mA & in sleep mode it consumes
less than 1uA current which made it a perfect choice for
his project [3].
c) GSM Module
Sim900 has been used as GSM module.
SIM900 module is a complete Quad-Band GSM/GPRS
module which combines GPS technology for satellite
navigation. The compact design which integrated GPRS
and GPS in a SMT package will significantly save both
time and costs. Power consumption (GSM engine in
sleep mode) around 1.5mA and Power consumption
(GSM engine in idle mode) around 77mA [4].
Figure 7 : GSM module Sim900
d) Bridge Rectifier
An AC power source is required for powering
major appliances but almost all electronic circuits
require a steady DC supply. A simple rectifier circuit
described in this project converts the input from AC
source to DC voltage. Firstly, the AC input from mains is
stepped down to a lower value of voltage. This AC
supply is then passed through a rectifier circuit to
remove the negative cycle of AC waveform. The
resulting signal is then filtered to get the DC output. The
major part of the circuit is connected to the secondary
coil of the transformer which is comprised by diodes
and capacitor. While the diodes act as a rectifiers,
capacitor filters out the DC component from the circuit.
Figure 8 : Bridge rectifier
IV. Simulation
The initial stage, the circuits have been
designed and simulated in PROTEUS. The circuit have
GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI
63
Year2014
© 2014 Global Journals Inc. (US)
Figure 6 : Atmega16 microcontroller
been utilized to analyze the line to line, single line to
Fault Analysis and Electrical Protection of Distribution Transformers
Figure 9 : Circuit Simulation
V. Hardware Implementation
In reference to figure 4, the transmitting and
receiving side can be described as follows:
a) Transmitting Side
Heart of the project is the microcontroller
ATMEGA 16. In general the normal distribution phase
voltage is 220 V, in this project we used a step down
transformer 220/12 V for converting the phase voltage
from 220 V to 12 V. Then, a bridge rectifier has been
used for converting the 12 V ac to 12 V dc; after that,
applied voltage divider converts the 12 V to 5 V because
the microcontroller works at maximum 5 V. By this
process the three distribution phase is connected into
three microcontroller pins and the power transformer is
connected by a narrow wire between 2 pins of the
microcontroller. At cases, when the distribution side is in
load shedding protection of transformer must be
ensured, which is why the microcontroller power is given
from an external power source (5 V battery) backup and
also the GSM module power is given from external
power source(9V battery) because GSM module
consumes lots of power. GSM module communicates
with atmeg16 through UART. RXD of GSM module is
connected with TXD of atmega16 and TXD of GSM
module is connected to RXD of atmega16.
b) Receiving Side
In receiver circuit another GSM Modem is
connected with PC via USB-To-Serial converter. The GUI
in MATLAB software has been is used such that it will
read the message and the data will save it in an excel
file and it will show a graph according to the data by
using the interface. If any fault occurs, it is also capable
to generate an alarm and a fault message box
according to the fault. The communication protocol is
UART and baud rate is 9600[4].
In view of the descriptions above, the
implemented hardware can be found in figure 10.
Figure 10 : Implemented Hardware model
Figure 11 : LCD status indicator
As viewed from figure 10, the system was found
to be balanced three phase system. In figure 11, the
corresponding representation appears in the LCD
display with the phase voltages in all the phases to be
around 219 V. The view from GUI interface is also shown
in figure 12.
Figure 12 : GUI interface from PC
GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI
64
Year2014
© 2014 Global Journals Inc. (US)
ground, double line to ground, open conductor, over
voltage and under voltage in the sides of the
transformer. The circuit diagram can be found in figure
9.
Fault Analysis and Electrical Protection of Distribution Transformers
VI. Future Prospects
In view of a wide range of possibilities on the
basis of microcontroller based protection system, a few
has been depicted below:
a) Fault detection of a wind turbine.
b) GPRS based network using internet for tracking
transformer.
c) Improvements to human-machine interface
d) Improvements in computer-based protection of
Industry automation
e) Long distance Data transmission.
VII. Conclusion
Microcontroller and GSM based protection
system is a reliable technique for monitoring and
controlling the electric distribution system, the
microcontroller works up to 100 ⁰C temperature. For
long distance data transmission, GSM technology is a
reliable and robust one. Any kind of fault occurring in the
distribution system results the GSM modules to send
instant messages automatically to the base station.
Frequent fault occurrence can be a problem; in this
case the cost of sending sms will increase resulting in
account recharge in the GSM SIM number. This can be
sloved in mutual agreement with telecom companies in
Bangladesh (such as GP, Airtel, Banglalink, etc,).
Nonetheless, GSM based microcontroller protection
system will serve as a reliable, easy and cost effective
solution for monitoring and controlling the electric
distribution system.
References Références Referencias
1. Grainger, John J. (2003). Power System Analysis.
Tata McGraw-Hill. p. 380. ISBN 978-0-07-058515-7.
2. V. Thiyagarajan & T. G. Palanivel “AN EFFICIENT
MONITORING OF SUBSTATIONSUSING MICRO-
CONTROLLER BASED MONITORING SYSTEM”
IJRRAS 4 (1). July 2010.
3. Datasheet of Atmega16" http://www.atmel.com/
images/7766s.pdf”
4. Datasheet of sim900" http://garden.seeedstudio.-
com/images/a/a8/SIM900_AT_Command_Manual_
V1.03.pdf"
5. Wadhwa, C. L. (2005). “Electrical Power Systems”.
New Age International (P) Ltd., Publishers: New
Delhi. Pp. 656-657.
GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI
65
Year2014
© 2014 Global Journals Inc. (US)
Fault Analysis and Electrical Protection of Distribution Transformers
This page is intentionally left blank
Fault Analysis and Electrical Protection of Distribution Transformers
GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI
66
Year2014
© 2014 Global Journals Inc. (US)

More Related Content

What's hot

Voltage sag
Voltage sagVoltage sag
Voltage sagAJAL A J
 
Effect of Voltage Sag on an Induction Motor
Effect of Voltage Sag on an Induction MotorEffect of Voltage Sag on an Induction Motor
Effect of Voltage Sag on an Induction Motorijtsrd
 
Voltage sag mitigationreport
Voltage sag mitigationreportVoltage sag mitigationreport
Voltage sag mitigationreportMayur Dhande
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substationPanneerselvam Rathinam
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Rajeev Kumar Raj
 
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER... VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...Gaddafi Sani
 
Area of vulnerabilty
Area of vulnerabiltyArea of vulnerabilty
Area of vulnerabiltyPrasadVJ
 
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...IDES Editor
 
Voltage harmonic mitigation using DVR
Voltage harmonic mitigation using DVRVoltage harmonic mitigation using DVR
Voltage harmonic mitigation using DVRAniket Naugariya
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level CalculationDinesh Sarda
 
Voltage sag and it’s mitigation
Voltage sag and it’s mitigationVoltage sag and it’s mitigation
Voltage sag and it’s mitigationMayur Dhande
 
Unsymmetrical fault analysis
Unsymmetrical fault analysisUnsymmetrical fault analysis
Unsymmetrical fault analysisnusrattoma
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectioAminu Bugaje
 
distribution system fault mangement
distribution system fault mangementdistribution system fault mangement
distribution system fault mangementManjunath Ds
 
Power system voltage stability
Power system voltage stabilityPower system voltage stability
Power system voltage stabilityAkash Choudhary
 

What's hot (20)

Voltage sag
Voltage sagVoltage sag
Voltage sag
 
Effect of Voltage Sag on an Induction Motor
Effect of Voltage Sag on an Induction MotorEffect of Voltage Sag on an Induction Motor
Effect of Voltage Sag on an Induction Motor
 
Voltage sag mitigationreport
Voltage sag mitigationreportVoltage sag mitigationreport
Voltage sag mitigationreport
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.
 
1 transmission
1 transmission1 transmission
1 transmission
 
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER... VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 
Area of vulnerabilty
Area of vulnerabiltyArea of vulnerabilty
Area of vulnerabilty
 
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
 
Voltage harmonic mitigation using DVR
Voltage harmonic mitigation using DVRVoltage harmonic mitigation using DVR
Voltage harmonic mitigation using DVR
 
Dvr
DvrDvr
Dvr
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
Voltage sag and it’s mitigation
Voltage sag and it’s mitigationVoltage sag and it’s mitigation
Voltage sag and it’s mitigation
 
Unsymmetrical fault analysis
Unsymmetrical fault analysisUnsymmetrical fault analysis
Unsymmetrical fault analysis
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectio
 
Power quality 1
Power quality 1Power quality 1
Power quality 1
 
distribution system fault mangement
distribution system fault mangementdistribution system fault mangement
distribution system fault mangement
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
Power system voltage stability
Power system voltage stabilityPower system voltage stability
Power system voltage stability
 

Viewers also liked

Harmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and MinimizationHarmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and MinimizationRamon Pinyol
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and EffectsLeonardo ENERGY
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniquesrifat maryum
 
Power System Stability & Control
Power System Stability & ControlPower System Stability & Control
Power System Stability & ControlAzimah Aziz
 
FAULT & EVENT TREE ANALYSIS
FAULT & EVENT TREE ANALYSISFAULT & EVENT TREE ANALYSIS
FAULT & EVENT TREE ANALYSISNitesh Dongare
 
FAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATION
FAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATIONFAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATION
FAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATIONOrange Slides
 
Power system stability
Power system  stabilityPower system  stability
Power system stabilityDeepak John
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis pptkarikalan123
 

Viewers also liked (9)

Harmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and MinimizationHarmonics: Causes, Effects and Minimization
Harmonics: Causes, Effects and Minimization
 
Harmonics: Causes and Effects
Harmonics: Causes and EffectsHarmonics: Causes and Effects
Harmonics: Causes and Effects
 
Unsymmetrical Fault
Unsymmetrical FaultUnsymmetrical Fault
Unsymmetrical Fault
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Power System Stability & Control
Power System Stability & ControlPower System Stability & Control
Power System Stability & Control
 
FAULT & EVENT TREE ANALYSIS
FAULT & EVENT TREE ANALYSISFAULT & EVENT TREE ANALYSIS
FAULT & EVENT TREE ANALYSIS
 
FAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATION
FAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATIONFAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATION
FAULT TREE ANALYSIS (FTA) SEMINAR PRESENTATION
 
Power system stability
Power system  stabilityPower system  stability
Power system stability
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 

Similar to Fault Protection Distribution Transformers

Transient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentTransient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentBruno De Wachter
 
Protection Strategies for Microgrids
Protection Strategies for MicrogridsProtection Strategies for Microgrids
Protection Strategies for MicrogridsHardik Parikh, E.I.T.
 
IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...
IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...
IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...IRJET Journal
 
IRJET - Transmission Line Fault Classification using DWT
IRJET -  	  Transmission Line Fault Classification using DWTIRJET -  	  Transmission Line Fault Classification using DWT
IRJET - Transmission Line Fault Classification using DWTIRJET Journal
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLCSageer Ali Khan
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET Journal
 
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...IRJET Journal
 
Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2IAEME Publication
 
Fault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided designFault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided designIJAAS Team
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault RelayIJSRED
 
Transformer failure prevent
Transformer failure preventTransformer failure prevent
Transformer failure preventVitthal Adhav
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...IOSR Journals
 
IRJET - Overview of Smart Tower Technology for Transmission Lines
IRJET - 	  Overview of Smart Tower Technology for Transmission LinesIRJET - 	  Overview of Smart Tower Technology for Transmission Lines
IRJET - Overview of Smart Tower Technology for Transmission LinesIRJET Journal
 
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...IRJET Journal
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerIRJET Journal
 
Power quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSPower quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSMOHANASUNDARAM ANTHONY
 

Similar to Fault Protection Distribution Transformers (20)

Transient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipmentTransient overvoltages and currents: system interaction and effects on equipment
Transient overvoltages and currents: system interaction and effects on equipment
 
Protection Strategies for Microgrids
Protection Strategies for MicrogridsProtection Strategies for Microgrids
Protection Strategies for Microgrids
 
IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...
IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...
IRJET- Study on Power Quality Problem and its Mitigation Techniques in Electr...
 
IRJET - Transmission Line Fault Classification using DWT
IRJET -  	  Transmission Line Fault Classification using DWTIRJET -  	  Transmission Line Fault Classification using DWT
IRJET - Transmission Line Fault Classification using DWT
 
Transformer Protection using PLC
Transformer Protection using PLCTransformer Protection using PLC
Transformer Protection using PLC
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
 
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
 
Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2
 
Fault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided designFault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided design
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault Relay
 
Transformer failure prevent
Transformer failure preventTransformer failure prevent
Transformer failure prevent
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
IRJET - Overview of Smart Tower Technology for Transmission Lines
IRJET - 	  Overview of Smart Tower Technology for Transmission LinesIRJET - 	  Overview of Smart Tower Technology for Transmission Lines
IRJET - Overview of Smart Tower Technology for Transmission Lines
 
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...IRJET-  	  Modeling, Simulation and Implementation of D-STATCOM for Improveme...
IRJET- Modeling, Simulation and Implementation of D-STATCOM for Improveme...
 
A0460109
A0460109A0460109
A0460109
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power Transformer
 
Bp36398403
Bp36398403Bp36398403
Bp36398403
 
Power quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUSPower quality unit i ANNA UNIVERSITY SYALLABUS
Power quality unit i ANNA UNIVERSITY SYALLABUS
 
L44086268
L44086268L44086268
L44086268
 
Bb4103331337
Bb4103331337Bb4103331337
Bb4103331337
 

Recently uploaded

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 

Recently uploaded (20)

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 

Fault Protection Distribution Transformers

  • 1. © 2014. Md Asaduzzaman Nur, Mehdi Hasan Sourov, M. S. Muhit & Md Khaled Hossain. This is a research/review paper, distributed under the terms of the Creative Commons Attribution-Noncommercial 3.0 Unported License http://creativecommons.org/licenses/by-nc/3.0/), permitting all non commercial use, distribution, and reproduction in any medium, provided the original work is properly cited. Global Journal of Researches in Engineering: F Electrical and Electronics Engineering Volume 14 Issue 3 Version 1.0 Year 2014 Type: Double Blind Peer Reviewed International Research Journal Publisher: Global Journals Inc. (USA) Online ISSN: 2249-4596 & Print ISSN: 0975-5861 Fault Analysis and Electrical Protection of Distribution Transformers By Md Asaduzzaman Nur, Mehdi Hasan Sourov, M. S. Muhit & Md Khaled Hossain American International University, Bangladesh Abstract- The demand on the electric power for the household, commercial and industrial loads is on the increase. Also, the management of electric distribution system is becoming more complex. Lack of information at the base station regarding status of the distribution network has been identified as the major bottleneck to its effective monitoring and control. The work described is a development of Microcontroller-based Protection of Electric Distribution system for the purpose of effective monitoring and control of distribution system. A powerful GSM networking is designed to send data from Distribution side to the Sub-station and a Matlab GUI system has been develop to show the data. In general, the proposed design is developed for the user to easily recognize the distribution transformer is safe or unsafe and the distribution line that is suffered by fault. The ultimate objective is to monitor the distribution line status continuously and hence to guard the fault of distribution line due to the constraints such as overvoltage, under voltage, SLG, DLG faults. If any of these does occurs then a message will be sent to the designed controlling unit or substation. Keywords: microcontroller, transformer protection, GSM module, GUI, bridge rectifier, wireless monitoring & control. GJRE-F Classification : FOR Code: 290901p FaultAnalysisandElectricalProtectionofDistributionTransformers Strictly as per the compliance and regulations of :
  • 2. Fault Analysis and Electrical Protection of Distribution Transformers Md Asaduzzaman Nur α , Mehdi Hasan Sourov σ , M. S. Muhit ρ & Md Khaled Hossain Ѡ Abstract- The demand on the electric power for the household, commercial and industrial loads is on the increase. Also, the management of electric distribution system is becoming more complex. Lack of information at the base station regarding status of the distribution network has been identified as the major bottleneck to its effective monitoring and control. The work described is a development of Microcontroller-based Protection of Electric Distribution system for the purpose of effective monitoring and control of distribution system. A powerful GSM networking is designed to send data from Distribution side to the Sub-station and a Matlab GUI system has been develop to show the data. In general, the proposed design is developed for the user to easily recognize the distribution transformer is safe or unsafe and the distribution line that is suffered by fault. The ultimate objective is to monitor the distribution line status continuously and hence to guard the fault of distribution line due to the constraints such as overvoltage, under voltage, SLG, DLG faults. If any of these does occurs then a message will be sent to the designed controlling unit or substation. Keywords: microcontroller, transformer protection, GSM module, GUI, bridge rectifier, wireless monitoring & control. I. INTRODUCTION rotection system’s main function is to clear faults from the power system at high speed to ensure safety, minimize equipment damage and maintain power system stability[2]. Protection of power systems requires an understanding of system faults, their detection, and safe isolation of the faulted device. By taking an inventory of all the essential electrical loads and doing a basic electrical load evaluation [2], an idea regarding how much power our system needs to produce has been obtained. We are also aware about the power fluctuation situations also that means what voltage minimum / maximum we are getting from the A.C supply mains. In doing this project we would be using concepts of microcontrollers, GSM network and GUI of MATLAB. II. Fault Types and Protection a) Single-Line-to-Ground Fault A short circuit between one line and ground, very often caused by physical contact, for example due Author α σ Ѡ: Student, Electrical and Electronic engineering department, AIUB, Dhaka, Bangladesh 1. e-mail: nur.aiub@yahoo.com Author ρ: Faculty, Electrical and Electronic engineering department, AIUB, Dhaka, Bangladesh 3. to lightning or other common means. The single line to ground fault can occur in any of the three phases [1]. However, it is sufficient to analyze only one of the cases. Figure 1 : Single Line to Ground fault b) Line-to-Line Fault A short circuit between lines, caused by ionization of air, or when lines come into physical contact[1], for example due to a broken insulator. For a Line-to-line fault, the currents will be high, because the fault current is only limited by the inherent (natural) series impedance of the power system up to the point of faulty (refer Ohms law). Figure 2 : Line to line fault P GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI 61 Year2014 © 2014 Global Journals Inc. (US) c) Double-Line-to Ground Fault Two lines come into contact with the ground (and each other), also commonly due to stormy weather or some other means [1].
  • 3. Figure 3 : Double line to Ground Fault d) Transformer Protection Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major goal of transformer protection will restrict the damage to a faulted transformer & also protect it from thieves to avoid long term area blackouts. The comprehensive transformer protection provided by multiple function protective relays is appropriate for critical transformers of all applications [2]. Organized theft of electric transformers from live transmission lines is widespread throughout the country making power distribution agencies and consumers counting losses in several millions of BDT and great sufferings. In the last 10 years, electric transformers worth BDT 2000 Million had been stolen. So, for an improved power system stability and efficiently innovative technology, a micro controller based protection system should be achieved to protect transformers. e) Lower Voltage Low voltage is a relative term, the definition varying by context. Different definitions are used in transmission and distribution line, and in the electronics industry. Electrical safety codes define "low voltage" circuits that are exempt from the protection required at higher voltages. These definitions vary by country and specific code. Lower voltage is defined as incoming line voltage at the point of use which is smaller than the Public Service Commission’s mandated legal limits; and/or smaller than the voltage ratings of the connected equipment. Lower voltage is considered a safety hazard by all industry standards and can cause premature failure of connected equipment. Devices could be damaged by lower line voltage. f) Over Voltage Overvoltage is defined as incoming line voltage at the point of use which is greater than the Public Service Commission’s mandated legal limits; and/or greater than the voltage ratings of the connected equipment. Overvoltage is considered a safety hazard by all industry standards, and can cause premature failure of connected equipment. Overvoltage has been a widely known industry problem for many years, but it is not generally understood by many who have to deal with it. Power companies have been unable to control it adequately. Overvoltage occurs most often during severe cold winter weather for the following reasons: (1) Inadequate size of power distribution systems; (2) slow reaction time for power company’s distribution systems to regulate voltage during extreme load variations; and (3) abrupt reductions of loads III. Block Diagram Arrangement In figure 4, the basic arrangement of the implemented project can be found. Figure 4 : Block diagram arrangement of the project Among the major components required to establish the project, few of them are the power transformers (step down), microcontroller ATMEGA 16 and GSM module, Bridge rectifier. a) Transformer Transformer is an electrical device used to step up and down the AC voltages. There are two types of transformers: Step up and step down transformer. Step up transformer increases the magnitude of voltage while step down transformer decrease the magnitude of voltage. Depending on the ratio of the number of turns in the primary & secondary winding a transformer is characterized as step up or step down. For this project purpose, considering 1Ф voltage to be around 220 V, 3 step down power transformer of rating 220/12 has been used to represent a realistic representation of the 3 Ф system. GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI 62 Year2014 © 2014 Global Journals Inc. (US) Fault Analysis and Electrical Protection of Distribution Transformers
  • 4. Figure 5 : 220v/12v transformer b) Microcontroller ATMEGA 16 Brain of this project is Atmega16 micro- controller. It is a 8 bit Micro controller with RISC architecture. Its speed is up to 16MIPS throughput at 16MHz. It has 16K bytes of flash and 512 bytes EEPROM. Operating voltage 2.7v -5.5v, in active mode it consumes only 1.1mA & in sleep mode it consumes less than 1uA current which made it a perfect choice for his project [3]. c) GSM Module Sim900 has been used as GSM module. SIM900 module is a complete Quad-Band GSM/GPRS module which combines GPS technology for satellite navigation. The compact design which integrated GPRS and GPS in a SMT package will significantly save both time and costs. Power consumption (GSM engine in sleep mode) around 1.5mA and Power consumption (GSM engine in idle mode) around 77mA [4]. Figure 7 : GSM module Sim900 d) Bridge Rectifier An AC power source is required for powering major appliances but almost all electronic circuits require a steady DC supply. A simple rectifier circuit described in this project converts the input from AC source to DC voltage. Firstly, the AC input from mains is stepped down to a lower value of voltage. This AC supply is then passed through a rectifier circuit to remove the negative cycle of AC waveform. The resulting signal is then filtered to get the DC output. The major part of the circuit is connected to the secondary coil of the transformer which is comprised by diodes and capacitor. While the diodes act as a rectifiers, capacitor filters out the DC component from the circuit. Figure 8 : Bridge rectifier IV. Simulation The initial stage, the circuits have been designed and simulated in PROTEUS. The circuit have GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI 63 Year2014 © 2014 Global Journals Inc. (US) Figure 6 : Atmega16 microcontroller been utilized to analyze the line to line, single line to Fault Analysis and Electrical Protection of Distribution Transformers
  • 5. Figure 9 : Circuit Simulation V. Hardware Implementation In reference to figure 4, the transmitting and receiving side can be described as follows: a) Transmitting Side Heart of the project is the microcontroller ATMEGA 16. In general the normal distribution phase voltage is 220 V, in this project we used a step down transformer 220/12 V for converting the phase voltage from 220 V to 12 V. Then, a bridge rectifier has been used for converting the 12 V ac to 12 V dc; after that, applied voltage divider converts the 12 V to 5 V because the microcontroller works at maximum 5 V. By this process the three distribution phase is connected into three microcontroller pins and the power transformer is connected by a narrow wire between 2 pins of the microcontroller. At cases, when the distribution side is in load shedding protection of transformer must be ensured, which is why the microcontroller power is given from an external power source (5 V battery) backup and also the GSM module power is given from external power source(9V battery) because GSM module consumes lots of power. GSM module communicates with atmeg16 through UART. RXD of GSM module is connected with TXD of atmega16 and TXD of GSM module is connected to RXD of atmega16. b) Receiving Side In receiver circuit another GSM Modem is connected with PC via USB-To-Serial converter. The GUI in MATLAB software has been is used such that it will read the message and the data will save it in an excel file and it will show a graph according to the data by using the interface. If any fault occurs, it is also capable to generate an alarm and a fault message box according to the fault. The communication protocol is UART and baud rate is 9600[4]. In view of the descriptions above, the implemented hardware can be found in figure 10. Figure 10 : Implemented Hardware model Figure 11 : LCD status indicator As viewed from figure 10, the system was found to be balanced three phase system. In figure 11, the corresponding representation appears in the LCD display with the phase voltages in all the phases to be around 219 V. The view from GUI interface is also shown in figure 12. Figure 12 : GUI interface from PC GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI 64 Year2014 © 2014 Global Journals Inc. (US) ground, double line to ground, open conductor, over voltage and under voltage in the sides of the transformer. The circuit diagram can be found in figure 9. Fault Analysis and Electrical Protection of Distribution Transformers
  • 6. VI. Future Prospects In view of a wide range of possibilities on the basis of microcontroller based protection system, a few has been depicted below: a) Fault detection of a wind turbine. b) GPRS based network using internet for tracking transformer. c) Improvements to human-machine interface d) Improvements in computer-based protection of Industry automation e) Long distance Data transmission. VII. Conclusion Microcontroller and GSM based protection system is a reliable technique for monitoring and controlling the electric distribution system, the microcontroller works up to 100 ⁰C temperature. For long distance data transmission, GSM technology is a reliable and robust one. Any kind of fault occurring in the distribution system results the GSM modules to send instant messages automatically to the base station. Frequent fault occurrence can be a problem; in this case the cost of sending sms will increase resulting in account recharge in the GSM SIM number. This can be sloved in mutual agreement with telecom companies in Bangladesh (such as GP, Airtel, Banglalink, etc,). Nonetheless, GSM based microcontroller protection system will serve as a reliable, easy and cost effective solution for monitoring and controlling the electric distribution system. References Références Referencias 1. Grainger, John J. (2003). Power System Analysis. Tata McGraw-Hill. p. 380. ISBN 978-0-07-058515-7. 2. V. Thiyagarajan & T. G. Palanivel “AN EFFICIENT MONITORING OF SUBSTATIONSUSING MICRO- CONTROLLER BASED MONITORING SYSTEM” IJRRAS 4 (1). July 2010. 3. Datasheet of Atmega16" http://www.atmel.com/ images/7766s.pdf” 4. Datasheet of sim900" http://garden.seeedstudio.- com/images/a/a8/SIM900_AT_Command_Manual_ V1.03.pdf" 5. Wadhwa, C. L. (2005). “Electrical Power Systems”. New Age International (P) Ltd., Publishers: New Delhi. Pp. 656-657. GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI 65 Year2014 © 2014 Global Journals Inc. (US) Fault Analysis and Electrical Protection of Distribution Transformers
  • 7. This page is intentionally left blank Fault Analysis and Electrical Protection of Distribution Transformers GlobalJournalofResearchesinEngineering()FVolumeXIVIssueIIIVersionI 66 Year2014 © 2014 Global Journals Inc. (US)