IOP Conference Series: Materials Science and Engineering
PAPER • OPEN ACCESS
Simulation of differential relay for transformer
protection
To cite this article: N S Azizan et al 2020 IOP Conf. Ser.: Mater. Sci. Eng. 767 012004
View the article online for updates and enhancements.
You may also like
Directed protection of the generator
N S Buryanina, Y F Korolyuk, M L
Koryakina et al.
-
Design and Application of Electronic
Analog Relay Protection Device with Load
Check
Yu Li, Yunzhi Li and Bo Zhao
-
Impact of negative capacitance on the
energy-delay property of an
electromechanical relay
Kihun Choe and Changhwan Shin
-
This content was downloaded from IP address 5.41.177.41 on 13/11/2022 at 19:03
Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution
of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.
Published under licence by IOP Publishing Ltd
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
1
Simulation of differential relay for transformer protection
N S Azizan1
, C L Wooi1
, B Ismail1
, S N M Arshad1
, M Isa1
, W A Mustafa2
and
MNK Rohani1
1
Centre of Excellence for Renewable Energy (CERE), School of Electrical System
Engineering, Pauh Putra Main Campus, Universiti Malaysia Perlis, 02600 Arau, Perlis,
Malaysia.
2
School of Engineering Technology, Kampus Sg. Chuchuh, Universiti Malaysia Perlis,
02100 Padang Besar, Perlis, Malaysia.
nursyuhadazizan@gmail.com
Abstract. In electric power system, transformers are an important element and their protection
are critical. As the transformer might be damaged during a fault, faster and more selective
protection was required. For this purpose, the design of differential protection was utilized. In
this study, the differential relay simulation has been successfully done using
MATLAB/Simulink. The essential approach is to protect the power transformer against internal
faults and avoid interference in the power system. The evaluation has been accomplished at
different fault conditions. Several types of faults including double line-to-ground, single line -
to-ground and line-to-line faults are studied. Simulation studies were performed and the relays
performance with different system parameters and conditions were investigated. The obtained
results illustrated for the differential relay represents an appropriate action.
1. Introduction
The appearance of protective relays in a power system is to detect system anomaly and to assassinate
proper ways to isolate swiftly only the faulty element from the healthy system. The flashover of lightning
and other faults in the transmission line leads to shortage of electricity [1]. The possibility of fault
occurrence on the overhead lines is much more due to their greater lengths and liability to atmospheric
conditions [2]. There are several methods for the protection of transmission and distribution lines [3-7].
Transmission and distribution networks have moved from being a local entity to becoming a continent
spanning machine, which consisted of power plants, wind turbine farms, country spanning transmission
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
2
line and etc. The joints connecting all these elements were the transformers. The transformers scale the
voltages to connect the lower level distribution networks to the highway of electricity: the transmission
network [8].
However, the transformer might be damaged during a fault. Therefore, a faster and more selective
protection was required for the continuity operation of the power system. For this purpose, differential
protection was utilized. By defining its zones using current transformers, differential relay could provide
100% selectivity, and tripping time could be controlled under one cycle. This was done by comparing
the currents flowing into the transformer [9]. Any internal error will show up as a differential current
and caused a trip. In the ideal system, this could be done easily. Under the internal and external faults,
any transformer protection should be able to operate. The main function of differential relay was to
send trip signal to circuit breaker when there is a certain difference current value between primary side
and secondary side of the transformer [1]. Current Transformers (CTs) were used to convert the primary
current to secondary current and the differential relay can be used to check if there is any differential
current.
Under the normal operating condition, the power output to the transformer should be equal to the
power input to the transformer. If internal faults happened in the power system, there will be a
differential current generated. In order to design a proper protection, the faults need to be located within
the protection zone [10]. Then, proper action should be done to isolate the faulty zone from the rest of
the power system. Current differential relays were one of the protection devices used to protect the
electrical equipment against the internal faults. This is due to the reason that current differential relays
have high sensitivity and simplicity. This paper aimed to study the modelling and simulation of
differential relay for transformer protection operation using MATLAB/Simulink.
2. Methodology
The power system model was simulated and performed using Simulink/MATLAB. In this model, there
are 11/33 kV power system with current relay protection scheme between the transmission line and
transformer. Figure 1 showed that the power transformer was connected to a power system consisting
of a three-phase power generator. In order to check the switching effect, it feeds the load over this
transformer between two circuit breakers, CB1 and CB2.
The differential relay was used to detect the internal fault and generated a trip signal to the associated
circuit breakers to segregate the faulted section from the rest of the power system [10]. This protection
minimized the harm to transformer and power system. Equation 1 explained the operation of differential
relay where the differential relay will operate once the differential current measured from CT1 and CT2
exceed certain value. The differential current that exceed certain value was called the pickup current. In
order to make system protected, the breaker will not send a tripping signal if the measured differential
current does not exceed the relay’s pickup current. The relay will send a tripping signal if there were
internal faults, the differential current formed in relay was higher than the pickup current. After the
tripping signal received, the breaker will disconnect and isolate the fault from power system.
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
3
Figure 1. Basic configuration of differential relay.
∆I = |𝐼1 − 𝐼2| (1)
where
∆I = The differential current
𝐼1 = The secondary current measured by CT1
𝐼2 = The secondary current measured by CT2
Figure 2 showed in detail on how the simulation of differential relay has been carried out. Basically,
when there was no power loss in ideal transformer, there was no operating current. But in practical, there
was an eddy current loss and core loss in transformer. There was also imbalance in phase shifting, tap-
changing, CTs ratio and transformer ratio because of the operated current will not be zero. This
differential relay was designed to respond to the circuit breaker when there is difference in current from
both CTs of transformer in the term of its inconsequential relation to the current flowing from the
protecting zone as shown in figure 1.
First, it read the current in transformer of primary and secondary then it will identify the differences
between the current measured from the primary side and secondary side of transformers. Then, the fault
was created to test the system. The relay will sense any changes in current flow through the transformer.
Finally, the information is collected from the results of tripping in the system.
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
4
Figure 2. Simulation process flowchart of differential relay.
2.1. Circuit Operation
A power system model has been developed using MATLAB/Simulink software. Figure 3 showed the
differential relay in power system model. The general overview of the power distribution system
consisted of three-phase source connected with three-phase breaker. Then, transmission line was
connected to the breaker. In between them, there were three-phase V-I measurement which is used to
measure the value of load current. Lastly, a three-phase series RLC load was connected at the end of
transmission line which resembled the load for the system.
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
5
Figure 3. Differential Relay Model in Simulink.
Figure 4 showed the design of differential relay in Simulink which consisted of two input portals
In1 and In2. The In1 and In2 represented the output currents of the CT1 and CT2 respectively. In order
to analyse the system, these two input signals would be divided into three parallel paths. All the signals
entered a block named amplitude comparator. The first signals entered a block named amplitude
comparator. The second signals made the signals to be impressed in the harmonic test and send the result
to a block named harmonic comparator.
The amplitudes of both input current In1 and In2 will be compared by amplitude comparator. Then,
the amplitude comparator sent an indicating signal to the comparator block and showed the difference
between the two signals. At the same time, the harmonic comparator block will receive two signals
from two blocks named subsystem. Then, it will send the result to the comparator. The subsystem block
will evaluate the input signal to investigate if harmonics exist in this signal.
Figure 4 also illustrated the contents of the subsystem block. There were two input entering the
subsystem. There were gain three at input two as the secondary winding of transformer is 33kV, in order
to balance the current on the first input of 11kV. The purpose of gain three is to increase the secondary
voltage side to become less in transformer.
The control system of relay is based on the digital operating system. The relational operator is used
to compare the input current with the pickup current as desired. The output of the relational operator
was connected to the SR flip flop.
Location 3 Location 1 Location 2
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
6
Figure 4. Differential Relay in Subsystem.
Table1. Truth Table of SR Flip Flop.
The basics of SR flip flop was shown in Table 1. Based on the truth table, to make the circuit breaker
tripped, all the input “R” of the flip-flop should be connected to ‘0’. All the ‘S’ inputs should be
connected to the output of relational operators. When a fault happened, the relational operator will
become 1 and with input ‘R’ equal to 0, the flip-flop output (Q) will become 1 (SET). Then, trip signal
will be sent.
3. Results and Discussions
The normal conventional relay was simulated in MATLAB using the Simpower system of SIMULINK.
The external and internal fault cases were simulated. When external fault appeared and the circuit
breakers were closed to connect the transformer, the currents were generated. In designing the
differential relay, there must be a relay before circuit breaker that assigns the tripping signal to it after
correlate input signals. The currents were measured by current transformers and then introduced to the
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
7
relay. The faults were created at three different condition; at three phase fault 1, three phase fault 2 and
three phase fault 3.
I(A)
Figure 5. Simulation result when no fault occurs in system.
Figure 5 showed the result for no fault condition in the system. Under this condition, relay did not
assign any tripping signal to the breaker hence the signal was in normal condition. Figures 6 and 7
showed the results for three-phase fault created at t=0.1s when fault occurred at location 1 which relay
sent a signal to the circuit breaker. Faults was created when three-phase faults at location load 2 trip the
circuit breaker at t=0.1s which showed that there were internal faults. Consequently, the transformer
was isolated from the grid. Figure 8 showed that there were no fault and no circuit breaker functioned
for three-phase I(A) fault at location 3 as it is located as an external three-phase faults.
Figure 6. Simulation result when three-phase fault is occurred at location 1 (L-L-L).
t(s)
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
8
Figure 7. Simulation result when three-phase fault is occurred at location 2 (L-L-L).
Figure 8. Simulation result when three-phase fault is occurred at location (L-L-L).
Figures 9 and 10 showed the results for LLG fault created at t=0.1 s in the system where the relay
sent signals to the circuit breaker. Faults were created at location 1 and 2, trip the circuit breaker at t=0.1
s shows it was an internal LLG fault. Figures 10 and 11 showed the results for the internal fault LLG.
The internal fault LLG was located inside the protected zone and therefore the corresponding relay sent
a tripping signal to the circuit breaker.
It was observed that in case of L-L-G fault, only the faulty phase was disconnected by the circuit
breaker. Thus, transformer was segregated from the grid. Double line to ground included 15 % of power
system faults. Figure 11 showed that there were no fault and no circuit breaker function at three phase
fault 3 because it was located as outside protection zone and it was an external L-L-G faults.
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
9
Figure 9. Simulation result when LLG fault is occurred on phase A and B at location1.
Figure 10. Simulation result when LLG fault is occurred on phase A and B at location2.
Figure 11. Simulation result when LLG fault is occurred on phase A and B at location 3.
Referring to Figures 12 and 13, there were small phase difference between the two currents which
caused by different source angles at t= 0.1 s. For an internal fault, with the polarity of the current
transformers, the current flow into the protected zone from both line terminals. For L-L at phase A and
phase B, the relay responses the fault and selectivity open one of the faulted phases so that other phases
able to supply power. Line to line included 15 % of power system faults.
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
10
For an external fault, the current flow into the line and out of the other. Figure 14 showed the result
for external L-L fault on system hence no tripping signal from the differential relay to the circuit breaker.
If the fault occurs outside the bounded area, it is not desirable to disconnect the transformer.
Figure 12. Simulation result when fault is occurred on phase A and B at three phase fault 1 (L-L).
Figure 13. Simulation result when fault is occurred on phase A and B at three phase fault 2 (L-L).
Figure 14. Simulation result when fault is occurred on phase A and B at three phase fault 3 (L-L).
Figures 15 and 16 showed the results for internal L-G fault, phase A to ground, at three phase fault
1 and 2. There was an internal fault inside the protected zone relay. The relay sent a tripping signal to
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
11
the circuit breaker at created fault t= 0.1s as there are differences between the currents. Simulation result
for L-G was shown in Figures 16 and 17. The proposed relay allowed a trip signal to the circuit breaker
as fault happen. It was noticed that in case of L-G fault, only the faulty phase was detached by the circuit
breaker over relay. The transformer was disconnected from grid as it opened all ungrounded conductors
of the faulted circuit.
Figure 17 showed the result for external L- G fault, phase A to ground, at three phase fault 3. On
the system, there are no tripping signal from the differential relay to the circuit breaker. The external
faults showed that the fault outside the protection zones of the differential relay. In external fault
condition, the current over transformer was changed but a decisive differential relay must not give a
tripping signal to the circuit breaker. The summary of fault and relay tripped is simulated as stated in
Table 2.
Figure 15. Simulation result when fault is occurred on phase A and ground at three phase fault 1 (L-G).
Figure 16. Simulation result when fault is occurred on phase A and ground at three phase fault 2 (L-G).
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
12
Figure 17. Simulation result when fault is occurred on phase A and ground at three phase fault 3 (L-G).
Table 2. Type of fault and clearing scheme.
Circuit breaker worn for the protection purpose in power system cannot work by its own
determination. The circuit breaker sends the tripping signal after correlate input signal with the logic.
The result is compared as in Table 2. The tests are conducted in two situations, external faults and
internal faults by phases. For faults inside the protection zone, the relay has reacted accurately, at the
presences of the located fault. In addition, for external fault in different conditions normally the relay
has not operated when fault located at three phase fault 3.
4. Conclusions
As conclusion, the differential relay simulation had been successfully done and the results were amazing
as all the types of fault tested, triggered the tripping system. The basic approach is to assure the power
Type of Fault Fault Relay
Location Tripped
Three Phase 1 Tripped
2 Tripped
3 Not Tripped
Double Line to 1 Tripped
Ground 2 Tripped
3 Not Tripped
Line to Line 1 Not In Phase
2 Not In Phase
3 Not Tripped
Single Line to 1 Tripped
Ground 2 Tripped
3 Not Tripped
1st International Symposium on Engineering and Technology (ISETech) 2019
IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004
IOP Publishing
doi:10.1088/1757-899X/767/1/012004
13
transformer across internal faults at created fault t=0.ls and prevent interruption due to other operating
conditions. In three phase faults, as fault happen, the transformer is consequently isolated from the grid.
In double line to ground and single line to ground, it is observed that only the faulty phase is detached
by the circuit breaker over the relay. In line to line fault, there are small differences between two current
which caused by different sources angle. The evaluation has been accomplished at different fault
conditions. Simulation studies are performed and the relays performance with different system
parameters and conditions is investigated. The obtained result illustrate that the proposed differential
relay represents an appropriate action.
Reference
[1] R. Haas IEEE Power Engineering Review 12 48-49.
[2] IEEE Guide for Protective Relay Applications to Power Transformers.
[3] C.-H. Einvall and J. Linders A three-phase differential relay for transformer protection IEEE
Transactions on Power Apparatus and Systems 94 1971-1980.
[4] J. Thorp and A. Phadke A microprocessor based three-phase transformer differential relay IEEE
Transactions on Power apparatus and Systems 2 426-432.
[5] C. Mathews An improved transformer differential relay Electrical Engineering, 73 648-648.
[6] A. L. Orille-Fernandez, N. K. I. Ghonaim, and J. A. Valencia A FIRANN as a differential relay
for three phase power transformer protection IEEE Transactions on Power Delivery 16 215-
218.
[7] I. Hall et al. New line current differential relay using GPS synchronization Power Tech
Conference Proceedings 2003 Bologna 2003 3 8.
[8] IEEE Standard Electrical Power System Device Function Numbers, Acronyms, and Contact
Designations - Redline IEEE Std C37.2-2008 (Revision of IEEE Std C37.2-1996) 1-62.
[9] W. Jiekang Microprocessor-based fundamental frequency tracking system for digital protection
relaying in Industrial Technology IEEE International Conference 2004 3 1276-1280.
[10] N. S. Jadhav and A. Thorat Design of a differential relay for 1000-kV transmission line using
MATLAB in 2013 International Conference on Energy Efficient Technologies for
Sustainability 2013 1164-1168.
Acknowledgement
The authors wish to thank the Centre of Excellence for Renewable Energy (CERE), School of Electrical
System Engineering, Universiti Malaysia Perlis and Ministry of Education (MOE) for the financial aid.

More Related Content

Similar to Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf

Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...ijtsrd
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdfThien Phan Bản
 
Microcontroller based multifunction_relay
Microcontroller based multifunction_relayMicrocontroller based multifunction_relay
Microcontroller based multifunction_relayRajeev Kumar
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...IAEME Publication
 
Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...IAEME Publication
 
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdfssuser3793c8
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET Journal
 
Analysis of Modeling of Current Differential Protection
Analysis of Modeling of Current Differential ProtectionAnalysis of Modeling of Current Differential Protection
Analysis of Modeling of Current Differential ProtectionIJPEDS-IAES
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfwhmonkey
 
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
 Wavelet based detection and location of faults in 400kv, 50km Underground Po... Wavelet based detection and location of faults in 400kv, 50km Underground Po...
Wavelet based detection and location of faults in 400kv, 50km Underground Po...ijceronline
 
Influencing Factors on Power Losses in Electric Distribution Network
Influencing Factors on Power Losses in Electric Distribution NetworkInfluencing Factors on Power Losses in Electric Distribution Network
Influencing Factors on Power Losses in Electric Distribution NetworkIJAEMSJORNAL
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substationijtsrd
 
Boukhriss Compeng Italy 2022.pdf
Boukhriss Compeng Italy 2022.pdfBoukhriss Compeng Italy 2022.pdf
Boukhriss Compeng Italy 2022.pdfALIBOUKHRISS
 
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...Iaetsd Iaetsd
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission linepamu17
 

Similar to Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf (20)

Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf
 
Lecture (11.11.22).pptx
Lecture (11.11.22).pptxLecture (11.11.22).pptx
Lecture (11.11.22).pptx
 
Microcontroller based multifunction_relay
Microcontroller based multifunction_relayMicrocontroller based multifunction_relay
Microcontroller based multifunction_relay
 
Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...Inrush current reduction in three phase power transformer by using prefluxing...
Inrush current reduction in three phase power transformer by using prefluxing...
 
Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...Analysis of distance protection relay in presence of static synchronous compe...
Analysis of distance protection relay in presence of static synchronous compe...
 
fault
faultfault
fault
 
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
2.Ourside.vip.Power quality improvement using dynamic voltage restorer.pdf
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 
Analysis of Modeling of Current Differential Protection
Analysis of Modeling of Current Differential ProtectionAnalysis of Modeling of Current Differential Protection
Analysis of Modeling of Current Differential Protection
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdf
 
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
 Wavelet based detection and location of faults in 400kv, 50km Underground Po... Wavelet based detection and location of faults in 400kv, 50km Underground Po...
Wavelet based detection and location of faults in 400kv, 50km Underground Po...
 
Influencing Factors on Power Losses in Electric Distribution Network
Influencing Factors on Power Losses in Electric Distribution NetworkInfluencing Factors on Power Losses in Electric Distribution Network
Influencing Factors on Power Losses in Electric Distribution Network
 
substation internship report
substation internship report substation internship report
substation internship report
 
Lp3619931999
Lp3619931999Lp3619931999
Lp3619931999
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
Boukhriss Compeng Italy 2022.pdf
Boukhriss Compeng Italy 2022.pdfBoukhriss Compeng Italy 2022.pdf
Boukhriss Compeng Italy 2022.pdf
 
Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...Review of the Most Applicable Regulator Collections to Control the Parallel A...
Review of the Most Applicable Regulator Collections to Control the Parallel A...
 
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
iaetsd Effect of superconducting fault current limiter (sfcl) on triumphant i...
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...Call Girls in Nagpur High Profile
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 

Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf

  • 1. IOP Conference Series: Materials Science and Engineering PAPER • OPEN ACCESS Simulation of differential relay for transformer protection To cite this article: N S Azizan et al 2020 IOP Conf. Ser.: Mater. Sci. Eng. 767 012004 View the article online for updates and enhancements. You may also like Directed protection of the generator N S Buryanina, Y F Korolyuk, M L Koryakina et al. - Design and Application of Electronic Analog Relay Protection Device with Load Check Yu Li, Yunzhi Li and Bo Zhao - Impact of negative capacitance on the energy-delay property of an electromechanical relay Kihun Choe and Changhwan Shin - This content was downloaded from IP address 5.41.177.41 on 13/11/2022 at 19:03
  • 2. Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by IOP Publishing Ltd 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 1 Simulation of differential relay for transformer protection N S Azizan1 , C L Wooi1 , B Ismail1 , S N M Arshad1 , M Isa1 , W A Mustafa2 and MNK Rohani1 1 Centre of Excellence for Renewable Energy (CERE), School of Electrical System Engineering, Pauh Putra Main Campus, Universiti Malaysia Perlis, 02600 Arau, Perlis, Malaysia. 2 School of Engineering Technology, Kampus Sg. Chuchuh, Universiti Malaysia Perlis, 02100 Padang Besar, Perlis, Malaysia. nursyuhadazizan@gmail.com Abstract. In electric power system, transformers are an important element and their protection are critical. As the transformer might be damaged during a fault, faster and more selective protection was required. For this purpose, the design of differential protection was utilized. In this study, the differential relay simulation has been successfully done using MATLAB/Simulink. The essential approach is to protect the power transformer against internal faults and avoid interference in the power system. The evaluation has been accomplished at different fault conditions. Several types of faults including double line-to-ground, single line - to-ground and line-to-line faults are studied. Simulation studies were performed and the relays performance with different system parameters and conditions were investigated. The obtained results illustrated for the differential relay represents an appropriate action. 1. Introduction The appearance of protective relays in a power system is to detect system anomaly and to assassinate proper ways to isolate swiftly only the faulty element from the healthy system. The flashover of lightning and other faults in the transmission line leads to shortage of electricity [1]. The possibility of fault occurrence on the overhead lines is much more due to their greater lengths and liability to atmospheric conditions [2]. There are several methods for the protection of transmission and distribution lines [3-7]. Transmission and distribution networks have moved from being a local entity to becoming a continent spanning machine, which consisted of power plants, wind turbine farms, country spanning transmission
  • 3. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 2 line and etc. The joints connecting all these elements were the transformers. The transformers scale the voltages to connect the lower level distribution networks to the highway of electricity: the transmission network [8]. However, the transformer might be damaged during a fault. Therefore, a faster and more selective protection was required for the continuity operation of the power system. For this purpose, differential protection was utilized. By defining its zones using current transformers, differential relay could provide 100% selectivity, and tripping time could be controlled under one cycle. This was done by comparing the currents flowing into the transformer [9]. Any internal error will show up as a differential current and caused a trip. In the ideal system, this could be done easily. Under the internal and external faults, any transformer protection should be able to operate. The main function of differential relay was to send trip signal to circuit breaker when there is a certain difference current value between primary side and secondary side of the transformer [1]. Current Transformers (CTs) were used to convert the primary current to secondary current and the differential relay can be used to check if there is any differential current. Under the normal operating condition, the power output to the transformer should be equal to the power input to the transformer. If internal faults happened in the power system, there will be a differential current generated. In order to design a proper protection, the faults need to be located within the protection zone [10]. Then, proper action should be done to isolate the faulty zone from the rest of the power system. Current differential relays were one of the protection devices used to protect the electrical equipment against the internal faults. This is due to the reason that current differential relays have high sensitivity and simplicity. This paper aimed to study the modelling and simulation of differential relay for transformer protection operation using MATLAB/Simulink. 2. Methodology The power system model was simulated and performed using Simulink/MATLAB. In this model, there are 11/33 kV power system with current relay protection scheme between the transmission line and transformer. Figure 1 showed that the power transformer was connected to a power system consisting of a three-phase power generator. In order to check the switching effect, it feeds the load over this transformer between two circuit breakers, CB1 and CB2. The differential relay was used to detect the internal fault and generated a trip signal to the associated circuit breakers to segregate the faulted section from the rest of the power system [10]. This protection minimized the harm to transformer and power system. Equation 1 explained the operation of differential relay where the differential relay will operate once the differential current measured from CT1 and CT2 exceed certain value. The differential current that exceed certain value was called the pickup current. In order to make system protected, the breaker will not send a tripping signal if the measured differential current does not exceed the relay’s pickup current. The relay will send a tripping signal if there were internal faults, the differential current formed in relay was higher than the pickup current. After the tripping signal received, the breaker will disconnect and isolate the fault from power system.
  • 4. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 3 Figure 1. Basic configuration of differential relay. ∆I = |𝐼1 − 𝐼2| (1) where ∆I = The differential current 𝐼1 = The secondary current measured by CT1 𝐼2 = The secondary current measured by CT2 Figure 2 showed in detail on how the simulation of differential relay has been carried out. Basically, when there was no power loss in ideal transformer, there was no operating current. But in practical, there was an eddy current loss and core loss in transformer. There was also imbalance in phase shifting, tap- changing, CTs ratio and transformer ratio because of the operated current will not be zero. This differential relay was designed to respond to the circuit breaker when there is difference in current from both CTs of transformer in the term of its inconsequential relation to the current flowing from the protecting zone as shown in figure 1. First, it read the current in transformer of primary and secondary then it will identify the differences between the current measured from the primary side and secondary side of transformers. Then, the fault was created to test the system. The relay will sense any changes in current flow through the transformer. Finally, the information is collected from the results of tripping in the system.
  • 5. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 4 Figure 2. Simulation process flowchart of differential relay. 2.1. Circuit Operation A power system model has been developed using MATLAB/Simulink software. Figure 3 showed the differential relay in power system model. The general overview of the power distribution system consisted of three-phase source connected with three-phase breaker. Then, transmission line was connected to the breaker. In between them, there were three-phase V-I measurement which is used to measure the value of load current. Lastly, a three-phase series RLC load was connected at the end of transmission line which resembled the load for the system.
  • 6. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 5 Figure 3. Differential Relay Model in Simulink. Figure 4 showed the design of differential relay in Simulink which consisted of two input portals In1 and In2. The In1 and In2 represented the output currents of the CT1 and CT2 respectively. In order to analyse the system, these two input signals would be divided into three parallel paths. All the signals entered a block named amplitude comparator. The first signals entered a block named amplitude comparator. The second signals made the signals to be impressed in the harmonic test and send the result to a block named harmonic comparator. The amplitudes of both input current In1 and In2 will be compared by amplitude comparator. Then, the amplitude comparator sent an indicating signal to the comparator block and showed the difference between the two signals. At the same time, the harmonic comparator block will receive two signals from two blocks named subsystem. Then, it will send the result to the comparator. The subsystem block will evaluate the input signal to investigate if harmonics exist in this signal. Figure 4 also illustrated the contents of the subsystem block. There were two input entering the subsystem. There were gain three at input two as the secondary winding of transformer is 33kV, in order to balance the current on the first input of 11kV. The purpose of gain three is to increase the secondary voltage side to become less in transformer. The control system of relay is based on the digital operating system. The relational operator is used to compare the input current with the pickup current as desired. The output of the relational operator was connected to the SR flip flop. Location 3 Location 1 Location 2
  • 7. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 6 Figure 4. Differential Relay in Subsystem. Table1. Truth Table of SR Flip Flop. The basics of SR flip flop was shown in Table 1. Based on the truth table, to make the circuit breaker tripped, all the input “R” of the flip-flop should be connected to ‘0’. All the ‘S’ inputs should be connected to the output of relational operators. When a fault happened, the relational operator will become 1 and with input ‘R’ equal to 0, the flip-flop output (Q) will become 1 (SET). Then, trip signal will be sent. 3. Results and Discussions The normal conventional relay was simulated in MATLAB using the Simpower system of SIMULINK. The external and internal fault cases were simulated. When external fault appeared and the circuit breakers were closed to connect the transformer, the currents were generated. In designing the differential relay, there must be a relay before circuit breaker that assigns the tripping signal to it after correlate input signals. The currents were measured by current transformers and then introduced to the
  • 8. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 7 relay. The faults were created at three different condition; at three phase fault 1, three phase fault 2 and three phase fault 3. I(A) Figure 5. Simulation result when no fault occurs in system. Figure 5 showed the result for no fault condition in the system. Under this condition, relay did not assign any tripping signal to the breaker hence the signal was in normal condition. Figures 6 and 7 showed the results for three-phase fault created at t=0.1s when fault occurred at location 1 which relay sent a signal to the circuit breaker. Faults was created when three-phase faults at location load 2 trip the circuit breaker at t=0.1s which showed that there were internal faults. Consequently, the transformer was isolated from the grid. Figure 8 showed that there were no fault and no circuit breaker functioned for three-phase I(A) fault at location 3 as it is located as an external three-phase faults. Figure 6. Simulation result when three-phase fault is occurred at location 1 (L-L-L). t(s)
  • 9. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 8 Figure 7. Simulation result when three-phase fault is occurred at location 2 (L-L-L). Figure 8. Simulation result when three-phase fault is occurred at location (L-L-L). Figures 9 and 10 showed the results for LLG fault created at t=0.1 s in the system where the relay sent signals to the circuit breaker. Faults were created at location 1 and 2, trip the circuit breaker at t=0.1 s shows it was an internal LLG fault. Figures 10 and 11 showed the results for the internal fault LLG. The internal fault LLG was located inside the protected zone and therefore the corresponding relay sent a tripping signal to the circuit breaker. It was observed that in case of L-L-G fault, only the faulty phase was disconnected by the circuit breaker. Thus, transformer was segregated from the grid. Double line to ground included 15 % of power system faults. Figure 11 showed that there were no fault and no circuit breaker function at three phase fault 3 because it was located as outside protection zone and it was an external L-L-G faults.
  • 10. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 9 Figure 9. Simulation result when LLG fault is occurred on phase A and B at location1. Figure 10. Simulation result when LLG fault is occurred on phase A and B at location2. Figure 11. Simulation result when LLG fault is occurred on phase A and B at location 3. Referring to Figures 12 and 13, there were small phase difference between the two currents which caused by different source angles at t= 0.1 s. For an internal fault, with the polarity of the current transformers, the current flow into the protected zone from both line terminals. For L-L at phase A and phase B, the relay responses the fault and selectivity open one of the faulted phases so that other phases able to supply power. Line to line included 15 % of power system faults.
  • 11. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 10 For an external fault, the current flow into the line and out of the other. Figure 14 showed the result for external L-L fault on system hence no tripping signal from the differential relay to the circuit breaker. If the fault occurs outside the bounded area, it is not desirable to disconnect the transformer. Figure 12. Simulation result when fault is occurred on phase A and B at three phase fault 1 (L-L). Figure 13. Simulation result when fault is occurred on phase A and B at three phase fault 2 (L-L). Figure 14. Simulation result when fault is occurred on phase A and B at three phase fault 3 (L-L). Figures 15 and 16 showed the results for internal L-G fault, phase A to ground, at three phase fault 1 and 2. There was an internal fault inside the protected zone relay. The relay sent a tripping signal to
  • 12. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 11 the circuit breaker at created fault t= 0.1s as there are differences between the currents. Simulation result for L-G was shown in Figures 16 and 17. The proposed relay allowed a trip signal to the circuit breaker as fault happen. It was noticed that in case of L-G fault, only the faulty phase was detached by the circuit breaker over relay. The transformer was disconnected from grid as it opened all ungrounded conductors of the faulted circuit. Figure 17 showed the result for external L- G fault, phase A to ground, at three phase fault 3. On the system, there are no tripping signal from the differential relay to the circuit breaker. The external faults showed that the fault outside the protection zones of the differential relay. In external fault condition, the current over transformer was changed but a decisive differential relay must not give a tripping signal to the circuit breaker. The summary of fault and relay tripped is simulated as stated in Table 2. Figure 15. Simulation result when fault is occurred on phase A and ground at three phase fault 1 (L-G). Figure 16. Simulation result when fault is occurred on phase A and ground at three phase fault 2 (L-G).
  • 13. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 12 Figure 17. Simulation result when fault is occurred on phase A and ground at three phase fault 3 (L-G). Table 2. Type of fault and clearing scheme. Circuit breaker worn for the protection purpose in power system cannot work by its own determination. The circuit breaker sends the tripping signal after correlate input signal with the logic. The result is compared as in Table 2. The tests are conducted in two situations, external faults and internal faults by phases. For faults inside the protection zone, the relay has reacted accurately, at the presences of the located fault. In addition, for external fault in different conditions normally the relay has not operated when fault located at three phase fault 3. 4. Conclusions As conclusion, the differential relay simulation had been successfully done and the results were amazing as all the types of fault tested, triggered the tripping system. The basic approach is to assure the power Type of Fault Fault Relay Location Tripped Three Phase 1 Tripped 2 Tripped 3 Not Tripped Double Line to 1 Tripped Ground 2 Tripped 3 Not Tripped Line to Line 1 Not In Phase 2 Not In Phase 3 Not Tripped Single Line to 1 Tripped Ground 2 Tripped 3 Not Tripped
  • 14. 1st International Symposium on Engineering and Technology (ISETech) 2019 IOP Conf. Series: Materials Science and Engineering 767 (2020) 012004 IOP Publishing doi:10.1088/1757-899X/767/1/012004 13 transformer across internal faults at created fault t=0.ls and prevent interruption due to other operating conditions. In three phase faults, as fault happen, the transformer is consequently isolated from the grid. In double line to ground and single line to ground, it is observed that only the faulty phase is detached by the circuit breaker over the relay. In line to line fault, there are small differences between two current which caused by different sources angle. The evaluation has been accomplished at different fault conditions. Simulation studies are performed and the relays performance with different system parameters and conditions is investigated. The obtained result illustrate that the proposed differential relay represents an appropriate action. Reference [1] R. Haas IEEE Power Engineering Review 12 48-49. [2] IEEE Guide for Protective Relay Applications to Power Transformers. [3] C.-H. Einvall and J. Linders A three-phase differential relay for transformer protection IEEE Transactions on Power Apparatus and Systems 94 1971-1980. [4] J. Thorp and A. Phadke A microprocessor based three-phase transformer differential relay IEEE Transactions on Power apparatus and Systems 2 426-432. [5] C. Mathews An improved transformer differential relay Electrical Engineering, 73 648-648. [6] A. L. Orille-Fernandez, N. K. I. Ghonaim, and J. A. Valencia A FIRANN as a differential relay for three phase power transformer protection IEEE Transactions on Power Delivery 16 215- 218. [7] I. Hall et al. New line current differential relay using GPS synchronization Power Tech Conference Proceedings 2003 Bologna 2003 3 8. [8] IEEE Standard Electrical Power System Device Function Numbers, Acronyms, and Contact Designations - Redline IEEE Std C37.2-2008 (Revision of IEEE Std C37.2-1996) 1-62. [9] W. Jiekang Microprocessor-based fundamental frequency tracking system for digital protection relaying in Industrial Technology IEEE International Conference 2004 3 1276-1280. [10] N. S. Jadhav and A. Thorat Design of a differential relay for 1000-kV transmission line using MATLAB in 2013 International Conference on Energy Efficient Technologies for Sustainability 2013 1164-1168. Acknowledgement The authors wish to thank the Centre of Excellence for Renewable Energy (CERE), School of Electrical System Engineering, Universiti Malaysia Perlis and Ministry of Education (MOE) for the financial aid.