Gensol	Engineering	Pvt	Ltd
1 21/02/16
Electrical	Parameters
Power	A.C.	(MW) 40 40
Voltage	(kV) 33 33
Current	(Amp)	 777.59893 777.59893
Conductor	
261	sqmm	
Panther
484	sqmm	
Zebra
Resistance	at	70	
Degree	(ohm/km)
0.16553635 0.0818573
Distance	(kms) 1 1
Power	Loss	(Watts) 150139.8379 74243.76431
%Losses 0.375349595 0.185609411
Electrical	Parameters
Power	A.C.	(MW) 40 40
Voltage	(kV) 66 66
Current	(Amp)	 388.799465 388.799465
Conductor	
261	sqmm	
Panther
484	sqmm	
Zebra
D.C.	Resistance	
(ohm/km)
0.16553635 0.0818573
Distance	(kms) 1 1
Power	Loss	(Watts) 37534.95948 18560.94108
%Losses 0.093837399 0.046402353
Electrical	Parameters
Power	A.C.	(MW) 40 40
Voltage	(kV) 132 132
Current	(Amp)	 194.3997325 194.3997325
Conductor	
261	sqmm	
Panther
484	sqmm	
Zebra
D.C.	Resistance	
(ohm/km)
0.16553635 0.0818573
Distance	(kms) 1 1
Power	Loss	(Watts) 9383.73987 4640.235269
%Losses 0.02345935 0.011600588
40	MW	(33kV	Double	Circuit	
Line)
40	MW	(66kV)
40	MW	(132kV)

Transmission Loss Calculation on 33 / 66 / 132 KV Lines for Solar Power Plant

  • 1.
    Gensol Engineering Pvt Ltd 1 21/02/16 Electrical Parameters Power A.C. (MW) 4040 Voltage (kV) 33 33 Current (Amp) 777.59893 777.59893 Conductor 261 sqmm Panther 484 sqmm Zebra Resistance at 70 Degree (ohm/km) 0.16553635 0.0818573 Distance (kms) 1 1 Power Loss (Watts) 150139.8379 74243.76431 %Losses 0.375349595 0.185609411 Electrical Parameters Power A.C. (MW) 40 40 Voltage (kV) 66 66 Current (Amp) 388.799465 388.799465 Conductor 261 sqmm Panther 484 sqmm Zebra D.C. Resistance (ohm/km) 0.16553635 0.0818573 Distance (kms) 1 1 Power Loss (Watts) 37534.95948 18560.94108 %Losses 0.093837399 0.046402353 Electrical Parameters Power A.C. (MW) 40 40 Voltage (kV) 132 132 Current (Amp) 194.3997325 194.3997325 Conductor 261 sqmm Panther 484 sqmm Zebra D.C. Resistance (ohm/km) 0.16553635 0.0818573 Distance (kms) 1 1 Power Loss (Watts) 9383.73987 4640.235269 %Losses 0.02345935 0.011600588 40 MW (33kV Double Circuit Line) 40 MW (66kV) 40 MW (132kV)