SlideShare a Scribd company logo
1
POWER FACTOR CORRECTION
Khalid Awan
2
OUTLINE
DEFINITION
CAUSES OF LOW POWER FACTOR
POWER FACTOR CORRECTION
ADVANTAGES OF POWER FACTOR CORRECTION
DISADVANTAGES OF LOW POWER FACTOR
CONCLUSION
REFERENCES
3
DEFINITION:
Power factor (P.F) is the ratio between actual power to
the apparent power.
Actual power/Apparent power.
P.F=Kw /Kva.
For a purely resistive load the power factor is unity. Active
and reactive power are designated by P &Q respectively.
The average power in a circuit is called active power and
the power that supplies the stored energy in reactive
elements is called reactive power.
4
Active Power:
Also known as “real power” or simply “power.” Active power
is the rate of producing, transferring, or using electrical
energy. It is measured in watts and often expressed in
kilowatts (KW) or megawatts (MW). The terms “active” or
“real” power are used in place of the term “power” alone to
differentiate it from “reactive power.
Apparent Power:
The product of the voltage (in volts) and the current
(in amperes). It comprises both active and reactive power .
It is measured in “volt-amperes” and often expressed in
“ kilovolt-amperes” (KVA) or “megavolt-amperes” (MVA).
5
POWER FACTOR DEFINITION
Inductive loads cause the current to lag behind the
voltage. The wave forms of voltage and current are then
"out of phase" with each other. The more out of phase
they become then the lower the Power Factor. Power
Factor is usually expressed as Cos Phi. (Ø)
6
Consider a canal boat being pulled by a horse.
If the horse could walk on water then the angle (Phi) Ø
would be zero and COSINE Ø=1. Meaning all the horse
power is being used to pull the load.
However the relative position of the horse influences the
power. As the horse gets closer to the barge, angle Ø1
increases and power is wasted, but, as the horse is
positioned further away, then angle Ø2 gets closer to
zero and less power is wasted.
7
CAUSES OF LOW POWER FACTOR
A poor power factor can be the result of either a
significant phase difference between the voltage and
current at the load terminals or it can be due to a high
harmonic content or distorted/discontinuous current
waveform. Poor load current phase angle is generally the
result of Poor load current phase angle is generally the
result of an inductive load such as an induction motor
power transformer, lighting ballasts, welder or induction
furnace, Induction generators Wind mill generators and
high intensity discharge lightings.
8
CAUSES OF LOW POWER FACTOR
A distorted current waveform can be the result of a
rectifier variable speed drive, switched mode power
supply, discharge lighting or other electronic load.
9
POWER FACTOR CORRECTION
Power factor decreases with the installation of non
resistive loads such as induction motors, Transformers.
Lighting ballasts and electronic equipments. Power
factors can be corrected by using capacitors. These are
rated in electrical units called VAR or KVAR.One VAR is
equivalent to one volt of reactive power. VAR then are
units of measurement for indicating just how much
reactive power the capacitor will supply.
10
As reactive power is usually measured in thousands the
letter K is used for thousand. the capacitor KVAR rating
then shows how much reactive power the capacitor will
supply. Each unit of the capacitor's KVAR will decrease
the inductive reactive power demand.
11
POWER FACTOR CORRECTION
Most loads on an electrical distribution system fall into
one of three categories; resistive, inductive or capacitive.
In most plant, the most common is likely to be inductive.
Typical examples of this include transformers, fluorescent
lighting and AC induction motors. Most inductive loads
use a conductive coil winding to produce an
electromagnetic field, allowing the motor to function.
12
All inductive loads require two kinds of power to operate:
Active power (KW) - to produce the motive force
Reactive power (KVAR) - to energize the magnetic field
The operating power from the distribution system is
composed of both active (working) and reactive (non-
working) elements. The active power does useful work in
driving the motor whereas the reactive power only
provides the magnetic field.
13
POWER FACTOR CORRECTION
The amount of Power Capacitor KVAR required to correct
A system to a desired Power Factor level is the difference
between the amount of KVAR in the uncorrected system
and the amount of desired KVAR in the corrected system.
The most efficient location for power factor capacitors is
at the load. Capacitors work from the point of installation
back to the generating source. Individual motor correction
is not always practical, sometimes it is more practical to
connect larger capacitors on the distribution bus or install
an automatic system at the incoming service along with
fixed capacitors at the load.
14
KVAR CORRECTION
Capacitive Power Factor correction (PFC) is applied to
electric circuits as a means of minimising the inductive
component of the current and thereby reducing the
losses in the supply.
The introduction of Power Factor Correction capacitors is
a widely recognised method of reducing an electrical
load, thus minimising wasted energy and hence
improving the efficiency of a plant and reducing the
electricity bill.
15
It is not usually necessary to reach unity, i.e. Power
Factor 1, since most supply companies are happy with a
PF of 0.95 to 0.98.
By installing suitably sized switched capacitors into the
circuit, the Power Factor is improved and the value
becomes nearer to 1 thus minimising wasted energy and
improving the efficiency of a plant or power factor can be
increased by synchronous motor or Synchronous
generators.
16
POWER FACTOR CORRECTION
METHODS
Static Var Compensator(SVC)
Fixed Capcitors
Switch Capacitors
Synchronous Condensors
Static Synchronous Compensator(STATCOM)
Modulated power filter capacitor compensator
17
STATIC VAR COMPENSATOR
(SVC)
The Static Var Compensator (SVC) is a shunt device of
the Flexible AC Transmission Systems (FACTS) family
using power electronics to control power flow and
improve transient stability on power grids [1]. The SVC
regulates voltage at its terminals by controlling the
amount of reactive power injected into or absorbed from
the power system. When system voltage is low, the SVC
generates reactive power (SVC capacitive). When
system voltage is high, it absorbs reactive power (SVC
inductive).
18
The variation of reactive power is performed by switching
three-phase capacitor banks and inductor banks
connected on the secondary side of a coupling
transformer. Each capacitor bank is switched on and off
by three thyristor switches (Thyristor Switched Capacitor
or TSC). Reactors are either switched on-off (Thyristor
Switched Reactor or TSR) or phase-controlled (Thyristor
Controlled Reactor or TCR).
19
A rapidly operating Static Var Compensator (SVC) can
continuously provide the reactive power required to
control dynamic voltage swings under various system
conditions and thereby improve the power system
transmission and distribution performance.
Installing an SVC at one or more suitable points in the
network will increase transfer capability through
enhanced voltage stability, while maintaining a smooth
voltage profile under different network conditions. In
addition, an SVC can mitigate active power oscillations
through voltage amplitude modulation
20
FIXED CAPACITOR
where the load does not change or where the capacitor
is switched with the load, such as the load side of a
Ideally suited for power factor correction in applications
motor contactor. It is suitable for locations using
induction motors, like food processing plants, or
where small multiple loads require reactive power
compensation.
Each Fixed Capacitor Bank is designed for high reliability
and long life. These products are designed for
applications that do not contain harmonic generating
21
SWITCHED CAPACITOR
It is suited for centralized power factor correction in
applications where plant loading is constantly changing,
resulting in the need for varying amounts of reactive
power. An advanced microprocessor-based reactive
power controller measures plant power factor via a
single remote current transformer (included), and
switches capacitor modules in and out of service to
maintain a user-selected target power factor. Typically
applied at service entrance or near fluctuating loads.
22
SYNCHRONOUS CONDENSER
Synchronous condenser is a salient pole synchronous
generator without prime mover. Synchronous condenser
stabilizes power system voltage by supplying reactive
power to the power system and Use for power factor
correction. It is more economical than capacitors.
23
SYNCHRONOUS CONDENSER
24
STATIC SYNCHRONOUS COMPENSTOR
(STATCOM)
The Static Synchronous Compensator (STATCOM) is a
shunt device of the Flexible AC Transmission Systems
(FACTS) family using power electronics to control power
flow and improve transient stability on power grids [1].
The STATCOM regulates voltage at its terminal by
controlling the amount of reactive power injected into or
absorbed from the power system. When system voltage
is low, the STATCOM generates reactive power
(STATCOM capacitive).
25
When system voltage is high, it absorbs reactive power
(STATCOM inductive).Similarly to the SVC the
STATCOM can provide instantaneous and continuously
variable reactive power in response to grid voltage
transients enhancing the grid voltage stability
26
Installing a STATCOM at one or more suitable points in
the network will increase the grid transfer capability
through enhanced voltage stability, while maintaining a
smooth voltage profile under different network
conditions. The STATCOM provides additional versatility
in terms of power quality improvement capabilities
27
DETERMINING CAPACITOR VALUE
Example
Power Factor1=74%
Actual Power=594 kw
Interested to boost up=97% ,Power Factor2=97%
Power Factor=KW/KVA
Cos = kW / kVA
 = Cos-1 (PF1)
 = Cos-1 (74%) =42.27 o
28
The reactive power was about:
Tan = kVAr / kW
kVAr = kW x tan
kVAr = 594 kW x tan (42.27) = 540 kVAr
If the power factor were increased to 97%, the reactive
power would be about:
Cos = kW / kVA
 = Cos-1 (PF2)
 = Cos-1 (97%) = 14.07 o
kVAr = kW x tan
kVAr = 594 kW x tan (14.07) = 149 kVAr
29
Thus, the amount of capacitance required to boost
power factor from 74% to 97% :
540 kVAr – 149 kVAr = 391 kVAr
So I recommended 400kvar
30
POWER CAPACITORS
Power Factor correction on site with
Pole Cap
31
POWER FACTOR MEASUREMENT
Power factor can measure by using power factor meter
which is well known in power industry.
Power factor can also be calculated by installing watt
meter along with the Ampere meter and volt meter by
using the power factor basic formula.
Power factor=Actual Power/ Apparent power
32
POWER FACTOR MEASUREMENT
33
ADVANTAGES OF POWER FACTOR
CORRECTION
Eliminate Power Factor Penalties
Increase System Capacity
Reduce Line Losses in distribution systems
Conserve Energy
Improve voltage stability
34
Increase equipment life
Save on utility cost
Enhance equipment operation by improving voltage
Improve energy efficiency
35
Reduction in size of transformers, cables and switchgear
in new installations.
Delay costly upgrades.
Less total plant KVA for the same KW working power.
Improved voltage regulation due to reduced line voltage
drop.
36
POWER COST REDUCTION
Utility companies in many areas include a penalty charge in
the electrical rate for low power factor. The installation of
power factor capacitors on the user's electrical distribution
system eliminates the necessity of paying premium rates to
the utility company for poor power factor.
37
The savings the utility company derives in reduced
generation, transmission and distribution costs are
passed on to the user in the form of lower electrical
charges. Three of the more common ways a utility
charges a user for poor power factor are based on
38
KW demand with a trigger point typically between 85%
and 95%
KVA demand
KVAR demand
When the utility uses either KVA demand or KVAR
demand as the basis for its penalty structure, all users
pay a penalty, but those with high power factor pay a
much lower penalty or none at all.
39
SYSTEM CAPACITY INCREASE
By adding capacitors to the system, the power factor is
improved and the KW capacity of the system is
increased. For example, a 1,000 KVA transformer with a
70% power factor provides 700 KW of power to the main
bus. With the installation of capacitors so that the power
factor is improved, say, to 90%, the KW capacity of the
system is increased to 900 KW. When a system power
factor is improved, the amount of reactive current flowing
Is lowered thus reducing transformer and distribution
circuit loads, and releasing system capacity.
40
VOLTAGE IMPROVEMENT AND POWER
LOSS REDUCTION
System losses are also reduced through power factor
correction by reducing the total current and power in the
system. A 20% reduction in current will yield a 36%
reduction in distribution system losses. In this situation,
an energy savings of as much as 50% will be realized
with the installation of power factor capacitors.
In addition, power factor capacitors decrease the
distribution system voltage drops and fluctuations.
41
DISADVANTAGES OF LOW POWER
FACTOR
Increases heating losses in the transformers and
distribution equipments.
Reduce plant life.
Unstabilise voltage levels.
Increase power losses.
Upgrade costly equipments.
Decrease energy efficiency.
Increase electricity costs by paying power factor
surcharges.
42
CONCLUSION
By observing all aspects of the power factor it is clear that
power factor is the most significant part for the utility
Company as well as for the consumer. Utility company
rid of from the power losses while the consumer free
from low power factor penalty charges.
By installing suitably sized power capacitors into the
circuit the Power Factor is improved and the value
becomes nearer to 1 thus minimising line losses and
improving the efficiency of a plant.
43
REFERENCES
Electrical Power System Design and Analysis
by M.E.EI-Hawary.
Power System Operations
by Robert H Miller.
IEEE papers
www.ABB.com
BC Hydro (www.bchydro.ca)

More Related Content

What's hot

Power factor improvement
Power factor improvement Power factor improvement
Power factor improvement
Saiful Islam Rukon
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
Rahul Aman
 
Interconnection issue in microgrid
Interconnection issue in microgridInterconnection issue in microgrid
Interconnection issue in microgrid
Amarjeet S Pandey
 
Power factor
Power factorPower factor
Power factor
NAVEEN KOREDDI
 
Statcom
StatcomStatcom
Statcom
jawaharramaya
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
D Målîk
 
Substations
SubstationsSubstations
Substations
itfakash
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
Nikhil Kachare
 
Sf6 circuit breakers
Sf6 circuit breakersSf6 circuit breakers
Sf6 circuit breakers
jawaharramaya
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devices
Manojkarader
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
Slides Hub
 
Electrostatic fields and field stress control
Electrostatic fields and field stress controlElectrostatic fields and field stress control
Electrostatic fields and field stress control
vhasmukh96
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power control
Caner Göksel Sonuzun
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
Himansu Pradhan
 
Electrical Substations and Switchyard Design
Electrical Substations and Switchyard DesignElectrical Substations and Switchyard Design
Electrical Substations and Switchyard Design
Living Online
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
SARAVANAN A
 
maximum power point tracking (mppt)
maximum power point tracking (mppt)maximum power point tracking (mppt)
maximum power point tracking (mppt)
Shashikumar Jeevan
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
VB Engineering
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
Living Online
 

What's hot (20)

Power factor improvement
Power factor improvement Power factor improvement
Power factor improvement
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Interconnection issue in microgrid
Interconnection issue in microgridInterconnection issue in microgrid
Interconnection issue in microgrid
 
Power factor
Power factorPower factor
Power factor
 
Statcom
StatcomStatcom
Statcom
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
 
Substations
SubstationsSubstations
Substations
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Sf6 circuit breakers
Sf6 circuit breakersSf6 circuit breakers
Sf6 circuit breakers
 
Switchgears and protection devices
Switchgears and protection devicesSwitchgears and protection devices
Switchgears and protection devices
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
Electrostatic fields and field stress control
Electrostatic fields and field stress controlElectrostatic fields and field stress control
Electrostatic fields and field stress control
 
Power systems voltage and power control
Power systems voltage and power controlPower systems voltage and power control
Power systems voltage and power control
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Electrical Substations and Switchyard Design
Electrical Substations and Switchyard DesignElectrical Substations and Switchyard Design
Electrical Substations and Switchyard Design
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
maximum power point tracking (mppt)
maximum power point tracking (mppt)maximum power point tracking (mppt)
maximum power point tracking (mppt)
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 

Similar to Power Factor Correction.ppt

Power Factor
Power FactorPower Factor
Power Factor
Tim Cohen
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
utkarsh srivastav
 
THE POWER FACTOR
THE POWER FACTOR THE POWER FACTOR
THE POWER FACTOR
amitmaholiya1
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
soham patel
 
IARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdfIARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdf
GayanBuddhikaAlahend
 
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfpowerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
BOOPATHIMADHAIYAN
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
manpreetsingh1076
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and Solutions
Abhinav Dubey
 
REACTIVE POWER
REACTIVE POWERREACTIVE POWER
REACTIVE POWER
JeetDatta3
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
khaliq ahmed
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
इन्दुभूषण कुमार
 
Automatic power factor correction and its advantage
Automatic power factor correction and its advantageAutomatic power factor correction and its advantage
Automatic power factor correction and its advantage
KASHYAPMOKARIYA1
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
ijceronline
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
Ameen San
 
Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)
MOHAMMADSHOAIBBABAR
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
harshal567
 

Similar to Power Factor Correction.ppt (20)

Power Factor
Power FactorPower Factor
Power Factor
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Mohsin rana
Mohsin ranaMohsin rana
Mohsin rana
 
THE POWER FACTOR
THE POWER FACTOR THE POWER FACTOR
THE POWER FACTOR
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
IARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdfIARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdf
 
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfpowerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and Solutions
 
REACTIVE POWER
REACTIVE POWERREACTIVE POWER
REACTIVE POWER
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
POWER FACTOR IMPROVE
POWER FACTOR IMPROVEPOWER FACTOR IMPROVE
POWER FACTOR IMPROVE
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Automatic power factor correction and its advantage
Automatic power factor correction and its advantageAutomatic power factor correction and its advantage
Automatic power factor correction and its advantage
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
 
Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 

More from SalmanHameed26

Advanced Antenna Topics-Lecture 3.pptx
Advanced Antenna Topics-Lecture 3.pptxAdvanced Antenna Topics-Lecture 3.pptx
Advanced Antenna Topics-Lecture 3.pptx
SalmanHameed26
 
Lecture#1-Introduction.ppt
Lecture#1-Introduction.pptLecture#1-Introduction.ppt
Lecture#1-Introduction.ppt
SalmanHameed26
 
ET_251_1.pptx
ET_251_1.pptxET_251_1.pptx
ET_251_1.pptx
SalmanHameed26
 
The Diode_Lecture2.ppt
The Diode_Lecture2.pptThe Diode_Lecture2.ppt
The Diode_Lecture2.ppt
SalmanHameed26
 
Chapter 02.pdf
Chapter 02.pdfChapter 02.pdf
Chapter 02.pdf
SalmanHameed26
 
ProgrammingIntroduction.ppt
ProgrammingIntroduction.pptProgrammingIntroduction.ppt
ProgrammingIntroduction.ppt
SalmanHameed26
 
SemiconductorBasics_Lecture1.pdf
SemiconductorBasics_Lecture1.pdfSemiconductorBasics_Lecture1.pdf
SemiconductorBasics_Lecture1.pdf
SalmanHameed26
 
Lecture 1& 2.pptx
Lecture 1& 2.pptxLecture 1& 2.pptx
Lecture 1& 2.pptx
SalmanHameed26
 
FlipFlopsLatches1 (3).ppt
FlipFlopsLatches1 (3).pptFlipFlopsLatches1 (3).ppt
FlipFlopsLatches1 (3).ppt
SalmanHameed26
 
MUX and Demux.ppt
MUX and Demux.pptMUX and Demux.ppt
MUX and Demux.ppt
SalmanHameed26
 
Basic Electrical Theory.ppt
Basic Electrical Theory.pptBasic Electrical Theory.ppt
Basic Electrical Theory.ppt
SalmanHameed26
 

More from SalmanHameed26 (13)

Advanced Antenna Topics-Lecture 3.pptx
Advanced Antenna Topics-Lecture 3.pptxAdvanced Antenna Topics-Lecture 3.pptx
Advanced Antenna Topics-Lecture 3.pptx
 
Lecture#1-Introduction.ppt
Lecture#1-Introduction.pptLecture#1-Introduction.ppt
Lecture#1-Introduction.ppt
 
ET_251_1.pptx
ET_251_1.pptxET_251_1.pptx
ET_251_1.pptx
 
UPS.pptx
UPS.pptxUPS.pptx
UPS.pptx
 
The Diode_Lecture2.ppt
The Diode_Lecture2.pptThe Diode_Lecture2.ppt
The Diode_Lecture2.ppt
 
Chapter 02.pdf
Chapter 02.pdfChapter 02.pdf
Chapter 02.pdf
 
ProgrammingIntroduction.ppt
ProgrammingIntroduction.pptProgrammingIntroduction.ppt
ProgrammingIntroduction.ppt
 
SemiconductorBasics_Lecture1.pdf
SemiconductorBasics_Lecture1.pdfSemiconductorBasics_Lecture1.pdf
SemiconductorBasics_Lecture1.pdf
 
Lecture 1& 2.pptx
Lecture 1& 2.pptxLecture 1& 2.pptx
Lecture 1& 2.pptx
 
FlipFlopsLatches1 (3).ppt
FlipFlopsLatches1 (3).pptFlipFlopsLatches1 (3).ppt
FlipFlopsLatches1 (3).ppt
 
MUX and Demux.ppt
MUX and Demux.pptMUX and Demux.ppt
MUX and Demux.ppt
 
lec7.ppt
lec7.pptlec7.ppt
lec7.ppt
 
Basic Electrical Theory.ppt
Basic Electrical Theory.pptBasic Electrical Theory.ppt
Basic Electrical Theory.ppt
 

Recently uploaded

Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
Investor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptxInvestor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptx
AmarGB2
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
manasideore6
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
ongomchris
 
DfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributionsDfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributions
gestioneergodomus
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
Robbie Edward Sayers
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
fxintegritypublishin
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
SyedAbiiAzazi1
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
ML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptxML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptx
Vijay Dialani, PhD
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
Aditya Rajan Patra
 

Recently uploaded (20)

Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
Investor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptxInvestor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptx
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
 
DfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributionsDfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributions
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
ML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptxML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptx
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
 

Power Factor Correction.ppt

  • 2. 2 OUTLINE DEFINITION CAUSES OF LOW POWER FACTOR POWER FACTOR CORRECTION ADVANTAGES OF POWER FACTOR CORRECTION DISADVANTAGES OF LOW POWER FACTOR CONCLUSION REFERENCES
  • 3. 3 DEFINITION: Power factor (P.F) is the ratio between actual power to the apparent power. Actual power/Apparent power. P.F=Kw /Kva. For a purely resistive load the power factor is unity. Active and reactive power are designated by P &Q respectively. The average power in a circuit is called active power and the power that supplies the stored energy in reactive elements is called reactive power.
  • 4. 4 Active Power: Also known as “real power” or simply “power.” Active power is the rate of producing, transferring, or using electrical energy. It is measured in watts and often expressed in kilowatts (KW) or megawatts (MW). The terms “active” or “real” power are used in place of the term “power” alone to differentiate it from “reactive power. Apparent Power: The product of the voltage (in volts) and the current (in amperes). It comprises both active and reactive power . It is measured in “volt-amperes” and often expressed in “ kilovolt-amperes” (KVA) or “megavolt-amperes” (MVA).
  • 5. 5 POWER FACTOR DEFINITION Inductive loads cause the current to lag behind the voltage. The wave forms of voltage and current are then "out of phase" with each other. The more out of phase they become then the lower the Power Factor. Power Factor is usually expressed as Cos Phi. (Ø)
  • 6. 6 Consider a canal boat being pulled by a horse. If the horse could walk on water then the angle (Phi) Ø would be zero and COSINE Ø=1. Meaning all the horse power is being used to pull the load. However the relative position of the horse influences the power. As the horse gets closer to the barge, angle Ø1 increases and power is wasted, but, as the horse is positioned further away, then angle Ø2 gets closer to zero and less power is wasted.
  • 7. 7 CAUSES OF LOW POWER FACTOR A poor power factor can be the result of either a significant phase difference between the voltage and current at the load terminals or it can be due to a high harmonic content or distorted/discontinuous current waveform. Poor load current phase angle is generally the result of Poor load current phase angle is generally the result of an inductive load such as an induction motor power transformer, lighting ballasts, welder or induction furnace, Induction generators Wind mill generators and high intensity discharge lightings.
  • 8. 8 CAUSES OF LOW POWER FACTOR A distorted current waveform can be the result of a rectifier variable speed drive, switched mode power supply, discharge lighting or other electronic load.
  • 9. 9 POWER FACTOR CORRECTION Power factor decreases with the installation of non resistive loads such as induction motors, Transformers. Lighting ballasts and electronic equipments. Power factors can be corrected by using capacitors. These are rated in electrical units called VAR or KVAR.One VAR is equivalent to one volt of reactive power. VAR then are units of measurement for indicating just how much reactive power the capacitor will supply.
  • 10. 10 As reactive power is usually measured in thousands the letter K is used for thousand. the capacitor KVAR rating then shows how much reactive power the capacitor will supply. Each unit of the capacitor's KVAR will decrease the inductive reactive power demand.
  • 11. 11 POWER FACTOR CORRECTION Most loads on an electrical distribution system fall into one of three categories; resistive, inductive or capacitive. In most plant, the most common is likely to be inductive. Typical examples of this include transformers, fluorescent lighting and AC induction motors. Most inductive loads use a conductive coil winding to produce an electromagnetic field, allowing the motor to function.
  • 12. 12 All inductive loads require two kinds of power to operate: Active power (KW) - to produce the motive force Reactive power (KVAR) - to energize the magnetic field The operating power from the distribution system is composed of both active (working) and reactive (non- working) elements. The active power does useful work in driving the motor whereas the reactive power only provides the magnetic field.
  • 13. 13 POWER FACTOR CORRECTION The amount of Power Capacitor KVAR required to correct A system to a desired Power Factor level is the difference between the amount of KVAR in the uncorrected system and the amount of desired KVAR in the corrected system. The most efficient location for power factor capacitors is at the load. Capacitors work from the point of installation back to the generating source. Individual motor correction is not always practical, sometimes it is more practical to connect larger capacitors on the distribution bus or install an automatic system at the incoming service along with fixed capacitors at the load.
  • 14. 14 KVAR CORRECTION Capacitive Power Factor correction (PFC) is applied to electric circuits as a means of minimising the inductive component of the current and thereby reducing the losses in the supply. The introduction of Power Factor Correction capacitors is a widely recognised method of reducing an electrical load, thus minimising wasted energy and hence improving the efficiency of a plant and reducing the electricity bill.
  • 15. 15 It is not usually necessary to reach unity, i.e. Power Factor 1, since most supply companies are happy with a PF of 0.95 to 0.98. By installing suitably sized switched capacitors into the circuit, the Power Factor is improved and the value becomes nearer to 1 thus minimising wasted energy and improving the efficiency of a plant or power factor can be increased by synchronous motor or Synchronous generators.
  • 16. 16 POWER FACTOR CORRECTION METHODS Static Var Compensator(SVC) Fixed Capcitors Switch Capacitors Synchronous Condensors Static Synchronous Compensator(STATCOM) Modulated power filter capacitor compensator
  • 17. 17 STATIC VAR COMPENSATOR (SVC) The Static Var Compensator (SVC) is a shunt device of the Flexible AC Transmission Systems (FACTS) family using power electronics to control power flow and improve transient stability on power grids [1]. The SVC regulates voltage at its terminals by controlling the amount of reactive power injected into or absorbed from the power system. When system voltage is low, the SVC generates reactive power (SVC capacitive). When system voltage is high, it absorbs reactive power (SVC inductive).
  • 18. 18 The variation of reactive power is performed by switching three-phase capacitor banks and inductor banks connected on the secondary side of a coupling transformer. Each capacitor bank is switched on and off by three thyristor switches (Thyristor Switched Capacitor or TSC). Reactors are either switched on-off (Thyristor Switched Reactor or TSR) or phase-controlled (Thyristor Controlled Reactor or TCR).
  • 19. 19 A rapidly operating Static Var Compensator (SVC) can continuously provide the reactive power required to control dynamic voltage swings under various system conditions and thereby improve the power system transmission and distribution performance. Installing an SVC at one or more suitable points in the network will increase transfer capability through enhanced voltage stability, while maintaining a smooth voltage profile under different network conditions. In addition, an SVC can mitigate active power oscillations through voltage amplitude modulation
  • 20. 20 FIXED CAPACITOR where the load does not change or where the capacitor is switched with the load, such as the load side of a Ideally suited for power factor correction in applications motor contactor. It is suitable for locations using induction motors, like food processing plants, or where small multiple loads require reactive power compensation. Each Fixed Capacitor Bank is designed for high reliability and long life. These products are designed for applications that do not contain harmonic generating
  • 21. 21 SWITCHED CAPACITOR It is suited for centralized power factor correction in applications where plant loading is constantly changing, resulting in the need for varying amounts of reactive power. An advanced microprocessor-based reactive power controller measures plant power factor via a single remote current transformer (included), and switches capacitor modules in and out of service to maintain a user-selected target power factor. Typically applied at service entrance or near fluctuating loads.
  • 22. 22 SYNCHRONOUS CONDENSER Synchronous condenser is a salient pole synchronous generator without prime mover. Synchronous condenser stabilizes power system voltage by supplying reactive power to the power system and Use for power factor correction. It is more economical than capacitors.
  • 24. 24 STATIC SYNCHRONOUS COMPENSTOR (STATCOM) The Static Synchronous Compensator (STATCOM) is a shunt device of the Flexible AC Transmission Systems (FACTS) family using power electronics to control power flow and improve transient stability on power grids [1]. The STATCOM regulates voltage at its terminal by controlling the amount of reactive power injected into or absorbed from the power system. When system voltage is low, the STATCOM generates reactive power (STATCOM capacitive).
  • 25. 25 When system voltage is high, it absorbs reactive power (STATCOM inductive).Similarly to the SVC the STATCOM can provide instantaneous and continuously variable reactive power in response to grid voltage transients enhancing the grid voltage stability
  • 26. 26 Installing a STATCOM at one or more suitable points in the network will increase the grid transfer capability through enhanced voltage stability, while maintaining a smooth voltage profile under different network conditions. The STATCOM provides additional versatility in terms of power quality improvement capabilities
  • 27. 27 DETERMINING CAPACITOR VALUE Example Power Factor1=74% Actual Power=594 kw Interested to boost up=97% ,Power Factor2=97% Power Factor=KW/KVA Cos = kW / kVA  = Cos-1 (PF1)  = Cos-1 (74%) =42.27 o
  • 28. 28 The reactive power was about: Tan = kVAr / kW kVAr = kW x tan kVAr = 594 kW x tan (42.27) = 540 kVAr If the power factor were increased to 97%, the reactive power would be about: Cos = kW / kVA  = Cos-1 (PF2)  = Cos-1 (97%) = 14.07 o kVAr = kW x tan kVAr = 594 kW x tan (14.07) = 149 kVAr
  • 29. 29 Thus, the amount of capacitance required to boost power factor from 74% to 97% : 540 kVAr – 149 kVAr = 391 kVAr So I recommended 400kvar
  • 30. 30 POWER CAPACITORS Power Factor correction on site with Pole Cap
  • 31. 31 POWER FACTOR MEASUREMENT Power factor can measure by using power factor meter which is well known in power industry. Power factor can also be calculated by installing watt meter along with the Ampere meter and volt meter by using the power factor basic formula. Power factor=Actual Power/ Apparent power
  • 33. 33 ADVANTAGES OF POWER FACTOR CORRECTION Eliminate Power Factor Penalties Increase System Capacity Reduce Line Losses in distribution systems Conserve Energy Improve voltage stability
  • 34. 34 Increase equipment life Save on utility cost Enhance equipment operation by improving voltage Improve energy efficiency
  • 35. 35 Reduction in size of transformers, cables and switchgear in new installations. Delay costly upgrades. Less total plant KVA for the same KW working power. Improved voltage regulation due to reduced line voltage drop.
  • 36. 36 POWER COST REDUCTION Utility companies in many areas include a penalty charge in the electrical rate for low power factor. The installation of power factor capacitors on the user's electrical distribution system eliminates the necessity of paying premium rates to the utility company for poor power factor.
  • 37. 37 The savings the utility company derives in reduced generation, transmission and distribution costs are passed on to the user in the form of lower electrical charges. Three of the more common ways a utility charges a user for poor power factor are based on
  • 38. 38 KW demand with a trigger point typically between 85% and 95% KVA demand KVAR demand When the utility uses either KVA demand or KVAR demand as the basis for its penalty structure, all users pay a penalty, but those with high power factor pay a much lower penalty or none at all.
  • 39. 39 SYSTEM CAPACITY INCREASE By adding capacitors to the system, the power factor is improved and the KW capacity of the system is increased. For example, a 1,000 KVA transformer with a 70% power factor provides 700 KW of power to the main bus. With the installation of capacitors so that the power factor is improved, say, to 90%, the KW capacity of the system is increased to 900 KW. When a system power factor is improved, the amount of reactive current flowing Is lowered thus reducing transformer and distribution circuit loads, and releasing system capacity.
  • 40. 40 VOLTAGE IMPROVEMENT AND POWER LOSS REDUCTION System losses are also reduced through power factor correction by reducing the total current and power in the system. A 20% reduction in current will yield a 36% reduction in distribution system losses. In this situation, an energy savings of as much as 50% will be realized with the installation of power factor capacitors. In addition, power factor capacitors decrease the distribution system voltage drops and fluctuations.
  • 41. 41 DISADVANTAGES OF LOW POWER FACTOR Increases heating losses in the transformers and distribution equipments. Reduce plant life. Unstabilise voltage levels. Increase power losses. Upgrade costly equipments. Decrease energy efficiency. Increase electricity costs by paying power factor surcharges.
  • 42. 42 CONCLUSION By observing all aspects of the power factor it is clear that power factor is the most significant part for the utility Company as well as for the consumer. Utility company rid of from the power losses while the consumer free from low power factor penalty charges. By installing suitably sized power capacitors into the circuit the Power Factor is improved and the value becomes nearer to 1 thus minimising line losses and improving the efficiency of a plant.
  • 43. 43 REFERENCES Electrical Power System Design and Analysis by M.E.EI-Hawary. Power System Operations by Robert H Miller. IEEE papers www.ABB.com BC Hydro (www.bchydro.ca)