SlideShare a Scribd company logo
1 
POWER FACTOR CORRECTION 
HASHMAT ALI SHAH 
STUDENT ID 3205388
2 
OUTLINE 
DEFINITION 
CAUSES OF LOW POWER FACTOR 
POWER FACTOR CORRECTION 
ADVANTAGES OF POWER FACTOR CORRECTION 
DISADVANTAGES OF LOW POWER FACTOR 
CONCLUSION 
REFERENCES
DEFINITION: 
Power factor (P.F) is the ratio between actual power to the 
apparent power. 
Actual power/Apparent power. 
P.F=Kw /Kva. 
For a purely resistive load the power factor is unity. Active 
and reactive power are designated by P &Q respectively. 
The average power in a circuit is called active power and 
the power that supplies the stored energy in reactive 
elements is called reactive power. 
3
Active Power: 
Also known as “real power” or simply “power.” Active power 
is the rate of producing, transferring, or using electrical 
energy. It is measured in watts and often expressed in 
kilowatts (KW) or megawatts (MW). The terms “active” or 
“real” power are used in place of the term “power” alone to 
differentiate it from “reactive power. 
Apparent Power: 
The product of the voltage (in volts) and the current 
(in amperes). It comprises both active and reactive power . 
It is measured in “volt-amperes” and often expressed in 
“ kilovolt-amperes” (KVA) or “megavolt-amperes” (MVA). 
4
5 
POWER FACTOR DEFINITION 
Inductive loads cause the current to lag behind the 
voltage. The wave forms of voltage and current are then 
"out of phase" with each other. The more out of phase 
they become then the lower the Power Factor. Power 
Factor is usually expressed as Cos Phi. (Ø)
6 
Consider a canal boat being pulled by a horse. 
If the horse could walk on water then the angle (Phi) Ø 
would be zero and COSINE Ø=1. Meaning all the horse 
power is being used to pull the load. 
However the relative position of the horse influences the 
power. As the horse gets closer to the barge, angle Ø1 
increases and power is wasted, but, as the horse is 
positioned further away, then angle Ø2 gets closer to 
zero and less power is wasted.
7 
CAUSES OF LOW POWER FACTOR 
A poor power factor can be the result of either a 
significant phase difference between the voltage and 
current at the load terminals or it can be due to a high 
harmonic content or distorted/discontinuous current 
waveform. Poor load current phase angle is generally the 
result of Poor load current phase angle is generally the 
result of an inductive load such as an induction motor 
power transformer, lighting ballasts, welder or induction 
furnace, Induction generators Wind mill generators and 
high intensity discharge lightings.
8 
CAUSES OF LOW POWER FACTOR 
A distorted current waveform can be the result of a 
rectifier variable speed drive, switched mode power 
supply, discharge lighting or other electronic load.
9 
POWER FACTOR CORRECTION 
Power factor decreases with the installation of non 
resistive loads such as induction motors, Transformers. 
Lighting ballasts and electronic equipments. Power 
factors can be corrected by using capacitors. These are 
rated in electrical units called VAR or KVAR.One VAR is 
equivalent to one volt of reactive power. VAR then are 
units of measurement for indicating just how much 
reactive power the capacitor will supply.
10 
As reactive power is usually measured in thousands the 
letter K is used for thousand. the capacitor KVAR rating 
then shows how much reactive power the capacitor will 
supply. Each unit of the capacitor's KVAR will decrease 
the inductive reactive power demand.
11 
POWER FACTOR CORRECTION 
Most loads on an electrical distribution system fall into 
one of three categories; resistive, inductive or capacitive. 
In most plant, the most common is likely to be inductive. 
Typical examples of this include transformers, fluorescent 
lighting and AC induction motors. Most inductive loads 
use a conductive coil winding to produce an 
electromagnetic field, allowing the motor to function.
All inductive loads require two kinds of power to operate: 
Active power (KW) - to produce the motive force 
Reactive power (KVAR) - to energize the magnetic field 
The operating power from the distribution system is 
composed of both active (working) and reactive (non-working) 
elements. The active power does useful work in 
12 
driving the motor whereas the reactive power only 
provides the magnetic field.
13 
POWER FACTOR CORRECTION 
The amount of Power Capacitor KVAR required to correct 
A system to a desired Power Factor level is the difference 
between the amount of KVAR in the uncorrected system 
and the amount of desired KVAR in the corrected system. 
The most efficient location for power factor capacitors is 
at the load. Capacitors work from the point of installation 
back to the generating source. Individual motor correction 
is not always practical, sometimes it is more practical to 
connect larger capacitors on the distribution bus or install 
an automatic system at the incoming service along with 
fixed capacitors at the load.
14 
KVAR CORRECTION 
Capacitive Power Factor correction (PFC) is applied to 
electric circuits as a means of minimising the inductive 
component of the current and thereby reducing the 
losses in the supply. 
The introduction of Power Factor Correction capacitors is 
a widely recognised method of reducing an electrical 
load, thus minimising wasted energy and hence 
improving the efficiency of a plant and reducing the 
electricity bill.
It is not usually necessary to reach unity, i.e. Power 
Factor 1, since most supply companies are happy with a 
PF of 0.95 to 0.98. 
By installing suitably sized switched capacitors into the 
circuit, the Power Factor is improved and the value 
becomes nearer to 1 thus minimising wasted energy and 
improving the efficiency of a plant or power factor can be 
increased by synchronous motor or Synchronous 
generators. 
15
16 
POWER FACTOR CORRECTION 
METHODS 
Static Var Compensator(SVC) 
Fixed Capcitors 
Switch Capacitors 
Synchronous Condensors 
Static Synchronous Compensator(STATCOM) 
Modulated power filter capacitor compensator
17 
STATIC VAR COMPENSATOR 
(SVC) 
The Static Var Compensator (SVC) is a shunt device of 
the Flexible AC Transmission Systems (FACTS) family 
using power electronics to control power flow and 
improve transient stability on power grids [1]. The SVC 
regulates voltage at its terminals by controlling the 
amount of reactive power injected into or absorbed from 
the power system. When system voltage is low, the SVC 
generates reactive power (SVC capacitive). When 
system voltage is high, it absorbs reactive power (SVC 
inductive).
The variation of reactive power is performed by switching 
three-phase capacitor banks and inductor banks 
connected on the secondary side of a coupling 
transformer. Each capacitor bank is switched on and off 
by three thyristor switches (Thyristor Switched Capacitor 
or TSC). Reactors are either switched on-off (Thyristor 
Switched Reactor or TSR) or phase-controlled (Thyristor 
Controlled Reactor or TCR). 
18
19 
A rapidly operating Static Var Compensator (SVC) can 
continuously provide the reactive power required to 
control dynamic voltage swings under various system 
conditions and thereby improve the power system 
transmission and distribution performance. 
Installing an SVC at one or more suitable points in the 
network will increase transfer capability through 
enhanced voltage stability, while maintaining a smooth 
voltage profile under different network conditions. In 
addition, an SVC can mitigate active power oscillations 
through voltage amplitude modulation
20 
FIXED CAPACITOR 
where the load does not change or where the capacitor 
is switched with the load, such as the load side of a 
Ideally suited for power factor correction in applications 
motor contactor. It is suitable for locations using 
induction motors, like food processing plants, or 
where small multiple loads require reactive power 
compensation. 
Each Fixed Capacitor Bank is designed for high reliability 
and long life. These products are designed for 
applications that do not contain harmonic generating
21 
SWITCHED CAPACITOR 
It is suited for centralized power factor correction in 
applications where plant loading is constantly changing, 
resulting in the need for varying amounts of reactive 
power. An advanced microprocessor-based reactive 
power controller measures plant power factor via a 
single remote current transformer (included), and 
switches capacitor modules in and out of service to 
maintain a user-selected target power factor. Typically 
applied at service entrance or near fluctuating loads.
22 
SYNCHRONOUS CONDENSER 
Synchronous condenser is a salient pole synchronous 
generator without prime mover. Synchronous condenser 
stabilizes power system voltage by supplying reactive 
power to the power system and Use for power factor 
correction. It is more economical than capacitors.
23 
SYNCHRONOUS CONDENSER
STATIC SYNCHRONOUS COMPENSTOR 
24 
(STATCOM) 
The Static Synchronous Compensator (STATCOM) is a 
shunt device of the Flexible AC Transmission Systems 
(FACTS) family using power electronics to control power 
flow and improve transient stability on power grids [1]. 
The STATCOM regulates voltage at its terminal by 
controlling the amount of reactive power injected into or 
absorbed from the power system. When system voltage 
is low, the STATCOM generates reactive power 
(STATCOM capacitive).
25 
When system voltage is high, it absorbs reactive power 
(STATCOM inductive).Similarly to the SVC the 
STATCOM can provide instantaneous and continuously 
variable reactive power in response to grid voltage 
transients enhancing the grid voltage stability
Installing a STATCOM at one or more suitable points in 
the network will increase the grid transfer capability 
through enhanced voltage stability, while maintaining a 
smooth voltage profile under different network 
conditions. The STATCOM provides additional versatility 
in terms of power quality improvement capabilities 
26
27 
DETERMINING CAPACITOR VALUE 
Example 
Power Factor1=74% 
Actual Power=594 kw 
Interested to boost up=97% ,Power Factor2=97% 
Power Factor=KW/KVA 
Cos = kW / kVA 
 = Cos-1 (PF1) 
 = Cos-1 (74%) =42.27 o
28 
The reactive power was about: 
Tan = kVAr / kW 
kVAr = kW x tan 
kVAr = 594 kW x tan (42.27) = 540 kVAr 
If the power factor were increased to 97%, the reactive 
power would be about: 
Cos = kW / kVA 
 = Cos-1 (PF2) 
 = Cos-1 (97%) = 14.07 o 
kVAr = kW x tan 
kVAr = 594 kW x tan (14.07) = 149 kVAr
29 
Thus, the amount of capacitance required to boost 
power factor from 74% to 97% : 
540 kVAr – 149 kVAr = 391 kVAr 
So I recommended 400kvar
30 
POWER CAPACITORS 
Power Factor correction on site with 
Pole Cap
31 
POWER FACTOR MEASUREMENT 
Power factor can measure by using power factor meter 
which is well known in power industry. 
Power factor can also be calculated by installing watt 
meter along with the Ampere meter and volt meter by 
using the power factor basic formula. 
Power factor=Actual Power/ Apparent power
32 
POWER FACTOR MEASUREMENT
33 
ADVANTAGES OF POWER FACTOR 
CORRECTION 
Eliminate Power Factor Penalties 
Increase System Capacity 
Reduce Line Losses in distribution systems 
Conserve Energy 
Improve voltage stability
34 
Increase equipment life 
Save on utility cost 
Enhance equipment operation by improving voltage 
Improve energy efficiency
Reduction in size of transformers, cables and switchgear 
in new installations. 
Delay costly upgrades. 
Less total plant KVA for the same KW working power. 
Improved voltage regulation due to reduced line voltage 
drop. 
35
36 
POWER COST REDUCTION 
Utility companies in many areas include a penalty charge in 
the electrical rate for low power factor. The installation of 
power factor capacitors on the user's electrical distribution 
system eliminates the necessity of paying premium rates to 
the utility company for poor power factor.
37 
The savings the utility company derives in reduced 
generation, transmission and distribution costs are 
passed on to the user in the form of lower electrical 
charges. Three of the more common ways a utility 
charges a user for poor power factor are based on
38 
KW demand with a trigger point typically between 85% 
and 95% 
KVA demand 
KVAR demand 
When the utility uses either KVA demand or KVAR 
demand as the basis for its penalty structure, all users 
pay a penalty, but those with high power factor pay a 
much lower penalty or none at all.
39 
SYSTEM CAPACITY INCREASE 
By adding capacitors to the system, the power factor is 
improved and the KW capacity of the system is 
increased. For example, a 1,000 KVA transformer with a 
70% power factor provides 700 KW of power to the main 
bus. With the installation of capacitors so that the power 
factor is improved, say, to 90%, the KW capacity of the 
system is increased to 900 KW. When a system power 
factor is improved, the amount of reactive current flowing 
Is lowered thus reducing transformer and distribution 
circuit loads, and releasing system capacity.
40 
VOLTAGE IMPROVEMENT AND POWER 
LOSS REDUCTION 
System losses are also reduced through power factor 
correction by reducing the total current and power in the 
system. A 20% reduction in current will yield a 36% 
reduction in distribution system losses. In this situation, 
an energy savings of as much as 50% will be realized 
with the installation of power factor capacitors. 
In addition, power factor capacitors decrease the 
distribution system voltage drops and fluctuations.
41 
DISADVANTAGES OF LOW POWER 
FACTOR 
Increases heating losses in the transformers and 
distribution equipments. 
Reduce plant life. 
Unstabilise voltage levels. 
Increase power losses. 
Upgrade costly equipments. 
Decrease energy efficiency. 
Increase electricity costs by paying power factor 
surcharges.
42 
CONCLUSION 
By observing all aspects of the power factor it is clear that 
power factor is the most significant part for the utility 
Company as well as for the consumer. Utility company 
rid of from the power losses while the consumer free 
from low power factor penalty charges. 
By installing suitably sized power capacitors into the 
circuit the Power Factor is improved and the value 
becomes nearer to 1 thus minimising line losses and 
improving the efficiency of a plant.
43 
REFERENCES 
Electrical Power System Design and Analysis 
by M.E.EI-Hawary. 
Power System Operations 
by Robert H Miller. 
IEEE papers 
www.ABB.com 
BC Hydro (www.bchydro.ca)

More Related Content

What's hot

power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
soham patel
 
FACTS
FACTS FACTS
FACTS
Komal Nigam
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentation
Azhar Abbas
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
sneh pratap singh
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
khemraj298
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
Raviraj solanki
 
An overview of FACTS devices
An overview of FACTS devicesAn overview of FACTS devices
An overview of FACTS devices
Indian Institute of Technology Guwahati
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
Nitish NIT
 
Automatic power factor correction unit
Automatic power factor correction unitAutomatic power factor correction unit
Automatic power factor correction unitBiswajit Pratihari
 
Statcom
StatcomStatcom
Statcom
jawaharramaya
 
Facts controller
Facts controllerFacts controller
Facts controller
Debayon Saha
 
Chapter 3 transmission line performance
Chapter 3  transmission line performanceChapter 3  transmission line performance
Chapter 3 transmission line performance
firaoltemesgen1
 
Electric substation
Electric substation Electric substation
Electric substation
ANNU KUMAR
 
Facts devices
Facts devicesFacts devices
Facts devices
Vinod Srivastava
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
Mamta Bagoria
 
Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
Prabhu R
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
MUET SZAB Campus Khairpur Mir's Sindh Pakistan
 
Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power system
Rahuldey1991
 
Economic Justification of Capacitors
Economic Justification of CapacitorsEconomic Justification of Capacitors
Economic Justification of Capacitors
Edwin Selva Rex
 

What's hot (20)

power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
FACTS
FACTS FACTS
FACTS
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentation
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
An overview of FACTS devices
An overview of FACTS devicesAn overview of FACTS devices
An overview of FACTS devices
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Automatic power factor correction unit
Automatic power factor correction unitAutomatic power factor correction unit
Automatic power factor correction unit
 
Statcom
StatcomStatcom
Statcom
 
Facts controller
Facts controllerFacts controller
Facts controller
 
Chapter 3 transmission line performance
Chapter 3  transmission line performanceChapter 3  transmission line performance
Chapter 3 transmission line performance
 
Electric substation
Electric substation Electric substation
Electric substation
 
Facts devices
Facts devicesFacts devices
Facts devices
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
 
Reactive power consumption in modern power system
Reactive power consumption in modern power systemReactive power consumption in modern power system
Reactive power consumption in modern power system
 
Economic Justification of Capacitors
Economic Justification of CapacitorsEconomic Justification of Capacitors
Economic Justification of Capacitors
 

Viewers also liked

Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
Working as a Lecturer
 
Power Factor Basics
Power Factor BasicsPower Factor Basics
Power Factor Basics
no suhaila
 
How Does Lightning Work?
How Does Lightning Work?How Does Lightning Work?
How Does Lightning Work?erowell
 
presentation of lightning
presentation of lightningpresentation of lightning
presentation of lightning
IcHa Diah Utami
 
Lighting design considerations
Lighting design considerationsLighting design considerations
Lighting design considerationsmominzaki
 
Fuse- Power system Protection
Fuse- Power system Protection  Fuse- Power system Protection
Fuse- Power system Protection
Md. Nahid Sarker
 
Light and architecture
Light and architectureLight and architecture
Light and architecture
Atul Pathak
 
Lighting Powerpoint
Lighting PowerpointLighting Powerpoint
Lighting Powerpoint
shawn8492
 

Viewers also liked (8)

Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
Power Factor Basics
Power Factor BasicsPower Factor Basics
Power Factor Basics
 
How Does Lightning Work?
How Does Lightning Work?How Does Lightning Work?
How Does Lightning Work?
 
presentation of lightning
presentation of lightningpresentation of lightning
presentation of lightning
 
Lighting design considerations
Lighting design considerationsLighting design considerations
Lighting design considerations
 
Fuse- Power system Protection
Fuse- Power system Protection  Fuse- Power system Protection
Fuse- Power system Protection
 
Light and architecture
Light and architectureLight and architecture
Light and architecture
 
Lighting Powerpoint
Lighting PowerpointLighting Powerpoint
Lighting Powerpoint
 

Similar to Power Factor

Power Factor Correction.ppt
Power Factor Correction.pptPower Factor Correction.ppt
Power Factor Correction.ppt
SalmanHameed26
 
IARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdfIARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdf
GayanBuddhikaAlahend
 
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfpowerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
BOOPATHIMADHAIYAN
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
manpreetsingh1076
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and Solutions
Abhinav Dubey
 
REACTIVE POWER
REACTIVE POWERREACTIVE POWER
REACTIVE POWER
JeetDatta3
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
khaliq ahmed
 
Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)
MOHAMMADSHOAIBBABAR
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
इन्दुभूषण कुमार
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
ijceronline
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
Ameen San
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
KLS' S GIT, BELGAUM
 
Automatic power factor correction and its advantage
Automatic power factor correction and its advantageAutomatic power factor correction and its advantage
Automatic power factor correction and its advantage
KASHYAPMOKARIYA1
 
Power factor
Power factorPower factor
Power factor
Narayan Datta
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET Journal
 
Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)
REVANTH CHINTU
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
Hussain Ali
 

Similar to Power Factor (20)

Power Factor Correction.ppt
Power Factor Correction.pptPower Factor Correction.ppt
Power Factor Correction.ppt
 
Mohsin rana
Mohsin ranaMohsin rana
Mohsin rana
 
IARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdfIARE_RPCM_PPT_0.pdf
IARE_RPCM_PPT_0.pdf
 
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdfpowerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
powerfactorintroductionanditscorrectionfinalokk-180401111606 (3).pdf
 
Power factor introduction and its correction final
Power factor introduction and its correction final Power factor introduction and its correction final
Power factor introduction and its correction final
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and Solutions
 
REACTIVE POWER
REACTIVE POWERREACTIVE POWER
REACTIVE POWER
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
POWER FACTOR IMPROVE
POWER FACTOR IMPROVEPOWER FACTOR IMPROVE
POWER FACTOR IMPROVE
 
Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur AreaReactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
Reactive Power Compensation in 132kv & 33kv Grid of Narsinghpur Area
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
 
Thyristor switched capacitor
Thyristor switched capacitorThyristor switched capacitor
Thyristor switched capacitor
 
Automatic power factor correction and its advantage
Automatic power factor correction and its advantageAutomatic power factor correction and its advantage
Automatic power factor correction and its advantage
 
Power factor
Power factorPower factor
Power factor
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
 
Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)Reactivepowercompensation 140401183847-phpapp01 (6)
Reactivepowercompensation 140401183847-phpapp01 (6)
 
Reactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcomReactive power management and voltage control by using statcom
Reactive power management and voltage control by using statcom
 

Recently uploaded

Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
Intella Parts
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
ShahidSultan24
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
MuhammadTufail242431
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
abh.arya
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
R&R Consult
 
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdfCOLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
Kamal Acharya
 
Event Management System Vb Net Project Report.pdf
Event Management System Vb Net  Project Report.pdfEvent Management System Vb Net  Project Report.pdf
Event Management System Vb Net Project Report.pdf
Kamal Acharya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
ankuprajapati0525
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
Jayaprasanna4
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
Kamal Acharya
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
PrashantGoswami42
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Recently uploaded (20)

Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
 
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdfCOLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
 
Event Management System Vb Net Project Report.pdf
Event Management System Vb Net  Project Report.pdfEvent Management System Vb Net  Project Report.pdf
Event Management System Vb Net Project Report.pdf
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 

Power Factor

  • 1. 1 POWER FACTOR CORRECTION HASHMAT ALI SHAH STUDENT ID 3205388
  • 2. 2 OUTLINE DEFINITION CAUSES OF LOW POWER FACTOR POWER FACTOR CORRECTION ADVANTAGES OF POWER FACTOR CORRECTION DISADVANTAGES OF LOW POWER FACTOR CONCLUSION REFERENCES
  • 3. DEFINITION: Power factor (P.F) is the ratio between actual power to the apparent power. Actual power/Apparent power. P.F=Kw /Kva. For a purely resistive load the power factor is unity. Active and reactive power are designated by P &Q respectively. The average power in a circuit is called active power and the power that supplies the stored energy in reactive elements is called reactive power. 3
  • 4. Active Power: Also known as “real power” or simply “power.” Active power is the rate of producing, transferring, or using electrical energy. It is measured in watts and often expressed in kilowatts (KW) or megawatts (MW). The terms “active” or “real” power are used in place of the term “power” alone to differentiate it from “reactive power. Apparent Power: The product of the voltage (in volts) and the current (in amperes). It comprises both active and reactive power . It is measured in “volt-amperes” and often expressed in “ kilovolt-amperes” (KVA) or “megavolt-amperes” (MVA). 4
  • 5. 5 POWER FACTOR DEFINITION Inductive loads cause the current to lag behind the voltage. The wave forms of voltage and current are then "out of phase" with each other. The more out of phase they become then the lower the Power Factor. Power Factor is usually expressed as Cos Phi. (Ø)
  • 6. 6 Consider a canal boat being pulled by a horse. If the horse could walk on water then the angle (Phi) Ø would be zero and COSINE Ø=1. Meaning all the horse power is being used to pull the load. However the relative position of the horse influences the power. As the horse gets closer to the barge, angle Ø1 increases and power is wasted, but, as the horse is positioned further away, then angle Ø2 gets closer to zero and less power is wasted.
  • 7. 7 CAUSES OF LOW POWER FACTOR A poor power factor can be the result of either a significant phase difference between the voltage and current at the load terminals or it can be due to a high harmonic content or distorted/discontinuous current waveform. Poor load current phase angle is generally the result of Poor load current phase angle is generally the result of an inductive load such as an induction motor power transformer, lighting ballasts, welder or induction furnace, Induction generators Wind mill generators and high intensity discharge lightings.
  • 8. 8 CAUSES OF LOW POWER FACTOR A distorted current waveform can be the result of a rectifier variable speed drive, switched mode power supply, discharge lighting or other electronic load.
  • 9. 9 POWER FACTOR CORRECTION Power factor decreases with the installation of non resistive loads such as induction motors, Transformers. Lighting ballasts and electronic equipments. Power factors can be corrected by using capacitors. These are rated in electrical units called VAR or KVAR.One VAR is equivalent to one volt of reactive power. VAR then are units of measurement for indicating just how much reactive power the capacitor will supply.
  • 10. 10 As reactive power is usually measured in thousands the letter K is used for thousand. the capacitor KVAR rating then shows how much reactive power the capacitor will supply. Each unit of the capacitor's KVAR will decrease the inductive reactive power demand.
  • 11. 11 POWER FACTOR CORRECTION Most loads on an electrical distribution system fall into one of three categories; resistive, inductive or capacitive. In most plant, the most common is likely to be inductive. Typical examples of this include transformers, fluorescent lighting and AC induction motors. Most inductive loads use a conductive coil winding to produce an electromagnetic field, allowing the motor to function.
  • 12. All inductive loads require two kinds of power to operate: Active power (KW) - to produce the motive force Reactive power (KVAR) - to energize the magnetic field The operating power from the distribution system is composed of both active (working) and reactive (non-working) elements. The active power does useful work in 12 driving the motor whereas the reactive power only provides the magnetic field.
  • 13. 13 POWER FACTOR CORRECTION The amount of Power Capacitor KVAR required to correct A system to a desired Power Factor level is the difference between the amount of KVAR in the uncorrected system and the amount of desired KVAR in the corrected system. The most efficient location for power factor capacitors is at the load. Capacitors work from the point of installation back to the generating source. Individual motor correction is not always practical, sometimes it is more practical to connect larger capacitors on the distribution bus or install an automatic system at the incoming service along with fixed capacitors at the load.
  • 14. 14 KVAR CORRECTION Capacitive Power Factor correction (PFC) is applied to electric circuits as a means of minimising the inductive component of the current and thereby reducing the losses in the supply. The introduction of Power Factor Correction capacitors is a widely recognised method of reducing an electrical load, thus minimising wasted energy and hence improving the efficiency of a plant and reducing the electricity bill.
  • 15. It is not usually necessary to reach unity, i.e. Power Factor 1, since most supply companies are happy with a PF of 0.95 to 0.98. By installing suitably sized switched capacitors into the circuit, the Power Factor is improved and the value becomes nearer to 1 thus minimising wasted energy and improving the efficiency of a plant or power factor can be increased by synchronous motor or Synchronous generators. 15
  • 16. 16 POWER FACTOR CORRECTION METHODS Static Var Compensator(SVC) Fixed Capcitors Switch Capacitors Synchronous Condensors Static Synchronous Compensator(STATCOM) Modulated power filter capacitor compensator
  • 17. 17 STATIC VAR COMPENSATOR (SVC) The Static Var Compensator (SVC) is a shunt device of the Flexible AC Transmission Systems (FACTS) family using power electronics to control power flow and improve transient stability on power grids [1]. The SVC regulates voltage at its terminals by controlling the amount of reactive power injected into or absorbed from the power system. When system voltage is low, the SVC generates reactive power (SVC capacitive). When system voltage is high, it absorbs reactive power (SVC inductive).
  • 18. The variation of reactive power is performed by switching three-phase capacitor banks and inductor banks connected on the secondary side of a coupling transformer. Each capacitor bank is switched on and off by three thyristor switches (Thyristor Switched Capacitor or TSC). Reactors are either switched on-off (Thyristor Switched Reactor or TSR) or phase-controlled (Thyristor Controlled Reactor or TCR). 18
  • 19. 19 A rapidly operating Static Var Compensator (SVC) can continuously provide the reactive power required to control dynamic voltage swings under various system conditions and thereby improve the power system transmission and distribution performance. Installing an SVC at one or more suitable points in the network will increase transfer capability through enhanced voltage stability, while maintaining a smooth voltage profile under different network conditions. In addition, an SVC can mitigate active power oscillations through voltage amplitude modulation
  • 20. 20 FIXED CAPACITOR where the load does not change or where the capacitor is switched with the load, such as the load side of a Ideally suited for power factor correction in applications motor contactor. It is suitable for locations using induction motors, like food processing plants, or where small multiple loads require reactive power compensation. Each Fixed Capacitor Bank is designed for high reliability and long life. These products are designed for applications that do not contain harmonic generating
  • 21. 21 SWITCHED CAPACITOR It is suited for centralized power factor correction in applications where plant loading is constantly changing, resulting in the need for varying amounts of reactive power. An advanced microprocessor-based reactive power controller measures plant power factor via a single remote current transformer (included), and switches capacitor modules in and out of service to maintain a user-selected target power factor. Typically applied at service entrance or near fluctuating loads.
  • 22. 22 SYNCHRONOUS CONDENSER Synchronous condenser is a salient pole synchronous generator without prime mover. Synchronous condenser stabilizes power system voltage by supplying reactive power to the power system and Use for power factor correction. It is more economical than capacitors.
  • 24. STATIC SYNCHRONOUS COMPENSTOR 24 (STATCOM) The Static Synchronous Compensator (STATCOM) is a shunt device of the Flexible AC Transmission Systems (FACTS) family using power electronics to control power flow and improve transient stability on power grids [1]. The STATCOM regulates voltage at its terminal by controlling the amount of reactive power injected into or absorbed from the power system. When system voltage is low, the STATCOM generates reactive power (STATCOM capacitive).
  • 25. 25 When system voltage is high, it absorbs reactive power (STATCOM inductive).Similarly to the SVC the STATCOM can provide instantaneous and continuously variable reactive power in response to grid voltage transients enhancing the grid voltage stability
  • 26. Installing a STATCOM at one or more suitable points in the network will increase the grid transfer capability through enhanced voltage stability, while maintaining a smooth voltage profile under different network conditions. The STATCOM provides additional versatility in terms of power quality improvement capabilities 26
  • 27. 27 DETERMINING CAPACITOR VALUE Example Power Factor1=74% Actual Power=594 kw Interested to boost up=97% ,Power Factor2=97% Power Factor=KW/KVA Cos = kW / kVA  = Cos-1 (PF1)  = Cos-1 (74%) =42.27 o
  • 28. 28 The reactive power was about: Tan = kVAr / kW kVAr = kW x tan kVAr = 594 kW x tan (42.27) = 540 kVAr If the power factor were increased to 97%, the reactive power would be about: Cos = kW / kVA  = Cos-1 (PF2)  = Cos-1 (97%) = 14.07 o kVAr = kW x tan kVAr = 594 kW x tan (14.07) = 149 kVAr
  • 29. 29 Thus, the amount of capacitance required to boost power factor from 74% to 97% : 540 kVAr – 149 kVAr = 391 kVAr So I recommended 400kvar
  • 30. 30 POWER CAPACITORS Power Factor correction on site with Pole Cap
  • 31. 31 POWER FACTOR MEASUREMENT Power factor can measure by using power factor meter which is well known in power industry. Power factor can also be calculated by installing watt meter along with the Ampere meter and volt meter by using the power factor basic formula. Power factor=Actual Power/ Apparent power
  • 32. 32 POWER FACTOR MEASUREMENT
  • 33. 33 ADVANTAGES OF POWER FACTOR CORRECTION Eliminate Power Factor Penalties Increase System Capacity Reduce Line Losses in distribution systems Conserve Energy Improve voltage stability
  • 34. 34 Increase equipment life Save on utility cost Enhance equipment operation by improving voltage Improve energy efficiency
  • 35. Reduction in size of transformers, cables and switchgear in new installations. Delay costly upgrades. Less total plant KVA for the same KW working power. Improved voltage regulation due to reduced line voltage drop. 35
  • 36. 36 POWER COST REDUCTION Utility companies in many areas include a penalty charge in the electrical rate for low power factor. The installation of power factor capacitors on the user's electrical distribution system eliminates the necessity of paying premium rates to the utility company for poor power factor.
  • 37. 37 The savings the utility company derives in reduced generation, transmission and distribution costs are passed on to the user in the form of lower electrical charges. Three of the more common ways a utility charges a user for poor power factor are based on
  • 38. 38 KW demand with a trigger point typically between 85% and 95% KVA demand KVAR demand When the utility uses either KVA demand or KVAR demand as the basis for its penalty structure, all users pay a penalty, but those with high power factor pay a much lower penalty or none at all.
  • 39. 39 SYSTEM CAPACITY INCREASE By adding capacitors to the system, the power factor is improved and the KW capacity of the system is increased. For example, a 1,000 KVA transformer with a 70% power factor provides 700 KW of power to the main bus. With the installation of capacitors so that the power factor is improved, say, to 90%, the KW capacity of the system is increased to 900 KW. When a system power factor is improved, the amount of reactive current flowing Is lowered thus reducing transformer and distribution circuit loads, and releasing system capacity.
  • 40. 40 VOLTAGE IMPROVEMENT AND POWER LOSS REDUCTION System losses are also reduced through power factor correction by reducing the total current and power in the system. A 20% reduction in current will yield a 36% reduction in distribution system losses. In this situation, an energy savings of as much as 50% will be realized with the installation of power factor capacitors. In addition, power factor capacitors decrease the distribution system voltage drops and fluctuations.
  • 41. 41 DISADVANTAGES OF LOW POWER FACTOR Increases heating losses in the transformers and distribution equipments. Reduce plant life. Unstabilise voltage levels. Increase power losses. Upgrade costly equipments. Decrease energy efficiency. Increase electricity costs by paying power factor surcharges.
  • 42. 42 CONCLUSION By observing all aspects of the power factor it is clear that power factor is the most significant part for the utility Company as well as for the consumer. Utility company rid of from the power losses while the consumer free from low power factor penalty charges. By installing suitably sized power capacitors into the circuit the Power Factor is improved and the value becomes nearer to 1 thus minimising line losses and improving the efficiency of a plant.
  • 43. 43 REFERENCES Electrical Power System Design and Analysis by M.E.EI-Hawary. Power System Operations by Robert H Miller. IEEE papers www.ABB.com BC Hydro (www.bchydro.ca)