L.V Technical Data
Outline
 Introduction about LV SWG.
 Alfanar LV products.
 Alfanar Terasaki.
 Alfanar’s Approvals.
Introduction for LV electrical characteristics
Circuit-breakers:
Disconnect and connect the power and provide protection for
cable, load and human against overload and overcurrent.
The following are the type of the CB:
MCB, RCCB, RCBO, MCCB, ICCB, ELCP, MCP, Power circuit and ACB.
Rated operational current (In, Ie):
Continuous current Without overheating
Rated operational voltage (Ue):
This is the voltage at which the equipment has been designed to
operate, in normal (undisturbed) conditions
Rated insulation voltage (Ui) for Circuit-breakers:
This is the value of voltage to which the dielectric tests voltage
and Creepage distances are referred too. The Ue ≤ Ui
Rated impulse-withstand voltage (Uimp) for Circuit-breakers:
This characteristic expresses, in kV peak, the value of voltage
which the equipment is capable of withstanding without failure,
under test conditions. Generally, for industrial circuit-breakers,
Uimp=8kV and for domestic types, Uimp=6kV, and in special cases
could be 12KV
Rated ultimate short-circuit breaking capacity (Icu):
The maximum current, that can be broken across the contacts,
twice times without being damage.
Introduction for LV electrical characteristics
Rated service short-circuit breaking capacity (Ics):
The maximum current, that can be broken across the contacts, without being
damage.
Rated short-time withstand current rating (Icw):
Is the maximum current, that the B category CB can withstand, thermally and
electro dynamically, without sustaining damage, for a period of time given by the
manufacturer.
Category A:
For which there is no calibrate delay in the operation of the “instantaneous” short-
circuit magnetic tripping device.
Category B:
For which, in order to discriminate with other circuit-breakers on a time basis, it is
possible to delay the tripping of the CB, where the fault-current level is lower than,
that of the short-time withstand current rating (Icw) of the CB.
Introduction for LV electrical characteristics
Co-ordination study:
 Discrimination/Selectivity:
Is the Co-ordination of protective device such that a fault is
cleared by the protective device installed immediately
upstream of the fault, and by that device alone.
 Total Discrimination:
Discrimination is said to be total if the downstream circuit
breaker opens and the upstream circuit breaker remains
closed. This ensure maximum availability of the system.
 Partial Discrimination:
Discrimination is partial if the above condition is not fulfilled
up to the prospective short-circuit current, but to lesser
value, above this value both circuit breakers could open,
resulting in loss selectivity.
 Cascading/Backup:
Is a technique where the current limiting capability of
upstream circuit breakers is used to permit the installation
of lower circuit breakers downstream.
Introduction for LV electrical characteristics
Introduction for LV electrical characteristics
 Discrimination/Selectivity:
 Cascading/Backup:
Introduction for LV Mechanical characteristics
Ingrees of Protection (IP X X):
Standard IEC 60529 (February 2001) indicates the degree of protection
provided by electrical equipment enclosures against accidental direct contact
with live parts and against the ingress of solid foreign objects or water.
IK Code “Mechanical Impact test:
The European standard EN 50102 dated March 1995 defines a coding system
(IK code) for indicating the degree of protection provided by electrical equipment
enclosures against external mechanical impact.
Introduction for LV Mechanical characteristics
Separation Forms:
Introduction for LV Mechanical characteristics
Form IEC standard definition Specific recommendations
1 No Internal separation Protection over busbar for customer
safety
2a Separation of busbars from the functional units Terminals not separated from busbars
2b Separation of busbars from the functional units Terminals separated from busbars
3a Separation of busbars from the functional units
and of all functional units from each other.
Terminals not separated from busbars
3b Separation of busbars from the functional units
and of all functional units from each other.
Terminals separated from busbars
4a Separation of busbars from the functional units
and of all functional units from each other, also
separation of terminals from any functional unit
Terminals in the same compartment
as associated functional units.
4b Separation of busbars from the functional units
and of all functional units from each other, also
separation of terminals from any functional unit
Terminals are not in the same
compartment as the associated
functional units
Introduction for LV Mechanical characteristics
IEC 61439:
Is a series of standard IEC 60439
 Fundamental change:
• The categories of TTA (Type Tested Assemblies) and PTTA (Partially
Type Tested Assemblies) have been discarded in favor of a design.
• The performance of assemblies is now determined by a “Design
Verification”.
IEC 61439 Vs IEC 60439:
Arc Flash protection:
International standards (IEC / ANSI) guidelines are
different but the objectives are the same,
i.e. defining minimum safety level for operators
 Assessment criteria for the internal arc test:
• Correctly secured doors, covers, etc. do not open.
• Parts of the assembly (which may cause a hazard) do
not fly off.
• Arcing does not cause holes in the external parts of
the enclosure.
• Indicators do not ignite (made from black cretonne).
• The protective circuit is still operational.
• The arc is to be confined in the same area where it
was ignited.
If these criteria are achieved by the panel, then the
test is a success.
Arc Flash protection:
Seismic :
Proper mounting of the equipment is the
single most important factor in
withstanding a seismic event.
The foundation must be level and
continuous under the entire assembly. The
foundation must be designed to withstand
the reaction loads imposed on it by the
equipment during a seismic event.
Earth quake protection (Seismic):
Product Portfolio :
 Main Distribution Switchboards
 ATS, Synch, 2 out of 3
 Motor Control Center (MCC)
 Control Panels & Panel Boards
 Power Factor Correction Capacitors (PFC)
 Switch rack
 ICP
alfanar L.V Factory:
• Applicable standards IEC 61439-2
• Ie Up to 6300A (No derating up to 6100A, tested at 40° C)
• ICW 100kA/1 sec or 50kA/3 sec
• Ue 690Vac/600Vdc
• Ui 1000Vac
• Uimp 12KV
• Form Form 1 to Form 4B
• Internal Arc Withstand 65kA/300 mSec (Upon Request)
• Seismic Withstand 8 on Richter Scale (Standard Feature)
Alfanar-Terasaki
alfanar L.V SWG:
Who is TERASAKI ?
Alfanar Low Voltage equipment:
ALFANAR TERASAKI Breakers:
 Tem Power-2 is ACB made in Japan up to 6300A/135kA.
 TemBreak2 is MCCB made in Japan up to 1600A/200kA.
 TemDin2 is MCB made in France up to 125A/15KA.
 All ACBs & MCCBs tested under 50°C w/o derating.
Alfanar Low Voltage equipment:
Air Circuit Breakers (World Class Circuit Breakers):
 Ie=800A to 6300A
 Icu=Ics=Icw/1sec
 Ue=690Vac/600Vdc
 Ui=1000Vac
 Uimp=12KV
 Three frame size (800-2000A, 2500-4000A and 5000-6300A)
 Fixed or Withdrawable (Front, vertical or horizontal connection)
 Manual or Motor charging
 Comply with IEC 60947-2
 Comply with ANSI C37.13 and NEMA PUB NO.SG3
 3P or 4P
 Category B
 Trip Unit is AGR (L, R for general feeder or Transformer and S for
generator protection)
Alfanar Low Voltage equipment:
Protection Relays:
The Tem Power-2 series is equipped with an RMS sensing over-current
release AGRB AR Protection Relay samples& calculates the load current
every
(500 micro seconds).
Alfanar Low Voltage equipment:
Harmonic Monitoring:
TemPower 2 AGRs can detect & protect up to the 31th Harmonic.
Protection Relays:
The Phase Rotation Protection function detects the negative phase
current occurring due to reverse phase or phase loss and prevents
burnout of a
Moto or damage to equipment.
Alfanar Low Voltage equipment:
Tempreture control:
CONTACT TEMPERATURE MONITORING, This AGR protection function
monitors the temperature of the ACBs main contacts.
An alarm when the temperature exceeds 155°C.
Continuous monitoring of the contact temperature provides valuable
information for BMS, preventative and predictive maintenance programs.
Alfanar Low Voltage equipment:
Double break:
The Tem Power-2 Air Circuit Breaker is the smallest depth Air Circuit
Breaker in the world with a one second Short Circuit Withstand.
The unique “Double Break” main contact system ensures extremely
fast interruption of short circuit currents.
Conventional break time is 70msec, TemPower 2 breaking time is
25~30msec.
Alfanar Low Voltage equipment:
Eeasy maintenance:
The unique design of Tem Power-2 incorporates its
isolating clusters and main contacts on the ACB body. Allowing for
quick easy maintenance of the main electrical contact points and for
maintenance to be completed without having to isolate the board.
Alfanar Low Voltage equipment:
Replacement of main contacts:
The fixed and moving main contacts can easily
be replaced in the field, thus prolonging the life
on the circuit breaker. Changing each pole takes
around 15 minutes.
Alfanar Low Voltage equipment:
Double opening and closing coils:
Double Opening and Closing Coils provides extended control
system redundancy to an ACB. Double coils allow designers to
implement back-up tripping and closing systems. It provides the
end user with ultimate reliability on critical UPS circuits connected
to critical loads.
Alfanar Low Voltage equipment:
ACB accessories:
Alfanar Low Voltage equipment:
Moulded Case Circuit Breakers Circuit Breakers:
 Ie=125A to 1600A
 Ue=690Vac/600Vdc
 Ui=800Vac
 Uimp=8KV
 Fixed or Withdrawable (Front, vertical or horizontal connection)
 Manual or Motor charging
 Comply with IEC 60947-2
 Comply with NEMA AB-1
 1P, 3P or 4P
 Category A/B
Alfanar Low Voltage equipment:
Moulded Case Circuit Breakers (Thermal Magnetic):
6
8
12
10
0.8
0.63
1
Ir (x ln) Ii (x ln)
125A
Alfanar Low Voltage equipment:
Moulded Case Circuit Breakers
(Electronic):
Electronic version with integrated
monitoring and communication, data
can be sent to integrated display
local display and Modbus network
simultaneously.
Alfanar Low Voltage equipment:
Direct opening “Yellow and red symbol “:
This symbol located on the MCCB rating label,
indicates that the MCCB has direct opening
action.
According to IEC 60204 provides a positive
off.
Alfanar Low Voltage equipment:
Plug-in safety lock:
MCCB can only be
withdrawn when MCCB is
switched off.
Alfanar Low Voltage equipment:
MCCB accessories:
Alfanar Low Voltage equipment:
Circuit breaker with integral Residual Current
Protection “CBR”:
Alfanar Low Voltage equipment:
Al Imam Muhammed
ibn Saud Islamic
University
King Abdullah
Financial District -
KAFD
King Abdullah Sport
City –Jeddah (KASC)
Haramain High Speed Railway
King Abdullah Port
Alfanar Low Voltage equipment:
Reference projects in KSA:
Alfanar Low Voltage equipment:
Reference projects in overseas:
Alfanar Low Voltage equipment:
Reference projects in overseas:
Alfanar Low Voltage equipment:
Reference projects in overseas:
Alfanar Low Voltage equipment:
Reference projects in overseas:
L.v tech presentation 2

More Related Content

What's hot

Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
Modal Holong Education
 
ETAP - Arc flash introduction
ETAP - Arc flash introductionETAP - Arc flash introduction
ETAP - Arc flash introduction
Himmelstern
 
Transformer & OLTC
Transformer & OLTCTransformer & OLTC
Transformer & OLTCRohit Dave
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
johny renoald
 
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Thorne & Derrick International
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Power System Operation
 
Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
 Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin... Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
vvsatyanarayana K
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
D Målîk
 
Switchgear Installation Precomissioning Inspection.PPT
Switchgear Installation  Precomissioning Inspection.PPTSwitchgear Installation  Precomissioning Inspection.PPT
Switchgear Installation Precomissioning Inspection.PPTAbdullah Al Dushaishi
 
Cable fault location methods (Megger)
Cable fault location methods (Megger)Cable fault location methods (Megger)
Cable fault location methods (Megger)
AHMED MOHAMED HEGAB
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
Himansu Pradhan
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
Nadir Baloch
 
ETAP - Ground grid systems
ETAP - Ground grid systemsETAP - Ground grid systems
ETAP - Ground grid systems
Himmelstern
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
Himmelstern
 
Arc flash analysis and electrical hazards
Arc flash analysis and electrical hazardsArc flash analysis and electrical hazards
Arc flash analysis and electrical hazards
VB Engineering
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
Nikhil Kachare
 
Electrical substation (one and half breaker scheme)
Electrical substation (one and half breaker scheme)Electrical substation (one and half breaker scheme)
Electrical substation (one and half breaker scheme)
Sourabh sharma
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
Bryan Johnson
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
karikalan123
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
Power System Operation
 

What's hot (20)

Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
ETAP - Arc flash introduction
ETAP - Arc flash introductionETAP - Arc flash introduction
ETAP - Arc flash introduction
 
Transformer & OLTC
Transformer & OLTCTransformer & OLTC
Transformer & OLTC
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
Baur - Cable Fault Locators & Location Specialists (LV MV HV Cables)
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash Analysis
 
Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
 Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin... Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
Online Condition Monitoring And Diagnosis Of Power Transformers Their Bushin...
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
 
Switchgear Installation Precomissioning Inspection.PPT
Switchgear Installation  Precomissioning Inspection.PPTSwitchgear Installation  Precomissioning Inspection.PPT
Switchgear Installation Precomissioning Inspection.PPT
 
Cable fault location methods (Megger)
Cable fault location methods (Megger)Cable fault location methods (Megger)
Cable fault location methods (Megger)
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
ETAP - Ground grid systems
ETAP - Ground grid systemsETAP - Ground grid systems
ETAP - Ground grid systems
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
 
Arc flash analysis and electrical hazards
Arc flash analysis and electrical hazardsArc flash analysis and electrical hazards
Arc flash analysis and electrical hazards
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Electrical substation (one and half breaker scheme)
Electrical substation (one and half breaker scheme)Electrical substation (one and half breaker scheme)
Electrical substation (one and half breaker scheme)
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 

Similar to L.v tech presentation 2

244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf
Barlomax
 
Lv switchgear & lv cable sizing
Lv switchgear & lv cable sizingLv switchgear & lv cable sizing
Lv switchgear & lv cable sizing
Asif Eqbal
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
Ritesh Kumawat
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
MANOJ964697
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBSheikh Imran
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
Satish Pydimarla
 
1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)nikeshdubey
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.
Rajeev Kumar Raj
 
Mcb catalogue
Mcb catalogueMcb catalogue
Mcb catalogue
Johnson lim
 
Tongou electrical catalogue
Tongou electrical catalogue Tongou electrical catalogue
Tongou electrical catalogue
Johnson lim
 
Dc mini-breaker
Dc mini-breakerDc mini-breaker
Dc mini-breaker
Jiandong Wu
 
Adjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power SupplyAdjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power Supply
Muhsin Fahim
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
Thorne & Derrick International
 
switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamleshKamlesh Vala
 
DPL Transmission And Distribution
DPL Transmission And DistributionDPL Transmission And Distribution
DPL Transmission And Distribution
Subhojeet Sinha ☁
 
Crouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & DistributionCrouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & Distribution
Crouzet
 
4.RCCB -Meba
4.RCCB -Meba 4.RCCB -Meba
4.RCCB -Meba
Meba Electric Co.,Ltd
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodination
michaeljmack
 

Similar to L.v tech presentation 2 (20)

244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf244109578 estandar-iec-60947-2-pdf
244109578 estandar-iec-60947-2-pdf
 
Lv switchgear & lv cable sizing
Lv switchgear & lv cable sizingLv switchgear & lv cable sizing
Lv switchgear & lv cable sizing
 
Thông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LSThông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LS
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Electrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCBElectrical Installations, MCB, MCCB, ELCB
Electrical Installations, MCB, MCCB, ELCB
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DB
 
Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 
1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.
 
Mcb catalogue
Mcb catalogueMcb catalogue
Mcb catalogue
 
Tongou electrical catalogue
Tongou electrical catalogue Tongou electrical catalogue
Tongou electrical catalogue
 
Dc mini-breaker
Dc mini-breakerDc mini-breaker
Dc mini-breaker
 
Adjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power SupplyAdjustable/Regulated DC Power Supply
Adjustable/Regulated DC Power Supply
 
havells ppt
havells ppthavells ppt
havells ppt
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamlesh
 
DPL Transmission And Distribution
DPL Transmission And DistributionDPL Transmission And Distribution
DPL Transmission And Distribution
 
Crouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & DistributionCrouzet Aerospace - Electrical Protection & Distribution
Crouzet Aerospace - Electrical Protection & Distribution
 
4.RCCB -Meba
4.RCCB -Meba 4.RCCB -Meba
4.RCCB -Meba
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodination
 

Recently uploaded

Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
Kamal Acharya
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdfCOLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
Kamal Acharya
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
obonagu
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
MuhammadTufail242431
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
ShahidSultan24
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
Kamal Acharya
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
abh.arya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
ankuprajapati0525
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 

Recently uploaded (20)

Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
 
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdfCOLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdf
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 

L.v tech presentation 2

  • 2. Outline  Introduction about LV SWG.  Alfanar LV products.  Alfanar Terasaki.  Alfanar’s Approvals.
  • 3.
  • 4. Introduction for LV electrical characteristics Circuit-breakers: Disconnect and connect the power and provide protection for cable, load and human against overload and overcurrent. The following are the type of the CB: MCB, RCCB, RCBO, MCCB, ICCB, ELCP, MCP, Power circuit and ACB. Rated operational current (In, Ie): Continuous current Without overheating Rated operational voltage (Ue): This is the voltage at which the equipment has been designed to operate, in normal (undisturbed) conditions
  • 5. Rated insulation voltage (Ui) for Circuit-breakers: This is the value of voltage to which the dielectric tests voltage and Creepage distances are referred too. The Ue ≤ Ui Rated impulse-withstand voltage (Uimp) for Circuit-breakers: This characteristic expresses, in kV peak, the value of voltage which the equipment is capable of withstanding without failure, under test conditions. Generally, for industrial circuit-breakers, Uimp=8kV and for domestic types, Uimp=6kV, and in special cases could be 12KV Rated ultimate short-circuit breaking capacity (Icu): The maximum current, that can be broken across the contacts, twice times without being damage. Introduction for LV electrical characteristics
  • 6. Rated service short-circuit breaking capacity (Ics): The maximum current, that can be broken across the contacts, without being damage. Rated short-time withstand current rating (Icw): Is the maximum current, that the B category CB can withstand, thermally and electro dynamically, without sustaining damage, for a period of time given by the manufacturer. Category A: For which there is no calibrate delay in the operation of the “instantaneous” short- circuit magnetic tripping device. Category B: For which, in order to discriminate with other circuit-breakers on a time basis, it is possible to delay the tripping of the CB, where the fault-current level is lower than, that of the short-time withstand current rating (Icw) of the CB. Introduction for LV electrical characteristics
  • 7. Co-ordination study:  Discrimination/Selectivity: Is the Co-ordination of protective device such that a fault is cleared by the protective device installed immediately upstream of the fault, and by that device alone.  Total Discrimination: Discrimination is said to be total if the downstream circuit breaker opens and the upstream circuit breaker remains closed. This ensure maximum availability of the system.  Partial Discrimination: Discrimination is partial if the above condition is not fulfilled up to the prospective short-circuit current, but to lesser value, above this value both circuit breakers could open, resulting in loss selectivity.  Cascading/Backup: Is a technique where the current limiting capability of upstream circuit breakers is used to permit the installation of lower circuit breakers downstream. Introduction for LV electrical characteristics
  • 8. Introduction for LV electrical characteristics  Discrimination/Selectivity:  Cascading/Backup:
  • 9. Introduction for LV Mechanical characteristics Ingrees of Protection (IP X X): Standard IEC 60529 (February 2001) indicates the degree of protection provided by electrical equipment enclosures against accidental direct contact with live parts and against the ingress of solid foreign objects or water.
  • 10. IK Code “Mechanical Impact test: The European standard EN 50102 dated March 1995 defines a coding system (IK code) for indicating the degree of protection provided by electrical equipment enclosures against external mechanical impact. Introduction for LV Mechanical characteristics
  • 11. Separation Forms: Introduction for LV Mechanical characteristics
  • 12. Form IEC standard definition Specific recommendations 1 No Internal separation Protection over busbar for customer safety 2a Separation of busbars from the functional units Terminals not separated from busbars 2b Separation of busbars from the functional units Terminals separated from busbars 3a Separation of busbars from the functional units and of all functional units from each other. Terminals not separated from busbars 3b Separation of busbars from the functional units and of all functional units from each other. Terminals separated from busbars 4a Separation of busbars from the functional units and of all functional units from each other, also separation of terminals from any functional unit Terminals in the same compartment as associated functional units. 4b Separation of busbars from the functional units and of all functional units from each other, also separation of terminals from any functional unit Terminals are not in the same compartment as the associated functional units Introduction for LV Mechanical characteristics
  • 13. IEC 61439: Is a series of standard IEC 60439  Fundamental change: • The categories of TTA (Type Tested Assemblies) and PTTA (Partially Type Tested Assemblies) have been discarded in favor of a design. • The performance of assemblies is now determined by a “Design Verification”. IEC 61439 Vs IEC 60439:
  • 14. Arc Flash protection: International standards (IEC / ANSI) guidelines are different but the objectives are the same, i.e. defining minimum safety level for operators  Assessment criteria for the internal arc test: • Correctly secured doors, covers, etc. do not open. • Parts of the assembly (which may cause a hazard) do not fly off. • Arcing does not cause holes in the external parts of the enclosure. • Indicators do not ignite (made from black cretonne). • The protective circuit is still operational. • The arc is to be confined in the same area where it was ignited. If these criteria are achieved by the panel, then the test is a success. Arc Flash protection:
  • 15. Seismic : Proper mounting of the equipment is the single most important factor in withstanding a seismic event. The foundation must be level and continuous under the entire assembly. The foundation must be designed to withstand the reaction loads imposed on it by the equipment during a seismic event. Earth quake protection (Seismic):
  • 16. Product Portfolio :  Main Distribution Switchboards  ATS, Synch, 2 out of 3  Motor Control Center (MCC)  Control Panels & Panel Boards  Power Factor Correction Capacitors (PFC)  Switch rack  ICP alfanar L.V Factory:
  • 17. • Applicable standards IEC 61439-2 • Ie Up to 6300A (No derating up to 6100A, tested at 40° C) • ICW 100kA/1 sec or 50kA/3 sec • Ue 690Vac/600Vdc • Ui 1000Vac • Uimp 12KV • Form Form 1 to Form 4B • Internal Arc Withstand 65kA/300 mSec (Upon Request) • Seismic Withstand 8 on Richter Scale (Standard Feature) Alfanar-Terasaki alfanar L.V SWG:
  • 18. Who is TERASAKI ? Alfanar Low Voltage equipment:
  • 19. ALFANAR TERASAKI Breakers:  Tem Power-2 is ACB made in Japan up to 6300A/135kA.  TemBreak2 is MCCB made in Japan up to 1600A/200kA.  TemDin2 is MCB made in France up to 125A/15KA.  All ACBs & MCCBs tested under 50°C w/o derating. Alfanar Low Voltage equipment:
  • 20. Air Circuit Breakers (World Class Circuit Breakers):  Ie=800A to 6300A  Icu=Ics=Icw/1sec  Ue=690Vac/600Vdc  Ui=1000Vac  Uimp=12KV  Three frame size (800-2000A, 2500-4000A and 5000-6300A)  Fixed or Withdrawable (Front, vertical or horizontal connection)  Manual or Motor charging  Comply with IEC 60947-2  Comply with ANSI C37.13 and NEMA PUB NO.SG3  3P or 4P  Category B  Trip Unit is AGR (L, R for general feeder or Transformer and S for generator protection) Alfanar Low Voltage equipment:
  • 21. Protection Relays: The Tem Power-2 series is equipped with an RMS sensing over-current release AGRB AR Protection Relay samples& calculates the load current every (500 micro seconds). Alfanar Low Voltage equipment:
  • 22. Harmonic Monitoring: TemPower 2 AGRs can detect & protect up to the 31th Harmonic. Protection Relays: The Phase Rotation Protection function detects the negative phase current occurring due to reverse phase or phase loss and prevents burnout of a Moto or damage to equipment. Alfanar Low Voltage equipment:
  • 23. Tempreture control: CONTACT TEMPERATURE MONITORING, This AGR protection function monitors the temperature of the ACBs main contacts. An alarm when the temperature exceeds 155°C. Continuous monitoring of the contact temperature provides valuable information for BMS, preventative and predictive maintenance programs. Alfanar Low Voltage equipment:
  • 24. Double break: The Tem Power-2 Air Circuit Breaker is the smallest depth Air Circuit Breaker in the world with a one second Short Circuit Withstand. The unique “Double Break” main contact system ensures extremely fast interruption of short circuit currents. Conventional break time is 70msec, TemPower 2 breaking time is 25~30msec. Alfanar Low Voltage equipment:
  • 25. Eeasy maintenance: The unique design of Tem Power-2 incorporates its isolating clusters and main contacts on the ACB body. Allowing for quick easy maintenance of the main electrical contact points and for maintenance to be completed without having to isolate the board. Alfanar Low Voltage equipment:
  • 26. Replacement of main contacts: The fixed and moving main contacts can easily be replaced in the field, thus prolonging the life on the circuit breaker. Changing each pole takes around 15 minutes. Alfanar Low Voltage equipment:
  • 27. Double opening and closing coils: Double Opening and Closing Coils provides extended control system redundancy to an ACB. Double coils allow designers to implement back-up tripping and closing systems. It provides the end user with ultimate reliability on critical UPS circuits connected to critical loads. Alfanar Low Voltage equipment:
  • 28. ACB accessories: Alfanar Low Voltage equipment:
  • 29. Moulded Case Circuit Breakers Circuit Breakers:  Ie=125A to 1600A  Ue=690Vac/600Vdc  Ui=800Vac  Uimp=8KV  Fixed or Withdrawable (Front, vertical or horizontal connection)  Manual or Motor charging  Comply with IEC 60947-2  Comply with NEMA AB-1  1P, 3P or 4P  Category A/B Alfanar Low Voltage equipment:
  • 30. Moulded Case Circuit Breakers (Thermal Magnetic): 6 8 12 10 0.8 0.63 1 Ir (x ln) Ii (x ln) 125A Alfanar Low Voltage equipment:
  • 31. Moulded Case Circuit Breakers (Electronic): Electronic version with integrated monitoring and communication, data can be sent to integrated display local display and Modbus network simultaneously. Alfanar Low Voltage equipment:
  • 32. Direct opening “Yellow and red symbol “: This symbol located on the MCCB rating label, indicates that the MCCB has direct opening action. According to IEC 60204 provides a positive off. Alfanar Low Voltage equipment:
  • 33. Plug-in safety lock: MCCB can only be withdrawn when MCCB is switched off. Alfanar Low Voltage equipment:
  • 34. MCCB accessories: Alfanar Low Voltage equipment:
  • 35. Circuit breaker with integral Residual Current Protection “CBR”: Alfanar Low Voltage equipment:
  • 36. Al Imam Muhammed ibn Saud Islamic University King Abdullah Financial District - KAFD King Abdullah Sport City –Jeddah (KASC) Haramain High Speed Railway King Abdullah Port Alfanar Low Voltage equipment: Reference projects in KSA:
  • 37. Alfanar Low Voltage equipment: Reference projects in overseas:
  • 38. Alfanar Low Voltage equipment: Reference projects in overseas:
  • 39. Alfanar Low Voltage equipment: Reference projects in overseas:
  • 40. Alfanar Low Voltage equipment: Reference projects in overseas: