The document provides specifications for several models of residual current circuit breakers (RCCBs) made by Meba, including the MPFIM4, CF-362, CF-364, and others. It lists the brand, model number, type, number of poles, rated voltage and current, rated residual operating current, technical standards, and dimensions for each model. The RCCBs are designed to detect earth leakage currents and open the connected circuit to protect people and equipment from faults.
Nobody is save against potential electricity failures. It does not take much for a current that serves us well to bring extreme danger to our everyday life. The most reasonable way to reduce the risk is to use a protection equipment RCCB (residual current device).
Protections:
The JB is a DC circuit breaker designed to protect cables between photovoltaic string and inverter from overloads and short circuits. It can be installed in a string PV protection enclosure and locked off for safety during inverter removal. The JB can detect bidirectional faults and must be combined with other safety devices depending on the application. It is not polarity sensitive and has barriers between connectors.
Residual Current Devices (RCDs), also known as ground fault circuit interrupters (GFCIs), are mechanical switching devices that open electric circuits when they detect that current to ground exceeds a predetermined value due to a ground fault. The document discusses different types of RCDs including RCCB, RCBO, RCD, and their applications based on standards like IEC 61008 and 61009. Key parameters for selecting RCDs include nominal current, tripping current, conditional breaking capacity, and device type. Proper RCD selection and circuit design are important for safety and discrimination.
Dc circuit supplementary protectors for photovoltaic installationsLangir Electric
The JB is a DC circuit breaker designed to protect strings of photovoltaic modules. It can detect and protect against bidirectional currents and is not polarity sensitive. The JB is available in 1-4 pole configurations with rated voltages from 250-1000V DC. It is combined with a switch and installed in enclosures at the end of each string to provide overcurrent and short circuit protection for the cables between the strings and inverter.
The document discusses residual current circuit breakers (RCCBs) that provide protection against earth faults and leakage currents. It lists various RCCB models that comply with IEC 61008 standards and have ratings up to 125A and 630A breaking capacity. The document provides details on RCCB construction, features, technical specifications, wiring diagrams, and dimensions for installation. It describes how RCCBs automatically disconnect circuits when earth faults exceed their rated sensitivity levels.
The document provides information on Meta Solution's upgraded Metasol molded case circuit breakers (MCCBs) and earth leakage circuit breakers (ELCBs), including:
- Increased breaking capacities of up to 85kA for various ampere ratings.
- 100% compatibility with the previous Meta-MEC series in dimensions and installation.
- Additional accessory options for installation and safety.
- Standardized dimensions and connection configurations for ease of panel construction and maintenance.
The document discusses moulded case circuit breakers in the TOS2 series. It provides specifications for various models of the TOS2 breaker, including rated currents from 12.5A to 1600A, rated voltages up to 750V, and rated short circuit and service short circuit breaking capacities. It describes the use of TOS2 breakers for distributing electric energy and protecting circuit equipment from overloads and short circuits. It also mentions electronic and motor protection releases available for some TOS2 models.
This document provides specifications for various TOC2 series AC contactors, including:
- Rated working currents from 9A to 620A
- Voltage ratings from 220/230V to 660/690V
- Electrical and mechanical lifespans
- Dimensions and mounting details for models ranging from TOC2-D09 to TOC2-D620
The TOC2 contactors can be used to control AC motors in circuits up to 660VAC 50/60Hz, and are suitable for applications such as making, breaking, starting, and controlling AC motors when combined with auxiliary devices.
Nobody is save against potential electricity failures. It does not take much for a current that serves us well to bring extreme danger to our everyday life. The most reasonable way to reduce the risk is to use a protection equipment RCCB (residual current device).
Protections:
The JB is a DC circuit breaker designed to protect cables between photovoltaic string and inverter from overloads and short circuits. It can be installed in a string PV protection enclosure and locked off for safety during inverter removal. The JB can detect bidirectional faults and must be combined with other safety devices depending on the application. It is not polarity sensitive and has barriers between connectors.
Residual Current Devices (RCDs), also known as ground fault circuit interrupters (GFCIs), are mechanical switching devices that open electric circuits when they detect that current to ground exceeds a predetermined value due to a ground fault. The document discusses different types of RCDs including RCCB, RCBO, RCD, and their applications based on standards like IEC 61008 and 61009. Key parameters for selecting RCDs include nominal current, tripping current, conditional breaking capacity, and device type. Proper RCD selection and circuit design are important for safety and discrimination.
Dc circuit supplementary protectors for photovoltaic installationsLangir Electric
The JB is a DC circuit breaker designed to protect strings of photovoltaic modules. It can detect and protect against bidirectional currents and is not polarity sensitive. The JB is available in 1-4 pole configurations with rated voltages from 250-1000V DC. It is combined with a switch and installed in enclosures at the end of each string to provide overcurrent and short circuit protection for the cables between the strings and inverter.
The document discusses residual current circuit breakers (RCCBs) that provide protection against earth faults and leakage currents. It lists various RCCB models that comply with IEC 61008 standards and have ratings up to 125A and 630A breaking capacity. The document provides details on RCCB construction, features, technical specifications, wiring diagrams, and dimensions for installation. It describes how RCCBs automatically disconnect circuits when earth faults exceed their rated sensitivity levels.
The document provides information on Meta Solution's upgraded Metasol molded case circuit breakers (MCCBs) and earth leakage circuit breakers (ELCBs), including:
- Increased breaking capacities of up to 85kA for various ampere ratings.
- 100% compatibility with the previous Meta-MEC series in dimensions and installation.
- Additional accessory options for installation and safety.
- Standardized dimensions and connection configurations for ease of panel construction and maintenance.
The document discusses moulded case circuit breakers in the TOS2 series. It provides specifications for various models of the TOS2 breaker, including rated currents from 12.5A to 1600A, rated voltages up to 750V, and rated short circuit and service short circuit breaking capacities. It describes the use of TOS2 breakers for distributing electric energy and protecting circuit equipment from overloads and short circuits. It also mentions electronic and motor protection releases available for some TOS2 models.
This document provides specifications for various TOC2 series AC contactors, including:
- Rated working currents from 9A to 620A
- Voltage ratings from 220/230V to 660/690V
- Electrical and mechanical lifespans
- Dimensions and mounting details for models ranging from TOC2-D09 to TOC2-D620
The TOC2 contactors can be used to control AC motors in circuits up to 660VAC 50/60Hz, and are suitable for applications such as making, breaking, starting, and controlling AC motors when combined with auxiliary devices.
The document discusses residual current circuit breakers (RCCBs) with overcurrent protection. It provides details on the construction, features, technical specifications, and wiring diagrams of various RCCB models for voltages up to 415V AC and currents up to 100A. The RCCBs provide protection against earth faults, leakage currents, overloads, and short circuits, while also isolating the circuit. They automatically disconnect when fault currents exceed the rated sensitivity level.
TONGOU Electrical is a leading Chinese manufacturer and exporter of modular electric terminal devices for household, commercial, industrial, and similar installations. It produces a wide range of products including miniature circuit breakers, residual current circuit breakers, moulded case circuit breakers, air circuit breakers, contactors, and more. TONGOU prides itself on innovative design, excellent craftsmanship, and high reliability. It has obtained certifications from international organizations and supplies products globally.
TONGOU Electrical is a leading Chinese manufacturer and exporter of modular electric terminal devices for household, commercial, industrial, and similar installations. It produces a wide range of products including miniature circuit breakers, residual current circuit breakers, moulded case circuit breakers, air circuit breakers, contactors, and more. TONGOU prides itself on innovative design, excellent craftsmanship, and high reliability. It has obtained certifications from international organizations and supplies products globally.
Catalog thiết bị đóng cắt Fuji Electric - 07 - ELCB
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
The document discusses several disconnector switch models - TOB10-100, TODH1-100, TOD71-100, TOD73-100, and TOD10-100. The switches are applicable for electric circuits rated up to 230/400V AC and 125A. They provide isolation and can be used as main switches for household and commercial installations. The switches have ratings like 3000A short-circuit capacity and can withstand 1500A current for 1 second. They are intended to mount on 35mm DIN rails or in panels.
Optimized Local I/O ESD Protection for SerDes In Advanced SOI, BiCMOS and Fin...Sofics
Sofics presentation (B2.2) at the 1st International EOS/ESD Symposium on Design and System (IEDS). IEDS is dedicated to the fundamental understanding of issues related to electrostatic discharge on design and system and the application of this knowledge to the solution of problems.
Semiconductor companies are developing ever faster interfaces to satisfy the need for higher data throughputs. However, the parasitic capacitance of the traditional ESD solutions limits the signal frequency. This paper demonstrates low-cap Analog I/Os for high speed SerDes (28Gbps to 112Gbps) circuits created in advanced BiCMOS, SOI and FinFET nodes.
This document provides diagrams and information about installing surge protective devices (SPDs) in different lightning protection zones (LPZs) of a building. It discusses the different LPZs (0A, 0B, 1, 2, etc.), the types of SPDs used in each zone (MBD1-B series for primary protection between LPZ0A/0B and LPZ1, MBD1-C series for secondary protection between LPZ1 and LPZ2), and how to properly install and connect the SPDs. Diagrams show examples of SPD installation in TT, TN-S, and other power supply systems.
Catalog thiết bị đóng cắt Fuji Electric - 12 - VCB & VMC
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
This document provides specifications and installation instructions for the HEXE1MM and HEXE1MM-53 motor monitors. Key specifications include:
- The modules have 4 digital DC inputs, 4 current transformer inputs, 1 PTC input, and 4 relay outputs.
- The digital inputs accept ±12/24VDC, current inputs include options for 0-5A, 0-100mA, and 0-1A, and relay outputs are rated for 3A at 230VAC.
- Installation instructions include wiring diagrams, I/O register mapping, and derating charts for relay life expectancy based on load current.
- Safety precautions are provided and technical support contact information is listed.
Catalog MCCB LS metasol tổng hợp - beeteco.comBeeteco
Catalog MCCB LS metasol tổng hợp, ABN803c, ABN104c, ABN204c, ABN54c, ABS203c, ABS104c
Beeteco.com là trang mua sắm trực tuyến thiết bị điện - Tự động hóa uy tín tại Việt Nam.
Chuyên cung cấp các thiết bị: Đèn báo nút nhấn, Relay, Timer, Contactor, MCCB ELCB, Biến tần, Van, Thiết bị cảm biến, phụ kiện tủ điện, .... Từ các thương hiệu hàng đầu trên thế giới.
www.beeteco.com @ Công ty TNHH TM KT ASTER
Địa chỉ : Số 7/31 KDC Thương Mại Sóng Thần, KP. Nhị Đồng 1, P. Dĩ An, Tx. Dĩ An, Tỉnh Bình Dương
FB: www.facebook.com/beeteco
Email: contact@beeteco.com
Tel: 0650 3617 012
Hotline: 0909.41.61.43
The document introduces the BT3 series of air circuit breakers produced by Fuji Electric, which come in four frame sizes ranging from 1600A to 6300A. The breakers have compact designs and can provide breaking capacities of up to 120kA. They are available as fixed or draw-out installations with manual or motorized operating mechanisms. The breakers also include protection functions and can be used with optional intelligent controllers that provide monitoring and control capabilities.
JMV’s highly efficient Data line Surge Protection Device are designed to widely used in server equipments, router, working stations (intranet) HUB and board band.
Source(s): http://www.jmv.co.in/surge-protection/
The document describes a 20mA LED driver demo board that operates from 10-400V DC or 10-265V AC input and can power a single 20mA LED or string of LEDs up to 9V. The circuit uses an HV9821 control IC to operate in three modes - clamped buck converter, buck converter, or resistive ballast - depending on the line and load conditions. The board is designed to meet EMI standards and provides LED current regulation within 3% over the input voltage range while consuming less than 1W of power.
Catalog thiết bị đóng cắt Fuji Electric - 11 - Power Fuses, VT & CT
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
This document provides an overview of surge protection devices (SPDs), including their selection, application and operating theory. It discusses the sources and types of transient overvoltages that can damage electrical equipment. SPDs help mitigate these dangers by limiting transient voltage spikes. The document reviews relevant lightning and surge protection standards like BS EN 62305 and BS 7671. It examines SPD types, design considerations, installation best practices, inspection and testing procedures. Protection against overcurrents and coordination of multiple SPDs is also covered.
1. Betagard 5SX4 miniature circuit breakers (MCBs) have rated breaking capacities up to 10kA and comply with national and international standards with current ratings from 0.5A to 63A.
2. 5SX4 MCBs significantly limit let-through current during faults, providing high protection. They have "C" and "D" tripping characteristics and an average service life of 20,000 operations.
3. 5SX4 MCBs provide selectivity (preventing unnecessary tripping of upstream devices) when used with fuses or other MCBs according to limits specified in the document.
This document describes an anti-bag snatching alarm circuit designed to prevent theft. The circuit uses an operational amplifier configured as a comparator to detect when a mono plug is detached from the circuit, activating a timer and alarm tone generator. A transistor amplifies the alarm tone to a loudspeaker. It operates on a 9V battery and produces a loud siren noise to draw attention if anyone attempts to snatch the bag containing the circuit. The document provides details on the components, working principle, applications and advantages of using this simple, low-cost anti-theft alarm system.
The document introduces Rockwell Automation's Bulletin 4983 Surge & Filter Protection product line for meeting industrial surge and filter protection requirements. It consists of DIN rail and panel mount surge protective devices (SPDs) and filters to protect against internally generated transients and high frequency noise. The products are certified and provide protection of data, control, and power systems from surges and noise through clamping and filtering technologies. Planning protection proactively can prevent costly equipment failures later.
The document provides an overview of protection against overvoltages in photovoltaic installations according to European standards. It discusses the lightning and surge risks in PV installations, including direct lightning strikes, surge voltages from the AC network, nearby lightning strikes, and electromagnetic coupling. It reviews the European insurance statistics on damages and the evolution of relevant standards to address surge protection. The document outlines the general design for lightning and surge protection of PV installations according to European guidelines. It presents typical surge protection solutions for domestic and industrial PV installations.
ABB low voltage surge arresters LOVOS-5 and LOVOS-10 are a new generation of LV surge arresters ensuring electrical protection of overhead lines, electric energy receivers, distributing transformers and low voltage electrical equipment. Specify and install ABB LOVOS type surge arresters to protect low voltage power equipment from the effects of lightning and switching overvoltages.
ABB low voltage surge arrester types LOVOS-5 and LOVOS-10 selection criteria : continuous operating voltage Uc, voltage protection level Up and energy absorption capability.
The ABB LOVOS range provides protection along LV overhead lines, cables, motors, switches, any equipment connected to the line, from the LV side of distribution transformers up to measuring instruments.
Typical places of installation
• low voltage switchgears, distribution transformers (LV side)
• transition points of insulated and uninsulated, overhead and underground lines and cables
• electricity service entrance locations to buildings (in cabinets or at poles)
• at junctions (branching])
• every 500 / 1000 m of overhead line in locations of high lightning activity
• at the end of dead-end feeder line
• at the sealing ends of inserted cables
• at any apparatuses connected to secondary voltage source
ABB Power Products - Low Voltage Capacitators, Low Voltage Surge Arresters, Low Voltage Surge Arresters, Low Voltage Plugs & Sockets ATEX, Medium - High Voltage Fuses (Indoor & Outdoor), Current Transformers, Voltage Transformers, Voltage Surge Arresters, Vacuum Contactors.
Low voltage circuit breakers & contactors general leaflet lsmaianhbao_6519
1) The document provides information on LS Industrial Systems' electric products including miniature circuit breakers, residual current circuit breakers, and surge protective devices.
2) The miniature circuit breakers and residual current circuit breakers come in various pole configurations and rated currents, and provide overload and short circuit protection.
3) The surge protective devices include DIN-rail mounted and box type models for single and three phase systems, and provide protection from surge overvoltages with response times less than 5 nanoseconds.
This document provides technical data on LV switchgear products from Alfanar including:
- Circuit breakers from Teraski for applications up to 6300A with short circuit ratings of 100kA/1s or 50kA/3s.
- MCCBs and MCBs from Teraski for applications up to 1600A and 125A respectively.
- Switchboards can be designed to IEC 61439-2 standards with IP65 protection, internal arc testing up to 65kA, and seismic withstand of 8 on the Richter scale.
The document discusses residual current circuit breakers (RCCBs) with overcurrent protection. It provides details on the construction, features, technical specifications, and wiring diagrams of various RCCB models for voltages up to 415V AC and currents up to 100A. The RCCBs provide protection against earth faults, leakage currents, overloads, and short circuits, while also isolating the circuit. They automatically disconnect when fault currents exceed the rated sensitivity level.
TONGOU Electrical is a leading Chinese manufacturer and exporter of modular electric terminal devices for household, commercial, industrial, and similar installations. It produces a wide range of products including miniature circuit breakers, residual current circuit breakers, moulded case circuit breakers, air circuit breakers, contactors, and more. TONGOU prides itself on innovative design, excellent craftsmanship, and high reliability. It has obtained certifications from international organizations and supplies products globally.
TONGOU Electrical is a leading Chinese manufacturer and exporter of modular electric terminal devices for household, commercial, industrial, and similar installations. It produces a wide range of products including miniature circuit breakers, residual current circuit breakers, moulded case circuit breakers, air circuit breakers, contactors, and more. TONGOU prides itself on innovative design, excellent craftsmanship, and high reliability. It has obtained certifications from international organizations and supplies products globally.
Catalog thiết bị đóng cắt Fuji Electric - 07 - ELCB
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
The document discusses several disconnector switch models - TOB10-100, TODH1-100, TOD71-100, TOD73-100, and TOD10-100. The switches are applicable for electric circuits rated up to 230/400V AC and 125A. They provide isolation and can be used as main switches for household and commercial installations. The switches have ratings like 3000A short-circuit capacity and can withstand 1500A current for 1 second. They are intended to mount on 35mm DIN rails or in panels.
Optimized Local I/O ESD Protection for SerDes In Advanced SOI, BiCMOS and Fin...Sofics
Sofics presentation (B2.2) at the 1st International EOS/ESD Symposium on Design and System (IEDS). IEDS is dedicated to the fundamental understanding of issues related to electrostatic discharge on design and system and the application of this knowledge to the solution of problems.
Semiconductor companies are developing ever faster interfaces to satisfy the need for higher data throughputs. However, the parasitic capacitance of the traditional ESD solutions limits the signal frequency. This paper demonstrates low-cap Analog I/Os for high speed SerDes (28Gbps to 112Gbps) circuits created in advanced BiCMOS, SOI and FinFET nodes.
This document provides diagrams and information about installing surge protective devices (SPDs) in different lightning protection zones (LPZs) of a building. It discusses the different LPZs (0A, 0B, 1, 2, etc.), the types of SPDs used in each zone (MBD1-B series for primary protection between LPZ0A/0B and LPZ1, MBD1-C series for secondary protection between LPZ1 and LPZ2), and how to properly install and connect the SPDs. Diagrams show examples of SPD installation in TT, TN-S, and other power supply systems.
Catalog thiết bị đóng cắt Fuji Electric - 12 - VCB & VMC
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
This document provides specifications and installation instructions for the HEXE1MM and HEXE1MM-53 motor monitors. Key specifications include:
- The modules have 4 digital DC inputs, 4 current transformer inputs, 1 PTC input, and 4 relay outputs.
- The digital inputs accept ±12/24VDC, current inputs include options for 0-5A, 0-100mA, and 0-1A, and relay outputs are rated for 3A at 230VAC.
- Installation instructions include wiring diagrams, I/O register mapping, and derating charts for relay life expectancy based on load current.
- Safety precautions are provided and technical support contact information is listed.
Catalog MCCB LS metasol tổng hợp - beeteco.comBeeteco
Catalog MCCB LS metasol tổng hợp, ABN803c, ABN104c, ABN204c, ABN54c, ABS203c, ABS104c
Beeteco.com là trang mua sắm trực tuyến thiết bị điện - Tự động hóa uy tín tại Việt Nam.
Chuyên cung cấp các thiết bị: Đèn báo nút nhấn, Relay, Timer, Contactor, MCCB ELCB, Biến tần, Van, Thiết bị cảm biến, phụ kiện tủ điện, .... Từ các thương hiệu hàng đầu trên thế giới.
www.beeteco.com @ Công ty TNHH TM KT ASTER
Địa chỉ : Số 7/31 KDC Thương Mại Sóng Thần, KP. Nhị Đồng 1, P. Dĩ An, Tx. Dĩ An, Tỉnh Bình Dương
FB: www.facebook.com/beeteco
Email: contact@beeteco.com
Tel: 0650 3617 012
Hotline: 0909.41.61.43
The document introduces the BT3 series of air circuit breakers produced by Fuji Electric, which come in four frame sizes ranging from 1600A to 6300A. The breakers have compact designs and can provide breaking capacities of up to 120kA. They are available as fixed or draw-out installations with manual or motorized operating mechanisms. The breakers also include protection functions and can be used with optional intelligent controllers that provide monitoring and control capabilities.
JMV’s highly efficient Data line Surge Protection Device are designed to widely used in server equipments, router, working stations (intranet) HUB and board band.
Source(s): http://www.jmv.co.in/surge-protection/
The document describes a 20mA LED driver demo board that operates from 10-400V DC or 10-265V AC input and can power a single 20mA LED or string of LEDs up to 9V. The circuit uses an HV9821 control IC to operate in three modes - clamped buck converter, buck converter, or resistive ballast - depending on the line and load conditions. The board is designed to meet EMI standards and provides LED current regulation within 3% over the input voltage range while consuming less than 1W of power.
Catalog thiết bị đóng cắt Fuji Electric - 11 - Power Fuses, VT & CT
*********************************************************************
CTY TNHH HẠO PHƯƠNG - Nhà phân phối chính thức các thiết bị điện công nghiệp và tự động hóa của hãng FUJI ELECTRIC JAPAN tại Việt Nam
Xem chi tiết các sản phẩm Fuji Electric tại
http://haophuong.com/b1033533/fuji-electric
This document provides an overview of surge protection devices (SPDs), including their selection, application and operating theory. It discusses the sources and types of transient overvoltages that can damage electrical equipment. SPDs help mitigate these dangers by limiting transient voltage spikes. The document reviews relevant lightning and surge protection standards like BS EN 62305 and BS 7671. It examines SPD types, design considerations, installation best practices, inspection and testing procedures. Protection against overcurrents and coordination of multiple SPDs is also covered.
1. Betagard 5SX4 miniature circuit breakers (MCBs) have rated breaking capacities up to 10kA and comply with national and international standards with current ratings from 0.5A to 63A.
2. 5SX4 MCBs significantly limit let-through current during faults, providing high protection. They have "C" and "D" tripping characteristics and an average service life of 20,000 operations.
3. 5SX4 MCBs provide selectivity (preventing unnecessary tripping of upstream devices) when used with fuses or other MCBs according to limits specified in the document.
This document describes an anti-bag snatching alarm circuit designed to prevent theft. The circuit uses an operational amplifier configured as a comparator to detect when a mono plug is detached from the circuit, activating a timer and alarm tone generator. A transistor amplifies the alarm tone to a loudspeaker. It operates on a 9V battery and produces a loud siren noise to draw attention if anyone attempts to snatch the bag containing the circuit. The document provides details on the components, working principle, applications and advantages of using this simple, low-cost anti-theft alarm system.
The document introduces Rockwell Automation's Bulletin 4983 Surge & Filter Protection product line for meeting industrial surge and filter protection requirements. It consists of DIN rail and panel mount surge protective devices (SPDs) and filters to protect against internally generated transients and high frequency noise. The products are certified and provide protection of data, control, and power systems from surges and noise through clamping and filtering technologies. Planning protection proactively can prevent costly equipment failures later.
The document provides an overview of protection against overvoltages in photovoltaic installations according to European standards. It discusses the lightning and surge risks in PV installations, including direct lightning strikes, surge voltages from the AC network, nearby lightning strikes, and electromagnetic coupling. It reviews the European insurance statistics on damages and the evolution of relevant standards to address surge protection. The document outlines the general design for lightning and surge protection of PV installations according to European guidelines. It presents typical surge protection solutions for domestic and industrial PV installations.
ABB low voltage surge arresters LOVOS-5 and LOVOS-10 are a new generation of LV surge arresters ensuring electrical protection of overhead lines, electric energy receivers, distributing transformers and low voltage electrical equipment. Specify and install ABB LOVOS type surge arresters to protect low voltage power equipment from the effects of lightning and switching overvoltages.
ABB low voltage surge arrester types LOVOS-5 and LOVOS-10 selection criteria : continuous operating voltage Uc, voltage protection level Up and energy absorption capability.
The ABB LOVOS range provides protection along LV overhead lines, cables, motors, switches, any equipment connected to the line, from the LV side of distribution transformers up to measuring instruments.
Typical places of installation
• low voltage switchgears, distribution transformers (LV side)
• transition points of insulated and uninsulated, overhead and underground lines and cables
• electricity service entrance locations to buildings (in cabinets or at poles)
• at junctions (branching])
• every 500 / 1000 m of overhead line in locations of high lightning activity
• at the end of dead-end feeder line
• at the sealing ends of inserted cables
• at any apparatuses connected to secondary voltage source
ABB Power Products - Low Voltage Capacitators, Low Voltage Surge Arresters, Low Voltage Surge Arresters, Low Voltage Plugs & Sockets ATEX, Medium - High Voltage Fuses (Indoor & Outdoor), Current Transformers, Voltage Transformers, Voltage Surge Arresters, Vacuum Contactors.
Low voltage circuit breakers & contactors general leaflet lsmaianhbao_6519
1) The document provides information on LS Industrial Systems' electric products including miniature circuit breakers, residual current circuit breakers, and surge protective devices.
2) The miniature circuit breakers and residual current circuit breakers come in various pole configurations and rated currents, and provide overload and short circuit protection.
3) The surge protective devices include DIN-rail mounted and box type models for single and three phase systems, and provide protection from surge overvoltages with response times less than 5 nanoseconds.
This document provides technical data on LV switchgear products from Alfanar including:
- Circuit breakers from Teraski for applications up to 6300A with short circuit ratings of 100kA/1s or 50kA/3s.
- MCCBs and MCBs from Teraski for applications up to 1600A and 125A respectively.
- Switchboards can be designed to IEC 61439-2 standards with IP65 protection, internal arc testing up to 65kA, and seismic withstand of 8 on the Richter scale.
Ls catalog thiet bi dien electric products e 1108_dienhathe.vnDien Ha The
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.org
Ls catalog thiet bi dien electric products e 1108Dien Ha The
Catalog LS, Catalog,
Catalog Thiết Bị Điện LS, Catalog Thiết Bị Điện,
http://dienhathe.com,
Chi tiết các sản phẩm khác của LS tại https://dienhathe.com
Xem thêm các Catalog khác của LS tại https://dienhathe.info
Để nhận báo giá sản phẩm LS vui lòng gọi: 0907.764.966
Catalogue mccb doi moi cua hang h yundaiDien Ha The
Catalogue mccb doi moi cua hang h yundai
Catalog Idec, Catalog,
Catalog Thiết Bị Điện Idec, Catalog Thiết Bị Điện,
Catalog Điện Công Nghiệp Idec, Catalog Điện Công Nghiệp,
http://dienhathe.com,
Chi tiết các sản phẩm khác của Idec tại https://dienhathe.com
Xem thêm các Catalog khác của Idec tại https://dienhathe.info
Để nhận báo giá sản phẩm Idec vui lòng gọi: 0907.764.966
This document provides information on electric equipment including miniature circuit breakers, residual current circuit breakers, and surge protective devices. It includes specifications such as rated current, number of poles, rated voltage, breaking capacity, standards, and dimensions for different product types. Replacement parts and operation status indicators are noted. Product series include BKN, BKH, RKP, BKS, and SP.
Catalog LS, Catalog,
Catalog Thiết Bị Điện LS, Catalog Thiết Bị Điện,
http://dienhathe.com,
Chi tiết các sản phẩm khác của LS tại https://dienhathe.com
Xem thêm các Catalog khác của LS tại https://dienhathe.info
Để nhận báo giá sản phẩm LS vui lòng gọi: 0907.764.966
This document provides information on miniature circuit breakers and residual current devices, including:
- Miniature circuit breakers of types BKP, BKN, and BKH with ratings from 1A to 125A and characteristics curves of B, C, and D.
- Residual current circuit breakers with overcurrent protection of types RKP, RKS, RKS-b, 32KGR, and 32GRh with ratings from 3A to 50A.
- Residual current circuit breakers of types RKN and RKN-b with ratings from 25A to 100A.
- Isolators of type BKD with ratings from 40A to 125A.
It provides specifications
Đang phục vụ cho hơn 30% nhu cầu của Việt nam với mức chất lượng cao nhất của thế giới ( high-end và Standard range). Sản phẩm này cũng đang được bán tại Mỹ, Nhật, Eu, và Trung đông,… Tại Việt nam, từ năm 1998 đến nay, LS đã và đang cung cấp cho hàng ngàn công trình lớn nhỏ tại Việt nam bao gồm các nhà đầu tư Nhật bản, Hàn Quốc, và các nhà đầu tư Việt nam.
This document provides an overview and selection guide for Siemens LV 30 residual current circuit breakers (RCCBs). It lists the standard product range of RCCBs including specifications such as: number of poles, rated currents from 16A to 125A, rated fault currents from 10mA to 1000mA, mounting options, standards compliance, and order numbers. Technical details are also provided on operating voltages, terminals, degree of protection, minimum operating voltages, ambient temperatures, and more.
These units convert a 4-20mA process current input into two identical isolated 4-20mA output signals. Power is obtained from the output loop (sinks current).
For easy troubleshooting, each unit has LEDs and diagnostic test points. Power LEDs help identify output open loop conditions. The precision 10-ohm sense resistor enables monitoring of the output signal without disturbing field wiring.
4-20mA process current inputs are isolated and transmitted as 4-20mA output signals. Each channel operates independently
and is isolated from the others to prevent interaction between channels.
This document provides information on Series datar miniature circuit breakers (MCBs) and earth leakage circuit breakers (ELCBs). It discusses the features, technical specifications, applications, standards, ordering procedures and diagrams of MCBs and ELCBs. The key points covered are the salient features of MCBs including current limiting design, trip-free mechanism, and padlocking facility. It also describes the tripping characteristics of B, C and D type MCBs and their applications. For ELCBs, it highlights their current-operated mechanism, neutral advance mechanism, and protection from electric shocks.
The document summarizes the product offerings of a switchgear plant located in Baddi, including miniature circuit breakers, residual current circuit breakers, distribution boards, and promotional materials. The plant produces a wide range of miniature circuit breakers, residual current circuit breakers, isolators, changeover switches, and distribution boards for domestic and industrial use under various international standards. It also provides promotional materials like catalogues, price lists, leaflets, posters, and danglers for marketing its electrical switchgear products.
Ls catalog thiet bi dien electric products e 1104Dien Ha The
Catalog LS, Catalog,
Catalog Thiết Bị Điện LS, Catalog Thiết Bị Điện,
http://dienhathe.com,
Chi tiết các sản phẩm khác của LS tại https://dienhathe.com
Xem thêm các Catalog khác của LS tại https://dienhathe.info
Để nhận báo giá sản phẩm LS vui lòng gọi: 0907.764.966
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnDien Ha The
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.org
iemens 3VJ molded case circuit breaker (MCCB) brochure provides information on the 3VJ series, which is designed for low-voltage power distribution and protection in industrial and commercial applications. The brochure may contain technical specifications, features, and benefits of the 3VJ series, such as:
Rated current from 100A to 630A
Breaking capacity up to 65kA at 415V AC
Adjustable overload protection and short-circuit protection
Compatibility with various accessories, including auxiliary switches, shunt trips, and undervoltage releases
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.org
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.org
Catalog LS, Catalog,
Catalog Thiết Bị Điện LS, Catalog Thiết Bị Điện,
http://dienhathe.com,
Chi tiết các sản phẩm khác của LS tại https://dienhathe.com
Xem thêm các Catalog khác của LS tại https://dienhathe.info
Để nhận báo giá sản phẩm LS vui lòng gọi: 0907.764.966
This document provides information about Meba's AD22 indicator lamp series. It describes the key features and specifications of various indicator lamp models including voltage ratings, dimensions, colors available, and circuit diagrams. The document aims to introduce customers to Meba's diverse range of high quality indicator lamps that comply with international standards.
AC Contactors come in many forms with varying capacities and features. Unlike a circuit breaker, a contactor is not intended to interrupt a short circuit current. Contactors range from those having a breaking current of several amperes to thousands of amperes and 24 V DC to many kilovolts. The physical size of contactors ranges from a device small enough to pick up with one hand, to large devices approximately a meter (yard) on a side.
A distribution board (also known as panelboard or breaker panel) is a component of an electricity supply system which divides an electrical power feed into subsidiary circuits, while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Normally, a main switch, and in recent boards, one or more residual-current devices (RCD) or residual current breakers with overcurrent protection (RCBO), are also incorporated.
Industrial and multiphase plugs and sockets provide a connection to the electrical mains rated at higher voltages and currents than household plugs and sockets .All from www.meba.net
Rated Current: 6-63A, 1-4Pole, pillar terminal with clamp easy mounting onto 35mm Din rail,thermal or thermal-magnetic operation. , professional circuit breaker manufacture since 1997.(www.meba.net)
MPFIM4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application. These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Meba is an Asian supplier of low voltage electrical components since 1993. They produce the MB-2 series of low-voltage distribution cabinets and the MBXL series of indoor/outdoor low-voltage power distribution boxes. The MB-2 cabinets use a bus bar system and modular components for compact distribution. The MBXL boxes are made of durable materials and use fuse-switch-disconnectors for protection and selective coordination up to 80kA. Both product lines meet international standards and provide high quality, reliable power distribution solutions.
This document provides information about Meba's AD22 indicator lamp series. It describes the key features and specifications of various indicator lamp models including voltage ratings, dimensions, colors available, and circuit diagrams. The document aims to introduce customers to Meba's diverse range of high quality indicator lamps that comply with international standards.
1. MPFIM4
www.mebamfg.com
Residual Current
Circuit Breaker
128
MPFIM4 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MPFIM4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
Specification:
MPFIM4, Residual CurrentDevices for earthleakage detection. It is tobe used in association with miniaturecircuit breakers, itsfunction
is to detectearth leakage currentand open the connected circuit to protect people and equipment, major usedin industrial app lication.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(In): 30, 100, 300, 500mA
Rated residual non-operating current(Ino): 0.5 In
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
Dimensions:
77 0.8
35.60.3
44.5
66
5.5
45
830.8
35.5 0.3
72
66.30.3
36
2. CF-362 Residual Current Circuit Breaker
www.mebamfg.com
Residual Current
Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-362
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
Specification:
CF-362, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is todetect earth leakage current and open theconnected circuit to protect people andequipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-364 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-364
Type: Residual Current Circuit Breaker or Residual Current Device)
Poles Number: 4P
Specification:
CF-364, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage currentand open theconnected circuit toprotect people andequipment , major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-362 CF-364
129
3. www.mebamfg.com
Specification:
Technical parameter:
Specification:
Technical parameter:
Residual Current
Circuit Breaker
CF-462 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-462
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
CF-462, Residual CurrentDevices for earthleakage detection. It is to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage curre nt and open the connected circuit to protect peopleand equipment, majorused in industrialapplication.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-464 Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: CF-464
Type: Residual Current Circuit Breaker or Residual Current Device)
Poles Number: 4P
CF-464, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage current andopen the connectedcircuit to protectpeople and equipment, major used in industri al application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
CF-462 CF-464
130
4. www.mebamfg.com
Residual Current
Circuit Breaker
DZ30L-32 Residual Current Circuit Breaker
Specification:
Technical parameter:
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ30L-32
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: DPN
DZ30L-32(DPN), combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 3KA
Rated current(A): 6, 16, 20, 25, 32A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
DZ47LE-63-2P Residual Current Circuit Breaker
Specification:
Technical parameter:
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ47LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 2 pole MCB + ELCB
DZ47LE-63 2Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up toa maximum short-circuit current 63A. All breaking capacitiescomply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6,16,20,25,32,40,50,63A
Rated leakage operating current(mA): 30,100,300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
131
DZ30L-32 DZ47LE-63-2P
5. M
www.mebamfg.com
Specification:
Technical parameter:
Residual Current
Circuit Breaker
DZ47LE-63-4P Residual Current Circuit Breaker
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: DZ47LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 4 pole MCB + ELCB
DZ47LE-63 4Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
132
DZ47LE-63-4P
M Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: M
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
Specification:
M series Residual Cur rent Devices for earth leakage detection. Itis to beused in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(In): 30, 100, 300, 500mA
Technical parameter:
Rated residual non-operating current(Ino): 0.5 In
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
6. www.mebamfg.com
Residual Current
Circuit Breaker
133
MB089/MB090 Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
Dimensions:
O. OFF
94
35.6
O. OFF
71.2
61.5
76
45
83
MB089/ MB090 4P RCD provide the function of isolation switchingand earth leakageprotection of electricalcircuits. They open a circuit
automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
MB089 MB090
7. www.mebamfg.com
Residual Current
Circuit Breaker
134
MB7L2-63 Residual Current Circuit Breaker
Applications:
MB7L2-63 RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit
automatically in the event of an earth fault between phase and earth and/or netural and earth. Awide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A, 50A, 63A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MB7L4-63 Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A, 50A, 63A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MB7L4-63 RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit
automatically in the event of an earth fault between phase and earth and/or netural and earth. A wide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
MB7L2-63 MB7L4-63
8. MBB8LE-63-1P
www.mebamfg.com
Residual Current
Circuit Breaker
135
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MBACH2 Residual Current Circuit Breaker
MBACH2RCCBprovidethe function ofisolation switching andearth leakage protectionof electrical circuits.Theyopena circuit automatically
in the event of an earth fault between phase and earth and/or neutral and earth. A wide range of current ratings and sensitivities are
available. Suitable for domestic, commercial and industrial applications.
Specification:
Technical parameter:
MBB8LE-63-1P Residual Current Circuit Breaker
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: MBB8LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 1 pole MCB + ELCB
MBB8LE-63 1Pole, combination by mini circuit breaker and leakage. Which protect human from the fault of electric because of over-
current, short circuit, earth fault current. It isself-protecting up to a maximum short-circuit current 63A. All breaking capacities comply
with Standard IEC/EN 61009.
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
MBACH2
9. www.mebamfg.com
Residual Current
Circuit Breaker
136
MBEA-63A Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A, 50A, 63A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MBEA-63A RCCB provide the function of isolation switching and earth leakage protection of electrical circuits. They open a circuit
automatically in the event of an earth fault be tween phase and earth and/or neutral and earth. A wide range of current ratings and
sensitivities are available. Suitable for domestic, commercial and industrial applications.
MBB8LE-63-2P Residual Current Circuit Breaker
Residual current circuit breaker with overload protection(RCBO)
Brand Name: Meba
Model Number: MBB8LE-63
Type: Residual current circuit breaker with overload protection(RCBO)
Poles Number: 2 pole MCB + ELCB
Specification:
MBB8LE-63 2Pole, combination by mini circuit breaker and leakage. Which protect humanfrom the fault of electric because of over-
current, short circuit, earth fault current. It is self-protecting up to a maximum short-circuit current 63A. All breakingcapacities comply
with Standard IEC/EN 61009.
Technical parameter:
Residual current device with overcurrent protection
Combine in residual current device function and MCB over-current protection function
Short circuit capacity: 6KA
Rated current(A): 6, 16, 20, 25, 32, 40, 50, 63A
Rated leakage operating current(mA): 30, 100, 300mA
AC types, B-C characteristic
Modular Din Rail products 35mm.
MBB8LE-63-2P MBEA-63A
10. www.mebamfg.com
Residual Current
Circuit Breaker
Applications:
MBEFI-2/MBEFI-4 Residual Current Circuit Breaker
Residual current circuitbreakers MBEFI areused for protectionagainst indirect touching of parts under voltage, for prevention of lasting
voltage on earthed par ts which should appear because of a defectin the electricalinstallation and for protection against direct conta cts
of parts under voltage in case of I n 30mA. Residual current circuit breakers can beused in TN-S, TN-C, TT and ITnetwork systems
or with other words in all systems where neutral and protective conductor are separated (VDE 0100 Teil 410).
Types - Our programme comprises residual current circuit breakers which are sensitive to alternating residu al current (AC-type) and
residual current circuit breakers which are sensitive to alternating and pulsating direct current (A-type).
For alternating residual current
For alternating and pulsating direct residual current
Short-circuit capacity with back-up fuse
lower temperature limit of application -25 C
VDE 0664, part 1 (up to 80 A)
Selective (time delayed min. 40 ms)
Short time delayed (min. 10 ms)
type A type AC type G type A type AC type S type G
MBEFI2 MBEFI4
MBEFI-2 Specification:
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
0,03
0,03
0,03
0,03
0,03
0,03
0,1
0,1
0,1
0,1
0,1
0,1
0,3
0,3
0,3
0,3
0,3
0,3
0.5
0,5
0,5
0,5
0,5
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
002062521
002062522
002062523
002062524
002062525
002063521
002063522
002063523
002063524
002063525
002063526
002064521
002064522
002064523
002064524
002064525
002064526
002065521
002065522
002065523
002065524
002065525
002062121
002062122
002062123
002062124
002062125
002062126
002063121
002063122
002063123
002063124
002063125
002064121
002064122
002064123
002064124
002064125
002064126
002065121
002065122
002065123
002065124
002065125
229
229
229
244
244
244
223
223
223
227
230
230
223
223
223
227
230
230
223
223
223
227
230
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
1/54
MBEFI-2 type A, MBEFI-2 type AC
In
[A]
I n
[A]
number
of poles code No.A code No.AC
weight
[g]
packaging
[pcs]
MBEFI-2 MBEFI-4
137
11. www.mebamfg.com
Residual Current
Circuit Breaker
MBEFI-2/MBEFI-4 Residual Current Circuit Breaker
MBEFI-2 type G
25
25
40
40
0,03
0,1
0,3
0,1
2
2
2
2
002062722*
002063722*
002062723*
002063723*
220
220
220
220
1/54
1/54
1/54
1/54
In
[A]
I n
[A]
number
of poles code No.AC
weight
[g]
packaging
[pcs]
*The same housing as MBEFI-2 100 A.
* type with N-pole on the left side is also available.
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
100
16
25
40
63
80
0,03
0,03
0,03
0,03
0,03
0,03
0,1
0,1
0,1
0,1
0,1
0,1
0,3
0,3
0,3
0,3
0,3
0,3
0.5
0,5
0,5
0,5
0,5
MBEFI-4 type A, MBEFI-4 type AC
In
[A]
I n
[A]
number
of poles code No.A code No.AC
weight
[g]
packaging
[pcs]
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
002062541
002062542
002062543
002062544
002062545
002062546
002063541
002063542
002063543
002063544
002063545
002063546
002064541
002064542
002064543
002064544
002064545
002064546
002065541
002065542
002065543
002065544
002065545
002062141
002062142
002062143
002062144
002062145
002062146
002063141
002063142
002063143
002063144
002063145
002063146
002064141
002064142
002064143
002064144
002064145
002064146
002065141
002065142
002065143
002065144
002065145
393
393
393
400
407
407
393
393
393
400
407
407
364
364
364
372
372
372
364
364
364
372
372
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
1/27
MBEFI-4 type G
40
40
0,03
0,1
4
4
320
320
1/27
1/27
In
[A]
I n
[A]
number
of poles code No.AC
weight
[g]
packaging
[pcs]
*The same housingas MBEFI-4 100 A.
002062743*
002063743*
MBEFI-4 type S
40
63
0,3
0,3
4
4
400
400
1/27
1/27
In
[A]
I n
[A]
number
of poles code No.AC
weight
[g]
packaging
[pcs]
002064243
002064244
MBEFI-4 Specification:
MBETI also manufactures tripping relaysused in residual current circuit breakers-the range of products and their technical data is available in
technical information published separately.
MBEFI-2 MBEFI-4
138
12. www.mebamfg.com
Residual Current
Circuit Breaker
PFIM-2P
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
Specification:
PFIM-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PFIM
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
PFIM 2P, Residual CurrentDevices for earthleakage detection. It isto be used in associationwith miniature circuitbreakers, its function
is to detect earth leakage current and openthe connected circuit to protect people andequipment, major usedin industrial appli cation.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
MBR2 Residual Current Circuit Breaker
Applications:
Specification:
Standard
Rated voltage(Un)
Rated current(In)
Rated residual operating current(In)
Rated residual non-operating current(I no)
Breaking capacity(A)
Residual current off-time
Operating temperature
IEC61008-1
1Pole+N: 230/240V AC, 3Pole+N: 400/415V AC
10, 16, 20, 25, 32, 40A
30, 100, 300, 500mA
0.5ls n
6000A
0.1s
-5 +55
MBR2 RCCB provide the function of isolat ion switching and earth leakage protection of electrical circuits . They open a circuit automatically
in the event of an earth fault between phase and earth and/or neutral and earth. A wide range of current ratings and sen sitivities are
available. Suitable for domestic, commercial and industrial applications.
MBR2
139
13. www.mebamfg.com
Residual Current
Circuit Breaker
PFIM-40-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PFIM
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
Specification:
PFIM 2P, Residual CurrentDevicesfor earth leakage detection.It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Technical parameter:
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
PFIM-40-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PFIM
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
Specification:
PFIM 4P, Residual CurrentDevices for earthleakage detection. Itis to beused in associationwith miniature circuitbreakers, its function
is to detect earth leakage current and open theconnected circuit toprotect people andequipment, major used in industrial applicati on.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
PFIM-40-2P PFIM-40-4P
Technical parameter:
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
140
14. www.mebamfg.com
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCCB-OLL4-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCCB-OLL4-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL4, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCCB-OLL4-2P RCCB-OLL4-4P
141
15. Technical parameter:
www.mebamfg.com
Specification:
Technical parameter:
Specification:
Residual Current
Circuit Breaker
RCD-FIN-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: FIN
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
FIN 2P, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-FIN-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: FIN
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
FIN, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function is
to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industr ial applicati on.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-FIN-2P RCD-FIN-4P
142
16. www.mebamfg.com
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-ID-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: ID
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
ID 2P, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-ID-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: ID
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
ID, Residual Current Devices for earth leakage det ection. It is to be used in association with miniature circuit breakers, its function is
to detect earth leakag e current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-ID-2P RCD-ID-4P
143
17. Technical parameter:
www.mebamfg.com
Specification:
Technical parameter:
Specification:
Residual Current
Circuit Breaker
RCD-MNL-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MNL
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
MNL, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-MNL-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: MNL
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
MNL, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-MNL-2P RCD-MNL-4P
144
18. www.mebamfg.com
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-NFIN Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: NFIN
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
NFIN, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL1-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL1
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL1, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-NFIN RCD-OLL1-2P
145
19. Specification:
OLL18-63, replace of DZ18-20, Residual Current Devic es for
earth leakage detection. Itis tobe usedin associationwith miniature
circuit breakers, its function is todetect earth leakagecurrent and
open the connectedcircuit to protect people and equipment, major
used in industrial application. These devices are designed to meet
the Earth LeakageProtection Standards of the IEC: IEC/EN 61008.
Technical parameter:
www.mebamfg.com
Specification:
Technical parameter:
Residual Current
Circuit Breaker
RCD-OLL1-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL1
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL1-4P, Residual CurrentDevices for earthleakage detection. It is to be usedin association with miniaturecircuit breakers, itsfunction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL18-63 Residual Current Circuit Breaker
Brand Name: Meba
Model Number: OLL18-63
Type: Residual Current CircuitBreaker or ResidualCurrent Device
Release Type:Electromagnetic
Electromagnetic
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
Dimensions(mm):
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
N 2
N 1
26.3 0.3
62 0.8
740.8
82.50.8
61 0.8
RCD-OLL1-4P RCD-OLL18-63
146
20. www.mebamfg.com
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-OLL2-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL2, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL2, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-2P RCD-OLL2-4P
147
21. www.mebamfg.com
Specification:
Technical parameter:
Residual Current
Circuit Breaker
RCD-OLL2-N-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2-N
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL2-N, Residual Current Devices for earth leakage detection. It is tobe used inassociation with miniaturecircuit breakers, itsfunction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-N-4P Residual Current Circuit Breaker
Specification:
Technical parameter:
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL2-N
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL2-N, Residual Current Devic es for earth leakage detection. It is tobe used inassociation with miniaturecircuit breakers, itsfunction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 6KA
RCD-OLL2-N-2P RCD-OLL2-N-4P
148
22. www.mebamfg.com
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-OLL7-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL7, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL7, Residual Current Devices for earth leakage detection. It is to be used in association with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole devices Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-2P RCD-OLL7-4P
149
23. www.mebamfg.com
Specification:
Technical parameter:
Residual Current
Circuit Breaker
Specification:
Technical parameter:
RCD-OLL7-3-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-3
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL7-3, Resid ual Current Devices forearth leakage detection. It is tobe used inassociati on with miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-3-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-3
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL7-3, Residual Current Devices for earth leakag e detection. It is to beused in associationwith miniature circuit breakers, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-3-2P RCD-OLL7-3-4P
150
24. www.mebamfg.com
Residual Current
Circuit Breaker
Specification:
Technical parameter:
Specification:
Technical parameter:
RCD-OLL7-4-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 2P
OLL7-4, Residual Current Devices forearth leakage detection.It is tobe used in associat ion with miniature circuit breakers, its fun ction
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-4-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: OLL7-4
Type: Residual Current Circuit Breaker or Residual Current Device
Poles Number: 4P
OLL7-4, Residual CurrentDevices for earthleakage detection. It isto be usedin association withminiatur e circuit breaker s, its function
is to detect earth leakage current and open the connected circuit to protect people and equipment, major used in industrial application.
These devices are designed to meet the Earth Leakage Protection Standards of the IEC: IEC/EN 61008.
Electromagnetic and Electronic type
70mm wide for 4 pole devices Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
RCD-OLL7-4-2P RCD-OLL7-4-4P
151
25. Technical parameter:
Electromagnetic and Electronic type
35mm wide for 2 pole Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 2pole, 230V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
www.mebamfg.com
Residual Current
Circuit Breaker
RCD-PF-2P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Specification:
Brand Name: Meba
Model Number: PF-2P
Type: ResidualCurrent Circuit Breakeror Residual Current Device
Poles Number: 2P
Flexibility:
Model PF, four pole, Residual Current Devices for earth leakage
detection to thestandards of IEC.It is tobe used inassociation with
miniature circuit breakers, its function is to detect earth leakage
current and open the connected circuit to protect people and
equip ment, major used in industrial application.These devicesare
designed to meet the Earth Leakage Protection Standardsof the
IEC: IEC/EN 61008.
With a wide range of currents and rated trip current available, the appropriate level of protection can be chosen for specific applications
for either personnel or equipment protection.
Specification:
Flexibility:
Technical parameter:
RCD-PF-4P Residual Current Circuit Breaker
Earth Leakage Circuit Breaker(ELCB), Residual Current Device(RCD), Residual Current Circuit Breaker(RCCB)
Brand Name: Meba
Model Number: PF-4P
Type: Residual CurrentCircuit Breaker orResidual Current Device
Poles Number: 4P
Model PF, four pole, Residual Current Devices for earth leakage
detection to thestandards of IEC.It is tobe used inassociation with
miniature circuit breakers, its function isto detect earth leakage
current and open the connected circuit to protect people and
equipment , major used in industrial application.These devicesare
designed to meet the Earth Leakage Protection Standards of the
IEC: IEC/EN 61008.
With a wide range of currents andrated trip current available, the
appropriate level ofprotection can bechosen for specificapplications
for either personnel or equipment protection.
Electromagnetic and Electronic type
70mm wide for 4 pole devices Din Rail installation.
Standsrd: IEC1008/EN61008
Rated Voltage(Un): 4pole, 400V AC
Rated Current(In): 25, 40, 63A
Rated residual operating current(I n): 30, 100, 300, 500mA
Rated residual non-operating current(I no): 0.5 I n
Residual current off-time: 0.1s
Minimum value of rated breaking capacity(lm): 630A
Rated conditional short-circuit capacity (lnc): 10KA
1 N
2 N
H
1 3 5 N
2 4 6 N
H
Operation Principle Fig:
Dimensions(mm):
77 0.8
35.60.3
44.5
66
5.5
45
83.2
66.30.3
35.3 0.3
7236
RCD-PF-2P RCD-PF-4P
152