This document summarizes a presentation on analyzing furan compounds in transformer oil to assess the condition of cellulosic insulation. It discusses how furan derivatives are extracted from oil samples using liquid-liquid extraction or solid phase separation, then analyzed using high performance liquid chromatography. Case studies are presented showing furan test results from various transformers, with levels classified as low, medium, or high. Furan levels above 2500 ppb indicate the need to rewind or replace solid insulation. The document concludes that regular oil treatment helps maintain transformer condition and insulation parameters.