FIRE PROTECTION SYSTEM
AX 272 F
c.) PRE-ACTION SYSTEM
(For Electrical Substation)
b.) STANDPIPE SYSTEM
a.) SPINKLER SYSTEM 4 ZONE
SPRINKLER SYSTEM
4 ZONES
ALARM VALVE STATION
STANDPIPE SYSTEM
CLASS III SYSTEM IS
PROVIDED
Class III Systems Provided 1 ½”
hose stations to supply water for use
by trained building occupants and
2½” hose connections to supply a
larger volume of water for use by
Fire Department.
FIRE HOSE STATION
ADVANTAGES
• Quick Suppression
• One Person Operation
• Minimal Water Damage
• Occupant Safety and Rescue
TYPICAL CLASS III FIRE HOSE STATION
OPERATION OF FIRE
HOSE STATIONS
1. Open valve completely
2. Pull hose entirely off rack
3. Open nozzle
THREE STEPS FOR OPERATION
1. Open valve completely.
2. Pull hose entirely off rack
(or else water will not flow)
3. Open nozzle. Water will flow when hose is
entirely off rack & nozzle is open.
PREACTION SYSTEM
FOR
ELECTRICAL SUBSTATION
• Preaction System Control Panel
• Smoke detectors
• Manual Pull Station (Electric)
• Alarm Bell
• Sounder cum flasher
PREACTION SYSTEM
COMPONENTS
• Deluge Valve w/ Double Interlock
Trim
• Isolation Valve
• Pressure Switch (Air)
• Pressure Switch (Water)
• Air Compressor
• Air Maintenance Device
PREACTION SYSTEM
COMPONENTS
PREACTION SYSTEM
SEQUENCE OF OPERATION
Smoke Detectors (Zone-1) and Pressure Switch
(Zone-2) Monitoring the System Air Pressure in
the piping are wired in a cross zoned
configuration
Activation of smoke detector or operation
of a sprinkler causes following.
• A visual indication on the System Control
Panel
• Audible alarm from bell
• Send “Fire” indication to the Fire Alarm
System
PREACTION SYSTEM
SEQUENCE OF OPERATION
PREACTION SYSTEM
SEQUENCE OF OPERATION
Activation of smoke detector & operation
of a sprinkler causes following.
• Visual indications on the System Control Panel
• Audible alarm from bell & sounder cum flasher
• Deluge valve operates
• Water flows in to the system piping and
discharges through the ‘opened’ sprinkler.
Manual Operation
• System can be operated manually by operating the
Pull Station (Electric or Hydraulic)
• Visual indications on the System Control Panel
• Audible alarm from bell & sounder cum flasher
• Deluge valve operates
• Water flows in to the system piping (if sprinkler is
not activated, piping will be filled with water)
PREACTION SYSTEM
SEQUENCE OF OPERATION
Operation of Air Compressor
Air compressor maintains constant air pressure
in the system piping.
PREACTION SYSTEM
SEQUENCE OF OPERATION

Fire protection system ax 272 f

  • 1.
    FIRE PROTECTION SYSTEM AX272 F c.) PRE-ACTION SYSTEM (For Electrical Substation) b.) STANDPIPE SYSTEM a.) SPINKLER SYSTEM 4 ZONE
  • 2.
  • 3.
  • 4.
  • 5.
    CLASS III SYSTEMIS PROVIDED Class III Systems Provided 1 ½” hose stations to supply water for use by trained building occupants and 2½” hose connections to supply a larger volume of water for use by Fire Department.
  • 6.
    FIRE HOSE STATION ADVANTAGES •Quick Suppression • One Person Operation • Minimal Water Damage • Occupant Safety and Rescue
  • 7.
    TYPICAL CLASS IIIFIRE HOSE STATION
  • 8.
    OPERATION OF FIRE HOSESTATIONS 1. Open valve completely 2. Pull hose entirely off rack 3. Open nozzle THREE STEPS FOR OPERATION
  • 9.
    1. Open valvecompletely.
  • 10.
    2. Pull hoseentirely off rack (or else water will not flow)
  • 11.
    3. Open nozzle.Water will flow when hose is entirely off rack & nozzle is open.
  • 12.
  • 13.
    • Preaction SystemControl Panel • Smoke detectors • Manual Pull Station (Electric) • Alarm Bell • Sounder cum flasher PREACTION SYSTEM COMPONENTS
  • 14.
    • Deluge Valvew/ Double Interlock Trim • Isolation Valve • Pressure Switch (Air) • Pressure Switch (Water) • Air Compressor • Air Maintenance Device PREACTION SYSTEM COMPONENTS
  • 16.
    PREACTION SYSTEM SEQUENCE OFOPERATION Smoke Detectors (Zone-1) and Pressure Switch (Zone-2) Monitoring the System Air Pressure in the piping are wired in a cross zoned configuration
  • 17.
    Activation of smokedetector or operation of a sprinkler causes following. • A visual indication on the System Control Panel • Audible alarm from bell • Send “Fire” indication to the Fire Alarm System PREACTION SYSTEM SEQUENCE OF OPERATION
  • 18.
    PREACTION SYSTEM SEQUENCE OFOPERATION Activation of smoke detector & operation of a sprinkler causes following. • Visual indications on the System Control Panel • Audible alarm from bell & sounder cum flasher • Deluge valve operates • Water flows in to the system piping and discharges through the ‘opened’ sprinkler.
  • 19.
    Manual Operation • Systemcan be operated manually by operating the Pull Station (Electric or Hydraulic) • Visual indications on the System Control Panel • Audible alarm from bell & sounder cum flasher • Deluge valve operates • Water flows in to the system piping (if sprinkler is not activated, piping will be filled with water) PREACTION SYSTEM SEQUENCE OF OPERATION
  • 20.
    Operation of AirCompressor Air compressor maintains constant air pressure in the system piping. PREACTION SYSTEM SEQUENCE OF OPERATION