SlideShare a Scribd company logo
The International Journal Of Engineering And Science (IJES)
|| Volume || 2 || Issue || 12 || Pages || 14-18 || 2013 ||
ISSN (e): 2319 – 1813 ISSN (p): 2319 – 1805

The Restricted Earth Fault Relay Operation: Impact of Current
Transformer Knee Point Voltages
Udoh, Benjamin E.
Department of Electrical/Electronic Engineering Federal Polytechnic Mubi Adamawa State, Nigeria

-------------------------------------------------------ABSTRACT--------------------------------------------------In this paper, the characteristic of current transformer (CT) magnetization curves are used to determine the
performance of restricted earth fault (REF) relays. This study was carried out at the150MVA 330/132/33kV
Gombe transmission substation. This is based on the field data obtained for the neutral current transformers
(NCTs) servicing the 150 MVA 330/132/33kV and 15MVA 132/33kV power transformers at the substation. From
the study, the knee-point voltages from the CT magnetization curves justify the voltage settings of the restricted
earth fault relays.

Keywords: Magnetization curve, Neutral current transformer, Restricted earth fault
--------------------------------------------------------------------------------------------------------------------------Date of Submission: 30 November 2013

Date of Acceptance: 28 December 13

--------------------------------------------------------------------------------------------------------------------------I.
INTRODUCTION
The magnetization currents of current transformers usually affect the overall setting of a protection
system. The effect may not be significant in the case of over current relays, but the effect can be seen in earth
fault relays and unit protection systems where large number of current transformers are connected together.
Because of the low setting of the restricted earth fault (REF) scheme the effect of current transformer (CT)
magnetization current is easily pronounced in the operation of its relays [1]. It is a well known fact that CT core
saturation is brought about by CT magnetization current on application of a voltage, when such voltage exceeds
its knee point value. Hence when considering the performance to be expected from a given CT, the exciting
current can be measured at various values of EMF. For this reason it is usually more convenient to apply a
varying voltage to the secondary winding, the primary winding being open circuited. Fig. 1 shows a typical
relationship. The point K on the curve is called the ‘Knee Point’, and is defined as the point in which an increase
of 10% in the exciting voltage of rated frequency produces an increase of 50% in the exciting current [2]. From
the curve in Fig. 1 point ‘A’ is known as the Ankle Point and the linear portion of the curve is between points
‘A’ and ‘K’.

V

Figure 1: Typical CT Magnetization Curve

www.theijes.com

The IJES

Page 14
The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages
The restricted earth fault (REF) protection scheme refers to the differential protection of transformers
against ground (earth) fault. It is called “restricted” because its zone of protection is limited only to the windings
of the transformer. The restricted earth fault protection scheme is designed to take care of internal earth fault on
transformer windings, which if omitted could cause the windings of such transformer to be damaged in the event
of such fault. Since power transformers are one of the most important and most expensive components of
transmission and distribution networks, it is very essential to prevent a scenario where this piece of equipment is
being put out of service. If such an event occurs, the implication will be long period of power outage which
according to [3] will generate unpleasant situations such as property loss and business disruption leading to loss
orders, damaged to perishable goods and inventories for businesses. Since the issue of lack of adequate
restricted earth fault for power transformer protection cannot be compromised, the REF relay must be made to
operate satisfactorily by ensuring adequate setting of the relay voltage. The relay voltage must be made to fall
within the linear portion of the CT magnetization curves for proper operation of the relays. In this regard, [4]
pointed out that to ensure satisfactory operation of the restricted earth fault relay under internal fault conditions,
the CT knee point voltage should not be less than twice the relay voltage setting. The relay will never operate
with the required speed if the knee point voltage is just in excess of the relay voltage setting and not double the
value at least [5]. The CT will normally transform the fault current of the electrical power system for operation
of the protection relays connected to the secondary of that CT. If the core of the CT becomes saturated at a
lower value of primary current, as in the case of metering CTs, the system fault will not reflect properly to the
secondary terminals, which may cause the relays to remain inoperative even when the fault level of the power
system is large enough. That is why the core of the protection CT is made in such a way that the saturation level
of that core must be high enough, but still with a limit that is not too high otherwise, total transformation of
primary current during huge fault may badly damage the protection relays.
The restricted earth fault (REF) protection schemes are particularly noted for their high speed of
operation; hence they are readily applied in the protection of high voltage systems where fast fault clearing is a
premium. This is made possible by the use of an instantaneous attracted armature type of relay. An internal earth
fault within a transformer could cause serious damage to the system and this has to be cleared instantaneously
[6]. Also high speed fault clearing is particularly beneficial for faults near large concentrations of generation and
long intertie lines to remote sources of generation. This is so because fault causes strong angular acceleration to
nearby generators, which in turn causes a reduction in plant output due to voltage suppression during fault [7].
Hence the knee point voltages of CTs servicing the REF relays protecting high voltage power transformers
should be of higher values, which must be multiples of the relay voltage setting and must be carefully chosen so
that the relay could function adequately in clearing its fault speedily. With high speed protection, it is desirable
that the transformer should not saturate when carrying maximum current caused by a fault at the critical point of
measurement. Where this is not possible, saturation would cause a reduction in the secondary current and
therefore reduces the reach of the instantaneous relay [8].

II.

RESEARCH METHOD AND ANALYSIS

The magnetization data for this study were obtained from the record of injection tests of the neutral
current transformers (NCTs) servicing the two 150MVA 330/132/33kV and the two 15MVA 132/33kV power
transformer at the substation under study. The data are presented in Tables (1) to (4). They were analyzed using
an engineering software programme known as Micro cal – Origin 5.0 adapted for power system simulation.
2.1 Data Analysis
The principle of the high impedance (REF) scheme is applied, and to do so the following assumptions are made.
1. One current transformer (or set of it) completely saturates and ceases to transform any part of the
primary fault current since its excitation impedance is negligible.
2. The whole of the primary fault current is perfectly transformed by the remaining current transformers.
3. The resistance of the secondary winding of the saturated current transformer together with the leads
connecting it constitutes the only burden in parallel with the relay.
Consistent with the above assumptions, the maximum voltage across the relay is calculated using:
VR
Where:

=

If (RCT + 2RL)

If
RCT
RL

=
=
=

Maximum through fault secondary current
CT secondary winding resistance
Maximum lead resistance from CT to the relay circuit terminals

www.theijes.com

(1)

The IJES

Page 15
The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages
In order to ensure satisfactory operations of the relay under internal fault conditions the CT knee point
voltage should not be less than twice the relay voltage setting, thus:
VK
=
2VR
(2)
Where:

VR

=

Relay voltage setting

The values of the knee point voltages are shown in Table 7 under the column “Calculated Value”.

III.

RESULTS AND DISCUSSIONS

Table 7 shows the relay voltage settings for the various power transformers and their corresponding
knee point voltages based on equation (2). The Table shows the calculated and the actual values at the
substation. The actual values are the minimum allowable setting values of the relays, in which case the values
could be increased to meet the local condition to which the relays are operational. For example, the actual value
of knee point voltage of 200V for the relay voltage setting of 100V as against 40V for the relay voltage of 20V
(calculated value) with respect to the 330/132/33kV power transformers is practically chosen by the substation
under study, as a means of preventing system mal-operation when fault occur outside the protected zone. This
observation is in order because one of the benefits of the high impedance restricted earth fault relay operation, is
the ability for the system to maintain stability when the voltage setting of the relay is greater than the maximum
voltage which can appear under a given through fault condition [9, 10].
Figs. 2 to 5 give the magnetization curves for the neutral current transformers servicing the REF relays
at the substation. The curves give a true picture of the magnetization characteristics from which the knee point
voltages are estimated. From the magnetization curve of Fig. 2, the knee point voltage is about 450V as against
the calculated value of 200V in Table 7. This knee point voltage of 450V estimated from the curve is a preferred
value than the 200V calculated directly from equation (2), and gives a higher multiple of the 100V relay voltage
setting. This shows that the performance of the neutral current transformer servicing the REF relay protecting
the 150MVA 330/132/33kV power transformer is good because the 100V relay setting falls within the linear
portion of the CT magnetization curve. From this it is quite certain that the neutral current transformer (NCT)
will never get saturated in the event of any through fault condition or when there is an internal earth fault [8].
All the values of the neutral current transformers (NCTs) knee point voltages as estimated from the
magnetization curves of Figs 2 to 5 are presented in Table 7. From the Table, the knee point voltage of the NCT
servicing the REF relay protecting transformer T2A is lower than the rest. It is on record that the windings of
that particular transformer were damaged some few years ago as a result of an inadequate restricted earth fault
protection, which plunged the whole of the North East region into total darkness for a period of six (6) months.
The whole set was replaced by the end of that year. It was the transformer failure that prompted this study.
It should be noted that the estimated values of the knee point voltages from the magnetization curves
give the actual operational condition of the neutral current transformers (NCTs) at the substation. They also
provide useful guides into the efficient operation of the REF relays in terms of speed [5]. On the other hand, the
calculated values of the knee point voltages directly from the formula as presented in this paper are used as
checks to determine the reliabilities of the estimated values from the curves. They do not describe the operating
condition of the NCTs.

IV.

CONCLUSION

The operational abilities of relays are sometimes affected by the magnetization characteristics of the
CTs servicing such relays. In this study, the knee point voltages that were determined from the magnetization
characteristics of the neutral current transformers have been found to be quite adequate in guaranteeing effective
operation of the restricted earth fault relays. This is so because the neutral current transformers have favourable
linear portion in their magnetization characteristics, which is a necessary requirement in the proper operation of
the relays, especially when it has to do with high voltage power systems. From the observation made in this
study, it will be safe to recommend that NCTs with high value knee point voltages should always be used to
service REF relays protecting high voltage power systems.

www.theijes.com

The IJES

Page 16
The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages
Table 1: Magnetization Data for T1A 150MVA 330/132/33kV Transformer NCT
Slated
Voltage
(V)
Neutral
Current
(mA)

Neutral
REF
CT

50

100

150

200

220

240

260

1.82

3.00

4.00

5.00

5.20

5.50

6.00

Table 2: Magnetization Data for T2A 150MVA 330/132/33kV Transformer NCT
Slated Voltage

(V)
50

100

150

200

220

240

260

1.75

Neutral
REF
CT

2.50

3.25

4.25

4.50

5.00

5.50

Neutral Current (mA)

Table 3: Magnetization Data for T1 15MVA 132/33kV Transformer NCT
Slated Voltage (V)
50

100

150

200

220

233

4.00

Neutral REF CT

7.00

9.75

12.25

13.25

14.00

Neutral Current (mA)

Table 4: Magnetization Data for T2 15MVA 132/33kV Transformer NCT
Slated Voltage (V)
50

100

150

200

220

233

5.00

Neutral REF CT

9.00

12.75

16.00

17.40

18.30

Neutral Current (mA)

Table 5: 150MVA 330/132/33kV Power Transformer Data
Secondary winding resistance (RCT)

5.8 Ohms

Maximum lead resistance (RL) from CT to the relay tapping point

0.54 Ohms

Percentage reactance (X)

11.53%

Current Transformer ratio

800/1A

Type: Star/Delta/Star

Table 6: 15MVA 132/33kV Power Transformer Data
Secondary winding resistance (RCT)

2.3 Ohms

Maximum lead resistance (RL) from CT to the relay tapping point

0.4 Ohms

Percentage reactance (X)

5.17%

Current Transformer ratio

600/1A

Type: Star/Delta

Table 7: Results of NCTs Knee Point Voltages Associated with the Power Transformers
Power
Transformer

T1A
T2A
T1
T2

www.theijes.com

Calculated Value
REF Relay
Knee Point
Voltage (V)
Voltage (V)
20
20
15
15

Actual Value
REF Relay
Knee Point
Voltage (V)
Voltage (V)

40
40
30
30

100
100
-

The IJES

200
200
-

NCT Knee
Point Voltage
From Curve (V)
450
280
400
480

Page 17
The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages

Figure 2: Magnetization curve for neutral
CT of transformer T1A

Figure 4: Magnetization curve for neutral
CT of transformer T1

Figure 3: Magnetization curve for neutral
CT of transformer T2A

Figure 5: Magnetization curve for neutral
CT of transformer T2

REFERENCES
[1]

[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]

Udoh, B. E., Evaluation of Restricted earth fault protection scheme for power transformers at Gombe
Transmission substation, unpublished M. Eng thesis, Abubakar Tafawa Belewa university, Bauchi – Nigeria
2002.
Electricity Training Association, Power system protection, vol. 1 (Peter Peregrinus Limited, 1995).
Campbell, Richard J., Weather related power outages and electric system resiliency, Congressional research
service report for United States congress, August 2012.
GEC Measurements, High stability circulating current relay (General Electric Company Ltd, England, 1982).
Davis, T., Protection of industrial power systems (Pergamos Press Ltd, 1984).
NEPA, Protection of transformer (NEPA zonal training center, Jos – Nigeria, 1998).
Berglund, R. O. et al, One cycle fault interruption at 500kV: system benefits and breaker design, IEEE transaction
On PAS, 93(5), 1974.
Cooper, W. F. and Jones, D. A. D., Electric safety engineering (3rd ed., Newness, 1993).
Franklin, A. C. and Franklin, D. P., The J and P Transformer book (11th ed., Butterworths, 1983).
Wright, A. and Christopoulos, C., Electric power system protection (Wiley and Sons, 1993).

www.theijes.com

The IJES

Page 18

More Related Content

What's hot

FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
Dr. Rohit Babu
 
1 transmission
1 transmission1 transmission
1 transmission
pradhuman deolia
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
ABHISHEK RAI
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
Panneerselvam Rathinam
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
michaeljmack
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Muhd Hafizi Idris
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
ijtsrd
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
michaeljmack
 
Ppt of current transformer
Ppt of current transformerPpt of current transformer
Ppt of current transformer
ROOPAL PANCHOLI
 
Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...
Shilpa Shukla
 
ijre paper
ijre paperijre paper
ijre paperNithin S
 
Design of substation
Design of substationDesign of substation
Design of substation
SayanSarkar55
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
Editor IJMTER
 
Introduction
IntroductionIntroduction
Introduction
jawaharramaya
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
D Målîk
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
Dr. Rohit Babu
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
Power System Operation
 
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
IDES Editor
 

What's hot (20)

FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
1 transmission
1 transmission1 transmission
1 transmission
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Ppt of current transformer
Ppt of current transformerPpt of current transformer
Ppt of current transformer
 
Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...Transformer protection from inrush currents: Discrimination of internal fault...
Transformer protection from inrush currents: Discrimination of internal fault...
 
ijre paper
ijre paperijre paper
ijre paper
 
Design of substation
Design of substationDesign of substation
Design of substation
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
Introduction
IntroductionIntroduction
Introduction
 
Fi3110651072
Fi3110651072Fi3110651072
Fi3110651072
 
Short circuit followup[1]
Short circuit followup[1]Short circuit followup[1]
Short circuit followup[1]
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
Characteristics Analysis of Voltage Sag in Distribution System using RMS Volt...
 

Viewers also liked

C0324011015
C0324011015C0324011015
C0324011015
theijes
 
H03202051073
H03202051073H03202051073
H03202051073
theijes
 
F021203036039
F021203036039F021203036039
F021203036039
theijes
 
G0324036043
G0324036043G0324036043
G0324036043
theijes
 
I03202074078
I03202074078I03202074078
I03202074078
theijes
 
A0331001008
A0331001008A0331001008
A0331001008
theijes
 
J03202079086
J03202079086 J03202079086
J03202079086
theijes
 
F03302045050
F03302045050F03302045050
F03302045050
theijes
 
E021203026035
E021203026035E021203026035
E021203026035
theijes
 
A03210106
A03210106A03210106
A03210106
theijes
 
D021201031040
D021201031040D021201031040
D021201031040
theijes
 
C021201024030
C021201024030C021201024030
C021201024030
theijes
 
D03310019025
D03310019025D03310019025
D03310019025
theijes
 
B032107011
B032107011B032107011
B032107011
theijes
 
I021201065070
I021201065070I021201065070
I021201065070
theijes
 
A02120201010
A02120201010A02120201010
A02120201010
theijes
 
H03302058066
H03302058066H03302058066
H03302058066
theijes
 
C03202012017
C03202012017C03202012017
C03202012017
theijes
 
G032030056067
G032030056067G032030056067
G032030056067
theijes
 

Viewers also liked (19)

C0324011015
C0324011015C0324011015
C0324011015
 
H03202051073
H03202051073H03202051073
H03202051073
 
F021203036039
F021203036039F021203036039
F021203036039
 
G0324036043
G0324036043G0324036043
G0324036043
 
I03202074078
I03202074078I03202074078
I03202074078
 
A0331001008
A0331001008A0331001008
A0331001008
 
J03202079086
J03202079086 J03202079086
J03202079086
 
F03302045050
F03302045050F03302045050
F03302045050
 
E021203026035
E021203026035E021203026035
E021203026035
 
A03210106
A03210106A03210106
A03210106
 
D021201031040
D021201031040D021201031040
D021201031040
 
C021201024030
C021201024030C021201024030
C021201024030
 
D03310019025
D03310019025D03310019025
D03310019025
 
B032107011
B032107011B032107011
B032107011
 
I021201065070
I021201065070I021201065070
I021201065070
 
A02120201010
A02120201010A02120201010
A02120201010
 
H03302058066
H03302058066H03302058066
H03302058066
 
C03202012017
C03202012017C03202012017
C03202012017
 
G032030056067
G032030056067G032030056067
G032030056067
 

Similar to C0212014018

IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET Journal
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET Journal
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
jawaharramaya
 
12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)
IAESIJEECS
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
Vivek Arun
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution network
megala venkatesan
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
Ritesh Verma
 
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
IJAPEJOURNAL
 
Newly fault-tolerant indirect vector control for traction inverter
Newly fault-tolerant indirect vector control for traction inverterNewly fault-tolerant indirect vector control for traction inverter
Newly fault-tolerant indirect vector control for traction inverter
International Journal of Power Electronics and Drive Systems
 
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
IRJET Journal
 
Power Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series CompensationPower Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series Compensation
IJMER
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Premier Publishers
 
pptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfpptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdf
Sunny268892
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
siddharam kantoli
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
SultanAlSaiari1
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017
Dipen Kantariya
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
IJERA Editor
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
IJERA Editor
 
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET Journal
 
R01043105113
R01043105113R01043105113
R01043105113
IOSR Journals
 

Similar to C0212014018 (20)

IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET-  	  Design a Fuzzy Distance Relay Including STATCOM EffectsIRJET-  	  Design a Fuzzy Distance Relay Including STATCOM Effects
IRJET- Design a Fuzzy Distance Relay Including STATCOM Effects
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)12 16134 paper 064 ijeecs(edit)
12 16134 paper 064 ijeecs(edit)
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution network
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
Impact of Thyristor Controlled Series Capacitor Insertion on Short-circuit Ca...
 
Newly fault-tolerant indirect vector control for traction inverter
Newly fault-tolerant indirect vector control for traction inverterNewly fault-tolerant indirect vector control for traction inverter
Newly fault-tolerant indirect vector control for traction inverter
 
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
Simulation of H6 full bridge Inverter for grid connected PV system using SPWM...
 
Power Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series CompensationPower Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series Compensation
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
 
pptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdfpptonprotectionofpowertransformers-161020085118 (1).pdf
pptonprotectionofpowertransformers-161020085118 (1).pdf
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
 
R01043105113
R01043105113R01043105113
R01043105113
 

Recently uploaded

Enterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdfEnterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdf
KaiNexus
 
Skye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto AirportSkye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto Airport
marketingjdass
 
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
BBPMedia1
 
Global Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdfGlobal Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdf
Henry Tapper
 
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptxCADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
fakeloginn69
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
HumanResourceDimensi1
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Lviv Startup Club
 
Digital Transformation in PLM - WHAT and HOW - for distribution.pdf
Digital Transformation in PLM - WHAT and HOW - for distribution.pdfDigital Transformation in PLM - WHAT and HOW - for distribution.pdf
Digital Transformation in PLM - WHAT and HOW - for distribution.pdf
Jos Voskuil
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
Nicola Wreford-Howard
 
What is the TDS Return Filing Due Date for FY 2024-25.pdf
What is the TDS Return Filing Due Date for FY 2024-25.pdfWhat is the TDS Return Filing Due Date for FY 2024-25.pdf
What is the TDS Return Filing Due Date for FY 2024-25.pdf
seoforlegalpillers
 
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
BBPMedia1
 
Discover the innovative and creative projects that highlight my journey throu...
Discover the innovative and creative projects that highlight my journey throu...Discover the innovative and creative projects that highlight my journey throu...
Discover the innovative and creative projects that highlight my journey throu...
dylandmeas
 
Putting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptxPutting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptx
Cynthia Clay
 
3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx
tanyjahb
 
Unveiling the Secrets How Does Generative AI Work.pdf
Unveiling the Secrets How Does Generative AI Work.pdfUnveiling the Secrets How Does Generative AI Work.pdf
Unveiling the Secrets How Does Generative AI Work.pdf
Sam H
 
Introduction to Amazon company 111111111111
Introduction to Amazon company 111111111111Introduction to Amazon company 111111111111
Introduction to Amazon company 111111111111
zoyaansari11365
 
Filing Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed GuideFiling Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed Guide
YourLegal Accounting
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
seri bangash
 
BeMetals Presentation_May_22_2024 .pdf
BeMetals Presentation_May_22_2024   .pdfBeMetals Presentation_May_22_2024   .pdf
BeMetals Presentation_May_22_2024 .pdf
DerekIwanaka1
 
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdfSearch Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Arihant Webtech Pvt. Ltd
 

Recently uploaded (20)

Enterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdfEnterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdf
 
Skye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto AirportSkye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto Airport
 
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
 
Global Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdfGlobal Interconnection Group Joint Venture[960] (1).pdf
Global Interconnection Group Joint Venture[960] (1).pdf
 
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptxCADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
 
Digital Transformation in PLM - WHAT and HOW - for distribution.pdf
Digital Transformation in PLM - WHAT and HOW - for distribution.pdfDigital Transformation in PLM - WHAT and HOW - for distribution.pdf
Digital Transformation in PLM - WHAT and HOW - for distribution.pdf
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
 
What is the TDS Return Filing Due Date for FY 2024-25.pdf
What is the TDS Return Filing Due Date for FY 2024-25.pdfWhat is the TDS Return Filing Due Date for FY 2024-25.pdf
What is the TDS Return Filing Due Date for FY 2024-25.pdf
 
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
 
Discover the innovative and creative projects that highlight my journey throu...
Discover the innovative and creative projects that highlight my journey throu...Discover the innovative and creative projects that highlight my journey throu...
Discover the innovative and creative projects that highlight my journey throu...
 
Putting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptxPutting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptx
 
3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx3.0 Project 2_ Developing My Brand Identity Kit.pptx
3.0 Project 2_ Developing My Brand Identity Kit.pptx
 
Unveiling the Secrets How Does Generative AI Work.pdf
Unveiling the Secrets How Does Generative AI Work.pdfUnveiling the Secrets How Does Generative AI Work.pdf
Unveiling the Secrets How Does Generative AI Work.pdf
 
Introduction to Amazon company 111111111111
Introduction to Amazon company 111111111111Introduction to Amazon company 111111111111
Introduction to Amazon company 111111111111
 
Filing Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed GuideFiling Your Delaware Franchise Tax A Detailed Guide
Filing Your Delaware Franchise Tax A Detailed Guide
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
 
BeMetals Presentation_May_22_2024 .pdf
BeMetals Presentation_May_22_2024   .pdfBeMetals Presentation_May_22_2024   .pdf
BeMetals Presentation_May_22_2024 .pdf
 
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdfSearch Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
 

C0212014018

  • 1. The International Journal Of Engineering And Science (IJES) || Volume || 2 || Issue || 12 || Pages || 14-18 || 2013 || ISSN (e): 2319 – 1813 ISSN (p): 2319 – 1805 The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages Udoh, Benjamin E. Department of Electrical/Electronic Engineering Federal Polytechnic Mubi Adamawa State, Nigeria -------------------------------------------------------ABSTRACT--------------------------------------------------In this paper, the characteristic of current transformer (CT) magnetization curves are used to determine the performance of restricted earth fault (REF) relays. This study was carried out at the150MVA 330/132/33kV Gombe transmission substation. This is based on the field data obtained for the neutral current transformers (NCTs) servicing the 150 MVA 330/132/33kV and 15MVA 132/33kV power transformers at the substation. From the study, the knee-point voltages from the CT magnetization curves justify the voltage settings of the restricted earth fault relays. Keywords: Magnetization curve, Neutral current transformer, Restricted earth fault --------------------------------------------------------------------------------------------------------------------------Date of Submission: 30 November 2013 Date of Acceptance: 28 December 13 --------------------------------------------------------------------------------------------------------------------------I. INTRODUCTION The magnetization currents of current transformers usually affect the overall setting of a protection system. The effect may not be significant in the case of over current relays, but the effect can be seen in earth fault relays and unit protection systems where large number of current transformers are connected together. Because of the low setting of the restricted earth fault (REF) scheme the effect of current transformer (CT) magnetization current is easily pronounced in the operation of its relays [1]. It is a well known fact that CT core saturation is brought about by CT magnetization current on application of a voltage, when such voltage exceeds its knee point value. Hence when considering the performance to be expected from a given CT, the exciting current can be measured at various values of EMF. For this reason it is usually more convenient to apply a varying voltage to the secondary winding, the primary winding being open circuited. Fig. 1 shows a typical relationship. The point K on the curve is called the ‘Knee Point’, and is defined as the point in which an increase of 10% in the exciting voltage of rated frequency produces an increase of 50% in the exciting current [2]. From the curve in Fig. 1 point ‘A’ is known as the Ankle Point and the linear portion of the curve is between points ‘A’ and ‘K’. V Figure 1: Typical CT Magnetization Curve www.theijes.com The IJES Page 14
  • 2. The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages The restricted earth fault (REF) protection scheme refers to the differential protection of transformers against ground (earth) fault. It is called “restricted” because its zone of protection is limited only to the windings of the transformer. The restricted earth fault protection scheme is designed to take care of internal earth fault on transformer windings, which if omitted could cause the windings of such transformer to be damaged in the event of such fault. Since power transformers are one of the most important and most expensive components of transmission and distribution networks, it is very essential to prevent a scenario where this piece of equipment is being put out of service. If such an event occurs, the implication will be long period of power outage which according to [3] will generate unpleasant situations such as property loss and business disruption leading to loss orders, damaged to perishable goods and inventories for businesses. Since the issue of lack of adequate restricted earth fault for power transformer protection cannot be compromised, the REF relay must be made to operate satisfactorily by ensuring adequate setting of the relay voltage. The relay voltage must be made to fall within the linear portion of the CT magnetization curves for proper operation of the relays. In this regard, [4] pointed out that to ensure satisfactory operation of the restricted earth fault relay under internal fault conditions, the CT knee point voltage should not be less than twice the relay voltage setting. The relay will never operate with the required speed if the knee point voltage is just in excess of the relay voltage setting and not double the value at least [5]. The CT will normally transform the fault current of the electrical power system for operation of the protection relays connected to the secondary of that CT. If the core of the CT becomes saturated at a lower value of primary current, as in the case of metering CTs, the system fault will not reflect properly to the secondary terminals, which may cause the relays to remain inoperative even when the fault level of the power system is large enough. That is why the core of the protection CT is made in such a way that the saturation level of that core must be high enough, but still with a limit that is not too high otherwise, total transformation of primary current during huge fault may badly damage the protection relays. The restricted earth fault (REF) protection schemes are particularly noted for their high speed of operation; hence they are readily applied in the protection of high voltage systems where fast fault clearing is a premium. This is made possible by the use of an instantaneous attracted armature type of relay. An internal earth fault within a transformer could cause serious damage to the system and this has to be cleared instantaneously [6]. Also high speed fault clearing is particularly beneficial for faults near large concentrations of generation and long intertie lines to remote sources of generation. This is so because fault causes strong angular acceleration to nearby generators, which in turn causes a reduction in plant output due to voltage suppression during fault [7]. Hence the knee point voltages of CTs servicing the REF relays protecting high voltage power transformers should be of higher values, which must be multiples of the relay voltage setting and must be carefully chosen so that the relay could function adequately in clearing its fault speedily. With high speed protection, it is desirable that the transformer should not saturate when carrying maximum current caused by a fault at the critical point of measurement. Where this is not possible, saturation would cause a reduction in the secondary current and therefore reduces the reach of the instantaneous relay [8]. II. RESEARCH METHOD AND ANALYSIS The magnetization data for this study were obtained from the record of injection tests of the neutral current transformers (NCTs) servicing the two 150MVA 330/132/33kV and the two 15MVA 132/33kV power transformer at the substation under study. The data are presented in Tables (1) to (4). They were analyzed using an engineering software programme known as Micro cal – Origin 5.0 adapted for power system simulation. 2.1 Data Analysis The principle of the high impedance (REF) scheme is applied, and to do so the following assumptions are made. 1. One current transformer (or set of it) completely saturates and ceases to transform any part of the primary fault current since its excitation impedance is negligible. 2. The whole of the primary fault current is perfectly transformed by the remaining current transformers. 3. The resistance of the secondary winding of the saturated current transformer together with the leads connecting it constitutes the only burden in parallel with the relay. Consistent with the above assumptions, the maximum voltage across the relay is calculated using: VR Where: = If (RCT + 2RL) If RCT RL = = = Maximum through fault secondary current CT secondary winding resistance Maximum lead resistance from CT to the relay circuit terminals www.theijes.com (1) The IJES Page 15
  • 3. The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages In order to ensure satisfactory operations of the relay under internal fault conditions the CT knee point voltage should not be less than twice the relay voltage setting, thus: VK = 2VR (2) Where: VR = Relay voltage setting The values of the knee point voltages are shown in Table 7 under the column “Calculated Value”. III. RESULTS AND DISCUSSIONS Table 7 shows the relay voltage settings for the various power transformers and their corresponding knee point voltages based on equation (2). The Table shows the calculated and the actual values at the substation. The actual values are the minimum allowable setting values of the relays, in which case the values could be increased to meet the local condition to which the relays are operational. For example, the actual value of knee point voltage of 200V for the relay voltage setting of 100V as against 40V for the relay voltage of 20V (calculated value) with respect to the 330/132/33kV power transformers is practically chosen by the substation under study, as a means of preventing system mal-operation when fault occur outside the protected zone. This observation is in order because one of the benefits of the high impedance restricted earth fault relay operation, is the ability for the system to maintain stability when the voltage setting of the relay is greater than the maximum voltage which can appear under a given through fault condition [9, 10]. Figs. 2 to 5 give the magnetization curves for the neutral current transformers servicing the REF relays at the substation. The curves give a true picture of the magnetization characteristics from which the knee point voltages are estimated. From the magnetization curve of Fig. 2, the knee point voltage is about 450V as against the calculated value of 200V in Table 7. This knee point voltage of 450V estimated from the curve is a preferred value than the 200V calculated directly from equation (2), and gives a higher multiple of the 100V relay voltage setting. This shows that the performance of the neutral current transformer servicing the REF relay protecting the 150MVA 330/132/33kV power transformer is good because the 100V relay setting falls within the linear portion of the CT magnetization curve. From this it is quite certain that the neutral current transformer (NCT) will never get saturated in the event of any through fault condition or when there is an internal earth fault [8]. All the values of the neutral current transformers (NCTs) knee point voltages as estimated from the magnetization curves of Figs 2 to 5 are presented in Table 7. From the Table, the knee point voltage of the NCT servicing the REF relay protecting transformer T2A is lower than the rest. It is on record that the windings of that particular transformer were damaged some few years ago as a result of an inadequate restricted earth fault protection, which plunged the whole of the North East region into total darkness for a period of six (6) months. The whole set was replaced by the end of that year. It was the transformer failure that prompted this study. It should be noted that the estimated values of the knee point voltages from the magnetization curves give the actual operational condition of the neutral current transformers (NCTs) at the substation. They also provide useful guides into the efficient operation of the REF relays in terms of speed [5]. On the other hand, the calculated values of the knee point voltages directly from the formula as presented in this paper are used as checks to determine the reliabilities of the estimated values from the curves. They do not describe the operating condition of the NCTs. IV. CONCLUSION The operational abilities of relays are sometimes affected by the magnetization characteristics of the CTs servicing such relays. In this study, the knee point voltages that were determined from the magnetization characteristics of the neutral current transformers have been found to be quite adequate in guaranteeing effective operation of the restricted earth fault relays. This is so because the neutral current transformers have favourable linear portion in their magnetization characteristics, which is a necessary requirement in the proper operation of the relays, especially when it has to do with high voltage power systems. From the observation made in this study, it will be safe to recommend that NCTs with high value knee point voltages should always be used to service REF relays protecting high voltage power systems. www.theijes.com The IJES Page 16
  • 4. The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages Table 1: Magnetization Data for T1A 150MVA 330/132/33kV Transformer NCT Slated Voltage (V) Neutral Current (mA) Neutral REF CT 50 100 150 200 220 240 260 1.82 3.00 4.00 5.00 5.20 5.50 6.00 Table 2: Magnetization Data for T2A 150MVA 330/132/33kV Transformer NCT Slated Voltage (V) 50 100 150 200 220 240 260 1.75 Neutral REF CT 2.50 3.25 4.25 4.50 5.00 5.50 Neutral Current (mA) Table 3: Magnetization Data for T1 15MVA 132/33kV Transformer NCT Slated Voltage (V) 50 100 150 200 220 233 4.00 Neutral REF CT 7.00 9.75 12.25 13.25 14.00 Neutral Current (mA) Table 4: Magnetization Data for T2 15MVA 132/33kV Transformer NCT Slated Voltage (V) 50 100 150 200 220 233 5.00 Neutral REF CT 9.00 12.75 16.00 17.40 18.30 Neutral Current (mA) Table 5: 150MVA 330/132/33kV Power Transformer Data Secondary winding resistance (RCT) 5.8 Ohms Maximum lead resistance (RL) from CT to the relay tapping point 0.54 Ohms Percentage reactance (X) 11.53% Current Transformer ratio 800/1A Type: Star/Delta/Star Table 6: 15MVA 132/33kV Power Transformer Data Secondary winding resistance (RCT) 2.3 Ohms Maximum lead resistance (RL) from CT to the relay tapping point 0.4 Ohms Percentage reactance (X) 5.17% Current Transformer ratio 600/1A Type: Star/Delta Table 7: Results of NCTs Knee Point Voltages Associated with the Power Transformers Power Transformer T1A T2A T1 T2 www.theijes.com Calculated Value REF Relay Knee Point Voltage (V) Voltage (V) 20 20 15 15 Actual Value REF Relay Knee Point Voltage (V) Voltage (V) 40 40 30 30 100 100 - The IJES 200 200 - NCT Knee Point Voltage From Curve (V) 450 280 400 480 Page 17
  • 5. The Restricted Earth Fault Relay Operation: Impact of Current Transformer Knee Point Voltages Figure 2: Magnetization curve for neutral CT of transformer T1A Figure 4: Magnetization curve for neutral CT of transformer T1 Figure 3: Magnetization curve for neutral CT of transformer T2A Figure 5: Magnetization curve for neutral CT of transformer T2 REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] Udoh, B. E., Evaluation of Restricted earth fault protection scheme for power transformers at Gombe Transmission substation, unpublished M. Eng thesis, Abubakar Tafawa Belewa university, Bauchi – Nigeria 2002. Electricity Training Association, Power system protection, vol. 1 (Peter Peregrinus Limited, 1995). Campbell, Richard J., Weather related power outages and electric system resiliency, Congressional research service report for United States congress, August 2012. GEC Measurements, High stability circulating current relay (General Electric Company Ltd, England, 1982). Davis, T., Protection of industrial power systems (Pergamos Press Ltd, 1984). NEPA, Protection of transformer (NEPA zonal training center, Jos – Nigeria, 1998). Berglund, R. O. et al, One cycle fault interruption at 500kV: system benefits and breaker design, IEEE transaction On PAS, 93(5), 1974. Cooper, W. F. and Jones, D. A. D., Electric safety engineering (3rd ed., Newness, 1993). Franklin, A. C. and Franklin, D. P., The J and P Transformer book (11th ed., Butterworths, 1983). Wright, A. and Christopoulos, C., Electric power system protection (Wiley and Sons, 1993). www.theijes.com The IJES Page 18