SlideShare a Scribd company logo
1 of 6
Download to read offline
300 Journal of Electrical Engineering & Technology, Vol. 2, No. 3, pp. 300~305, 2007
Investigation and Mitigation of Overvoltage Due to Ferroresonance
in the Distribution Network
Preecha Sakarung†
, Teratam Bunyagul* and Somchai Chatratana**
Abstract – This paper reports an investigation of overvoltages caused by ferroresonance in the
distribution system, which consists of a bank of open-delta single-phase voltage transformers. The high
voltage sides of the voltage transformer are connected to the distribution system via three single-phase
fuse cutouts. Due to the saturation characteristic of the transformer cores, ferroresonance can occur in
the condition that the transformer is energized or deenergized with single-phase switching operation of
the fuse cutouts. The simulation tool based on EMTP is used to investigate the overvoltages at the high
side of voltage transformer. Bifurcation diagrams are used to present the ferroresonance behavior in
ranges of different operating conditions. The simulation results are in good agreement with the results
from the experiment of 22 kV voltage transformers. The mitigation technique with additional damping
resistors in the secondary windings of the voltage transformers will be introduced. Brief discussion
will be made on the physical phenomena related to the overvoltage and the damage of voltage
transformer.
Keywords: Ferroresonance, Voltage Transformer, Bifurcation Diagram, EMTP, PSCAD/EMTDC
1. Introduction
In recent years, the Provincial Electricity Authority
(PEA), Thailand which supplies the electricity to all parts
of the country except Bangkok Metropolitan area, is at
higher risk of ferroresonance. There are many reports on
damages of three-phase distribution transformers with
single-phase energization/de-energization operation at no
load. An abnormally high number of cases were also
reported on the damages of voltage transformers (VT) used
for supplying measuring instrument. Insulation of the high
side of transformer coil was often burnt particularly at the
area of top windings of the coil. Deformations of the tank
and the damages near the base of the bushings of VT were
found in general. The damages occurred when the VTs
were operated for 8 to 10 hours after energization.
2. Description of PEA’s Distribution System
The Provincial Electricity Authority (PEA) uses
Supervisory Control and Data Acquisition (SCADA) system
for its network control. Due to very large service area, the
problem of voltage collapse has been taken very seriously by
PEA. Therefore, on-line operation with SCADA is essential
for PEA operation. In SCADA system, many voltage
transformers (VTs) are needed to supply the power to the
measuring systems with low voltage ratings. Due to low
power consumption of the measuring system, open-delta
connection is normally used for banking the two single-phase
transformers to form three-phase configuration. The two
single-phase transformers are normally put in the same tank
for the sake of economy. The problem of damaged VT
occurred mostly in the area which VT was already installed
but SCADA system was not yet put in operation.
The circuit diagram of a typical supply system for measuring
equipment is shown in Fig.1 Three-phase distribution system
supplies voltage to VT via short transmission lines and three
single-phase fuse cutouts (a, b, c).
Fig. 1. Typical circuit diagram of the distribution system
with voltage transformer connection
For economic reason, the three-phase VT is built from
two single-phase transformers connected in open-delta.
The center tap of the low side of the transformer is
connected to the ground. The physical structure of the
voltage transformer is shown in Fig. 2.
† Corresponding Author: Department of Electrical Engineering,
Dhurakij-Pundit University (preecha@dpu.ac.th)
* Department of Electrical Engineering, King Mongkut’s Institute of
Technology North Bangkok, Thailand
** National Science and Technology Development Agency (NSTDA)
Received 8 August, 2006; Accepted 13 January, 2007
Preecha Sakarung, Teratam Bunyagul and Somchai Chatratana 301
Fig. 2. The physical structure of VT
3. System Modeling
In standard PSCAD/EMTDC simulation tool, the
model for two single-phase transformers with different
magnetic cores, which are connected in open-delta and
put together in the same tank, is not available. It is
therefore necessary to build the approximate model from
the single-phase transformer and the configuration of VT
as shown in Fig.1.
Three-phase voltage source is 22 kV, 50 Hz, and its
positive sequence impedance is 2.8086 ohm with 83.979
degree phase angle. The voltage rating of the single-phase
voltage transformer is 22 kV on high side and 110 V phase
on low side. The power rating is only 25 VA. The core
losses in the magnetic component are 22 watt. Copper loss
is very low and can be neglected. The approximate
characteristic of saturation is obtained from the experiment
and the compensating current source for core saturation in
EMTDC is used. The parameters for the saturation curve
are Air Core Reactance (XAIR) = 0.001 p.u., Rated
Magnetizing Current (IMR) = 1.29 p.u. and Knee Point
(XKNEE) = 45.0 %. To verify the saturation model of the
transformer, an actual curve of saturation curve was
compared with approximate saturation characteristic
shown in Fig. 3.
Fig.3. Comparison of actual saturation v-i curve and approximate
saturation curve(low sideof transformer)
If the length of distribution line is less than 20 km. and
the time step used in the calculation is 50 .secμ , Pi section
type of transmission line model is recommended in
EMTDC. In this case, the length of the line is
approximately a few meters only (~3 meters). Therefore,
modeling the line with Pi section can produce good results.
4. Experiment Result
The objective of the experiment is to observe
ferroresonance phenomenon. The test circuit is shown in
Fig. 4. Three single-phase circuit breakers were connected
with VT (SW1a, SW1b and SW1c). The measuring
equipment represented by VC was made from 30 ΩM
resistor connected in series with a 30 Ωk resistor and a
500 pF capacitor connected in parallel. Simple test
procedure involved the random of single-phase switching
of the circuit breaker at different angles of the voltage
waveform. It was found that overvoltages occurred several
times. The overvoltages caused by de-energization of VT
of phase C at the angles of 90 degrees and 270 degrees are
shown in Fig.5 and Fig.6, respectively. From Fig. 5 and Fig.
6, it can be seen that ferroresonance occurred with
fundamental mode (50 Hz) and the highest magnitude of
overvoltage was 3 p.u.
Fig. 4. Circuit diagram of experimental set up
Fig. 5. Voltage (top) and current (bottom) waveforms of
phase C resulting from de-energization at 90
degrees (scale: 50 kV/Div and 4.5 mA/Div.)
302 Investigation and Mitigation of Overvoltage Due to Ferroresonance in the Distribution Network
Fig. 6. Voltage (top) and current (bottom) waveforms of
phase C resulting from de-energization at 270
degrees (scale: 50 kV/Div and 4.5 mA/Div.)
5. Mitigation Technique
Ref. [2] presents a technique for ferroresonance
mitigation by installing of a damping resistor at the
secondary side of the transformer. However the resistance
value was selected by the trial and error method.
Approximate results when a burden resistor was used to
damp ferroresonance are shown through the field test and
EMTP simulation as in [3]. Serial resistor and damping
reactor were used to reduce overvoltage demonstrated in
[4]. Saturation characteristic allows the reactor to act like
magnetic switch. In normal operation, the impedance of
reactor is high, but with overvoltage, the impedance of the
reactor reduces significantly due to the saturation. The
reactor must be designed to reach saturation level before
the core of the voltage transformer does. With this design,
the serial connected resistor and the reactor become the
burden resistor during overvoltage. Simulation was carried
out several times in [5] to determine the optimum
resistance value to be installed at the secondary side of VT.
Burden resistor or damping resistor is a popular mitigation
technique introduced in [2-5]. It is simple, effective, and
easy to install in the field.
The resistance value should effectively damp the
ferroresonance but with constant secondary voltage, it should
be high enough to keep the loss in the burden resistor low. If
damping resistor is installed permanently on secondary side of
VT, loss of energy occurs continuously. The combination of
advantages of not only suppressing overvoltage but also of
saving of energy, the power electronic switch is recommended
to connect the burden resistor with the secondary side of VT
only when overvoltage occurs.
6. Application of Bifurcation Diagrams for
Ferroresonance Investigation
Optimal values of burden resistor can be determined
from bifurcation diagram. It is more effective and more
time saving than the trial and error method reported in the
past. Bifurcation diagrams are also useful for investigation
of ferroresonance due to other parameters and operating
conditions.
6.1 Simulation of single-phase switching
Fig. 7 shows the result of simulation of single-phase
switching of the circuit in Fig. 1. The energization
sequence was: switching of only phase A at 0.1 second,
followed by switching of phase B at 0.5 second and
switching of phase C at 0.7 second. It can be seen that the
highest overvoltage occurred at phase C only after a single
cycle of switching time. The overvoltage reached the peak
at 4.5 p.u. and maintained at 4 p.u. with fundamental mode.
When phase B was energized, the overvoltage at phase C
was decayed with subharmonic mode. The overvoltage
disappeared when phase C was energized and all three
lines were connected to the supply.
6.2 Bifurcation diagrams for ferroresonance investigation
The bifurcation diagrams can be created from the plot of
collection points obtained from the Poincaré Sections with
20 ms sampling time. Three system parameters were
investigated to determine their effects on ferroresonance.
Fig. 7. Waveforms of phase voltages resulting from single
phase switching of voltage transformer
Fig. 8. Bifurcation diagram with varying resistance of
burden resistor
Preecha Sakarung, Teratam Bunyagul and Somchai Chatratana 303
Fig. 9. Bifurcation diagram with varying magnitudes of
voltage source
Fig. 8 shows the effect of damping resistance on the
overvoltage. The resistance value was varied from 100 Ω
up to 3000 with 1 varying step. It can be seen that
overvoltage did not occur when the value of resistance was
between 100 and 500. Fig. 9 shows the bifurcation diagram
of the magnitude of system voltages with varying source
voltage from 0 p.u. to 2.0 p.u. It can be seen that, without
damping resistor, overvoltage occurred even at the very
low magnitude of voltage source (0.1 p.u.). The mode of
ferrorresonance changed from fundamental mode to
chaotic mode at the source voltage from 1.22 p.u. to 1.7
p.u. The effect of de-energization angles on overvoltages is
shown by the bifurcation diagram in Fig. 10. From the
bifurcation diagram, ferroresonance occurred at all de-
energization angles with single-phase switching operation
at 1 p.u. source voltage and without damping resistor.
Fig. 10. Bifurcation diagram with varying de-energization
angles
6.3 Simulation of single-phase switching with damping
resistor
From bifurcation diagram in Fig.8, the resistance value
from 100 to 500 can be used to damp the overvoltage at VT.
Fig. 11 shows the simulation result of the circuit in Fig. 1
with the damping resistance of 440. The value of 440 was
chosen to optimize both the power loss and the common
value of resistance to be easily obtained over the counter.
In comparison with Fig. 7, for the same switching
conditions, it can be seen that there is no overvoltage. No
ferroresonance occurred from the first instant of switching
at 0.1 second until the end of the energization process at
0.7 second.
6.4 Experimental result of single-phase switching
with damping resistor
The result of the investigation was confirmed by
installing 440 damping resistors in the VT. Then Fig. 12,
the VT was tested with the same conditions as in Fig. 6
(270 degrees de-energization angle).
Fig. 11. Waveforms of phase voltages resulting from
single-phase switching of voltage transformer
with damping resistor of 440 Ω
Fig. 12. Voltage (top) and current (bottom) waveforms of
phase C resulting from de-energization at 270
degrees with 440 ohm damping resistors at
secondary side
7. Practical Aspect of Overvoltage on Voltage
Tramsformer
Manual single-phase energization/de-energization of
three phase network by operator usually takes about 15
minutes. This is due to the fact that the receptor part of the
304 Investigation and Mitigation of Overvoltage Due to Ferroresonance in the Distribution Network
fuse cutout is rather tight. When ferroresonance occurs, the
magnitude of overvoltage can be as high as 3 to 4 p.u.
High electrical stress can occur at the insulation close to
the transformer tank. During overvoltage, the insulation
characteristic of transformer coil deteriorates. Complete
damage of VT was reported after being put into operation
for 16 hours or in some cases even within shorter operation
time.
Coils at phase B and C also face with higher risk from
overvoltages if the sequence of energization is A-B-C.
Overvoltages damage the insulation of the transformer
coils. Insulation failure leads to high current due to short
circuits between the windings turns. Burnt insulation was
found at groups of high side coil particularly at top
position of the coil. Tears between high side terminal and
connector were also reported. High internal pressure
resulted from high temperature distorted the oil-filled
transformer tank and broke the bushing at the base position.
Fig. 13. Internal view of the damaged VT
8. Conclusion
Single-phase energization and deenergization of no-load
saturable voltage transformer can cause ferroresonance in the
distribution system. The overvoltages caused by
ferroresonance can last several minutes after energization
process. Overvoltages lead to insulation failure and high
short circuit currents. Insulation failure and short circuit
current finally destroy the voltage transformer.
EMTP is a popular simulation tool for ferroresonance
investigation. With the help of Poincare’ sections,
bifurcation diagrams can be produced to demonstrate
various effects of operating parameters on ferroresonance.
In this paper, bifurcation diagrams were produced to study
the effects of damping resistors, magnitude of the source
voltages, and de-energization angles on the ferroresonance
caused by single-phase operation.
The results obtained from the simulation of damping
resistor were confirmed by the test in which the damping
resistor was installed with the secondary circuit of the VT.
Test result confirms that the damping resistor of 440 can
successfully eliminate ferroresonance. This procedure can
be used to determine ferroresonance suppression circuit in
the future.
Acknowledgements
The authors would like to thank Precise Electric MFG.
CO., LTD. for the permission to use the information and
the test results from the company’s Internal Report dated
March 2005.
Appendix
Table 1. Pi section line data
Positive sequence Zero sequence
Resistance .21435E-3 [ohms/m]
.39186E-3
[ohms/m]
Inductive
reactance
.33976E-3 [ohms/m]
.15538E-2
[ohms/m]
Capacitive
reactance
289.695 [Mohms*m] 647.332 [Mohms*m]
References
[1] P. Sakarung and S. Chatratana, “Application of
PSCAD/ EMTDC and Chaos Theory to Power
System Terroresonanc eAnalysis”, International
Conference on Power Systems Transients, Canada,
June 19-23, 2005.
[2] Robert Hoerauf and Neil Nichols, “Avoiding
Potential Transformer Ferroresonant Problems in
Industrial Power Systems”, Industrial and
Commercial Power Systems Technical Conference,
pp. 61 – 68 (1989).
[3] William S. Vilcheck and Michael V. Haddad,
“Voltage Transformer Ferroresonance in Cogeneration
Substation”, Pulp and Paper Industry Technical
Conference, pp. 148 - 158 (1992).
[4] D. Shein and S. Zissu, “Domains of Ferroresonance
Occurrence in Voltage Transformers with or without
Damping Reactor”, Eighteenth Convention of
Electrical and Electronics Engineers in Israel, pp.
1.5.2/1 - 1.5.2/5 (1995).
[5] M. R. Iravani et-al, “Modeling and Analysis
Guidelines for Slow Transients Part III: The Study of
Ferroresonance”, IEEE Trans. On Power Delivery,
Vol. 15, No.1, pp. 255-265, Jan. 2000.
Preecha Sakarung, Teratam Bunyagul and Somchai Chatratana 305
Preecha Sakarung
He received the B.Eng. and M.Eng.
degree from the King Mongkut’s
Institute of Technology North
Bangkok, (KMIT’NB) Thailand, in
1995 and 1999 respectively. Currently,
he is an assistant professor in the
Department of Electrical Engineering at the Dhurakijpundit
University and a Ph.D. student majoring in electrical
engineering at the King Mongkut’s Institute of Technology
North Bangkok, (KMIT’NB). His Ph.D. research is on the
area of modeling and analysis of power system transient
using digital program.
Teratam Bunyagul
He received BEng (second class honor)
degree in electrical engineering from
King Mongkut’s Institute of
Technology North Bangkok (KMITNB)
in 1995. He obtained his M.Sc and
Ph.D degrees from University
Manchester Institute of Science and Technology (UMIST),
UK in 1998 and 2003 respectively. He currently holds the
position Head of Power System Laboratory for the
department of electrical engineering at KMITNB. His main
activity during academic career has involved research into
new techniques in power system protection and control,
the design and development of new types of protection
relays and control systems.
Somchai Chatratana
He received his B.Eng. degree
(Honors) in Electrical Engineering
from Kasetsart University, Thailand,
in 1974, M.Sc. D.I.C. and Ph.D.
degree from Imperial College, London
University, U.K., in 1978 and 1982
respectively. He was an Associate Professor at Electrical
Engineering Department, King Mongkut’s Institute of
Technology North Bangkok until 2003. He is now an
Assistant to the President of National Science and
Technology Development Agency(NSTDA). His currently
research interests include control of electrical drives,
power quality and FACTS.

More Related Content

What's hot

Unit I - Basic Electrical and Electronics Engineering
Unit I - Basic Electrical and Electronics EngineeringUnit I - Basic Electrical and Electronics Engineering
Unit I - Basic Electrical and Electronics Engineeringarunatshare
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationIJECEIAES
 
Power Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series CompensationPower Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series CompensationIJMER
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
 
FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
 FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEMPoliteknik Negeri Ujung Pandang
 
Optimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlOptimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlIJMER
 
199833536 ee2404-lab-manual
199833536 ee2404-lab-manual199833536 ee2404-lab-manual
199833536 ee2404-lab-manualhomeworkping4
 
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt ReactorTransients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt ReactorBérengère VIGNAUX
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notesAcot Benard
 
EM_2131005_3_phasetransformers
EM_2131005_3_phasetransformersEM_2131005_3_phasetransformers
EM_2131005_3_phasetransformersJitin Pillai
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Bérengère VIGNAUX
 
Practical of Power System Analysis (PSA)
Practical of Power System Analysis (PSA)Practical of Power System Analysis (PSA)
Practical of Power System Analysis (PSA)Aneel-k Suthar
 
Power flow solution
Power flow solutionPower flow solution
Power flow solutionBalaram Das
 
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS) POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS) Mathankumar S
 

What's hot (20)

Unit I - Basic Electrical and Electronics Engineering
Unit I - Basic Electrical and Electronics EngineeringUnit I - Basic Electrical and Electronics Engineering
Unit I - Basic Electrical and Electronics Engineering
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulation
 
Power Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series CompensationPower Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series Compensation
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
IEEEpaper.
IEEEpaper.IEEEpaper.
IEEEpaper.
 
FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
 FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
FAULT ANALYSIS USING PSCAD/EMTDC for 150 kV SOUTH SULAWESI TRANSMISSION SYSTEM
 
Optimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlOptimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow Control
 
199833536 ee2404-lab-manual
199833536 ee2404-lab-manual199833536 ee2404-lab-manual
199833536 ee2404-lab-manual
 
Electrical power system
Electrical power system Electrical power system
Electrical power system
 
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt ReactorTransients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
Transients Caused by Switching of 420 kV Three-Phase Variable Shunt Reactor
 
Pdu 2021 s2
Pdu 2021 s2Pdu 2021 s2
Pdu 2021 s2
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notes
 
HVDC System
HVDC SystemHVDC System
HVDC System
 
EM_2131005_3_phasetransformers
EM_2131005_3_phasetransformersEM_2131005_3_phasetransformers
EM_2131005_3_phasetransformers
 
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks
 
Practical of Power System Analysis (PSA)
Practical of Power System Analysis (PSA)Practical of Power System Analysis (PSA)
Practical of Power System Analysis (PSA)
 
Power flow solution
Power flow solutionPower flow solution
Power flow solution
 
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS) POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
 
0178__Waseda__HCMUT
0178__Waseda__HCMUT0178__Waseda__HCMUT
0178__Waseda__HCMUT
 

Similar to overvoltage in distribution network

ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...IAES-IJPEDS
 
Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityParth Patel
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
C0212014018
C0212014018C0212014018
C0212014018theijes
 
IRJET- Design of Single Phase Transformerless Inverter
IRJET- Design of Single Phase Transformerless InverterIRJET- Design of Single Phase Transformerless Inverter
IRJET- Design of Single Phase Transformerless InverterIRJET Journal
 
IRJET- Design of Single Phase Transformerless Inverter
IRJET-  	  Design of Single Phase Transformerless InverterIRJET-  	  Design of Single Phase Transformerless Inverter
IRJET- Design of Single Phase Transformerless InverterIRJET Journal
 
A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...
A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...
A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...saif ulla baig
 
Three phase vienna rectifier for wind power generation system
Three phase vienna rectifier for wind power generation systemThree phase vienna rectifier for wind power generation system
Three phase vienna rectifier for wind power generation systemeSAT Publishing House
 
Research on High Frequency PI Section Control of Electrochemical DC Power Supply
Research on High Frequency PI Section Control of Electrochemical DC Power SupplyResearch on High Frequency PI Section Control of Electrochemical DC Power Supply
Research on High Frequency PI Section Control of Electrochemical DC Power Supplyiosrjce
 

Similar to overvoltage in distribution network (20)

Ba4101300306
Ba4101300306Ba4101300306
Ba4101300306
 
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
 
I41045662
I41045662I41045662
I41045662
 
Lecture (11.11.22).pptx
Lecture (11.11.22).pptxLecture (11.11.22).pptx
Lecture (11.11.22).pptx
 
Solid-State Transformer (S2T) of Single Phase Matrix Converter
Solid-State Transformer (S2T) of Single Phase Matrix ConverterSolid-State Transformer (S2T) of Single Phase Matrix Converter
Solid-State Transformer (S2T) of Single Phase Matrix Converter
 
Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power Quality
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
C0212014018
C0212014018C0212014018
C0212014018
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
685 calavia
685 calavia685 calavia
685 calavia
 
IRJET- Design of Single Phase Transformerless Inverter
IRJET- Design of Single Phase Transformerless InverterIRJET- Design of Single Phase Transformerless Inverter
IRJET- Design of Single Phase Transformerless Inverter
 
IRJET- Design of Single Phase Transformerless Inverter
IRJET-  	  Design of Single Phase Transformerless InverterIRJET-  	  Design of Single Phase Transformerless Inverter
IRJET- Design of Single Phase Transformerless Inverter
 
A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...
A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...
A MULTILEVEL MEDIUM VOLTAGE INVERTER FOR STEP UP TRANSFORMER LESS GRID CONNEC...
 
Three phase vienna rectifier for wind power generation system
Three phase vienna rectifier for wind power generation systemThree phase vienna rectifier for wind power generation system
Three phase vienna rectifier for wind power generation system
 
N012628790
N012628790N012628790
N012628790
 
Research on High Frequency PI Section Control of Electrochemical DC Power Supply
Research on High Frequency PI Section Control of Electrochemical DC Power SupplyResearch on High Frequency PI Section Control of Electrochemical DC Power Supply
Research on High Frequency PI Section Control of Electrochemical DC Power Supply
 
N012628790
N012628790N012628790
N012628790
 
A011110108
A011110108A011110108
A011110108
 
Soft Switching of Three-Phase AC to DC CIHRC with Wireless Power Transfer (WP...
Soft Switching of Three-Phase AC to DC CIHRC with Wireless Power Transfer (WP...Soft Switching of Three-Phase AC to DC CIHRC with Wireless Power Transfer (WP...
Soft Switching of Three-Phase AC to DC CIHRC with Wireless Power Transfer (WP...
 

Recently uploaded

OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 

Recently uploaded (20)

OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 

overvoltage in distribution network

  • 1. 300 Journal of Electrical Engineering & Technology, Vol. 2, No. 3, pp. 300~305, 2007 Investigation and Mitigation of Overvoltage Due to Ferroresonance in the Distribution Network Preecha Sakarung† , Teratam Bunyagul* and Somchai Chatratana** Abstract – This paper reports an investigation of overvoltages caused by ferroresonance in the distribution system, which consists of a bank of open-delta single-phase voltage transformers. The high voltage sides of the voltage transformer are connected to the distribution system via three single-phase fuse cutouts. Due to the saturation characteristic of the transformer cores, ferroresonance can occur in the condition that the transformer is energized or deenergized with single-phase switching operation of the fuse cutouts. The simulation tool based on EMTP is used to investigate the overvoltages at the high side of voltage transformer. Bifurcation diagrams are used to present the ferroresonance behavior in ranges of different operating conditions. The simulation results are in good agreement with the results from the experiment of 22 kV voltage transformers. The mitigation technique with additional damping resistors in the secondary windings of the voltage transformers will be introduced. Brief discussion will be made on the physical phenomena related to the overvoltage and the damage of voltage transformer. Keywords: Ferroresonance, Voltage Transformer, Bifurcation Diagram, EMTP, PSCAD/EMTDC 1. Introduction In recent years, the Provincial Electricity Authority (PEA), Thailand which supplies the electricity to all parts of the country except Bangkok Metropolitan area, is at higher risk of ferroresonance. There are many reports on damages of three-phase distribution transformers with single-phase energization/de-energization operation at no load. An abnormally high number of cases were also reported on the damages of voltage transformers (VT) used for supplying measuring instrument. Insulation of the high side of transformer coil was often burnt particularly at the area of top windings of the coil. Deformations of the tank and the damages near the base of the bushings of VT were found in general. The damages occurred when the VTs were operated for 8 to 10 hours after energization. 2. Description of PEA’s Distribution System The Provincial Electricity Authority (PEA) uses Supervisory Control and Data Acquisition (SCADA) system for its network control. Due to very large service area, the problem of voltage collapse has been taken very seriously by PEA. Therefore, on-line operation with SCADA is essential for PEA operation. In SCADA system, many voltage transformers (VTs) are needed to supply the power to the measuring systems with low voltage ratings. Due to low power consumption of the measuring system, open-delta connection is normally used for banking the two single-phase transformers to form three-phase configuration. The two single-phase transformers are normally put in the same tank for the sake of economy. The problem of damaged VT occurred mostly in the area which VT was already installed but SCADA system was not yet put in operation. The circuit diagram of a typical supply system for measuring equipment is shown in Fig.1 Three-phase distribution system supplies voltage to VT via short transmission lines and three single-phase fuse cutouts (a, b, c). Fig. 1. Typical circuit diagram of the distribution system with voltage transformer connection For economic reason, the three-phase VT is built from two single-phase transformers connected in open-delta. The center tap of the low side of the transformer is connected to the ground. The physical structure of the voltage transformer is shown in Fig. 2. † Corresponding Author: Department of Electrical Engineering, Dhurakij-Pundit University (preecha@dpu.ac.th) * Department of Electrical Engineering, King Mongkut’s Institute of Technology North Bangkok, Thailand ** National Science and Technology Development Agency (NSTDA) Received 8 August, 2006; Accepted 13 January, 2007
  • 2. Preecha Sakarung, Teratam Bunyagul and Somchai Chatratana 301 Fig. 2. The physical structure of VT 3. System Modeling In standard PSCAD/EMTDC simulation tool, the model for two single-phase transformers with different magnetic cores, which are connected in open-delta and put together in the same tank, is not available. It is therefore necessary to build the approximate model from the single-phase transformer and the configuration of VT as shown in Fig.1. Three-phase voltage source is 22 kV, 50 Hz, and its positive sequence impedance is 2.8086 ohm with 83.979 degree phase angle. The voltage rating of the single-phase voltage transformer is 22 kV on high side and 110 V phase on low side. The power rating is only 25 VA. The core losses in the magnetic component are 22 watt. Copper loss is very low and can be neglected. The approximate characteristic of saturation is obtained from the experiment and the compensating current source for core saturation in EMTDC is used. The parameters for the saturation curve are Air Core Reactance (XAIR) = 0.001 p.u., Rated Magnetizing Current (IMR) = 1.29 p.u. and Knee Point (XKNEE) = 45.0 %. To verify the saturation model of the transformer, an actual curve of saturation curve was compared with approximate saturation characteristic shown in Fig. 3. Fig.3. Comparison of actual saturation v-i curve and approximate saturation curve(low sideof transformer) If the length of distribution line is less than 20 km. and the time step used in the calculation is 50 .secμ , Pi section type of transmission line model is recommended in EMTDC. In this case, the length of the line is approximately a few meters only (~3 meters). Therefore, modeling the line with Pi section can produce good results. 4. Experiment Result The objective of the experiment is to observe ferroresonance phenomenon. The test circuit is shown in Fig. 4. Three single-phase circuit breakers were connected with VT (SW1a, SW1b and SW1c). The measuring equipment represented by VC was made from 30 ΩM resistor connected in series with a 30 Ωk resistor and a 500 pF capacitor connected in parallel. Simple test procedure involved the random of single-phase switching of the circuit breaker at different angles of the voltage waveform. It was found that overvoltages occurred several times. The overvoltages caused by de-energization of VT of phase C at the angles of 90 degrees and 270 degrees are shown in Fig.5 and Fig.6, respectively. From Fig. 5 and Fig. 6, it can be seen that ferroresonance occurred with fundamental mode (50 Hz) and the highest magnitude of overvoltage was 3 p.u. Fig. 4. Circuit diagram of experimental set up Fig. 5. Voltage (top) and current (bottom) waveforms of phase C resulting from de-energization at 90 degrees (scale: 50 kV/Div and 4.5 mA/Div.)
  • 3. 302 Investigation and Mitigation of Overvoltage Due to Ferroresonance in the Distribution Network Fig. 6. Voltage (top) and current (bottom) waveforms of phase C resulting from de-energization at 270 degrees (scale: 50 kV/Div and 4.5 mA/Div.) 5. Mitigation Technique Ref. [2] presents a technique for ferroresonance mitigation by installing of a damping resistor at the secondary side of the transformer. However the resistance value was selected by the trial and error method. Approximate results when a burden resistor was used to damp ferroresonance are shown through the field test and EMTP simulation as in [3]. Serial resistor and damping reactor were used to reduce overvoltage demonstrated in [4]. Saturation characteristic allows the reactor to act like magnetic switch. In normal operation, the impedance of reactor is high, but with overvoltage, the impedance of the reactor reduces significantly due to the saturation. The reactor must be designed to reach saturation level before the core of the voltage transformer does. With this design, the serial connected resistor and the reactor become the burden resistor during overvoltage. Simulation was carried out several times in [5] to determine the optimum resistance value to be installed at the secondary side of VT. Burden resistor or damping resistor is a popular mitigation technique introduced in [2-5]. It is simple, effective, and easy to install in the field. The resistance value should effectively damp the ferroresonance but with constant secondary voltage, it should be high enough to keep the loss in the burden resistor low. If damping resistor is installed permanently on secondary side of VT, loss of energy occurs continuously. The combination of advantages of not only suppressing overvoltage but also of saving of energy, the power electronic switch is recommended to connect the burden resistor with the secondary side of VT only when overvoltage occurs. 6. Application of Bifurcation Diagrams for Ferroresonance Investigation Optimal values of burden resistor can be determined from bifurcation diagram. It is more effective and more time saving than the trial and error method reported in the past. Bifurcation diagrams are also useful for investigation of ferroresonance due to other parameters and operating conditions. 6.1 Simulation of single-phase switching Fig. 7 shows the result of simulation of single-phase switching of the circuit in Fig. 1. The energization sequence was: switching of only phase A at 0.1 second, followed by switching of phase B at 0.5 second and switching of phase C at 0.7 second. It can be seen that the highest overvoltage occurred at phase C only after a single cycle of switching time. The overvoltage reached the peak at 4.5 p.u. and maintained at 4 p.u. with fundamental mode. When phase B was energized, the overvoltage at phase C was decayed with subharmonic mode. The overvoltage disappeared when phase C was energized and all three lines were connected to the supply. 6.2 Bifurcation diagrams for ferroresonance investigation The bifurcation diagrams can be created from the plot of collection points obtained from the Poincaré Sections with 20 ms sampling time. Three system parameters were investigated to determine their effects on ferroresonance. Fig. 7. Waveforms of phase voltages resulting from single phase switching of voltage transformer Fig. 8. Bifurcation diagram with varying resistance of burden resistor
  • 4. Preecha Sakarung, Teratam Bunyagul and Somchai Chatratana 303 Fig. 9. Bifurcation diagram with varying magnitudes of voltage source Fig. 8 shows the effect of damping resistance on the overvoltage. The resistance value was varied from 100 Ω up to 3000 with 1 varying step. It can be seen that overvoltage did not occur when the value of resistance was between 100 and 500. Fig. 9 shows the bifurcation diagram of the magnitude of system voltages with varying source voltage from 0 p.u. to 2.0 p.u. It can be seen that, without damping resistor, overvoltage occurred even at the very low magnitude of voltage source (0.1 p.u.). The mode of ferrorresonance changed from fundamental mode to chaotic mode at the source voltage from 1.22 p.u. to 1.7 p.u. The effect of de-energization angles on overvoltages is shown by the bifurcation diagram in Fig. 10. From the bifurcation diagram, ferroresonance occurred at all de- energization angles with single-phase switching operation at 1 p.u. source voltage and without damping resistor. Fig. 10. Bifurcation diagram with varying de-energization angles 6.3 Simulation of single-phase switching with damping resistor From bifurcation diagram in Fig.8, the resistance value from 100 to 500 can be used to damp the overvoltage at VT. Fig. 11 shows the simulation result of the circuit in Fig. 1 with the damping resistance of 440. The value of 440 was chosen to optimize both the power loss and the common value of resistance to be easily obtained over the counter. In comparison with Fig. 7, for the same switching conditions, it can be seen that there is no overvoltage. No ferroresonance occurred from the first instant of switching at 0.1 second until the end of the energization process at 0.7 second. 6.4 Experimental result of single-phase switching with damping resistor The result of the investigation was confirmed by installing 440 damping resistors in the VT. Then Fig. 12, the VT was tested with the same conditions as in Fig. 6 (270 degrees de-energization angle). Fig. 11. Waveforms of phase voltages resulting from single-phase switching of voltage transformer with damping resistor of 440 Ω Fig. 12. Voltage (top) and current (bottom) waveforms of phase C resulting from de-energization at 270 degrees with 440 ohm damping resistors at secondary side 7. Practical Aspect of Overvoltage on Voltage Tramsformer Manual single-phase energization/de-energization of three phase network by operator usually takes about 15 minutes. This is due to the fact that the receptor part of the
  • 5. 304 Investigation and Mitigation of Overvoltage Due to Ferroresonance in the Distribution Network fuse cutout is rather tight. When ferroresonance occurs, the magnitude of overvoltage can be as high as 3 to 4 p.u. High electrical stress can occur at the insulation close to the transformer tank. During overvoltage, the insulation characteristic of transformer coil deteriorates. Complete damage of VT was reported after being put into operation for 16 hours or in some cases even within shorter operation time. Coils at phase B and C also face with higher risk from overvoltages if the sequence of energization is A-B-C. Overvoltages damage the insulation of the transformer coils. Insulation failure leads to high current due to short circuits between the windings turns. Burnt insulation was found at groups of high side coil particularly at top position of the coil. Tears between high side terminal and connector were also reported. High internal pressure resulted from high temperature distorted the oil-filled transformer tank and broke the bushing at the base position. Fig. 13. Internal view of the damaged VT 8. Conclusion Single-phase energization and deenergization of no-load saturable voltage transformer can cause ferroresonance in the distribution system. The overvoltages caused by ferroresonance can last several minutes after energization process. Overvoltages lead to insulation failure and high short circuit currents. Insulation failure and short circuit current finally destroy the voltage transformer. EMTP is a popular simulation tool for ferroresonance investigation. With the help of Poincare’ sections, bifurcation diagrams can be produced to demonstrate various effects of operating parameters on ferroresonance. In this paper, bifurcation diagrams were produced to study the effects of damping resistors, magnitude of the source voltages, and de-energization angles on the ferroresonance caused by single-phase operation. The results obtained from the simulation of damping resistor were confirmed by the test in which the damping resistor was installed with the secondary circuit of the VT. Test result confirms that the damping resistor of 440 can successfully eliminate ferroresonance. This procedure can be used to determine ferroresonance suppression circuit in the future. Acknowledgements The authors would like to thank Precise Electric MFG. CO., LTD. for the permission to use the information and the test results from the company’s Internal Report dated March 2005. Appendix Table 1. Pi section line data Positive sequence Zero sequence Resistance .21435E-3 [ohms/m] .39186E-3 [ohms/m] Inductive reactance .33976E-3 [ohms/m] .15538E-2 [ohms/m] Capacitive reactance 289.695 [Mohms*m] 647.332 [Mohms*m] References [1] P. Sakarung and S. Chatratana, “Application of PSCAD/ EMTDC and Chaos Theory to Power System Terroresonanc eAnalysis”, International Conference on Power Systems Transients, Canada, June 19-23, 2005. [2] Robert Hoerauf and Neil Nichols, “Avoiding Potential Transformer Ferroresonant Problems in Industrial Power Systems”, Industrial and Commercial Power Systems Technical Conference, pp. 61 – 68 (1989). [3] William S. Vilcheck and Michael V. Haddad, “Voltage Transformer Ferroresonance in Cogeneration Substation”, Pulp and Paper Industry Technical Conference, pp. 148 - 158 (1992). [4] D. Shein and S. Zissu, “Domains of Ferroresonance Occurrence in Voltage Transformers with or without Damping Reactor”, Eighteenth Convention of Electrical and Electronics Engineers in Israel, pp. 1.5.2/1 - 1.5.2/5 (1995). [5] M. R. Iravani et-al, “Modeling and Analysis Guidelines for Slow Transients Part III: The Study of Ferroresonance”, IEEE Trans. On Power Delivery, Vol. 15, No.1, pp. 255-265, Jan. 2000.
  • 6. Preecha Sakarung, Teratam Bunyagul and Somchai Chatratana 305 Preecha Sakarung He received the B.Eng. and M.Eng. degree from the King Mongkut’s Institute of Technology North Bangkok, (KMIT’NB) Thailand, in 1995 and 1999 respectively. Currently, he is an assistant professor in the Department of Electrical Engineering at the Dhurakijpundit University and a Ph.D. student majoring in electrical engineering at the King Mongkut’s Institute of Technology North Bangkok, (KMIT’NB). His Ph.D. research is on the area of modeling and analysis of power system transient using digital program. Teratam Bunyagul He received BEng (second class honor) degree in electrical engineering from King Mongkut’s Institute of Technology North Bangkok (KMITNB) in 1995. He obtained his M.Sc and Ph.D degrees from University Manchester Institute of Science and Technology (UMIST), UK in 1998 and 2003 respectively. He currently holds the position Head of Power System Laboratory for the department of electrical engineering at KMITNB. His main activity during academic career has involved research into new techniques in power system protection and control, the design and development of new types of protection relays and control systems. Somchai Chatratana He received his B.Eng. degree (Honors) in Electrical Engineering from Kasetsart University, Thailand, in 1974, M.Sc. D.I.C. and Ph.D. degree from Imperial College, London University, U.K., in 1978 and 1982 respectively. He was an Associate Professor at Electrical Engineering Department, King Mongkut’s Institute of Technology North Bangkok until 2003. He is now an Assistant to the President of National Science and Technology Development Agency(NSTDA). His currently research interests include control of electrical drives, power quality and FACTS.