SlideShare a Scribd company logo
1 of 37
Download to read offline
Transformer Calculations
Transformer Overcurrent
Protection
Calculations & Settings
Transformer Overcurrent
Protection
Calculations & Settings
Transformer Calculations
X
XF3
F4
X
X
F1
F2
51
50 51
51G
87T
63
SPR
ANSI / IEEE C37.91
F1: Fault cleared by
transformer primary side
relays
F2: Fault cleared by
transformer primary
side devices or neutral
protection relays
F3: Fault cleared by
transformer primary
side devices or by
secondary side relays
F4: Fault cleared by feeder
protection relays
Transformer Calculations
Transformer Calculations
X
XF3
F4
X
X
F1
F2
50 51
50G 51G
87H87T
50 51
87GD
Current Function
50 – Phase Instantaneous
Overcurrent
51 – Phase Time Overcurrent
Transformer Calculations
Typical Single Line Diagram
Transformer Calculations
1. Instantaneous units should be set so they do not
trip for fault levels equal or lower to those at
busbars or elements protected by downstream
instantaneous relays.
2. Time delay units should be set to clear faults in a
selective and reliable way, assuring the proper
coverage of the thermal limits of the equipment
protected.
Protection Coordinate Principles
Transformer Calculations
R1
CURRENT
t
R2
Coordination
Time Interval
Overcurrent inverse time relay curves associated
with two breakers on the same feeder
Coordination of TOC Delay
Transformer Calculations
A margin between two successive devices in the
order of 0.2 to 0.4 seconds should be used to avoid
losing selectivity due to one or more of the following
reasons:
Instantaneous units should be set so they do not
trip for fault levels equal or lower to those at
busbars or elements protected by downstream
instantaneous relays.
Time delay units should be set to clear faults in a
selective and reliable way, assuring the proper
coverage of the thermal limits of the equipment
protected.
Coordination Time Interval (CTI)
Transformer Calculations
Operating time defined by IEC and ANSI/IEEE:
t = Relay operating time in
seconds
TD = Time dial, or time multiplier
setting
I = Fault current level in
secondary amps
IP = Tap or pick up current
selected
B = Constant
p = Slope constant
A = Slope constant
P
M =
I
I
* IEEE equation constants are defined at TD of 5
=
A
TDt
− 1M
p
IEEE equation *
IEC equation
=t B+
A
− 1M
p
TD
5
Expression for Time Delay Setting
Transformer Calculations
Setting Time Delay on Overcurrent Relays
IDMT Curve Description Standard p A B
Moderately Inverse IEEE 0.02 0.0515 0.114
Very Inverse IEEE 2 19.61 0.491
Extremely Inverse IEEE 2 28.2 0.1217
Standard Inverse IEC 0.02 0.14
Very inverse IEC 1.0 13.5
Extremely inverse IEC 2.0 80.0
ANSI/IEEE and IEC constants for overcurrent relays
* IEEE equation constants are defined at TD of 5
Transformer Calculations
Operatingtime(s)
Current (Multiples of Is)
IEC EI
IEC VI
IEC SI
UK LTI
Current (Multiples of Is)
Operatingtime(s)
IEEE MI
IEEE VI
IEEE EI
US C08
US C02
IEC/UK
overcurrent
relay curves
IEEE/US
overcurrent
relay curves
IEC curves are IMDT
(Inverse Minimum Definite Time)
Standards of Time/Current Characteristics
Transformer Calculations
Dac Y
Dy11
X
X
X
1.0
1.0
1.0 1.0
1.0
1.0
1.0
1.0
1.0
0.58
0.58
0.58
Three phase fault on secondary
I
X
VI LG
F
==
31
2
I
N
N
IIdelta
==
III deltaprimary
== 3
Coordination across D-y Transformer
Transformer Calculations
Dac Y
Dy11
X
X
0.5
1.0
0.5 0.87
0.87
0
0.87
0.87
0
0.5
0.5
0
Phase-to-Phase Fault
I
x
V
X
V
I LG
F
2
3
2
3
2
===
22
3
1
2 I
N
N
IIdelta
=××=
III deltaprimary == 2
LL
Coordination across D-y Transformer
Transformer Calculations
Dac Y
Dy11
X
X
0
0.58
0.58 1.0
0
0
1.0
0
0
0.58
0
0
Phase-to-Ground Fault
3
I
Iprimary
=
31
2
I
N
N
IIdelta
==
I
X
VI LG
F
==
Coordination across D-y Transformer
Transformer Calculations
Fault Iprimary Isecondary
Three phase I I
Phase-to-phase
I 0.87I
Phase-to-earth 0.58I I
For SLGF on wye side, current withstand capability is
58% of that utilized for Delta-Delta
For Phase-Phase Faults on wye side, only 87% fault
current flows in secondary while 100% flows in primary
protector. 16% margin must be taken into account to
maintain primary to secondary protection selectivity.
Coordination across D-y Transformer
Transformer Calculations
A
t
If
2
3
If
0.4 Sec
Coordination of overcurrent relays for a Dy transformer
Coordination across D-y Transformer
Transformer Calculations
Minimum nameplate (kVA)
Category Single-phase Three-phase
I 5-500 15-500
II 501-1667 501-5000
III 1668-10,000 5001-30,000
IV above 10,000 above 30,000
IEEE Std. C57.109-1985 Curves
Transformer Categories
Transformer Calculations
X
XF3
F4
X
X
F1
F2
Infrequent Fault
Incident Zone
Frequent Fault
Incident Zone
Category 2 > 10
Category 3 > 5
Mechanical Damage:
Number Faults in Lifetime
Category II & III Fault Frequency
Transformer Calculations
Category II:
Thermal Limit: I ² t = 1250
Mechanical Limit: I ² t = K = (1/ZT) ² x t
K is determined at t = 2 seconds and at maximum I
in terms of multiples of self-cooled full load current.
The transition from thermal to mechanical plot
occurs at 70% of max possible multiplies of I, or
0.70x(1/ZT)
Category II Transformers
Transformer Calculations
2
Thermal Limit: I t = 1250
Category II – Transformer Through Fault Curves
Transformer Calculations
Thermal Limit: I ² t = 1250
ANSI C57.12 Appendix
Short-time thermal loading capability oil-immersed transformers
Time Multiples of I RATED
2 s 25.0 x
10 s 11.3 x
30 s 6.3 x
60 s 4.75 x
300 s 3.0 x
1800 s 2.0 x
All Category Transformers
Transformer Calculations
Times Normal Base Current
I TN = 16.67 p.u.
Transition from the Mechanical to
Thermal curve occurs at 70% of I TN:
0.70 x (1/ZT) = 11.67 p.u.
I TN = 11.67 p.u.
2
Thermal Limit: I t = 1250
ITN = Times Normal Current
K = I TN = (16.67) x 2 = 556
2
Mechanical Limit: K = I t = (1/ZT) t
defined at t = 2 seconds.
for ZT = 6%
I TN = 1/.06 =16.67 p.u.
2 2
2
t = 556 / (11.67) = 4.0
K = I t = (11.67) x t =5562 2
Wye-Wye or
Delta-Delta
Category II – Transformer Through Fault Curves
Transformer Calculations
Category 3:
Thermal Limit: I 2 t = 1250
Mechanical Limit: I 2 t = K = [ 1 / (ZT + ZS) ]2 x t
K is determined at t = 2 seconds and at maximum I in
terms of multiples of self-cooled full load current. The
transition from thermal to mechanical occurs at 50% of
max possible multiples of I, or
0.50x1/(ZT + ZS)
Category III Transformers
Transformer Calculations
Mechanical to Thermal
occurs at 50% of I TN:
0.50 x 1/(ZT+ ZS) = 7.15 p.u.
I TN = 7.15 p.u.
I TN = 14.3 p.u.
I TN = Times Normal Current
Thermal Limit: I t = 1250
2
K = (I TN) x t = (7.15) x t = 40922
t = 409 / (7.15) = 8.0
2
2
Mechanical Limit
K = I t = [1/ (ZS + ZT)]
defined at t = 2 seconds.
for ZT = 6% & ZS = 1%
K = (I TN) x t = (14.3) x 2 = 40922
I TN = (1/.07) = 14.3 p.u.
Wye-Wye or
Delta-Delta
Category III – Transformer Through Fault Curves
Transformer Calculations
Mechanical to Thermal
occurs at 50% of I TN:
0.50 x 1/(ZT+ ZS) = 7.14 p.u.
Delta-wye:
7.14 p.u. x 0.58 = 4.14 p.u.
I TN = 4.1 p.u.
I TN = 8.3 p.u.
2 2
Mechanical Limit
2
t = 138 / (4.14) = 8.0
I TN = Times Normal Current
Thermal Limit: I t = 1250
2
K = I TN x t = (8.3) x 2 = 138
22
K = I t = [1/ (ZS + ZT)]
defined at t = 2 seconds.
for ZT = 6% & ZS = 1%
I TN = 1/.07 =14.3 p.u.
Delta-wye:
14.3p.u. x 0.58 = 8.3 p.u.
Delta-Wye
Category III – Transformer Through Fault Curves
Transformer Calculations
OFAF (OA/FA/FOA)
30/40/50 MVA
230kV / 34.5 kV
X
X
X
X
F1 F2
F3 F4
Zs230kV
Z= 7%
Calculation Setting Example
Transformer Calculations
0.01 p.u. 0.07 p.u. 4.80 p.u.
VS = 1.0 p.u.
F1
X
F2/F3
X
F4
X
X
F1 ZT
A B
50
X
F3
Vs = 230kV
51
230kV / 34.5kV
30/40/50MVA
Z = 7%
ZLT = 25 MVAZS = 1.0%
on 230kV
ZS = 0.01 p.u.
ZT = 0.07 p.u.
F2
X
F4
X
51
51
50
Z Base =
30MVA
230kV 2
= 1763.3 ohm
ZLT =
25MVA
34.5kV 2
= 47.6 ohms
VBase = 230kV
MVA Base = 30MVA
Z LT at 230kV =
34.5kV
230kV 2
x 47.6 ohms = 2115.6 ohms
Z LT = (2115.6/1763.3) = 1.20 p.u.
ZL4 = 6.25MVA
Z L4 = 4.8 p.u.
ZL4 = 1/4 ZL4
Calculation Setting Example
Transformer Calculations
0.01 p.u. 0.07 p.u. 4.80 p.u.VS = 1.00 p.u. F1
X
F2/F3
X
F4
X
IBase at 230kV =
30MVA
3 x 230kV
= 75.3 A IBase at 34.5kV =
30MVA
3 x 34.5kV
= 502 A
IF1 =
IF2/F3 =
IF4 =
= 100.0 p.u.
= 12.5 p.u.
= 0.205 p.u.
0.01
(0.01 + 0.07)
(0.01 + 0.07 + 4.80)
1.00
1.00
1.00
IF1 = 100.0 x 75.3A = 7530A
12.5 x 75.3A = 941A
0.205 x 502A =103A at 34.5kV
IF4 =
IF2/F3 =
12.5 x 502 = 6275A at 34.5kV
0.205 x 75.3A = 15.4A
Short Circuit Currents
Transformer Calculations
Compatible with transformer overload capacity ≈ 200% of self-
cooled rating for wye CT’s and 350% (√3 x 200%) for Delta-
connected CT’s.
Wye - Wye CT’s:
230kV: IFL = 75.3A IF1 = 7530A
IF1(ASYS) = 1.6 x 7530A = 12,048A
Select CT 600:5 CTR = 120
34.5kV: IFL = 502A IF2 = 6275A
IF2(ASYS) = 1.6 x 6275A = 10,040A
CT Selected at 2 x IFL
Select CT 1000:5 CTR = 200
CT Criteria
Transformer Calculations
Set above Inrush current:
8 x IFL (Transformers 500 to 2500KVA)
10 x IFL (Transformers > 2500KVA) *
Inrush point at 0.1 second
* For Digital Relay using DFT use 5-6 x IFL
Set above maximum asymmetrical secondary fault current:
1.6 x IF SYM for Voltage > 5kV
1.5 x IF SYM for Voltage < 5kV
IOC Setting Criteria
Transformer Calculations
IOC Setting Criteria
Secondary side of transformer
The IOC function at the LV side is not used unless there
is communication (interlocking) with relays protecting
the feeders
Transformer Calculations
Set above Inrush current: ≈ 10 x IFL at 0.1 second.
10 X 73.5A = 735A
Set above maximum asymmetrical secondary fault current:
≈ 1.6 x IF SYM
1.6 x 941 = 1506A = 20.0 x IFL
I PICKUP = 1506A ÷ CTR = 1526A ÷ 120 = 12.65 Amps
IFL =
30MVA
3x 230kV
= 75.3 A IF2/F3 = 954A
IOC Relay Setting
Transformer Calculations
For phase relays, three-phase faults and
maximum short time overload should be
considered
For ground relays, line-to-ground faults and max
3Io should be considered
TOC Setting Criteria
Transformer Calculations
For phase relays, the Pickup value is determined by:
Pickup = (OLF x IFL) ÷ CTR
For ground fault relays, the Pickup value is determined,
with the maximum unbalance, typically around 20%:
Pickup = [(0.2) x IFL] ÷ CTR
Typical OLF for transformers = 1.25 to 1.5
TOC Setting Criteria
Transformer Calculations
Transformer: ZT < 6%
Primary Setting < 6 x IFL
Secondary Setting < 3 x IFL
Transformer: 6% > ZT < 10%
Primary Setting < 4 x IFL
Secondary Setting < 2.5 x IFL
Tap is set to meet NEC 450-3 and ANSI C37.91*
* Primary & secondary >600V with circuit breakers
TOC Setting Criteria
Transformer Calculations
Pickup = OLF x IFL ÷ CTR
I Pickup = 1.5 x 75.3 ÷ 120 = 0.94 Amps
I Relay setting = 0.94 ÷ 1.5 = 0.63 Amps
TD # 8 Very Inverse Curve
IFL =
30MVA
3x 230kV
= 75.3 A IF2/F3 = 954A
TOC Relay Setting
Transformer Calculations
I RELAY = 0.63 Amps
TD # 8
Very Inverse Curve
TOC Relay Curve
Transformer Calculations
50% of I TN = 0.50 x 1/(ZT+ ZS)
t = 105.1 / (3.625) = 8.0
I TN = Times Normal Current
Thermal Limit: I t = 1250
2
Mechanical Limit
K = I TN = (7.6) x 2 = 105.1
2
defined at t = 2 seconds.
for ZT = 7% & ZS = 1.0%
I TN = 1/.08 =12.5 p.u.
Delta-wye:
2 2
K = I t = [1/ (ZS + ZT)] x t
58% x 12.5 p.u. = 7.25 p.u.
Mechanical to Thermal
Delta-wye:
50% of I TN = 0.50 x 12.5 = 6.25 p.u.
58% x 6.25 p.u. = 3.625 p.u.
IOC set at 12.6A pickup
1.6 x IFL/CTR = 1.6 x 941/120 = 12.6A
1.6 x IFL =1.6 x 12.5p.u. = 20.0 ITN
TOC set at 0.63A pickup
1.5 x ITN/CTR = 1.5 x 73.5A/120 = 0.94A
Minimum multiple of pickup is 1.5
0.94A/1.5 = 0.63A, TD#8
Very Inverse TOC curve
0
0
1
10
100
1000
10000
0 1 10 100
TIMES NORMAL BASE CURRENT
TIME(SECONDS)
IFLSYM
IFL
I inrush
0.1
0.01
0.1
2.5xIFL
4.0xIFL
IFLASYM
2
IFL SYM
3-phase
IFL SYM
phase-phase
Coordination
Interval
50/51
51
50/51
51
2
IOC & TOC Coordination
Transformer Calculations
Questions ?Questions ?
©2008 Beckwith Electric Co., Inc.

More Related Content

What's hot

Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 
Current transformer (ct)
Current transformer (ct)Current transformer (ct)
Current transformer (ct)Jay Ranvir
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordinationmichaeljmack
 
ETAP - Transformer mva sizing
ETAP - Transformer mva sizingETAP - Transformer mva sizing
ETAP - Transformer mva sizingHimmelstern
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNadir Baloch
 
Loss of excitation
Loss of excitationLoss of excitation
Loss of excitationNTPC
 
Current differential line protection setting considerations
Current differential line protection setting considerationsCurrent differential line protection setting considerations
Current differential line protection setting considerationsAsim Ihsan
 
Ipsa mv relay co-ordiantion shaik adam
Ipsa  mv relay  co-ordiantion shaik adamIpsa  mv relay  co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adamShaik Abdullah Adam
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector groupShyamkant Vasekar
 

What's hot (20)

Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Fault level calculations
Fault level calculationsFault level calculations
Fault level calculations
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Current transformer (ct)
Current transformer (ct)Current transformer (ct)
Current transformer (ct)
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
ETAP - Transformer mva sizing
ETAP - Transformer mva sizingETAP - Transformer mva sizing
ETAP - Transformer mva sizing
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Loss of excitation
Loss of excitationLoss of excitation
Loss of excitation
 
Current differential line protection setting considerations
Current differential line protection setting considerationsCurrent differential line protection setting considerations
Current differential line protection setting considerations
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Ipsa mv relay co-ordiantion shaik adam
Ipsa  mv relay  co-ordiantion shaik adamIpsa  mv relay  co-ordiantion shaik adam
Ipsa mv relay co-ordiantion shaik adam
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Overcurrent coordination
Overcurrent coordinationOvercurrent coordination
Overcurrent coordination
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
 

Viewers also liked

Scheme logic implement pwr plant cntrl
Scheme logic implement pwr plant cntrlScheme logic implement pwr plant cntrl
Scheme logic implement pwr plant cntrlmichaeljmack
 
Interconnet protection of
Interconnet protection ofInterconnet protection of
Interconnet protection ofmichaeljmack
 
oshpd emergency power supply systems
oshpd emergency power supply systemsoshpd emergency power supply systems
oshpd emergency power supply systemsmichaeljmack
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and groundingmichaeljmack
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systemsmichaeljmack
 
Auto synch considerations methods
Auto synch considerations methodsAuto synch considerations methods
Auto synch considerations methodsmichaeljmack
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Transformer protection commissioning tools
Transformer protection commissioning toolsTransformer protection commissioning tools
Transformer protection commissioning toolsmichaeljmack
 
Automatic synch of gen
Automatic synch of genAutomatic synch of gen
Automatic synch of genmichaeljmack
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodinationmichaeljmack
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic conceptsmichaeljmack
 

Viewers also liked (13)

Scheme logic implement pwr plant cntrl
Scheme logic implement pwr plant cntrlScheme logic implement pwr plant cntrl
Scheme logic implement pwr plant cntrl
 
Interconnet protection of
Interconnet protection ofInterconnet protection of
Interconnet protection of
 
oshpd emergency power supply systems
oshpd emergency power supply systemsoshpd emergency power supply systems
oshpd emergency power supply systems
 
Out of step
Out of stepOut of step
Out of step
 
Ieee pes psrc
Ieee pes psrcIeee pes psrc
Ieee pes psrc
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and grounding
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systems
 
Auto synch considerations methods
Auto synch considerations methodsAuto synch considerations methods
Auto synch considerations methods
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Transformer protection commissioning tools
Transformer protection commissioning toolsTransformer protection commissioning tools
Transformer protection commissioning tools
 
Automatic synch of gen
Automatic synch of genAutomatic synch of gen
Automatic synch of gen
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodination
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic concepts
 

Similar to Transformer overcurrent

Original IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New Toshiba
Original IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New ToshibaOriginal IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New Toshiba
Original IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New Toshibaauthelectroniccom
 
132kv-substation-settings_compress.pdf
132kv-substation-settings_compress.pdf132kv-substation-settings_compress.pdf
132kv-substation-settings_compress.pdfssuser4d1f4f
 
Chapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfChapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfLiewChiaPing
 
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 NewOriginal Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 NewAUTHELECTRONIC
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionChandrabhan Sharma
 
03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.pptssuserce455a1
 
Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...
Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...
Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...authelectroniccom
 
Transformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.docTransformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.docMdAbdullahAlMamun258178
 
Bus ele tech_lib_electrical_formulas
Bus ele tech_lib_electrical_formulasBus ele tech_lib_electrical_formulas
Bus ele tech_lib_electrical_formulasCasi G Morales
 
Original Opto LTV-354T LTV354T 354T 354 SOP-4 New
Original Opto LTV-354T LTV354T 354T 354 SOP-4 NewOriginal Opto LTV-354T LTV354T 354T 354 SOP-4 New
Original Opto LTV-354T LTV354T 354T 354 SOP-4 NewAUTHELECTRONIC
 
AVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.pptAVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.pptprasadkappala
 
CURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxCURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxManishPandya29
 

Similar to Transformer overcurrent (20)

5010566.ppt
5010566.ppt5010566.ppt
5010566.ppt
 
CT and VT.pptx
CT and VT.pptxCT and VT.pptx
CT and VT.pptx
 
Original IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New Toshiba
Original IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New ToshibaOriginal IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New Toshiba
Original IGBT N-CHANNEL GT15J321 15J321 15A 600V TO-220 New Toshiba
 
K2917.pptx
K2917.pptxK2917.pptx
K2917.pptx
 
132kv-substation-settings_compress.pdf
132kv-substation-settings_compress.pdf132kv-substation-settings_compress.pdf
132kv-substation-settings_compress.pdf
 
Chapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdfChapter 3 Controlled Rectifier.pdf
Chapter 3 Controlled Rectifier.pdf
 
DC Component of Fault Current
DC Component of Fault CurrentDC Component of Fault Current
DC Component of Fault Current
 
Spx29300 t 2.5-tr
Spx29300 t 2.5-trSpx29300 t 2.5-tr
Spx29300 t 2.5-tr
 
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 NewOriginal Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent Protection
 
03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt
 
219118530 day-1-part-2-c ts-and-vts
219118530 day-1-part-2-c ts-and-vts219118530 day-1-part-2-c ts-and-vts
219118530 day-1-part-2-c ts-and-vts
 
Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...
Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...
Original Opto TLP620GB TLP620 P620 620 DIP-4 New ToshibaOriginal Opto TLP620G...
 
Transformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.docTransformerprotectionrelaycalculations.doc
Transformerprotectionrelaycalculations.doc
 
Bus ele tech_lib_electrical_formulas
Bus ele tech_lib_electrical_formulasBus ele tech_lib_electrical_formulas
Bus ele tech_lib_electrical_formulas
 
Lm331
Lm331Lm331
Lm331
 
Trafo arus
Trafo arusTrafo arus
Trafo arus
 
Original Opto LTV-354T LTV354T 354T 354 SOP-4 New
Original Opto LTV-354T LTV354T 354T 354 SOP-4 NewOriginal Opto LTV-354T LTV354T 354T 354 SOP-4 New
Original Opto LTV-354T LTV354T 354T 354 SOP-4 New
 
AVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.pptAVR_GENERAL KOSTI.ppt
AVR_GENERAL KOSTI.ppt
 
CURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxCURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptx
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 

Recently uploaded

Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 

Recently uploaded (20)

Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 

Transformer overcurrent

  • 1. Transformer Calculations Transformer Overcurrent Protection Calculations & Settings Transformer Overcurrent Protection Calculations & Settings
  • 2. Transformer Calculations X XF3 F4 X X F1 F2 51 50 51 51G 87T 63 SPR ANSI / IEEE C37.91 F1: Fault cleared by transformer primary side relays F2: Fault cleared by transformer primary side devices or neutral protection relays F3: Fault cleared by transformer primary side devices or by secondary side relays F4: Fault cleared by feeder protection relays Transformer Calculations
  • 3. Transformer Calculations X XF3 F4 X X F1 F2 50 51 50G 51G 87H87T 50 51 87GD Current Function 50 – Phase Instantaneous Overcurrent 51 – Phase Time Overcurrent Transformer Calculations Typical Single Line Diagram
  • 4. Transformer Calculations 1. Instantaneous units should be set so they do not trip for fault levels equal or lower to those at busbars or elements protected by downstream instantaneous relays. 2. Time delay units should be set to clear faults in a selective and reliable way, assuring the proper coverage of the thermal limits of the equipment protected. Protection Coordinate Principles
  • 5. Transformer Calculations R1 CURRENT t R2 Coordination Time Interval Overcurrent inverse time relay curves associated with two breakers on the same feeder Coordination of TOC Delay
  • 6. Transformer Calculations A margin between two successive devices in the order of 0.2 to 0.4 seconds should be used to avoid losing selectivity due to one or more of the following reasons: Instantaneous units should be set so they do not trip for fault levels equal or lower to those at busbars or elements protected by downstream instantaneous relays. Time delay units should be set to clear faults in a selective and reliable way, assuring the proper coverage of the thermal limits of the equipment protected. Coordination Time Interval (CTI)
  • 7. Transformer Calculations Operating time defined by IEC and ANSI/IEEE: t = Relay operating time in seconds TD = Time dial, or time multiplier setting I = Fault current level in secondary amps IP = Tap or pick up current selected B = Constant p = Slope constant A = Slope constant P M = I I * IEEE equation constants are defined at TD of 5 = A TDt − 1M p IEEE equation * IEC equation =t B+ A − 1M p TD 5 Expression for Time Delay Setting
  • 8. Transformer Calculations Setting Time Delay on Overcurrent Relays IDMT Curve Description Standard p A B Moderately Inverse IEEE 0.02 0.0515 0.114 Very Inverse IEEE 2 19.61 0.491 Extremely Inverse IEEE 2 28.2 0.1217 Standard Inverse IEC 0.02 0.14 Very inverse IEC 1.0 13.5 Extremely inverse IEC 2.0 80.0 ANSI/IEEE and IEC constants for overcurrent relays * IEEE equation constants are defined at TD of 5
  • 9. Transformer Calculations Operatingtime(s) Current (Multiples of Is) IEC EI IEC VI IEC SI UK LTI Current (Multiples of Is) Operatingtime(s) IEEE MI IEEE VI IEEE EI US C08 US C02 IEC/UK overcurrent relay curves IEEE/US overcurrent relay curves IEC curves are IMDT (Inverse Minimum Definite Time) Standards of Time/Current Characteristics
  • 10. Transformer Calculations Dac Y Dy11 X X X 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.58 0.58 0.58 Three phase fault on secondary I X VI LG F == 31 2 I N N IIdelta == III deltaprimary == 3 Coordination across D-y Transformer
  • 11. Transformer Calculations Dac Y Dy11 X X 0.5 1.0 0.5 0.87 0.87 0 0.87 0.87 0 0.5 0.5 0 Phase-to-Phase Fault I x V X V I LG F 2 3 2 3 2 === 22 3 1 2 I N N IIdelta =××= III deltaprimary == 2 LL Coordination across D-y Transformer
  • 12. Transformer Calculations Dac Y Dy11 X X 0 0.58 0.58 1.0 0 0 1.0 0 0 0.58 0 0 Phase-to-Ground Fault 3 I Iprimary = 31 2 I N N IIdelta == I X VI LG F == Coordination across D-y Transformer
  • 13. Transformer Calculations Fault Iprimary Isecondary Three phase I I Phase-to-phase I 0.87I Phase-to-earth 0.58I I For SLGF on wye side, current withstand capability is 58% of that utilized for Delta-Delta For Phase-Phase Faults on wye side, only 87% fault current flows in secondary while 100% flows in primary protector. 16% margin must be taken into account to maintain primary to secondary protection selectivity. Coordination across D-y Transformer
  • 14. Transformer Calculations A t If 2 3 If 0.4 Sec Coordination of overcurrent relays for a Dy transformer Coordination across D-y Transformer
  • 15. Transformer Calculations Minimum nameplate (kVA) Category Single-phase Three-phase I 5-500 15-500 II 501-1667 501-5000 III 1668-10,000 5001-30,000 IV above 10,000 above 30,000 IEEE Std. C57.109-1985 Curves Transformer Categories
  • 16. Transformer Calculations X XF3 F4 X X F1 F2 Infrequent Fault Incident Zone Frequent Fault Incident Zone Category 2 > 10 Category 3 > 5 Mechanical Damage: Number Faults in Lifetime Category II & III Fault Frequency
  • 17. Transformer Calculations Category II: Thermal Limit: I ² t = 1250 Mechanical Limit: I ² t = K = (1/ZT) ² x t K is determined at t = 2 seconds and at maximum I in terms of multiples of self-cooled full load current. The transition from thermal to mechanical plot occurs at 70% of max possible multiplies of I, or 0.70x(1/ZT) Category II Transformers
  • 18. Transformer Calculations 2 Thermal Limit: I t = 1250 Category II – Transformer Through Fault Curves
  • 19. Transformer Calculations Thermal Limit: I ² t = 1250 ANSI C57.12 Appendix Short-time thermal loading capability oil-immersed transformers Time Multiples of I RATED 2 s 25.0 x 10 s 11.3 x 30 s 6.3 x 60 s 4.75 x 300 s 3.0 x 1800 s 2.0 x All Category Transformers
  • 20. Transformer Calculations Times Normal Base Current I TN = 16.67 p.u. Transition from the Mechanical to Thermal curve occurs at 70% of I TN: 0.70 x (1/ZT) = 11.67 p.u. I TN = 11.67 p.u. 2 Thermal Limit: I t = 1250 ITN = Times Normal Current K = I TN = (16.67) x 2 = 556 2 Mechanical Limit: K = I t = (1/ZT) t defined at t = 2 seconds. for ZT = 6% I TN = 1/.06 =16.67 p.u. 2 2 2 t = 556 / (11.67) = 4.0 K = I t = (11.67) x t =5562 2 Wye-Wye or Delta-Delta Category II – Transformer Through Fault Curves
  • 21. Transformer Calculations Category 3: Thermal Limit: I 2 t = 1250 Mechanical Limit: I 2 t = K = [ 1 / (ZT + ZS) ]2 x t K is determined at t = 2 seconds and at maximum I in terms of multiples of self-cooled full load current. The transition from thermal to mechanical occurs at 50% of max possible multiples of I, or 0.50x1/(ZT + ZS) Category III Transformers
  • 22. Transformer Calculations Mechanical to Thermal occurs at 50% of I TN: 0.50 x 1/(ZT+ ZS) = 7.15 p.u. I TN = 7.15 p.u. I TN = 14.3 p.u. I TN = Times Normal Current Thermal Limit: I t = 1250 2 K = (I TN) x t = (7.15) x t = 40922 t = 409 / (7.15) = 8.0 2 2 Mechanical Limit K = I t = [1/ (ZS + ZT)] defined at t = 2 seconds. for ZT = 6% & ZS = 1% K = (I TN) x t = (14.3) x 2 = 40922 I TN = (1/.07) = 14.3 p.u. Wye-Wye or Delta-Delta Category III – Transformer Through Fault Curves
  • 23. Transformer Calculations Mechanical to Thermal occurs at 50% of I TN: 0.50 x 1/(ZT+ ZS) = 7.14 p.u. Delta-wye: 7.14 p.u. x 0.58 = 4.14 p.u. I TN = 4.1 p.u. I TN = 8.3 p.u. 2 2 Mechanical Limit 2 t = 138 / (4.14) = 8.0 I TN = Times Normal Current Thermal Limit: I t = 1250 2 K = I TN x t = (8.3) x 2 = 138 22 K = I t = [1/ (ZS + ZT)] defined at t = 2 seconds. for ZT = 6% & ZS = 1% I TN = 1/.07 =14.3 p.u. Delta-wye: 14.3p.u. x 0.58 = 8.3 p.u. Delta-Wye Category III – Transformer Through Fault Curves
  • 24. Transformer Calculations OFAF (OA/FA/FOA) 30/40/50 MVA 230kV / 34.5 kV X X X X F1 F2 F3 F4 Zs230kV Z= 7% Calculation Setting Example
  • 25. Transformer Calculations 0.01 p.u. 0.07 p.u. 4.80 p.u. VS = 1.0 p.u. F1 X F2/F3 X F4 X X F1 ZT A B 50 X F3 Vs = 230kV 51 230kV / 34.5kV 30/40/50MVA Z = 7% ZLT = 25 MVAZS = 1.0% on 230kV ZS = 0.01 p.u. ZT = 0.07 p.u. F2 X F4 X 51 51 50 Z Base = 30MVA 230kV 2 = 1763.3 ohm ZLT = 25MVA 34.5kV 2 = 47.6 ohms VBase = 230kV MVA Base = 30MVA Z LT at 230kV = 34.5kV 230kV 2 x 47.6 ohms = 2115.6 ohms Z LT = (2115.6/1763.3) = 1.20 p.u. ZL4 = 6.25MVA Z L4 = 4.8 p.u. ZL4 = 1/4 ZL4 Calculation Setting Example
  • 26. Transformer Calculations 0.01 p.u. 0.07 p.u. 4.80 p.u.VS = 1.00 p.u. F1 X F2/F3 X F4 X IBase at 230kV = 30MVA 3 x 230kV = 75.3 A IBase at 34.5kV = 30MVA 3 x 34.5kV = 502 A IF1 = IF2/F3 = IF4 = = 100.0 p.u. = 12.5 p.u. = 0.205 p.u. 0.01 (0.01 + 0.07) (0.01 + 0.07 + 4.80) 1.00 1.00 1.00 IF1 = 100.0 x 75.3A = 7530A 12.5 x 75.3A = 941A 0.205 x 502A =103A at 34.5kV IF4 = IF2/F3 = 12.5 x 502 = 6275A at 34.5kV 0.205 x 75.3A = 15.4A Short Circuit Currents
  • 27. Transformer Calculations Compatible with transformer overload capacity ≈ 200% of self- cooled rating for wye CT’s and 350% (√3 x 200%) for Delta- connected CT’s. Wye - Wye CT’s: 230kV: IFL = 75.3A IF1 = 7530A IF1(ASYS) = 1.6 x 7530A = 12,048A Select CT 600:5 CTR = 120 34.5kV: IFL = 502A IF2 = 6275A IF2(ASYS) = 1.6 x 6275A = 10,040A CT Selected at 2 x IFL Select CT 1000:5 CTR = 200 CT Criteria
  • 28. Transformer Calculations Set above Inrush current: 8 x IFL (Transformers 500 to 2500KVA) 10 x IFL (Transformers > 2500KVA) * Inrush point at 0.1 second * For Digital Relay using DFT use 5-6 x IFL Set above maximum asymmetrical secondary fault current: 1.6 x IF SYM for Voltage > 5kV 1.5 x IF SYM for Voltage < 5kV IOC Setting Criteria
  • 29. Transformer Calculations IOC Setting Criteria Secondary side of transformer The IOC function at the LV side is not used unless there is communication (interlocking) with relays protecting the feeders
  • 30. Transformer Calculations Set above Inrush current: ≈ 10 x IFL at 0.1 second. 10 X 73.5A = 735A Set above maximum asymmetrical secondary fault current: ≈ 1.6 x IF SYM 1.6 x 941 = 1506A = 20.0 x IFL I PICKUP = 1506A ÷ CTR = 1526A ÷ 120 = 12.65 Amps IFL = 30MVA 3x 230kV = 75.3 A IF2/F3 = 954A IOC Relay Setting
  • 31. Transformer Calculations For phase relays, three-phase faults and maximum short time overload should be considered For ground relays, line-to-ground faults and max 3Io should be considered TOC Setting Criteria
  • 32. Transformer Calculations For phase relays, the Pickup value is determined by: Pickup = (OLF x IFL) ÷ CTR For ground fault relays, the Pickup value is determined, with the maximum unbalance, typically around 20%: Pickup = [(0.2) x IFL] ÷ CTR Typical OLF for transformers = 1.25 to 1.5 TOC Setting Criteria
  • 33. Transformer Calculations Transformer: ZT < 6% Primary Setting < 6 x IFL Secondary Setting < 3 x IFL Transformer: 6% > ZT < 10% Primary Setting < 4 x IFL Secondary Setting < 2.5 x IFL Tap is set to meet NEC 450-3 and ANSI C37.91* * Primary & secondary >600V with circuit breakers TOC Setting Criteria
  • 34. Transformer Calculations Pickup = OLF x IFL ÷ CTR I Pickup = 1.5 x 75.3 ÷ 120 = 0.94 Amps I Relay setting = 0.94 ÷ 1.5 = 0.63 Amps TD # 8 Very Inverse Curve IFL = 30MVA 3x 230kV = 75.3 A IF2/F3 = 954A TOC Relay Setting
  • 35. Transformer Calculations I RELAY = 0.63 Amps TD # 8 Very Inverse Curve TOC Relay Curve
  • 36. Transformer Calculations 50% of I TN = 0.50 x 1/(ZT+ ZS) t = 105.1 / (3.625) = 8.0 I TN = Times Normal Current Thermal Limit: I t = 1250 2 Mechanical Limit K = I TN = (7.6) x 2 = 105.1 2 defined at t = 2 seconds. for ZT = 7% & ZS = 1.0% I TN = 1/.08 =12.5 p.u. Delta-wye: 2 2 K = I t = [1/ (ZS + ZT)] x t 58% x 12.5 p.u. = 7.25 p.u. Mechanical to Thermal Delta-wye: 50% of I TN = 0.50 x 12.5 = 6.25 p.u. 58% x 6.25 p.u. = 3.625 p.u. IOC set at 12.6A pickup 1.6 x IFL/CTR = 1.6 x 941/120 = 12.6A 1.6 x IFL =1.6 x 12.5p.u. = 20.0 ITN TOC set at 0.63A pickup 1.5 x ITN/CTR = 1.5 x 73.5A/120 = 0.94A Minimum multiple of pickup is 1.5 0.94A/1.5 = 0.63A, TD#8 Very Inverse TOC curve 0 0 1 10 100 1000 10000 0 1 10 100 TIMES NORMAL BASE CURRENT TIME(SECONDS) IFLSYM IFL I inrush 0.1 0.01 0.1 2.5xIFL 4.0xIFL IFLASYM 2 IFL SYM 3-phase IFL SYM phase-phase Coordination Interval 50/51 51 50/51 51 2 IOC & TOC Coordination
  • 37. Transformer Calculations Questions ?Questions ? ©2008 Beckwith Electric Co., Inc.