Power System Protection
Dr. Ibrahim El-Amin
Protective Device Coordination
Definition
 Overcurrent Coordination
 A systematic study of current responsive devices
in an electrical power system.
Objective
 To determine the ratings and settings of
fuses, breakers, relay, etc.
 To isolate the fault or overloads.
Criteria
 Economics
 Available Measures of Fault
 Operating Practices
 Previous Experience
Design
 Open only PD upstream of the fault or overload
 Provide satisfactory protection for overloads
 Interrupt SC as rapidly (instantaneously) as
possible
 Comply with all applicable standards and codes
 Plot the Time Current Characteristics of
different PDs
Analysis
When:
 New electrical systems
 Plant electrical system expansion/retrofits
 Coordination failure in an existing plant
Protection vs. Coordination
 Coordination is not an exact science
 Compromise between protection and
coordination
 Reliability
 Speed
 Performance
 Economics
 Simplicity
Protection
 Prevent injury to personnel
 Minimize damage to components
 Quickly isolate the affected portion of the system
 Minimize the magnitude of available short-circuit
Spectrum Of Currents
 Load Current
 Up to 100% of full-load
 115-125% (mild overload)
 Overcurrent
 Abnormal loading condition (Locked-Rotor)
 Fault Current
 Fault condition
 Ten times the full-load current and higher
Coordination
 Limit the extend and duration of service
interruption
 Selective fault isolation
 Provide alternate circuits
Coordination
t
I
C B A
C
D
D B
A
Equipment
 Motor
 Transformer
 Generator
 Cable
 Busway
Capability / Damage Curves
t
I
I2
2
t
Gen
I2
t
Motor
Xfmr
I2
t
Cable
I2
t
Transformer Category
ANSI/IEEE C-57.109
Minimum nameplate (kVA)
Category Single-phase Three-phase
I 5-500 15-500
II 501-1667 501-5000
III 1668-10,000 5001-30,000
IV above 1000 above 30,000
Infrequent Fault Incidence Zones for Category II & III Transformers
* Should be selected by reference to the frequent-fault-incidence protection curve or for
transformers serving industrial, commercial and institutional power systems with secondary-side
conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by
reference to the infrequent-fault-incidence protection curve.
Source: IEEE C57
Source
Transformer primary-side protective device
(fuses, relayed circuit breakers, etc.) may be
selected by reference to the infrequent-fault-
incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer
primary-side protective device
Optional main secondary –side protective device.
May be selected by reference to the infrequent-fault-
incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side
protective device or by optional main secondary-
side protection device
Fault will be cleared by
feeder protective device
Infrequent-Fault
Incidence Zone*
Feeders
Frequent-Fault
Incidence Zone*
Transformer
t
(sec)
I (pu)
Thermal
200
2.5
I
2
t = 1250
2
25
Isc
Mechanical
K=(1/Z)
2
t
(D-D LL) 0.87
(D-R LG) 0.58
Frequent Fault
Infrequent Fault
Inrush
FLA
Transformer Protection
MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE
PRIMARY SECONDARY
Over 600 Volts Over 600 Volts 600 Volts or Below
Transformer
Rated
Impedance
Circuit
Breaker
Setting
Fuse
Rating
Circuit
Breaker
Setting
Fuse
Rating
Circuit Breaker
Setting or Fuse
Rating
Not more than
6%
600 % 300 % 300 % 250% 125%
(250% supervised)
More than 6%
and not more
than 10%
400 % 300 % 250% 225% 125%
(250% supervised)
Table 450-3(a) source: NEC
Protective Devices
 Fuse
 Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, …)
 Thermal Magnetic
 Low Voltage Solid State Trip
 Electro-Mechanical
 MCP
 Overload Heater
Fuse
 Non Adjustable Device
 Continuous and Interrupting Rating
 Voltage Levels
 Characteristic Curves
 Min. Melting
 Total Clearing
 Application
Minimum Melting
Time Curve
Total Clearing
Time Curve
Current Limiting Fuse
(CLF)
 Limits the peak current of short-circuit
 Reduces magnetic stresses (mechanical
damage)
 Reduces thermal energy
Symmetrical RMS Amperes
Peak
Let-Through
Amperes
100 A
60 A
15% PF (X/R = 6.6)
12,500
5,200
230,000
300 A
100,000
Let-Through Chart
Fuse
Generally:
 CLF is a better short-circuit protection
 Non-CLF (expulsion fuse) is a better Overload
protection
Selectivity Criteria
Typically:
 Non-CLF: 140% of full load
 CLF: 150% of full load
Molder Case CB
 Thermal-Magnetic
 Magnetic Only
 Integrally Fused
 Current Limiting
 High Interrupting
Capacity
Types
 Frame Size
 Trip Rating
 Interrupting Capability
 Voltage
Thermal Minimum
Thermal Maximum
Magnetic
(instantaneous)
LVPCB
 Voltage and Frequency Ratings
 Continuous Current / Frame Size
 Override (12 times cont. current)
 Interrupting Rating
 Short-Time Rating (30 cycle)
 Fairly Simple to Coordinate
480 kV
CB 2
CB 1
CB 2
CB 1
IT
ST PU
ST Band
LT PU
LT Band
If =30 kA
Motor Protection
 Motor Starting Curve
 Thermal Protection
 Locked Rotor Protection
 Fault Protection
Motor Overload Protection
(NEC Art 430-32)
 Thermal O/L (Device 49)
 Motors with SF not less than 1.15
 125% of FLA
 Motors with temp. rise not over 40
 125% of FLA
 All other motors
 115% of FLA
Locked Rotor Protection
 Thermal Locked Rotor (Device 51)
 Starting Time (TS < TLR)
 LRA
 LRA sym
 LRA asym (1.5-1.6 x LRA sym) + 10% margin
Fault Protection
(NEC Art 430-52)
 Non-Time Delay Fuses
 300% of FLA
 Dual Element (Time-Delay Fuses)
 175% of FLA
 Instantaneous Trip Breaker
 800% of FLA*
 Inverse Time Breakers
 250% of FLA
*MCPs can be set higher
200 HP
MCP
O/L
Starting Curve
I
2
T
(49)
MCP (50)
(51)
ts
tLR
LRAs LRAasym
Overcurrent Relay
 Time-Delay (51 – I>)
 Short-Time Instantaneous ( I>>)
 Instantaneous (50 – I>>>)
 Electromagnetic (induction Disc)
 Solid State (Multi Function / Multi Level)
 Application
Time-Overcurrent Unit
 Ampere Tap Calculation
 Ampere Pickup (P.U.) = CT Ratio x A.T. Setting
 Relay Current (IR) = Actual Line Current (IL) / CT
Ratio
 Multiples of A.T. = IR/A.T. Setting
= IL/(CT Ratio x A.T. Setting)
IL
IR
CT
51
Instantaneous Unit
 Instantaneous Calculation
 Ampere Pickup (P.U.) = CT Ratio x IT Setting
 Relay Current (IR) = Actual Line Current (IL) / CT
Ratio
 Multiples of IT= IR/IT Setting
= IL/(CT Ratio x IT Setting)
IL
IR
CT
50
41
Relay Coordination
 Time margins should be maintained between T/C
curves
 Adjustment should be made for CB opening time
 Shorter time intervals may be used for solid state
relays
 Upstream relay should have the same inverse T/C
characteristic as the downstream relay (CO-8 to CO-8)
or be less inverse (CO-8 upstream to CO-6
downstream)
 Extremely inverse relays coordinates very well with
CLFs
Fixed Points
 Motor starting curves
 Transformer damage curves & inrush
points
 Cable damage curves
 SC maximum fault points
 Cable ampacities
Points or curves which do not change
regardless of protective device settings:
Situation
Calculate Relay Setting (Tap, Inst. Tap & Time Dial)
For This System
4.16 kV
DS 5 MVA
Cable
1-3/C 500 kcmil
CU - EPR
CB
Isc = 30,000 A
6 %
50/51 Relay: IFC 53
CT 800:5
Solution
A
Inrsuh 328
,
8
694
12
I 


A
338
.
4
800
5
I
I L
R 


Transformer: A
kV
kVA
L 694
16
.
4
3
000
,
5
I 


IL
CT
R
IR
Set Relay:
A
55
1
.
52
800
5
328
,
8
)
50
(
1
)
38
.
1
(6/4.338
0
.
6
4
.
5
338
.
4
%
125









A
Inst
TD
A
TAP
A
Question
What is ANSI Shift Curve?
Answer
 For delta-delta connected transformers, with
line-to-line faults on the secondary side, the
curve must be reduced to 87% (shift to the left
by a factor of 0.87)
 For delta-wye connection, with single line-to-
ground faults on the secondary side, the curve
values must be reduced to 58% (shift to the left
by a factor of 0.58)
Question
What is meant by Frequent and
Infrequent for transformers?
Answer
Infrequent Fault Incidence Zones for Category II & III Transformers
Source
Transformer primary-side protective device
(fuses, relayed circuit breakers, etc.) May be
selected by reference to the infrequent-fault-
incidence protection curve
Category II or III Transformer
Fault will be cleared by transformer
primary-side protective device
Optional main secondary –side protective device.
May be selected by reference to the infrequent-fault-
incidence protection curve
Feeder protective device
Fault will be cleared by transformer primary-side
protective device or by optional main secondary-
side protection device
Fault will be cleared by
feeder protective device
Infrequent-Fault
Incidence Zone*
Feeders
Frequent-Fault
Incidence Zone*
Question
What T/C Coordination interval should be
maintained between relays?
Answer
A
t
I
B
CB Opening Time
+
Induction Disc Overtravel (0.1 sec)
+
Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
Question
What is Class 10 and Class 20
Thermal OLR curves?
Answer
 Class 10 for fast trip, 10 seconds or less
 Class 20 for, 20 seconds or less
 There is also a Class 30 for long trip time
Answer

More Related Content

Similar to 5010566.ppt

03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.pptssuserce455a1
 
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptxLecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptxssuserb444c3
 
An-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfAn-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfRamprasadSarkar1
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsJames S Nasby
 
Switchgear and Protection.................
Switchgear and Protection.................Switchgear and Protection.................
Switchgear and Protection.................MANOJ KHARADE
 
Switchgear and Protection ...........................
Switchgear and Protection ...........................Switchgear and Protection ...........................
Switchgear and Protection ...........................MANOJ KHARADE
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 
Lecture 7 Relay Coordination.pptx
Lecture 7 Relay Coordination.pptxLecture 7 Relay Coordination.pptx
Lecture 7 Relay Coordination.pptxssuserb444c3
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
What is Power Quality?
What is Power Quality?What is Power Quality?
What is Power Quality?svergin
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power Systemvkmalik
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxshivendra68
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protectionDinesh Sharma
 
Electrical Protection systems in Thermal power stations.ppt
Electrical Protection systems in Thermal power stations.pptElectrical Protection systems in Thermal power stations.ppt
Electrical Protection systems in Thermal power stations.pptNarasimhanRengarajan1
 
17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdfThien Phan Bản
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. katoAgrey Kato
 
Generator protection
Generator protectionGenerator protection
Generator protectionKeshar Rawal
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substationPanneerselvam Rathinam
 

Similar to 5010566.ppt (20)

03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt03-Non-Dir. Overcurrent.ppt
03-Non-Dir. Overcurrent.ppt
 
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptxLecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
Lecture 1. INTRODUCTION TO BASIC PROTECTION AND RELAYING SCHEMES.pptx
 
An-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdfAn-Overview-of-Protection-System-Analysis-3.pdf
An-Overview-of-Protection-System-Analysis-3.pdf
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC Considerations
 
Switchgear and Protection.................
Switchgear and Protection.................Switchgear and Protection.................
Switchgear and Protection.................
 
Switchgear and Protection ...........................
Switchgear and Protection ...........................Switchgear and Protection ...........................
Switchgear and Protection ...........................
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
Lecture 7 Relay Coordination.pptx
Lecture 7 Relay Coordination.pptxLecture 7 Relay Coordination.pptx
Lecture 7 Relay Coordination.pptx
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
What is Power Quality?
What is Power Quality?What is Power Quality?
What is Power Quality?
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptx
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
Electrical Protection systems in Thermal power stations.ppt
Electrical Protection systems in Thermal power stations.pptElectrical Protection systems in Thermal power stations.ppt
Electrical Protection systems in Thermal power stations.ppt
 
17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 

More from Nafir Anas

dokumen.tips_500-kv-substation-grounding-presentation.pdf
dokumen.tips_500-kv-substation-grounding-presentation.pdfdokumen.tips_500-kv-substation-grounding-presentation.pdf
dokumen.tips_500-kv-substation-grounding-presentation.pdfNafir Anas
 
1694355611974.pdf
1694355611974.pdf1694355611974.pdf
1694355611974.pdfNafir Anas
 
ITEP-2021-03-FCL Expertise.pdf
ITEP-2021-03-FCL Expertise.pdfITEP-2021-03-FCL Expertise.pdf
ITEP-2021-03-FCL Expertise.pdfNafir Anas
 
sqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdfsqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdfNafir Anas
 
330377138-Conf-Tested-Assemblies-Iec-61439.pdf
330377138-Conf-Tested-Assemblies-Iec-61439.pdf330377138-Conf-Tested-Assemblies-Iec-61439.pdf
330377138-Conf-Tested-Assemblies-Iec-61439.pdfNafir Anas
 
PPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).ppt
PPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).pptPPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).ppt
PPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).pptNafir Anas
 
1VGA671004 - UniGear ZVC Standard Product.ppt
1VGA671004 - UniGear ZVC Standard Product.ppt1VGA671004 - UniGear ZVC Standard Product.ppt
1VGA671004 - UniGear ZVC Standard Product.pptNafir Anas
 
acsr-standard.pdf
acsr-standard.pdfacsr-standard.pdf
acsr-standard.pdfNafir Anas
 
150110188-SUBSTATION-AUTOMATION.pdf
150110188-SUBSTATION-AUTOMATION.pdf150110188-SUBSTATION-AUTOMATION.pdf
150110188-SUBSTATION-AUTOMATION.pdfNafir Anas
 

More from Nafir Anas (12)

dokumen.tips_500-kv-substation-grounding-presentation.pdf
dokumen.tips_500-kv-substation-grounding-presentation.pdfdokumen.tips_500-kv-substation-grounding-presentation.pdf
dokumen.tips_500-kv-substation-grounding-presentation.pdf
 
D.pdf
D.pdfD.pdf
D.pdf
 
1694355611974.pdf
1694355611974.pdf1694355611974.pdf
1694355611974.pdf
 
ITEP-2021-03-FCL Expertise.pdf
ITEP-2021-03-FCL Expertise.pdfITEP-2021-03-FCL Expertise.pdf
ITEP-2021-03-FCL Expertise.pdf
 
sqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdfsqd-app-guide-2-25c.pdf
sqd-app-guide-2-25c.pdf
 
330377138-Conf-Tested-Assemblies-Iec-61439.pdf
330377138-Conf-Tested-Assemblies-Iec-61439.pdf330377138-Conf-Tested-Assemblies-Iec-61439.pdf
330377138-Conf-Tested-Assemblies-Iec-61439.pdf
 
PPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).ppt
PPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).pptPPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).ppt
PPT-Surge-Protection-Technical-Background-and-Basics-Presentation_1 (1).ppt
 
231896.ppt
231896.ppt231896.ppt
231896.ppt
 
1VGA671004 - UniGear ZVC Standard Product.ppt
1VGA671004 - UniGear ZVC Standard Product.ppt1VGA671004 - UniGear ZVC Standard Product.ppt
1VGA671004 - UniGear ZVC Standard Product.ppt
 
3.-Invar.pdf
3.-Invar.pdf3.-Invar.pdf
3.-Invar.pdf
 
acsr-standard.pdf
acsr-standard.pdfacsr-standard.pdf
acsr-standard.pdf
 
150110188-SUBSTATION-AUTOMATION.pdf
150110188-SUBSTATION-AUTOMATION.pdf150110188-SUBSTATION-AUTOMATION.pdf
150110188-SUBSTATION-AUTOMATION.pdf
 

Recently uploaded

Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...
Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...
Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...Miss joya
 
Housewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment Booking
Housewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment BookingHousewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment Booking
Housewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment Bookingnarwatsonia7
 
Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...
Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...
Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...narwatsonia7
 
Vip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls Available
Vip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls AvailableVip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls Available
Vip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls AvailableNehru place Escorts
 
Call Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service Availablenarwatsonia7
 
VIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service Mumbai
VIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service MumbaiVIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service Mumbai
VIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service Mumbaisonalikaur4
 
Call Girls ITPL Just Call 7001305949 Top Class Call Girl Service Available
Call Girls ITPL Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls ITPL Just Call 7001305949 Top Class Call Girl Service Available
Call Girls ITPL Just Call 7001305949 Top Class Call Girl Service Availablenarwatsonia7
 
Aspirin presentation slides by Dr. Rewas Ali
Aspirin presentation slides by Dr. Rewas AliAspirin presentation slides by Dr. Rewas Ali
Aspirin presentation slides by Dr. Rewas AliRewAs ALI
 
Call Girls Thane Just Call 9910780858 Get High Class Call Girls Service
Call Girls Thane Just Call 9910780858 Get High Class Call Girls ServiceCall Girls Thane Just Call 9910780858 Get High Class Call Girls Service
Call Girls Thane Just Call 9910780858 Get High Class Call Girls Servicesonalikaur4
 
Call Girls Hosur Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Hosur Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls Hosur Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Hosur Just Call 7001305949 Top Class Call Girl Service Availablenarwatsonia7
 
Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...
Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...
Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...narwatsonia7
 
Call Girls Budhwar Peth 7001305949 All Area Service COD available Any Time
Call Girls Budhwar Peth 7001305949 All Area Service COD available Any TimeCall Girls Budhwar Peth 7001305949 All Area Service COD available Any Time
Call Girls Budhwar Peth 7001305949 All Area Service COD available Any Timevijaych2041
 
Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...
Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...
Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...narwatsonia7
 
Call Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort Service
Call Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort ServiceCall Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort Service
Call Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort Serviceparulsinha
 
Call Girls Whitefield Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Whitefield Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls Whitefield Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Whitefield Just Call 7001305949 Top Class Call Girl Service Availablenarwatsonia7
 
Call Girls In Andheri East Call 9920874524 Book Hot And Sexy Girls
Call Girls In Andheri East Call 9920874524 Book Hot And Sexy GirlsCall Girls In Andheri East Call 9920874524 Book Hot And Sexy Girls
Call Girls In Andheri East Call 9920874524 Book Hot And Sexy Girlsnehamumbai
 
Bangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% Safe
Bangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% SafeBangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% Safe
Bangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% Safenarwatsonia7
 
Book Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbers
Book Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbersBook Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbers
Book Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbersnarwatsonia7
 
Kolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Kolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call NowKolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Kolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call NowNehru place Escorts
 
Sonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Sonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call NowSonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Sonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call NowRiya Pathan
 

Recently uploaded (20)

Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...
Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...
Low Rate Call Girls Pune Esha 9907093804 Short 1500 Night 6000 Best call girl...
 
Housewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment Booking
Housewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment BookingHousewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment Booking
Housewife Call Girls Hoskote | 7001305949 At Low Cost Cash Payment Booking
 
Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...
Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...
Call Girls Electronic City Just Call 7001305949 Top Class Call Girl Service A...
 
Vip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls Available
Vip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls AvailableVip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls Available
Vip Call Girls Anna Salai Chennai 👉 8250192130 ❣️💯 Top Class Girls Available
 
Call Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Jp Nagar Just Call 7001305949 Top Class Call Girl Service Available
 
VIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service Mumbai
VIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service MumbaiVIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service Mumbai
VIP Call Girls Mumbai Arpita 9910780858 Independent Escort Service Mumbai
 
Call Girls ITPL Just Call 7001305949 Top Class Call Girl Service Available
Call Girls ITPL Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls ITPL Just Call 7001305949 Top Class Call Girl Service Available
Call Girls ITPL Just Call 7001305949 Top Class Call Girl Service Available
 
Aspirin presentation slides by Dr. Rewas Ali
Aspirin presentation slides by Dr. Rewas AliAspirin presentation slides by Dr. Rewas Ali
Aspirin presentation slides by Dr. Rewas Ali
 
Call Girls Thane Just Call 9910780858 Get High Class Call Girls Service
Call Girls Thane Just Call 9910780858 Get High Class Call Girls ServiceCall Girls Thane Just Call 9910780858 Get High Class Call Girls Service
Call Girls Thane Just Call 9910780858 Get High Class Call Girls Service
 
Call Girls Hosur Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Hosur Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls Hosur Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Hosur Just Call 7001305949 Top Class Call Girl Service Available
 
Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...
Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...
Russian Call Girls Chickpet - 7001305949 Booking and charges genuine rate for...
 
Call Girls Budhwar Peth 7001305949 All Area Service COD available Any Time
Call Girls Budhwar Peth 7001305949 All Area Service COD available Any TimeCall Girls Budhwar Peth 7001305949 All Area Service COD available Any Time
Call Girls Budhwar Peth 7001305949 All Area Service COD available Any Time
 
Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...
Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...
Call Girls Service in Bommanahalli - 7001305949 with real photos and phone nu...
 
Call Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort Service
Call Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort ServiceCall Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort Service
Call Girls Service In Shyam Nagar Whatsapp 8445551418 Independent Escort Service
 
Call Girls Whitefield Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Whitefield Just Call 7001305949 Top Class Call Girl Service AvailableCall Girls Whitefield Just Call 7001305949 Top Class Call Girl Service Available
Call Girls Whitefield Just Call 7001305949 Top Class Call Girl Service Available
 
Call Girls In Andheri East Call 9920874524 Book Hot And Sexy Girls
Call Girls In Andheri East Call 9920874524 Book Hot And Sexy GirlsCall Girls In Andheri East Call 9920874524 Book Hot And Sexy Girls
Call Girls In Andheri East Call 9920874524 Book Hot And Sexy Girls
 
Bangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% Safe
Bangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% SafeBangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% Safe
Bangalore Call Girls Marathahalli 📞 9907093804 High Profile Service 100% Safe
 
Book Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbers
Book Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbersBook Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbers
Book Call Girls in Kasavanahalli - 7001305949 with real photos and phone numbers
 
Kolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Kolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call NowKolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Kolkata Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
 
Sonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Sonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call NowSonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
Sonagachi Call Girls Services 9907093804 @24x7 High Class Babes Here Call Now
 

5010566.ppt

  • 1. Power System Protection Dr. Ibrahim El-Amin
  • 3. Definition  Overcurrent Coordination  A systematic study of current responsive devices in an electrical power system.
  • 4. Objective  To determine the ratings and settings of fuses, breakers, relay, etc.  To isolate the fault or overloads.
  • 5. Criteria  Economics  Available Measures of Fault  Operating Practices  Previous Experience
  • 6. Design  Open only PD upstream of the fault or overload  Provide satisfactory protection for overloads  Interrupt SC as rapidly (instantaneously) as possible  Comply with all applicable standards and codes  Plot the Time Current Characteristics of different PDs
  • 7. Analysis When:  New electrical systems  Plant electrical system expansion/retrofits  Coordination failure in an existing plant
  • 8. Protection vs. Coordination  Coordination is not an exact science  Compromise between protection and coordination  Reliability  Speed  Performance  Economics  Simplicity
  • 9. Protection  Prevent injury to personnel  Minimize damage to components  Quickly isolate the affected portion of the system  Minimize the magnitude of available short-circuit
  • 10. Spectrum Of Currents  Load Current  Up to 100% of full-load  115-125% (mild overload)  Overcurrent  Abnormal loading condition (Locked-Rotor)  Fault Current  Fault condition  Ten times the full-load current and higher
  • 11. Coordination  Limit the extend and duration of service interruption  Selective fault isolation  Provide alternate circuits
  • 13. Equipment  Motor  Transformer  Generator  Cable  Busway
  • 14. Capability / Damage Curves t I I2 2 t Gen I2 t Motor Xfmr I2 t Cable I2 t
  • 15. Transformer Category ANSI/IEEE C-57.109 Minimum nameplate (kVA) Category Single-phase Three-phase I 5-500 15-500 II 501-1667 501-5000 III 1668-10,000 5001-30,000 IV above 1000 above 30,000
  • 16. Infrequent Fault Incidence Zones for Category II & III Transformers * Should be selected by reference to the frequent-fault-incidence protection curve or for transformers serving industrial, commercial and institutional power systems with secondary-side conductors enclosed in conduit, bus duct, etc., the feeder protective device may be selected by reference to the infrequent-fault-incidence protection curve. Source: IEEE C57 Source Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) may be selected by reference to the infrequent-fault- incidence protection curve Category II or III Transformer Fault will be cleared by transformer primary-side protective device Optional main secondary –side protective device. May be selected by reference to the infrequent-fault- incidence protection curve Feeder protective device Fault will be cleared by transformer primary-side protective device or by optional main secondary- side protection device Fault will be cleared by feeder protective device Infrequent-Fault Incidence Zone* Feeders Frequent-Fault Incidence Zone*
  • 17. Transformer t (sec) I (pu) Thermal 200 2.5 I 2 t = 1250 2 25 Isc Mechanical K=(1/Z) 2 t (D-D LL) 0.87 (D-R LG) 0.58 Frequent Fault Infrequent Fault Inrush FLA
  • 18.
  • 19. Transformer Protection MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE PRIMARY SECONDARY Over 600 Volts Over 600 Volts 600 Volts or Below Transformer Rated Impedance Circuit Breaker Setting Fuse Rating Circuit Breaker Setting Fuse Rating Circuit Breaker Setting or Fuse Rating Not more than 6% 600 % 300 % 300 % 250% 125% (250% supervised) More than 6% and not more than 10% 400 % 300 % 250% 225% 125% (250% supervised) Table 450-3(a) source: NEC
  • 20. Protective Devices  Fuse  Relay (50/51 P, N, G, SG, 51V, 67, 46, 79, 21, …)  Thermal Magnetic  Low Voltage Solid State Trip  Electro-Mechanical  MCP  Overload Heater
  • 21. Fuse  Non Adjustable Device  Continuous and Interrupting Rating  Voltage Levels  Characteristic Curves  Min. Melting  Total Clearing  Application
  • 22. Minimum Melting Time Curve Total Clearing Time Curve
  • 23. Current Limiting Fuse (CLF)  Limits the peak current of short-circuit  Reduces magnetic stresses (mechanical damage)  Reduces thermal energy
  • 24.
  • 25. Symmetrical RMS Amperes Peak Let-Through Amperes 100 A 60 A 15% PF (X/R = 6.6) 12,500 5,200 230,000 300 A 100,000 Let-Through Chart
  • 26. Fuse Generally:  CLF is a better short-circuit protection  Non-CLF (expulsion fuse) is a better Overload protection
  • 27. Selectivity Criteria Typically:  Non-CLF: 140% of full load  CLF: 150% of full load
  • 28. Molder Case CB  Thermal-Magnetic  Magnetic Only  Integrally Fused  Current Limiting  High Interrupting Capacity Types  Frame Size  Trip Rating  Interrupting Capability  Voltage
  • 30. LVPCB  Voltage and Frequency Ratings  Continuous Current / Frame Size  Override (12 times cont. current)  Interrupting Rating  Short-Time Rating (30 cycle)  Fairly Simple to Coordinate
  • 31. 480 kV CB 2 CB 1 CB 2 CB 1 IT ST PU ST Band LT PU LT Band If =30 kA
  • 32. Motor Protection  Motor Starting Curve  Thermal Protection  Locked Rotor Protection  Fault Protection
  • 33. Motor Overload Protection (NEC Art 430-32)  Thermal O/L (Device 49)  Motors with SF not less than 1.15  125% of FLA  Motors with temp. rise not over 40  125% of FLA  All other motors  115% of FLA
  • 34. Locked Rotor Protection  Thermal Locked Rotor (Device 51)  Starting Time (TS < TLR)  LRA  LRA sym  LRA asym (1.5-1.6 x LRA sym) + 10% margin
  • 35. Fault Protection (NEC Art 430-52)  Non-Time Delay Fuses  300% of FLA  Dual Element (Time-Delay Fuses)  175% of FLA  Instantaneous Trip Breaker  800% of FLA*  Inverse Time Breakers  250% of FLA *MCPs can be set higher
  • 36. 200 HP MCP O/L Starting Curve I 2 T (49) MCP (50) (51) ts tLR LRAs LRAasym
  • 37. Overcurrent Relay  Time-Delay (51 – I>)  Short-Time Instantaneous ( I>>)  Instantaneous (50 – I>>>)  Electromagnetic (induction Disc)  Solid State (Multi Function / Multi Level)  Application
  • 38.
  • 39. Time-Overcurrent Unit  Ampere Tap Calculation  Ampere Pickup (P.U.) = CT Ratio x A.T. Setting  Relay Current (IR) = Actual Line Current (IL) / CT Ratio  Multiples of A.T. = IR/A.T. Setting = IL/(CT Ratio x A.T. Setting) IL IR CT 51
  • 40. Instantaneous Unit  Instantaneous Calculation  Ampere Pickup (P.U.) = CT Ratio x IT Setting  Relay Current (IR) = Actual Line Current (IL) / CT Ratio  Multiples of IT= IR/IT Setting = IL/(CT Ratio x IT Setting) IL IR CT 50
  • 41. 41 Relay Coordination  Time margins should be maintained between T/C curves  Adjustment should be made for CB opening time  Shorter time intervals may be used for solid state relays  Upstream relay should have the same inverse T/C characteristic as the downstream relay (CO-8 to CO-8) or be less inverse (CO-8 upstream to CO-6 downstream)  Extremely inverse relays coordinates very well with CLFs
  • 42. Fixed Points  Motor starting curves  Transformer damage curves & inrush points  Cable damage curves  SC maximum fault points  Cable ampacities Points or curves which do not change regardless of protective device settings:
  • 43. Situation Calculate Relay Setting (Tap, Inst. Tap & Time Dial) For This System 4.16 kV DS 5 MVA Cable 1-3/C 500 kcmil CU - EPR CB Isc = 30,000 A 6 % 50/51 Relay: IFC 53 CT 800:5
  • 44. Solution A Inrsuh 328 , 8 694 12 I    A 338 . 4 800 5 I I L R    Transformer: A kV kVA L 694 16 . 4 3 000 , 5 I    IL CT R IR Set Relay: A 55 1 . 52 800 5 328 , 8 ) 50 ( 1 ) 38 . 1 (6/4.338 0 . 6 4 . 5 338 . 4 % 125          A Inst TD A TAP A
  • 45. Question What is ANSI Shift Curve?
  • 46. Answer  For delta-delta connected transformers, with line-to-line faults on the secondary side, the curve must be reduced to 87% (shift to the left by a factor of 0.87)  For delta-wye connection, with single line-to- ground faults on the secondary side, the curve values must be reduced to 58% (shift to the left by a factor of 0.58)
  • 47. Question What is meant by Frequent and Infrequent for transformers?
  • 48. Answer Infrequent Fault Incidence Zones for Category II & III Transformers Source Transformer primary-side protective device (fuses, relayed circuit breakers, etc.) May be selected by reference to the infrequent-fault- incidence protection curve Category II or III Transformer Fault will be cleared by transformer primary-side protective device Optional main secondary –side protective device. May be selected by reference to the infrequent-fault- incidence protection curve Feeder protective device Fault will be cleared by transformer primary-side protective device or by optional main secondary- side protection device Fault will be cleared by feeder protective device Infrequent-Fault Incidence Zone* Feeders Frequent-Fault Incidence Zone*
  • 49. Question What T/C Coordination interval should be maintained between relays?
  • 50. Answer A t I B CB Opening Time + Induction Disc Overtravel (0.1 sec) + Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
  • 51. Question What is Class 10 and Class 20 Thermal OLR curves?
  • 52. Answer  Class 10 for fast trip, 10 seconds or less  Class 20 for, 20 seconds or less  There is also a Class 30 for long trip time