SlideShare a Scribd company logo
1 of 16
Download to read offline
A current transformer (CT) is a type of transformer that is used to measure alternating
current (AC). It produces a current in its secondary which is proportional to the current
in its primary.
Current transformers, along with voltage or potential transformers are instrument
transformers. Instrument transformers scale the large values of voltage or current to
small, standardized values that are easy to handle for instruments and protective
relays. The instrument transformers isolate measurement or protection circuits from
the high voltage of the primary system. A current transformer provides a secondary
current that is accurately proportional to the current flowing in its primary. The current
transformer presents a negligible load to the primary circuit.
Current transformers are the current-sensing units of the power system and are used
at generating stations, electrical substations, and in industrial and commercial electric
power distribution.
 Like any transformer, a current transformer has a primary winding, a
core and a secondary winding, although some transformers, including
current transformers, use an air core. In principle, the only difference
between a current transformer and a voltage transformer (normal type)
is that the former is fed with a 'constant' current while the latter is fed
with a 'constant' voltage, where 'constant' has the strict circuit theory
meaning. The alternating current in the primary produces an
alternating magnetic field in the core, which then induces an
alternating current in the secondary. The primary circuit is largely
unaffected by the insertion of the CT. Accurate current transformers
need close coupling between the primary and secondary to ensure that
the secondary current is proportional to the primary current over a wide
current range. The current in the secondary is the current in the
primary (assuming a single turn primary) divided by the number of turns
of the secondary. In the illustration on the right, 'I' is the current in the
primary, 'B' is the magnetic field, 'N' is the number of turns on the
secondary, and 'A' is an AC ammeter.
Current transformers typically consist of a silicon steel ring core wound with many
turns of copper wire as shown in the illustration to the right. The conductor carrying
the primary current is passed through the ring. The CT's primary, therefore, consists
of a single 'turn'. The primary 'winding' may be a permanent part of the current
transformer, i.e. a heavy copper bar to carry current through the core. Window-type
current transformers are also common, which can have circuit cables run through the
middle of an opening in the core to provide a single-turn primary winding. To assist
accuracy, the primary conductor should be centered in the aperture.
CTs are specified by their current ratio from primary to secondary. The rated
secondary current is normally standardized at 1 or 5 amperes. For example, a 4000:5
CT secondary winding will supply an output current of 5 amperes when the primary
winding current is 4000 amperes. This ratio can also be used to find the impedance
or voltage on one side of the transformer, given the appropriate value at the other
side. For the 4000:5 CT, the secondary impedance can be found as ZS = NZP = 800ZP,
and the secondary voltage can be found as VS = NVP = 800VP. In some cases, the
secondary impedance is referred to the primary side, and is found as ZS′ = N2ZP.
Referring the impedance is done simply by multiplying initial secondary impedance
value by the current ratio. The secondary winding of a CT can have taps to provide a
range of ratios, five taps being common.
Current transformer shapes and sizes vary depending on the end user or switch
gear manufacturer. Low-voltage single ratio metering current transformers are
either a ring type or plastic molded case.
Split-core current transformers either have a two-part core or a core with a
removable section. This allows the transformer to be placed around a conductor
without having to disconnect it first. Split-core current transformers are typically
used in low current measuring instruments, often portable, battery-operated, and
hand-held (see illustration lower right).
 Current transformers are used extensively for measuring current and
monitoring the operation of the power grid. Along with voltage leads,
revenue-grade CTs drive the electrical utility's watt-hour meter on
virtually every building with three-phase service and single-phase
services greater than 200 amperes.
 High-voltage current transformers are mounted on porcelain or polymer
insulators to isolate them from ground. Some CT configurations slip
around the bushing of a high-voltage transformer or circuit breaker,
which automatically centers the conductor inside the CT window.
 Current transformers can be mounted on the low voltage or high
voltage leads of a power transformer. Sometimes a section of a bus bar
can be removed to replace a current transformer.
 Often, multiple CTs are installed as a "stack" for various uses. For
example, protection devices and revenue metering may use separate
CTs to provide isolation between metering and protection circuits and
allows current transformers with different characteristics (accuracy,
overload performance) to be used for the devices.
The burden (load) impedance should not exceed the specified maximum value
to avoid the secondary voltage exceeding the limits for the current transformer.
The primary current rating of a current transformer should not be exceeded or
the core may enter its non linear region and ultimately saturate. This would
occur near the end of the first half of each half (positive and negative) of the AC
sine wave in the primary and would compromise the accuracy.
 Current transformers are often used to monitor high currents or
currents at high voltages. Technical standards and design practices
are used to ensure the safety of installations using current
transformers.
 The secondary of a current transformer should not be disconnected
from its burden while current is in the primary, as the secondary will
attempt to continue driving current into an effective
infinite impedance up to its insulation break-down voltage and thus
compromise operator safety. For certain current transformers, this
voltage may reach several kilovolts and may cause arcing. Exceeding
the secondary voltage may also degrade the accuracy of the
transformer or destroy it. Energizing a current transformer with an
open circuit secondary is equivalent to energizing a voltage
transformer (normal type) with a short circuit secondary. In the first
case the secondary tries to produce an infinite voltage and in the
second case the secondary tries to produce an infinite current. Both
scenarios can be dangerous and damage the transformer.
The accuracy of a CT is affected by a number of factors including:
1. Burden
2. Burden class/saturation class
3. Rating factor
4. Load
5. External electromagnetic fields
6. Temperature
7. Physical configuration
8. The selected tap, for multi-ratio CTs
9. Phase change
10. Capacitive coupling between primary and secondary
11. Resistance of primary and secondary
12. Core magnetizing current
Accuracy classes for various types of measurement and at standard loads
in the secondary circuit (burdens) are defined in IEC 61869-1 as classes
0.1, 0.2s, 0.2, 0.5, 0.5s, 1 and 3. The class designation is an
approximate measure of the CT's accuracy. The ratio (primary to
secondary current) error of a Class 1 CT is 1% at rated current; the ratio
error of a Class 0.5 CT is 0.5% or less. Errors in phase are also important,
especially in power measuring circuits. Each class has an allowable
maximum phase error for a specified load impedance.
Current transformers used for protective relaying also have accuracy
requirements at overload currents in excess of the normal rating to
ensure accurate performance of relays during system faults. A CT with a
rating of 2.5L400 specifies with an output from its secondary winding of
twenty times its rated secondary current (usually 5 A × 20 = 100 A) and
400 V (IZ drop) its output accuracy will be within 2.5 percent.
Burden
The secondary load of a current transformer is termed the "burden" to
distinguish it from the primary load.
The burden in a CT metering circuit is
largely resistive impedance presented to its secondary winding. Typical
burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA, 15 VA,
20 VA, 30 VA, 45 VA and 60 VA. ANSI/IEEE burden ratings are B-0.1,
B-0.2, B-0.5, B-1.0, B-2.0 and B-4.0. This means a CT with a burden
rating of B-0.2 will maintain its stated accuracy with up to 0.2 Ω on the
secondary circuit. These specification diagrams show accuracy
parallelograms on a grid incorporating magnitude and phase angle
error scales at the CT's rated burden. Items that contribute to the
burden of a current measurement circuit are switch-blocks, meters and
intermediate conductors.
The most common cause of excess burden impedance is the conductor
between the meter and the CT. When substation meters are located far
from the meter cabinets, the excessive length of cable creates a large
resistance. This problem can be reduced by using thicker cables and
CTs with lower secondary currents (1 A), both of which will produce
less voltage drop between the CT and its metering devices.
Knee-point core-saturation voltage
The knee-point voltage of a current transformer is the magnitude of the
secondary voltage above which the output current ceases to linearly
follow the input current within declared accuracy. In testing, if a voltage
is applied across the secondary terminals the magnetizing current will
increase in proportion to the applied voltage, until the knee point is
reached. The knee point is defined as the voltage at which a 10%
increase in applied voltage increases the magnetizing current by
50%.[citation needed] For voltages greater than the knee point, the
magnetizing current increases considerably even for small increments in
voltage across the secondary terminals. The knee-point voltage is less
applicable for metering current transformers as their accuracy is
generally much higher but constrained within a very small range of the
current transformer rating, typically 1.2 to 1.5 times rated current.
However, the concept of knee point voltage is very pertinent to protection
current transformers, since they are necessarily exposed to fault
currents of 20 to 30 times rated current.
Phase shift
Ideally, the primary and secondary currents of a current transformer
should be in phase. In practice, this is impossible, but, at normal
power frequencies, phase shifts of a few tenths of a degree are
achievable, while simpler CTs may have phase shifts up to six
degrees.[2] For current measurement, phase shift is immaterial
as ammeters only display the magnitude of the current. However,
in wattmeters, energy meters, and power factor meters, phase shift
produces errors. For power and energy measurement, the errors are
considered to be negligible at unity power factor but become more
significant as the power factor approaches zero. At zero power-factor,
any indicated power is entirely due to the current transformer's phase
error.[2] The introduction of electronic power and energy meters has
allowed current phase error to be calibrated out.
Construction
Bar-type current transformers have terminals for source and load connections of
the primary circuit, and the body of the current transformer provides insulation
between the primary circuit and ground. By use of oil insulation and porcelain
bushings, such transformers can be applied at the highest transmission
voltages.
Ring-type current transformers are installed over a bus bar or an insulated cable
and have only a low level of insulation on the secondary coil. To obtain non-
standard ratios or for other special purposes, more than one turn of the primary
cable may be passed through the ring. Where a metal shield is present in the
cable jacket, it must be terminated so no net sheath current passes through the
ring, to ensure accuracy. Current transformers used to sense ground fault (zero
sequence) currents, such as in a three-phase installation, may have three
primary conductors passed through the ring. Only the net unbalanced current
produces a secondary current - this can be used to detect a fault from an
energized conductor to ground. Ring-type transformers usually use dry insulation
systems, with a hard rubber or plastic case over the secondary windings.
For temporary connections, a split ring-type current transformer
can be slipped over a cable without disconnecting it. This type
has a laminated iron core, with a hinged section that allows it to
be installed over the cable; the core links the magnetic flux
produced by the single turn primary winding to a wound
secondary with many turns. Because the gaps in the hinged
segment introduce inaccuracy, such devices are not normally
used for revenue metering.
Current transformers, especially those intended for high voltage
substation service, may have multiple taps on their secondary
windings, providing several ratios in the same device. This can
be done to allow for reduced inventory of spare units, or to
allow for load growth in an installation. A high-voltage current
transformer may have several secondary windings with the same
primary, to allow for separate metering and protection circuits,
or for connection to different types of protective devices. For
example, one secondary may be used for branch overcurrent
protection, while a second winding may be used in a bus
differential protective scheme, and a third winding used for
power and current measurement.
Special types
Specially constructed wideband current transformers are also used (usually with
an oscilloscope) to measure waveforms of high frequency or pulsed currents
within pulsed powersystems. Unlike CTs used for power circuitry, wideband CTs are
rated in output volts per ampere of primary current.
If the burden resistance is much less than inductive impedance of the secondary
winding at the measurement frequency then the current in the secondary tracks
the primary current and the transformer provides a current output that is
proportional to the measured current. On the other hand, if that condition is not
true, then the transformer is inductive and gives a differential output.
The Rogowski coil uses this effect and requires an external integrator in order to
provide a voltage output that is proportional to the measured current.
Chemtrols Solar Pvt Limited, Amar Hill Saki Vihar Road, Powai Mumbai – 400 072
, Jay Ranvir- 9594998390
Email jay.ranvir@chemtrolssolar.com

More Related Content

What's hot

Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionAman Ansari
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CTParth Patel
 
Transformers 1
Transformers 1Transformers 1
Transformers 1SHREYAS321
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.Geetesh Verma
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformervikasgupta1965
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)RP6997
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter johny renoald
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Comparison of ac and dc transmission
Comparison of ac and dc transmissionComparison of ac and dc transmission
Comparison of ac and dc transmissionjawaharramaya
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zonesSlides Hub
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Major electrical equipment in power plants
Major electrical equipment in power plantsMajor electrical equipment in power plants
Major electrical equipment in power plantsFateh Singh
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector groupShyamkant Vasekar
 
Over current Relays
Over current RelaysOver current Relays
Over current RelaysASWANTH6270
 

What's hot (20)

Types of relay
Types of relayTypes of relay
Types of relay
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_version
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CT
 
Transformers 1
Transformers 1Transformers 1
Transformers 1
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.
 
Overcurrent Protection
Overcurrent ProtectionOvercurrent Protection
Overcurrent Protection
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter Unit-2 Three Phase controlled converter
Unit-2 Three Phase controlled converter
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Comparison of ac and dc transmission
Comparison of ac and dc transmissionComparison of ac and dc transmission
Comparison of ac and dc transmission
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Major electrical equipment in power plants
Major electrical equipment in power plantsMajor electrical equipment in power plants
Major electrical equipment in power plants
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
 
Over current Relays
Over current RelaysOver current Relays
Over current Relays
 
Relays
RelaysRelays
Relays
 

Similar to CURRENT TRANSFORMER ACCURACY

Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement & measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement & measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]Md Irshad Ahmad
 
Substation equipments & its functions
Substation equipments & its functionsSubstation equipments & its functions
Substation equipments & its functionsMonzer Abdallah Eisa
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side managementMark Anthony Enoy
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)kaushal boghani
 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer PresentationRishi Raj
 
current transformers.pptx
current transformers.pptxcurrent transformers.pptx
current transformers.pptxmrsupercool455
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
Uttar pradesh power corporation limited
Uttar pradesh power corporation limitedUttar pradesh power corporation limited
Uttar pradesh power corporation limitedVSRAGHU
 
Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)Md Abu Jauad Khan Aliv
 
Voltage Regulators IC
Voltage Regulators ICVoltage Regulators IC
Voltage Regulators ICDr.Raja R
 

Similar to CURRENT TRANSFORMER ACCURACY (20)

Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement & measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement & measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement & measuring instruments [emmi (nee-302) -unit-2]
 
Lecture (11.11.22).pptx
Lecture (11.11.22).pptxLecture (11.11.22).pptx
Lecture (11.11.22).pptx
 
CT & PT.pptx
CT & PT.pptxCT & PT.pptx
CT & PT.pptx
 
Sub station training
Sub station trainingSub station training
Sub station training
 
Substation equipments & its functions
Substation equipments & its functionsSubstation equipments & its functions
Substation equipments & its functions
 
Introduction to CTs and PTs
Introduction to CTs and PTsIntroduction to CTs and PTs
Introduction to CTs and PTs
 
Introduction to CTs and PTs
Introduction to CTs and PTsIntroduction to CTs and PTs
Introduction to CTs and PTs
 
Introduction to CTs and PTs
Introduction to CTs and PTsIntroduction to CTs and PTs
Introduction to CTs and PTs
 
132kV GSS ppt
132kV GSS ppt132kV GSS ppt
132kV GSS ppt
 
Power quality & demand side management
Power quality & demand side managementPower quality & demand side management
Power quality & demand side management
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer Presentation
 
current transformers.pptx
current transformers.pptxcurrent transformers.pptx
current transformers.pptx
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Current transformers theory
Current transformers theoryCurrent transformers theory
Current transformers theory
 
Uttar pradesh power corporation limited
Uttar pradesh power corporation limitedUttar pradesh power corporation limited
Uttar pradesh power corporation limited
 
Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)
 
E044043336
E044043336E044043336
E044043336
 
Voltage Regulators IC
Voltage Regulators ICVoltage Regulators IC
Voltage Regulators IC
 
Study tour to optcl
Study tour to optclStudy tour to optcl
Study tour to optcl
 

More from Jay Ranvir

Solar net metering policy
Solar net metering policySolar net metering policy
Solar net metering policyJay Ranvir
 
Open access mp
Open access mpOpen access mp
Open access mpJay Ranvir
 
Profile on the production retreaded tyre
Profile on the production retreaded tyreProfile on the production retreaded tyre
Profile on the production retreaded tyreJay Ranvir
 
Tyre Retreading by Hot Retreading Process
Tyre Retreading by Hot Retreading ProcessTyre Retreading by Hot Retreading Process
Tyre Retreading by Hot Retreading ProcessJay Ranvir
 
Open Access Charges Rajasthan
Open Access Charges RajasthanOpen Access Charges Rajasthan
Open Access Charges RajasthanJay Ranvir
 
Response to msedcl demands
Response to msedcl demandsResponse to msedcl demands
Response to msedcl demandsJay Ranvir
 
Practice directions rts net metering regulations 2015
Practice directions  rts  net metering regulations 2015Practice directions  rts  net metering regulations 2015
Practice directions rts net metering regulations 2015Jay Ranvir
 
Ppa agreement draft
Ppa agreement draftPpa agreement draft
Ppa agreement draftJay Ranvir
 
Notified f &s regulations 2018
Notified f &s  regulations 2018Notified f &s  regulations 2018
Notified f &s regulations 2018Jay Ranvir
 
Detailed comparison of capex vs opex
Detailed comparison of capex vs opexDetailed comparison of capex vs opex
Detailed comparison of capex vs opexJay Ranvir
 
Plastics to oil report
Plastics to oil reportPlastics to oil report
Plastics to oil reportJay Ranvir
 
Detail information of 5 t pyrolysis plant
Detail information of 5 t pyrolysis plantDetail information of 5 t pyrolysis plant
Detail information of 5 t pyrolysis plantJay Ranvir
 
Model ppa for renewable energy sources
Model ppa for renewable energy sourcesModel ppa for renewable energy sources
Model ppa for renewable energy sourcesJay Ranvir
 
Verification of compliance of renewable purchase obligation
Verification of compliance of renewable purchase obligationVerification of compliance of renewable purchase obligation
Verification of compliance of renewable purchase obligationJay Ranvir
 
Short term open access status for march 17
Short term open access status for march 17Short term open access status for march 17
Short term open access status for march 17Jay Ranvir
 
The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)Jay Ranvir
 
The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)Jay Ranvir
 
Forecasting, scheduling and imbalance handling for Solar Wind Energy
Forecasting, scheduling and imbalance handling for Solar Wind EnergyForecasting, scheduling and imbalance handling for Solar Wind Energy
Forecasting, scheduling and imbalance handling for Solar Wind EnergyJay Ranvir
 
Ppa model presentation
Ppa model presentationPpa model presentation
Ppa model presentationJay Ranvir
 

More from Jay Ranvir (20)

Solar net metering policy
Solar net metering policySolar net metering policy
Solar net metering policy
 
Open access mp
Open access mpOpen access mp
Open access mp
 
Profile on the production retreaded tyre
Profile on the production retreaded tyreProfile on the production retreaded tyre
Profile on the production retreaded tyre
 
Tyre Retreading by Hot Retreading Process
Tyre Retreading by Hot Retreading ProcessTyre Retreading by Hot Retreading Process
Tyre Retreading by Hot Retreading Process
 
Ch21
Ch21Ch21
Ch21
 
Open Access Charges Rajasthan
Open Access Charges RajasthanOpen Access Charges Rajasthan
Open Access Charges Rajasthan
 
Response to msedcl demands
Response to msedcl demandsResponse to msedcl demands
Response to msedcl demands
 
Practice directions rts net metering regulations 2015
Practice directions  rts  net metering regulations 2015Practice directions  rts  net metering regulations 2015
Practice directions rts net metering regulations 2015
 
Ppa agreement draft
Ppa agreement draftPpa agreement draft
Ppa agreement draft
 
Notified f &s regulations 2018
Notified f &s  regulations 2018Notified f &s  regulations 2018
Notified f &s regulations 2018
 
Detailed comparison of capex vs opex
Detailed comparison of capex vs opexDetailed comparison of capex vs opex
Detailed comparison of capex vs opex
 
Plastics to oil report
Plastics to oil reportPlastics to oil report
Plastics to oil report
 
Detail information of 5 t pyrolysis plant
Detail information of 5 t pyrolysis plantDetail information of 5 t pyrolysis plant
Detail information of 5 t pyrolysis plant
 
Model ppa for renewable energy sources
Model ppa for renewable energy sourcesModel ppa for renewable energy sources
Model ppa for renewable energy sources
 
Verification of compliance of renewable purchase obligation
Verification of compliance of renewable purchase obligationVerification of compliance of renewable purchase obligation
Verification of compliance of renewable purchase obligation
 
Short term open access status for march 17
Short term open access status for march 17Short term open access status for march 17
Short term open access status for march 17
 
The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)
 
The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)The indian-sunshine-the-solar-energy-landscape-in-india (1)
The indian-sunshine-the-solar-energy-landscape-in-india (1)
 
Forecasting, scheduling and imbalance handling for Solar Wind Energy
Forecasting, scheduling and imbalance handling for Solar Wind EnergyForecasting, scheduling and imbalance handling for Solar Wind Energy
Forecasting, scheduling and imbalance handling for Solar Wind Energy
 
Ppa model presentation
Ppa model presentationPpa model presentation
Ppa model presentation
 

Recently uploaded

pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIkoyaldeepu123
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixingviprabot1
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 

Recently uploaded (20)

pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
EduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AIEduAI - E learning Platform integrated with AI
EduAI - E learning Platform integrated with AI
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixing
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 

CURRENT TRANSFORMER ACCURACY

  • 1.
  • 2. A current transformer (CT) is a type of transformer that is used to measure alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary. Current transformers, along with voltage or potential transformers are instrument transformers. Instrument transformers scale the large values of voltage or current to small, standardized values that are easy to handle for instruments and protective relays. The instrument transformers isolate measurement or protection circuits from the high voltage of the primary system. A current transformer provides a secondary current that is accurately proportional to the current flowing in its primary. The current transformer presents a negligible load to the primary circuit. Current transformers are the current-sensing units of the power system and are used at generating stations, electrical substations, and in industrial and commercial electric power distribution.
  • 3.  Like any transformer, a current transformer has a primary winding, a core and a secondary winding, although some transformers, including current transformers, use an air core. In principle, the only difference between a current transformer and a voltage transformer (normal type) is that the former is fed with a 'constant' current while the latter is fed with a 'constant' voltage, where 'constant' has the strict circuit theory meaning. The alternating current in the primary produces an alternating magnetic field in the core, which then induces an alternating current in the secondary. The primary circuit is largely unaffected by the insertion of the CT. Accurate current transformers need close coupling between the primary and secondary to ensure that the secondary current is proportional to the primary current over a wide current range. The current in the secondary is the current in the primary (assuming a single turn primary) divided by the number of turns of the secondary. In the illustration on the right, 'I' is the current in the primary, 'B' is the magnetic field, 'N' is the number of turns on the secondary, and 'A' is an AC ammeter.
  • 4. Current transformers typically consist of a silicon steel ring core wound with many turns of copper wire as shown in the illustration to the right. The conductor carrying the primary current is passed through the ring. The CT's primary, therefore, consists of a single 'turn'. The primary 'winding' may be a permanent part of the current transformer, i.e. a heavy copper bar to carry current through the core. Window-type current transformers are also common, which can have circuit cables run through the middle of an opening in the core to provide a single-turn primary winding. To assist accuracy, the primary conductor should be centered in the aperture. CTs are specified by their current ratio from primary to secondary. The rated secondary current is normally standardized at 1 or 5 amperes. For example, a 4000:5 CT secondary winding will supply an output current of 5 amperes when the primary winding current is 4000 amperes. This ratio can also be used to find the impedance or voltage on one side of the transformer, given the appropriate value at the other side. For the 4000:5 CT, the secondary impedance can be found as ZS = NZP = 800ZP, and the secondary voltage can be found as VS = NVP = 800VP. In some cases, the secondary impedance is referred to the primary side, and is found as ZS′ = N2ZP. Referring the impedance is done simply by multiplying initial secondary impedance value by the current ratio. The secondary winding of a CT can have taps to provide a range of ratios, five taps being common.
  • 5. Current transformer shapes and sizes vary depending on the end user or switch gear manufacturer. Low-voltage single ratio metering current transformers are either a ring type or plastic molded case. Split-core current transformers either have a two-part core or a core with a removable section. This allows the transformer to be placed around a conductor without having to disconnect it first. Split-core current transformers are typically used in low current measuring instruments, often portable, battery-operated, and hand-held (see illustration lower right).
  • 6.  Current transformers are used extensively for measuring current and monitoring the operation of the power grid. Along with voltage leads, revenue-grade CTs drive the electrical utility's watt-hour meter on virtually every building with three-phase service and single-phase services greater than 200 amperes.  High-voltage current transformers are mounted on porcelain or polymer insulators to isolate them from ground. Some CT configurations slip around the bushing of a high-voltage transformer or circuit breaker, which automatically centers the conductor inside the CT window.  Current transformers can be mounted on the low voltage or high voltage leads of a power transformer. Sometimes a section of a bus bar can be removed to replace a current transformer.  Often, multiple CTs are installed as a "stack" for various uses. For example, protection devices and revenue metering may use separate CTs to provide isolation between metering and protection circuits and allows current transformers with different characteristics (accuracy, overload performance) to be used for the devices.
  • 7. The burden (load) impedance should not exceed the specified maximum value to avoid the secondary voltage exceeding the limits for the current transformer. The primary current rating of a current transformer should not be exceeded or the core may enter its non linear region and ultimately saturate. This would occur near the end of the first half of each half (positive and negative) of the AC sine wave in the primary and would compromise the accuracy.
  • 8.  Current transformers are often used to monitor high currents or currents at high voltages. Technical standards and design practices are used to ensure the safety of installations using current transformers.  The secondary of a current transformer should not be disconnected from its burden while current is in the primary, as the secondary will attempt to continue driving current into an effective infinite impedance up to its insulation break-down voltage and thus compromise operator safety. For certain current transformers, this voltage may reach several kilovolts and may cause arcing. Exceeding the secondary voltage may also degrade the accuracy of the transformer or destroy it. Energizing a current transformer with an open circuit secondary is equivalent to energizing a voltage transformer (normal type) with a short circuit secondary. In the first case the secondary tries to produce an infinite voltage and in the second case the secondary tries to produce an infinite current. Both scenarios can be dangerous and damage the transformer.
  • 9. The accuracy of a CT is affected by a number of factors including: 1. Burden 2. Burden class/saturation class 3. Rating factor 4. Load 5. External electromagnetic fields 6. Temperature 7. Physical configuration 8. The selected tap, for multi-ratio CTs 9. Phase change 10. Capacitive coupling between primary and secondary 11. Resistance of primary and secondary 12. Core magnetizing current
  • 10. Accuracy classes for various types of measurement and at standard loads in the secondary circuit (burdens) are defined in IEC 61869-1 as classes 0.1, 0.2s, 0.2, 0.5, 0.5s, 1 and 3. The class designation is an approximate measure of the CT's accuracy. The ratio (primary to secondary current) error of a Class 1 CT is 1% at rated current; the ratio error of a Class 0.5 CT is 0.5% or less. Errors in phase are also important, especially in power measuring circuits. Each class has an allowable maximum phase error for a specified load impedance. Current transformers used for protective relaying also have accuracy requirements at overload currents in excess of the normal rating to ensure accurate performance of relays during system faults. A CT with a rating of 2.5L400 specifies with an output from its secondary winding of twenty times its rated secondary current (usually 5 A × 20 = 100 A) and 400 V (IZ drop) its output accuracy will be within 2.5 percent.
  • 11. Burden The secondary load of a current transformer is termed the "burden" to distinguish it from the primary load. The burden in a CT metering circuit is largely resistive impedance presented to its secondary winding. Typical burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA, 15 VA, 20 VA, 30 VA, 45 VA and 60 VA. ANSI/IEEE burden ratings are B-0.1, B-0.2, B-0.5, B-1.0, B-2.0 and B-4.0. This means a CT with a burden rating of B-0.2 will maintain its stated accuracy with up to 0.2 Ω on the secondary circuit. These specification diagrams show accuracy parallelograms on a grid incorporating magnitude and phase angle error scales at the CT's rated burden. Items that contribute to the burden of a current measurement circuit are switch-blocks, meters and intermediate conductors. The most common cause of excess burden impedance is the conductor between the meter and the CT. When substation meters are located far from the meter cabinets, the excessive length of cable creates a large resistance. This problem can be reduced by using thicker cables and CTs with lower secondary currents (1 A), both of which will produce less voltage drop between the CT and its metering devices.
  • 12. Knee-point core-saturation voltage The knee-point voltage of a current transformer is the magnitude of the secondary voltage above which the output current ceases to linearly follow the input current within declared accuracy. In testing, if a voltage is applied across the secondary terminals the magnetizing current will increase in proportion to the applied voltage, until the knee point is reached. The knee point is defined as the voltage at which a 10% increase in applied voltage increases the magnetizing current by 50%.[citation needed] For voltages greater than the knee point, the magnetizing current increases considerably even for small increments in voltage across the secondary terminals. The knee-point voltage is less applicable for metering current transformers as their accuracy is generally much higher but constrained within a very small range of the current transformer rating, typically 1.2 to 1.5 times rated current. However, the concept of knee point voltage is very pertinent to protection current transformers, since they are necessarily exposed to fault currents of 20 to 30 times rated current.
  • 13. Phase shift Ideally, the primary and secondary currents of a current transformer should be in phase. In practice, this is impossible, but, at normal power frequencies, phase shifts of a few tenths of a degree are achievable, while simpler CTs may have phase shifts up to six degrees.[2] For current measurement, phase shift is immaterial as ammeters only display the magnitude of the current. However, in wattmeters, energy meters, and power factor meters, phase shift produces errors. For power and energy measurement, the errors are considered to be negligible at unity power factor but become more significant as the power factor approaches zero. At zero power-factor, any indicated power is entirely due to the current transformer's phase error.[2] The introduction of electronic power and energy meters has allowed current phase error to be calibrated out.
  • 14. Construction Bar-type current transformers have terminals for source and load connections of the primary circuit, and the body of the current transformer provides insulation between the primary circuit and ground. By use of oil insulation and porcelain bushings, such transformers can be applied at the highest transmission voltages. Ring-type current transformers are installed over a bus bar or an insulated cable and have only a low level of insulation on the secondary coil. To obtain non- standard ratios or for other special purposes, more than one turn of the primary cable may be passed through the ring. Where a metal shield is present in the cable jacket, it must be terminated so no net sheath current passes through the ring, to ensure accuracy. Current transformers used to sense ground fault (zero sequence) currents, such as in a three-phase installation, may have three primary conductors passed through the ring. Only the net unbalanced current produces a secondary current - this can be used to detect a fault from an energized conductor to ground. Ring-type transformers usually use dry insulation systems, with a hard rubber or plastic case over the secondary windings.
  • 15. For temporary connections, a split ring-type current transformer can be slipped over a cable without disconnecting it. This type has a laminated iron core, with a hinged section that allows it to be installed over the cable; the core links the magnetic flux produced by the single turn primary winding to a wound secondary with many turns. Because the gaps in the hinged segment introduce inaccuracy, such devices are not normally used for revenue metering. Current transformers, especially those intended for high voltage substation service, may have multiple taps on their secondary windings, providing several ratios in the same device. This can be done to allow for reduced inventory of spare units, or to allow for load growth in an installation. A high-voltage current transformer may have several secondary windings with the same primary, to allow for separate metering and protection circuits, or for connection to different types of protective devices. For example, one secondary may be used for branch overcurrent protection, while a second winding may be used in a bus differential protective scheme, and a third winding used for power and current measurement.
  • 16. Special types Specially constructed wideband current transformers are also used (usually with an oscilloscope) to measure waveforms of high frequency or pulsed currents within pulsed powersystems. Unlike CTs used for power circuitry, wideband CTs are rated in output volts per ampere of primary current. If the burden resistance is much less than inductive impedance of the secondary winding at the measurement frequency then the current in the secondary tracks the primary current and the transformer provides a current output that is proportional to the measured current. On the other hand, if that condition is not true, then the transformer is inductive and gives a differential output. The Rogowski coil uses this effect and requires an external integrator in order to provide a voltage output that is proportional to the measured current. Chemtrols Solar Pvt Limited, Amar Hill Saki Vihar Road, Powai Mumbai – 400 072 , Jay Ranvir- 9594998390 Email jay.ranvir@chemtrolssolar.com