SlideShare a Scribd company logo
Lesson
25
Analysis Of Complete
Vapour Compression
Refrigeration Systems
Version 1 ME, IIT Kharagpur 1
The specific objectives of this lecture are to:
1. Importance of complete vapour compression refrigeration system analysis and
the methods used (Section 25.1)
2. Performance characteristics of reciprocating compressors (Section 25.2)
3. Performance characteristics of reciprocating condensers (Section 25.3)
4. Performance characteristics of evaporators (Section 25.4)
5. Performance characteristics of expansion valves (Section 25.5)
6. Performance characteristics of condensing unit (Section 25.6)
7. Performance characteristics of complete system by matching characteristics of
evaporator and condensing unit (Section 25.7)
8. Effect of expansion valve on complete system performance (Section 25.8)
9. Meaning of sensitivity analysis (Section 25.9)
At the end of the lecture, the student should be able to:
1. Explain the concept of complete system analysis and the characteristics of
graphical and analytical methods
2. Express or plot the performance characteristics of individual components such
as compressors, condensers and evaporators and enumerate the influence of
operating parameters such as cooling water and brine flow rates, inlet
temperatures etc.
3. Obtain balance point for a condensing unit by matching the characteristics of
compressors and condensers
4. Obtain the balance point and characteristics curves for a complete system
assuming an ideal expansion valve
5. Explain the effect of expansion device on system performance
6. Explain the meaning of sensitivity analysis and its importance in system design
and optimization
Version 1 ME, IIT Kharagpur 2
25.1. Introduction
A basic vapour compression refrigeration system consists of four essential
components, namely compressor, condenser, expansion valve and evaporator.
The individual performance characteristics of these components have been
discussed in earlier lectures. However, in an actual system these components
work in unison. The performance of a complete system is a result of the balance
between these four components. For example, when the heat sink temperature
varies, it affects the performance of the condenser, which in turn, affects the
performance of the expansion device, evaporator and the compressor.
It is seen in Chapter 24 that expansion valve and compressor work in such
a manner that the mass flow rate through the two components is the same at
steady state. The balance point at steady state was obtained by equating the
mass flow rates through these components. This is an example of balancing two
components. Similar procedure can be extended to include the other two
components also, so that a balance point for the entire system can be obtained
by taking into account the individual characteristics. In principle, the balance
point for the system can be obtained either by a graphical method or by an
analytical method.
In graphical method, the performance of two interdependent components
is plotted for the same two variables of common interest. For example, mass flow
rate and evaporator temperature (or pressure) are plotted along y and x axes
respectively for combination of compressor – expansion device at constant
condenser temperature. The point of intersection of the two resulting curves will
indicate the conditions at which the mass flow rate and evaporator temperature
will be same for the two components. This point is called the balance point and in
steady-state the combination will achieve these conditions.
In analytical method, the mass flow rate through expansion valve can be
represented by an algebraic equation in terms of evaporator and condenser
temperatures. Similarly, the mass flow rate through a given compressor can also
be represented by an algebraic equation in terms of evaporator and condenser
temperatures by regression analysis of experimental or analytical data. The
balance point of the two components can be obtained by simultaneous solution
of the two algebraic equations.
Since the graphical method uses two-dimensional plots, it considers only
two components at a time while the system analysis by mathematical means can
consider more than two components simultaneously. Further, considering time
variation of parameters in form of differential equations can simulate the dynamic
performance also. Steady–state system analysis will involve simultaneous
solution of algebraic equations.
Version 1 ME, IIT Kharagpur 3
In this chapter, balance points of condensing unit, compressor-evaporator
combination have been considered for illustration. As a first step the performance
data of industrial components is presented in the form of plots or equations. The
raw data for this purpose can be obtained from the catalogues of manufacturers.
These are plotted either directly or after processing in terms of required
variables.
25.2. Reciprocating compressor performance characteristics:
The power requirement and mass flow rate as function of evaporator
temperature with condenser temperature as a parameter were presented in the
chapter on compressors. For the purpose of balancing, the refrigeration capacity
is required as a function of evaporator and condenser temperatures. This can be
easily determined by considering the refrigeration cycle or from the catalogue
data of the manufacturer. Figure 25.1 shows a theoretical single stage saturated
cycle on T-s chart.
S
T
4 1
2
2'3
Pc
Pe
Tc
Te
Fig.25.1: A single stage, saturated vapour compression refrigeration cycle
For the above cycle, the refrigeration capacity and power input to
compressor are given by:
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛ −
=−=
1
41
1
.
41r
.
e
.
v
hh
V)hh(mQ (25.1)
where is the refrigeration capacity, are the refrigerant mass
flow rate and volumetric flow rate of refrigerant at compressor inlet, respectively,
1
.
r
.
Vandme
.
Q
Version 1 ME, IIT Kharagpur 4
v is the specific volume of refrigerant at compressor inlet, and h and h1 1 4 are the
enthalpies of refrigerant at the exit and inlet of evaporator.
The volumetric flow rate of a reciprocating compressor is given by:
⎟
⎠
⎞
⎜
⎝
⎛
⎟
⎟
⎠
⎞
⎜
⎜
⎝
⎛ π
η=
60
N
4
LD
.nV
2
V1
.
(25.2)
where n is the number of cylinders, ηV is the volumetric efficiency, D, L and N are
the bore, stroke and speed (in RPM) of the compressor, respectively.
It is seen in Chapter 19 that at a given condenser temperature the cooling
capacity associated with mass flow rate given by a compressor increases as the
evaporator temperature increases. On the other hand, for a given evaporator
temperature, the cooling capacity decreases with increase in condenser
temperature. These characteristics are shown graphically in Fig.25.2.
Evaporator temperature, Te
Capacity, Qe
T = 30o
c C
T = 35o
c C
T = 40o
Cc
Fig.25.2. Variation of refrigeration capacity of a reciprocating compressor with
evaporator and condenser temperatures at a fixed RPM
Version 1 ME, IIT Kharagpur 5
The following equation may represent the above trends:
2 2 2 2 2 2
Q =a +a +a T +a T +a T +a T T +a T T +a T T +a T TT (25.3)e e e c c e c e c e c e c1 2 3 4 5 6 7 8 9
and Twhere Te c are evaporator and condenser temperatures, respectively. The
a to a1 9 are constants which can be determined by curve fitting the experimental
or manufacturers’ data using least square method, or by solving nine
simultaneous equations of the type (25.3) for the nine constants ai using nine
values of Q from given catalogue data for various values of T and Te e c. Similar
expression can be obtained for power input to the compressor.
25.3. Condenser performance characteristics:
Actual representation of condenser performance can be quite complex as
it consists of a de-superheating zone followed by condensing and subcooling
zones. The heat transfer coefficient varies continuously along the length of the
condenser due to the continuously changing state of the refrigerant. Hence a
detailed analysis should include these aspects. However, as discussed in an
earlier chapter on condensers, most of the time a simplified procedure is adopted
by assuming the temperature to remain constant at a saturated temperature
corresponding to the condensing pressure and a constant average condensing
heat transfer coefficient is assumed.
For air-cooled condensers, it is possible to represent the total heat
rejection rate from the condenser as a function of temperature difference and the
overall heat transfer coefficient as follows:
Q = U A (T - Tc c c c ∞) (25.4)
where, T is the ambient temperature and Tc∞ is the condensing temperature of
refrigerant.
For water-cooled condenser, one has to consider the water flow rate and
inlet water temperature as additional parameters. In this case also a single region
with constant condenser temperature Tc is considered. The heat transfer rate for
a water-cooled condenser is expressed as follows:
)TT(Cpm i,wo,www −Q = U A LMTD = (25.5)c c c
where is the water flow rate, U is overall heat transfer coefficient, Twm and Tc w,i w,o
are the inlet and outlet water temperatures respectively. The log mean
temperature difference of condenser LMTD is expressed as follows:c
Version 1 ME, IIT Kharagpur 6
⎭
⎬
⎫
⎩
⎨
⎧
−
−
−
=
o,wc
i,wc
i,wo,w
TT
TT
ln
TT
LMTDc (25.6)
From Eqns.(25.5) and (25.6) it can easily be shown that:
NTUCm
AU
pww
cc
−⎟
⎟
⎠
⎞
⎜
⎜
⎝
⎛
−
−−=−−= e)TT(Te)TT(TT i,wcci,wcco,w (25.6)
NTU is the Number of Transfer Units equal to ⎟
⎟
⎠
⎞
⎜
⎜
⎝
⎛
ww
.
cc Cpm/AU
The matching or the determination of balance point requires that its
characteristics be represented in the same form as done for compressor, that is,
cooling capacity vs. evaporator temperature. The condenser by itself does not
give cooling capacity. One finds out the condensation rate of liquid refrigerant
from the heat rejection capacity of condenser. The condensate rate multiplied by
refrigeration capacity gives the cooling capacity. Hence from the given heat
rejection capacity Qc, one finds the condensate rate for the SSS cycle as
follows:
refm
rm = Q /(h – h ) (25.7)c 2 3
The corresponding refrigeration of the condenser is given by,
rmQ (h – h= ) (25.8)e 1 4
The condenser characteristics are shown in Fig.25.3 for a fixed value of
and Twm w,i. It is observed that for a fixed evaporator temperature the capacity is
higher at higher condenser temperature. A higher condenser temperature leads
to a larger value of LMTDc, which in turn gives a larger heat transfer rate and a
larger condensate rate.
Further it is observed that at fixed condenser temperature, the cooling
capacity increases with increase in evaporator temperature. The heat rejection
ratio decreases with increase in evaporator temperature hence less heat
rejection Qc is required per unit cooling capacity, therefore the condensate rate of
condenser can give larger cooling capacity. Figure 25.4 shows the effect of
entering water temperature Tw,i on cooling capacity for various condenser
temperatures. The cooling capacity is zero when the entering water temperature
Version 1 ME, IIT Kharagpur 7
is equal to condenser temperature. As the inlet water temperature increases for a
fixed condenser temperature, the LMTDc decreases, which decreases the
cooling capacity. The following algebraic equation representing the curves of Fig.
25.3 at constant inlet temperature and flow rate of water can represent these
characteristics.
2 2 2 2 2 2
Q =b +b T +b T +b T +b T +b T T +b T T +b T T +b T T (25.9)e e e c c e c e c e c e c1 2 3 4 5 6 7 8 9
Evaporator temperature, Te
Capacity, Qe
T = 40o
Cc
T = 35o
Cc
T = 30o
Cc
Fig.25.3. Condenser performance at fixed water inlet temperature and flow rate
Version 1 ME, IIT Kharagpur 8
The characteristics in Fig. 25.4 are straight lines with almost same slope
for all the condenser temperatures. These may be represented by the following
equation with a constant G.
Qe = G(Tc - Tw,i ) (25.10)
Water inlet temperature, o
C
Capacity, Qe
T = 40o
C
T
c
= 35o
C
T
c
= 30c
o
C
T = 25o
c C
40o
C35o
C30o
C25o
C
0
Fig.25.4. Condenser performance with water inlet temperature at fixed flow rate
Version 1 ME, IIT Kharagpur 9
25.4. Evaporator Performance
Evaporator is also a heat exchanger just like condenser. For the sake of
illustration, consider an evaporator that is used for chilling a brine. The cooling
capacity of brine chiller is shown in Fig. 25.5 as a function of brine flow rate for
different values of LMTD of evaporator. The brine side heat transfer coefficient hb
increases as the brine flow rate increases as a result, the overall heat transfer
coefficient of the evaporator increases. Figure 25.5 shows that the cooling
capacity increases with flow rate for fixed LMTD for this reason.e
Brine flow rate
Capacity, Qe
LMTDe = 4o
C
LMTDe = 7o
C
LMTDe = 6o
C
LMTDe = 5o
C
Fig.25.5: Evaporator performance with brine flow rate and LMTDe
One can obtain the data for cooling capacity at various brine inlet
temperatures from the characteristics of evaporator as shown in Fig.25.5. For
example, if a plot for brine inlet temperature T o
of 10b,i C is required, then we may
choose an LMTDe of 5o
C and read the capacity Qe for the chosen brine flow rate
. Then the brine outlet temperature Tbm is obtained from the equation:b,o
Q = Cbme pb (T - Tb,i b,o) (25.11)
is obtained from the expression for LMTD :Then the evaporator temperature Te e
Version 1 ME, IIT Kharagpur 10
⎪⎭
⎪
⎬
⎫
⎪⎩
⎪
⎨
⎧
−
−
−
=
eo,b
ei,b
o,bi,b
e
TT
TT
ln
TT
LMTD (25.12)
The capacity Q and evaporator temperature Te e are determined for
different values of LMTDe for a fixed brine flow rate and brine inlet temperature
of 10o
C. Figure 25.6 shows a plot obtained by this method. In this plot the brine
flow rate is constant hence the brine side heat transfer coefficient is constant. If
the evaporation heat transfer coefficient was also constant then overall heat
transfer coefficient will also be constant and these lines will be straight lines. The
evaporation heat transfer coefficient increases with increases in evaporator
temperature hence these lines deviate slightly from straight lines. The capacity
for these lines may be expressed as follows:
2
Q = c (T -T )+c (T -T )e 0 b,i e 1 b,i e (25.13)
Evaporator temperature, Te
Capacity, Qe
Brine inlet temp.,Tb,i = 15o
C
Brine inlet temp. ,Tb,i = 10o
C
Brine inlet temp. ,Tb,i = 5o
C
15o
C10o
C5o
C
0
Fig.25.6: Performance characteristics of evaporator at fixed brine flow rate
Version 1 ME, IIT Kharagpur 11
25.5. Expansion valve Characteristics:
The characteristics of expansion valve play an important role in deciding
the conditions achieved by the refrigeration system. It was shown in Chapter 24
that compressor and expansion valve seek an evaporator temperature such that
under steady state conditions, the mass flow rate is same through the
compressor and expansion valve. This was the result under the constraint that
the condenser and evaporator have sufficiently large heat transfer areas and do
not influence the performance of expansion device and compressor. In this
chapter it is assumed that the expansion valve is capable of providing sufficient
mass flow rate at all condenser and evaporator temperatures. This is assumed to
simplify the matching problem. A float type of expansion valve or thermostatic
expansion valve will meet this requirement. If the analysis is being done by
computational method then the valve performance may also be included with
some additional computational effort.
25.6.Condensing unit:
As mentioned before, if graphical procedure is used to find performance
evaluation of various components, then only two components can be considered
at a time. In view of this the first sub-system considered is the condensing unit.
Condensing unit is a combination of compressor and condenser. This unit draws
refrigerant from the evaporator, compresses it in the compressor, condenses it in
the condenser and then feeds the condensed liquid refrigerant to the expansion
valve. It is available off-the-shelf as a packaged unit from the manufacturer with
matched set of compressor, compressor motor and condenser along with
reservoir and controls. This may be air-cooled or water-cooled unit which may be
installed as an outdoor unit.
The performance of condensing unit as function of evaporator temperature
is obtained by combining the cooling capacity versus evaporator temperature
characteristics of compressor and condenser. First we consider cooling capacity
versus evaporator temperature assuming the compressor sped, the temperature
and mass flow rate and entering water to condenser to be constant. This
matching is obtained by superimposing the compressor performance curve given
in Fig.25.2 on the condenser performance given in Fig.25.3 as shown in Fig.25.7.
The intersection of compressor and condenser characteristics is at point A for
30o
C condenser temperature. The combination of compressor and condenser will
achieve a cooling capacity and evaporator temperature corresponding to this
point at a condensing temperature of 30o
C. Similarly, points B and C are the
intersections at condenser temperatures of 35 and 40o
C, respectively. These
points are called balance points and the line A-B-C is called the performance
characteristics of the condensing unit.
Version 1 ME, IIT Kharagpur 12
Compressor
Condenser
Balance line
Evaporator temperature, Te
It is observed that as the evaporator temperature decreases, the
condensing temperature for the combination also decreases. This is explained as
follows: at lower evaporator temperatures, the volumetric efficiency and the mass
flow rate through the compressor decreases. This decreases the load on the
condenser. A large condenser heat transfer area is available for small mass flow
rate, hence condensation can occur at lower condenser temperature. It is also
seen that as the evaporator temperature decreases, the refrigeration capacity of
the condensing unit also decreases. This is due to the lower mass flow rate
through the compressor due to lower volumetric efficiency and lower vapour
density at compressor inlet.
Figure 25.8 shows the variation of refrigeration capacity of the condensing
unit with variation in inlet water temperature to the condenser. This is obtained by
superimposition of compressor characteristics of Fig.25.2 on the variation of
condenser performance with inlet water temperature given in Fig.25.4. The two
figures are shown side-by-side. At constant evaporator temperature of say, – 5o
C
and condenser temperature of 30o
C, the inlet water temperature corresponding
to point D is required to match the two components. Points E and F are the
balance points at condenser temperatures of 35 and 40o
C respectively. Line DEF
is the characteristics of the condensing unit at an evaporator temperature of –
5o
C. It is observed that the cooling capacity decreases as the inlet water
temperature to condenser increases.temperature to condenser increases.
Capacity, Qe
Tc=30o
C
Tc=35o
C
T =40o
Cc
C
A
B
At fixed compressor speed,
condenser water flow rate and
water inlet temperature
Fig.25.7: Performance characteristics of a condensing unit as a function of
evaporator and condensing temperatures
Version 1 ME, IIT Kharagpur 13
These characteristics can also be obtained by simultaneous solution of
Eqns. (25.3) and (25.9) for constant water temperature at condenser inlet and
constant water flow rate. For example, we wish to find the condenser
temperature and capacity for a given evaporator temperature of say 10o
C. An
iterative procedure may be devised as follows:
(i) For Te = 10o
C assume a condensing temperature Tc = 35o
C
(ii) Find Qe from Eqn.(25.3)
(iii) Substitution of Te = 10o
C and Qe in Eqn.(25.9) will yield a quadratic
equation for Tc. The value of Tc is found and checked against the
assumed value of Tc (35o
C being the first iterate) and iteration is
continued until the calculated value matches with the assumed
value of condenser temperature.
25.7. Performance of complete system - condensing unit and
evaporator:
In steady state, a balance condition must prevail between all the
components, that is, between condensing unit and evaporator assuming that the
expansion valve will provide appropriate mass flow rate. This confluence will
represent the performance of complete single-stage vapour compression
refrigeration system. The combined curves will also give insight into the off-
Evaporator temperature, o
C Temperature of entering water, o
C
Qe
Qe
T =30o
C
T
c
c=30o
C
Tc=35o
C
T
=30o
C
T
c=40o
C
Tc
=35o
Cc
F
D
E
−5o
C
Fig.25.8: Performance of the condensing unit as a function of water temperature at condenser
inlet
Version 1 ME, IIT Kharagpur 14
design performance of the system and operational problems. Superimposing
Fig.25.6 for the evaporator characteristics and Fig.25.7 for condensing unit
characteristics yields the balance point of the system. This is shown in Fig.25.9.
The characteristic curve shown in Fig.25.9 is for constant water temperature at
condenser inlet, constant flow rate to the condenser, constant compressor speed
and constant brine temperature at the inlet to the evaporator. The point of
intersection of the two curves gives the refrigeration capacity and the evaporator
temperature that the system will achieve.
One can study the response of the system in transient state also by this
figure. In a transient state, say the evaporator temperature is 5o
C. The figure
shows that at this point the condensing unit has a capacity corresponding to point
B while the evaporator has capacity corresponding to a lower value at C. Hence
the condensing unit has excess capacity. The excess capacity will reduce the
temperature of refrigerant and the metallic wall of the evaporator. This will
continue until the balance point of 3o
C is reached at point A.
Figure 25.10 shows the effect of brine mass flow rate compared to that at
the balance point. If the brine flow rate is increased, it is observed that cooling
capacity increases to point D. At higher flow rate the overall heat transfer
coefficient increases while (Tb,i-Tb,o) decreases permitting a larger mean
temperature difference between refrigerant and brine. Therefore with increase in
mass flow rate of brine, the cooling capacity increases. The pump power also
Evaporator temperature, Te
Capacity, Qe
Condensing unit
Evaporator
(Brine inlet = 10o
C)
Excess capacity
A
B
C
15o
C
5o
C
Fig.25.9: Performance of the complete system as an intersection of evaporator
and condensing unit characteristics at a brine inlet temperature of 10o
C
5o
C
Version 1 ME, IIT Kharagpur 15
increases for the increased brine mass flow rate. Hence one has to make a
compromise between increased capacity and increased cost of pump power.
Figure 25.10 shows the condition for lower brine flow rate when the heat transfer
coefficient on brine side decreases and temperature difference (T -Tb,i b,o)
increases. This is referred to as starving of evaporator.
Evaporator temperature,Te
Capacity, Qe
Condensing unit
Increased brine flow rate
Design flow rate
Evaporator starving
D
A
Fig.25.10: Influence of brine flow rate on system cooling capacity
25.8. Effect of expansion valve:
So far we have considered the balance between compressor, condenser
and evaporator assuming that expansion valve can feed sufficient refrigerant to
the evaporator so that heat transfer surface of the evaporator is wetted with
refrigerant. Thermostatic expansion valve meets this requirement. Automatic
expansion valve and capillary tube as observed in Chapter 24, result in a
condition where sufficient quantity of refrigerant could not be supplied to
evaporator. This condition was referred to as starving of evaporator. Starving
reduces the heat transfer coefficient in evaporator since there is not sufficient
refrigerant to wet the heat transfer surface consequently the cooling capacity
reduces. There are other conditions also which may lead to this situation. These
are as follows:
Version 1 ME, IIT Kharagpur 16
(i) Expansion valve is too small,
(ii) Some vapour is present in the liquid entering the expansion valve, and
(iii) Pressure difference across the expansion valve is small
If the refrigerant charge in the system is small then condition (ii) is likely to
occur. Also if the frictional pressure drop in the liquid line is large or the valve is
located at higher elevation than condenser then this condition may occur. During
winter months the ambient temperature is low hence in air-cooled condenser the
condenser pressure is low and the difference between evaporator and condenser
pressure is small, as a result the starving condition (iii) is likely to occur. In this
condition the expansion valve does not feed sufficient refrigerant to the
evaporator since the driving force; the pressure difference across the expansion
valve is small. The evaporator pressure also decreases in response to drop in
condenser pressure. The evaporator pressure may become so low that mass
flow rate through compressor may decrease due to lower volumetric efficiency.
Hermetic compressor depends upon the mass flow rate of refrigerant for cooling
on motor and compressor. This may be adversely affected under starved
condition.
25.9. Conclusion:
The methods presented in this chapter are useful when compressor,
condenser, evaporator and expansion valve have been selected and the
performance of combined system is desired. This analysis may not be useful in
selecting the initial equipment. The techniques presented in this chapter are
useful in predicting system performance for off-design conditions like a change in
ambient temperature, condenser inlet water temperature and brine inlet
temperature etc. The power requirement of the compressor has not been given
due emphasis in the analysis. In fact, an equation similar to Eqn. (25.3) may be
written for this also. This can also be found from known values of condenser and
evaporator loads.
An important aspect of refrigeration system performance is the sensitivity
analysis which deals with % change in, say cooling capacity with % change in
capacity of individual components like the compressor size, heat transfer area of
evaporator and condenser etc. This can easily be done by mathematical
simulation using the performance characteristics of the components given by
empirical equations. It has been shown in Stoecker and Jones that compressor
capacity has the dominant effect on system capacity and evaporator is next in
importance. An increase in compressor capacity by 10% has the effect of 6.3%
increase in system capacity. A 10% increase in evaporator gives 2.1% increase
in system capacity, while 10% increase in condenser gives 1.3 % increase in
system capacity. Such a data along with the relative costs of the components can
be used for optimization of the first cost of the system. Table 25.1 taken from
Stoecker and Jones illustrates the results of sensitivity analysis.
Version 1 ME, IIT Kharagpur 17
Ratio of component capacity to base capacity
Compressor Condenser Evaporator Refrigeration
capacity, TR
% increase
1.0 1.0 1.0 95.6 -
1.1 1.0 1.0 101.6 6.3
1.0 1.1 1.0 96.8 1.3
1.0 1.0 1.1 97.6 2.1
1.1 1.1 1.1 1.1 10.0
Table 25.1: Results of sensitivity analysis of a vapour compression refrigeration
system (Stoecker and Jones, 1982)
Questions and answers:
1. Which of the following statements are TRUE?
a) A graphical method generally considers two components at a time for system
analysis
b) An analytical method can consider more than two components at a time for
system analysis
c) Use of analytical method requires simultaneous solution of algebraic equations
d) All of the above
Ans.: d)
2. Which of the following statements are TRUE?
a) At a fixed RPM, the cooling capacity of a reciprocating compressor decreases
as the evaporator temperature decreases and condensing temperature increases
b) At fixed water inlet temperature and flow rate, the capacity of a condenser
increases as the condensing temperature and evaporator temperature increase
c) At fixed water flow rate and condensing temperature, the capacity of a
condenser increases as the water inlet temperature increases
d) At fixed water flow rate and cooling capacity, the condensing temperature
increases as the water inlet temperature increases
Ans.: a), b) and d)
3. Which of the following statements are TRUE?
a) At a fixed evaporator LMTD, the cooling capacity of a brine chilling evaporator
increases with brine flow rate
Version 1 ME, IIT Kharagpur 18
b) At a constant brine flow rate and a given evaporator temperature, the cooling
capacity of the evaporator increases as the brine temperature at evaporator inlet
increases
c) At a constant brine flow rate and a given evaporator temperature, the cooling
capacity of the evaporator increases as the brine temperature at evaporator inlet
decreases
d) For constant cooling capacity and brine flow rate, the evaporator temperature
has to decrease as the brine temperature at the inlet decreases
Ans.: a), b) and d)
4. Which of the following statements are TRUE?
a) The performance characteristics of a condensing unit are obtained by
matching the characteristics of compressor and condenser
b) The performance characteristics of a condensing unit are obtained by
matching the characteristics of evaporator and condenser
c) The performance characteristics of a condensing unit are obtained by
matching the characteristics of expansion valve and condenser
d) The performance characteristics of a condensing unit are obtained by
matching the characteristics of compressor and evaporator
Ans.: a)
5. Which of the following statements are TRUE?
a) At constant RPM, cooling water flow rate and inlet temperature, the balance
point condensing temperature increases as evaporator temperature increases
b) At constant RPM, cooling water flow rate and inlet temperature, the balance
point condensing temperature increases as evaporator temperature decreases
c) At constant RPM, cooling water flow rate and inlet temperature, the cooling
capacity at balance point increases as evaporator temperature increases
d) At constant RPM, cooling water flow rate and inlet temperature, the cooling
capacity at balance point increases as evaporator temperature decreases
Ans.: a) and c)
6. Starving of evaporator followed by reduction cooling capacity occurs when:
a) The capacity of expansion valve is larger than required
b) The inlet to the expansion valve is in two-phase region
c) The expansion valve is located at a higher elevation compared to condenser
d) There is a refrigerant leakage in the system
Ans.: b), c) and d)
Version 1 ME, IIT Kharagpur 19

More Related Content

What's hot

THERMODYNAMICS Unit III
THERMODYNAMICS Unit  III THERMODYNAMICS Unit  III
THERMODYNAMICS Unit III
sureshkcet
 
Se prod thermo_chapter_2_compressor
Se prod thermo_chapter_2_compressorSe prod thermo_chapter_2_compressor
Se prod thermo_chapter_2_compressorVJTI Production
 
Chapter03.pure substance
Chapter03.pure substanceChapter03.pure substance
Chapter03.pure substance
PASRINIVASAN_79
 
Rayegan thermo i-cengel-chapter 3-p2
Rayegan thermo i-cengel-chapter 3-p2Rayegan thermo i-cengel-chapter 3-p2
Rayegan thermo i-cengel-chapter 3-p2Larry Howard
 
A05v24n4
A05v24n4A05v24n4
A05v24n4
y1r2m
 
Chapter 7 pure substance
Chapter 7 pure substanceChapter 7 pure substance
Chapter 7 pure substance
Aaba Tambe
 
Mathematical modeling of continuous stirred tank reactor systems (cstr)
Mathematical modeling of continuous stirred tank reactor systems (cstr)Mathematical modeling of continuous stirred tank reactor systems (cstr)
Mathematical modeling of continuous stirred tank reactor systems (cstr)
Karnav Rana
 
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tubeNumerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
eSAT Publishing House
 
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tubeNumerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
eSAT Journals
 
SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...
SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...
SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...
AEIJjournal2
 
Rayegan thermo i-cengel-chapter 4-p2
Rayegan thermo i-cengel-chapter 4-p2Rayegan thermo i-cengel-chapter 4-p2
Rayegan thermo i-cengel-chapter 4-p2Larry Howard
 
Properties of pure substances
Properties of pure substancesProperties of pure substances
Properties of pure substances
HarishDAV
 
East Area GT fuel study_3 July 2014
East Area GT fuel study_3 July 2014East Area GT fuel study_3 July 2014
East Area GT fuel study_3 July 2014CangTo Cheah
 
Mass and energy balance
Mass and energy balanceMass and energy balance
Mass and energy balance
sjobli74
 
EQ-COMP - Process Simulation Software
EQ-COMP - Process Simulation SoftwareEQ-COMP - Process Simulation Software
EQ-COMP - Process Simulation Software
sandiptis
 
Gas turbine details
Gas turbine detailsGas turbine details
Gas turbine details
Aditya Sharma
 

What's hot (17)

THERMODYNAMICS Unit III
THERMODYNAMICS Unit  III THERMODYNAMICS Unit  III
THERMODYNAMICS Unit III
 
Se prod thermo_chapter_2_compressor
Se prod thermo_chapter_2_compressorSe prod thermo_chapter_2_compressor
Se prod thermo_chapter_2_compressor
 
Chapter03.pure substance
Chapter03.pure substanceChapter03.pure substance
Chapter03.pure substance
 
Rayegan thermo i-cengel-chapter 3-p2
Rayegan thermo i-cengel-chapter 3-p2Rayegan thermo i-cengel-chapter 3-p2
Rayegan thermo i-cengel-chapter 3-p2
 
A05v24n4
A05v24n4A05v24n4
A05v24n4
 
Chapter 7 pure substance
Chapter 7 pure substanceChapter 7 pure substance
Chapter 7 pure substance
 
Mathematical modeling of continuous stirred tank reactor systems (cstr)
Mathematical modeling of continuous stirred tank reactor systems (cstr)Mathematical modeling of continuous stirred tank reactor systems (cstr)
Mathematical modeling of continuous stirred tank reactor systems (cstr)
 
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tubeNumerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
 
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tubeNumerical analysis of heat transfer in refrigerant flow through a condenser tube
Numerical analysis of heat transfer in refrigerant flow through a condenser tube
 
Lab4_HeatExchange
Lab4_HeatExchangeLab4_HeatExchange
Lab4_HeatExchange
 
SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...
SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...
SPLIT SECOND ANALYSIS COVERING HIGH PRESSURE GAS FLOW DYNAMICS AT PIPE OUTLET...
 
Rayegan thermo i-cengel-chapter 4-p2
Rayegan thermo i-cengel-chapter 4-p2Rayegan thermo i-cengel-chapter 4-p2
Rayegan thermo i-cengel-chapter 4-p2
 
Properties of pure substances
Properties of pure substancesProperties of pure substances
Properties of pure substances
 
East Area GT fuel study_3 July 2014
East Area GT fuel study_3 July 2014East Area GT fuel study_3 July 2014
East Area GT fuel study_3 July 2014
 
Mass and energy balance
Mass and energy balanceMass and energy balance
Mass and energy balance
 
EQ-COMP - Process Simulation Software
EQ-COMP - Process Simulation SoftwareEQ-COMP - Process Simulation Software
EQ-COMP - Process Simulation Software
 
Gas turbine details
Gas turbine detailsGas turbine details
Gas turbine details
 

Viewers also liked

Refrigrationairconditioning 140423035013-phpapp01 (1)
Refrigrationairconditioning 140423035013-phpapp01 (1)Refrigrationairconditioning 140423035013-phpapp01 (1)
Refrigrationairconditioning 140423035013-phpapp01 (1)
Parth Bhingaradiya
 
B.tech i eme u 4 r & ac
B.tech i eme u 4 r & acB.tech i eme u 4 r & ac
B.tech i eme u 4 r & ac
Rai University
 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
naphis ahamad
 
Seminar presentation on Vapour Compression Refrigeration
Seminar presentation on Vapour Compression RefrigerationSeminar presentation on Vapour Compression Refrigeration
Seminar presentation on Vapour Compression Refrigeration
Ujjwal Nautiyal
 
Vapour absorption refrigeration systems
Vapour absorption refrigeration systemsVapour absorption refrigeration systems
Vapour absorption refrigeration systems
Akshay Mistri
 
Refrigeration and air conditioning ppt
Refrigeration and air conditioning pptRefrigeration and air conditioning ppt
Refrigeration and air conditioning ppt
Shubham Hadadare
 
Refrigration & air conditioning
Refrigration & air conditioningRefrigration & air conditioning
Refrigration & air conditioning
Siddharth Bedarker
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air ConditioningSaurabh Jain
 
Wind turbine doc
Wind turbine docWind turbine doc
Wind turbine doc
sayed fathy
 
Sayed hashim
Sayed hashimSayed hashim
Sayed hashim
sayed fathy
 
Enterprise Systems _ Introduction, Sales & Distribution
Enterprise Systems _ Introduction, Sales & DistributionEnterprise Systems _ Introduction, Sales & Distribution
Enterprise Systems _ Introduction, Sales & Distribution
CONNECTWELL concepts
 
EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...
EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...
EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...
Journal For Research
 
K11019(samant singh)rac
K11019(samant singh)racK11019(samant singh)rac
K11019(samant singh)rac
cpume
 
rac k10998 ppt
rac k10998 pptrac k10998 ppt
rac k10998 ppt
Ankush Prajapati
 
Data standard - IGES
Data standard - IGESData standard - IGES
Data standard - IGES
Himanshu Shrivastava
 
Successive improvement of refrigerants in vapour compression refrigeration sy...
Successive improvement of refrigerants in vapour compression refrigeration sy...Successive improvement of refrigerants in vapour compression refrigeration sy...
Successive improvement of refrigerants in vapour compression refrigeration sy...
Rahul Singh
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
msharma3646
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
sankar murthy
 
graphic stadards
graphic stadardsgraphic stadards
graphic stadards
Arjun Betageri
 

Viewers also liked (20)

Refrigrationairconditioning 140423035013-phpapp01 (1)
Refrigrationairconditioning 140423035013-phpapp01 (1)Refrigrationairconditioning 140423035013-phpapp01 (1)
Refrigrationairconditioning 140423035013-phpapp01 (1)
 
B.tech i eme u 4 r & ac
B.tech i eme u 4 r & acB.tech i eme u 4 r & ac
B.tech i eme u 4 r & ac
 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
 
Seminar presentation on Vapour Compression Refrigeration
Seminar presentation on Vapour Compression RefrigerationSeminar presentation on Vapour Compression Refrigeration
Seminar presentation on Vapour Compression Refrigeration
 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
 
Vapour absorption refrigeration systems
Vapour absorption refrigeration systemsVapour absorption refrigeration systems
Vapour absorption refrigeration systems
 
Refrigeration and air conditioning ppt
Refrigeration and air conditioning pptRefrigeration and air conditioning ppt
Refrigeration and air conditioning ppt
 
Refrigration & air conditioning
Refrigration & air conditioningRefrigration & air conditioning
Refrigration & air conditioning
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air Conditioning
 
Wind turbine doc
Wind turbine docWind turbine doc
Wind turbine doc
 
Sayed hashim
Sayed hashimSayed hashim
Sayed hashim
 
Enterprise Systems _ Introduction, Sales & Distribution
Enterprise Systems _ Introduction, Sales & DistributionEnterprise Systems _ Introduction, Sales & Distribution
Enterprise Systems _ Introduction, Sales & Distribution
 
EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...
EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...
EXPERIMENTAL ANALYSIS OF ZEOLITE BASE SOLAR VAPOUR ADSORPTION REFRIGERATION S...
 
K11019(samant singh)rac
K11019(samant singh)racK11019(samant singh)rac
K11019(samant singh)rac
 
rac k10998 ppt
rac k10998 pptrac k10998 ppt
rac k10998 ppt
 
Data standard - IGES
Data standard - IGESData standard - IGES
Data standard - IGES
 
Successive improvement of refrigerants in vapour compression refrigeration sy...
Successive improvement of refrigerants in vapour compression refrigeration sy...Successive improvement of refrigerants in vapour compression refrigeration sy...
Successive improvement of refrigerants in vapour compression refrigeration sy...
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
graphic stadards
graphic stadardsgraphic stadards
graphic stadards
 

Similar to R&ac lecture 25

Air-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdfAir-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdf
EssaYimer
 
Control system
Control systemControl system
Control system
abhishek ambhore
 
R&ac lecture 24
R&ac lecture 24R&ac lecture 24
R&ac lecture 24
sayed fathy
 
CENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIAL
CENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIALCENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIAL
CENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIAL
Vijay Sarathy
 
Brayton cycle (Gas Cycle)-Introduction
Brayton cycle (Gas Cycle)-IntroductionBrayton cycle (Gas Cycle)-Introduction
Brayton cycle (Gas Cycle)-Introduction
Hashim Hasnain Hadi
 
project cooling tower.docx
project cooling tower.docxproject cooling tower.docx
project cooling tower.docx
Mahamad Jawhar
 
Touil 1487
Touil 1487Touil 1487
Touil 1487
Dalila AMMAR
 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
shone john
 
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art  Phased Array Radar CoolingSBIR, Low Cost High Performance State-of-the Art  Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
martyp01
 
Basics of refrigeration engineering section b
Basics of refrigeration engineering  section bBasics of refrigeration engineering  section b
Basics of refrigeration engineering section b
Akshit Kohli
 
Chapter_9_Instrument.pdf
Chapter_9_Instrument.pdfChapter_9_Instrument.pdf
Chapter_9_Instrument.pdf
AnshuChandola1
 
S130304109117
S130304109117S130304109117
S130304109117
IOSR Journals
 
Design and Control of a Hydraulic Servo System and Simulation Analysis
Design and Control of a Hydraulic Servo System and Simulation AnalysisDesign and Control of a Hydraulic Servo System and Simulation Analysis
Design and Control of a Hydraulic Servo System and Simulation Analysis
IJMREMJournal
 
R&ac lecture 19
R&ac lecture 19R&ac lecture 19
R&ac lecture 19
sayed fathy
 
Heat Transfer Analysis of Refrigerant Flow in an Evaporator Tube
Heat Transfer Analysis of Refrigerant Flow in an Evaporator  TubeHeat Transfer Analysis of Refrigerant Flow in an Evaporator  Tube
Heat Transfer Analysis of Refrigerant Flow in an Evaporator Tube
IJMER
 
Steam Condenser Exergy Analysis of Steam Power Plant at Different Loads
Steam Condenser Exergy Analysis of Steam Power Plant at Different LoadsSteam Condenser Exergy Analysis of Steam Power Plant at Different Loads
Steam Condenser Exergy Analysis of Steam Power Plant at Different Loads
NAAR Journal
 
Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...
Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...
Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...
NAAR Journal
 

Similar to R&ac lecture 25 (20)

Air-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdfAir-Cycle refrigeration.pdf
Air-Cycle refrigeration.pdf
 
Control system
Control systemControl system
Control system
 
R&ac lecture 24
R&ac lecture 24R&ac lecture 24
R&ac lecture 24
 
CENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIAL
CENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIALCENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIAL
CENTRIFUGAL COMPRESSOR SETTLE OUT CONDITIONS TUTORIAL
 
Brayton cycle (Gas Cycle)-Introduction
Brayton cycle (Gas Cycle)-IntroductionBrayton cycle (Gas Cycle)-Introduction
Brayton cycle (Gas Cycle)-Introduction
 
project cooling tower.docx
project cooling tower.docxproject cooling tower.docx
project cooling tower.docx
 
02 GTP-14-1384
02 GTP-14-138402 GTP-14-1384
02 GTP-14-1384
 
Touil 1487
Touil 1487Touil 1487
Touil 1487
 
HHO driven CCPP
HHO driven CCPPHHO driven CCPP
HHO driven CCPP
 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
 
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art  Phased Array Radar CoolingSBIR, Low Cost High Performance State-of-the Art  Phased Array Radar Cooling
SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling
 
Basics of refrigeration engineering section b
Basics of refrigeration engineering  section bBasics of refrigeration engineering  section b
Basics of refrigeration engineering section b
 
Chapter_9_Instrument.pdf
Chapter_9_Instrument.pdfChapter_9_Instrument.pdf
Chapter_9_Instrument.pdf
 
S130304109117
S130304109117S130304109117
S130304109117
 
Design and Control of a Hydraulic Servo System and Simulation Analysis
Design and Control of a Hydraulic Servo System and Simulation AnalysisDesign and Control of a Hydraulic Servo System and Simulation Analysis
Design and Control of a Hydraulic Servo System and Simulation Analysis
 
R&ac lecture 19
R&ac lecture 19R&ac lecture 19
R&ac lecture 19
 
Artigo sea
Artigo seaArtigo sea
Artigo sea
 
Heat Transfer Analysis of Refrigerant Flow in an Evaporator Tube
Heat Transfer Analysis of Refrigerant Flow in an Evaporator  TubeHeat Transfer Analysis of Refrigerant Flow in an Evaporator  Tube
Heat Transfer Analysis of Refrigerant Flow in an Evaporator Tube
 
Steam Condenser Exergy Analysis of Steam Power Plant at Different Loads
Steam Condenser Exergy Analysis of Steam Power Plant at Different LoadsSteam Condenser Exergy Analysis of Steam Power Plant at Different Loads
Steam Condenser Exergy Analysis of Steam Power Plant at Different Loads
 
Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...
Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...
Distribution, Habitat Utilization and Threats to Chinese Pangolin (Manis Pent...
 

More from sayed fathy

R&ac lecture 23
R&ac lecture 23R&ac lecture 23
R&ac lecture 23
sayed fathy
 
R&ac lecture 22
R&ac lecture 22R&ac lecture 22
R&ac lecture 22
sayed fathy
 
R&ac lecture 21
R&ac lecture 21R&ac lecture 21
R&ac lecture 21
sayed fathy
 
R&ac lecture 20
R&ac lecture 20R&ac lecture 20
R&ac lecture 20
sayed fathy
 
R&ac lecture 18
R&ac lecture 18R&ac lecture 18
R&ac lecture 18
sayed fathy
 
R&ac lecture 16
R&ac lecture 16R&ac lecture 16
R&ac lecture 16
sayed fathy
 
refrigeration home
refrigeration home refrigeration home
refrigeration home
sayed fathy
 
type of refrigeration
type  of   refrigeration type  of   refrigeration
type of refrigeration
sayed fathy
 
Vapor copressor
Vapor copressorVapor copressor
Vapor copressor
sayed fathy
 
Turbine base drawings
Turbine base drawingsTurbine base drawings
Turbine base drawings
sayed fathy
 
Turbine assem drawings
Turbine assem drawingsTurbine assem drawings
Turbine assem drawings
sayed fathy
 
Turbine mast drawings
Turbine mast drawingsTurbine mast drawings
Turbine mast drawings
sayed fathy
 
Turbine hub drawings
Turbine hub drawingsTurbine hub drawings
Turbine hub drawings
sayed fathy
 
Interview
InterviewInterview
Interview
sayed fathy
 
Kaizen 130610225436-phpapp01
Kaizen 130610225436-phpapp01Kaizen 130610225436-phpapp01
Kaizen 130610225436-phpapp01
sayed fathy
 

More from sayed fathy (15)

R&ac lecture 23
R&ac lecture 23R&ac lecture 23
R&ac lecture 23
 
R&ac lecture 22
R&ac lecture 22R&ac lecture 22
R&ac lecture 22
 
R&ac lecture 21
R&ac lecture 21R&ac lecture 21
R&ac lecture 21
 
R&ac lecture 20
R&ac lecture 20R&ac lecture 20
R&ac lecture 20
 
R&ac lecture 18
R&ac lecture 18R&ac lecture 18
R&ac lecture 18
 
R&ac lecture 16
R&ac lecture 16R&ac lecture 16
R&ac lecture 16
 
refrigeration home
refrigeration home refrigeration home
refrigeration home
 
type of refrigeration
type  of   refrigeration type  of   refrigeration
type of refrigeration
 
Vapor copressor
Vapor copressorVapor copressor
Vapor copressor
 
Turbine base drawings
Turbine base drawingsTurbine base drawings
Turbine base drawings
 
Turbine assem drawings
Turbine assem drawingsTurbine assem drawings
Turbine assem drawings
 
Turbine mast drawings
Turbine mast drawingsTurbine mast drawings
Turbine mast drawings
 
Turbine hub drawings
Turbine hub drawingsTurbine hub drawings
Turbine hub drawings
 
Interview
InterviewInterview
Interview
 
Kaizen 130610225436-phpapp01
Kaizen 130610225436-phpapp01Kaizen 130610225436-phpapp01
Kaizen 130610225436-phpapp01
 

Recently uploaded

一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
ydteq
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
ViniHema
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
English lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdfEnglish lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdf
BrazilAccount1
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
SupreethSP4
 
AP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specificAP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specific
BrazilAccount1
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
R&R Consult
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
Kamal Acharya
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 

Recently uploaded (20)

一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
English lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdfEnglish lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdf
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
 
AP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specificAP LAB PPT.pdf ap lab ppt no title specific
AP LAB PPT.pdf ap lab ppt no title specific
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 

R&ac lecture 25

  • 1. Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Version 1 ME, IIT Kharagpur 1
  • 2. The specific objectives of this lecture are to: 1. Importance of complete vapour compression refrigeration system analysis and the methods used (Section 25.1) 2. Performance characteristics of reciprocating compressors (Section 25.2) 3. Performance characteristics of reciprocating condensers (Section 25.3) 4. Performance characteristics of evaporators (Section 25.4) 5. Performance characteristics of expansion valves (Section 25.5) 6. Performance characteristics of condensing unit (Section 25.6) 7. Performance characteristics of complete system by matching characteristics of evaporator and condensing unit (Section 25.7) 8. Effect of expansion valve on complete system performance (Section 25.8) 9. Meaning of sensitivity analysis (Section 25.9) At the end of the lecture, the student should be able to: 1. Explain the concept of complete system analysis and the characteristics of graphical and analytical methods 2. Express or plot the performance characteristics of individual components such as compressors, condensers and evaporators and enumerate the influence of operating parameters such as cooling water and brine flow rates, inlet temperatures etc. 3. Obtain balance point for a condensing unit by matching the characteristics of compressors and condensers 4. Obtain the balance point and characteristics curves for a complete system assuming an ideal expansion valve 5. Explain the effect of expansion device on system performance 6. Explain the meaning of sensitivity analysis and its importance in system design and optimization Version 1 ME, IIT Kharagpur 2
  • 3. 25.1. Introduction A basic vapour compression refrigeration system consists of four essential components, namely compressor, condenser, expansion valve and evaporator. The individual performance characteristics of these components have been discussed in earlier lectures. However, in an actual system these components work in unison. The performance of a complete system is a result of the balance between these four components. For example, when the heat sink temperature varies, it affects the performance of the condenser, which in turn, affects the performance of the expansion device, evaporator and the compressor. It is seen in Chapter 24 that expansion valve and compressor work in such a manner that the mass flow rate through the two components is the same at steady state. The balance point at steady state was obtained by equating the mass flow rates through these components. This is an example of balancing two components. Similar procedure can be extended to include the other two components also, so that a balance point for the entire system can be obtained by taking into account the individual characteristics. In principle, the balance point for the system can be obtained either by a graphical method or by an analytical method. In graphical method, the performance of two interdependent components is plotted for the same two variables of common interest. For example, mass flow rate and evaporator temperature (or pressure) are plotted along y and x axes respectively for combination of compressor – expansion device at constant condenser temperature. The point of intersection of the two resulting curves will indicate the conditions at which the mass flow rate and evaporator temperature will be same for the two components. This point is called the balance point and in steady-state the combination will achieve these conditions. In analytical method, the mass flow rate through expansion valve can be represented by an algebraic equation in terms of evaporator and condenser temperatures. Similarly, the mass flow rate through a given compressor can also be represented by an algebraic equation in terms of evaporator and condenser temperatures by regression analysis of experimental or analytical data. The balance point of the two components can be obtained by simultaneous solution of the two algebraic equations. Since the graphical method uses two-dimensional plots, it considers only two components at a time while the system analysis by mathematical means can consider more than two components simultaneously. Further, considering time variation of parameters in form of differential equations can simulate the dynamic performance also. Steady–state system analysis will involve simultaneous solution of algebraic equations. Version 1 ME, IIT Kharagpur 3
  • 4. In this chapter, balance points of condensing unit, compressor-evaporator combination have been considered for illustration. As a first step the performance data of industrial components is presented in the form of plots or equations. The raw data for this purpose can be obtained from the catalogues of manufacturers. These are plotted either directly or after processing in terms of required variables. 25.2. Reciprocating compressor performance characteristics: The power requirement and mass flow rate as function of evaporator temperature with condenser temperature as a parameter were presented in the chapter on compressors. For the purpose of balancing, the refrigeration capacity is required as a function of evaporator and condenser temperatures. This can be easily determined by considering the refrigeration cycle or from the catalogue data of the manufacturer. Figure 25.1 shows a theoretical single stage saturated cycle on T-s chart. S T 4 1 2 2'3 Pc Pe Tc Te Fig.25.1: A single stage, saturated vapour compression refrigeration cycle For the above cycle, the refrigeration capacity and power input to compressor are given by: ⎟⎟ ⎠ ⎞ ⎜⎜ ⎝ ⎛ − =−= 1 41 1 . 41r . e . v hh V)hh(mQ (25.1) where is the refrigeration capacity, are the refrigerant mass flow rate and volumetric flow rate of refrigerant at compressor inlet, respectively, 1 . r . Vandme . Q Version 1 ME, IIT Kharagpur 4
  • 5. v is the specific volume of refrigerant at compressor inlet, and h and h1 1 4 are the enthalpies of refrigerant at the exit and inlet of evaporator. The volumetric flow rate of a reciprocating compressor is given by: ⎟ ⎠ ⎞ ⎜ ⎝ ⎛ ⎟ ⎟ ⎠ ⎞ ⎜ ⎜ ⎝ ⎛ π η= 60 N 4 LD .nV 2 V1 . (25.2) where n is the number of cylinders, ηV is the volumetric efficiency, D, L and N are the bore, stroke and speed (in RPM) of the compressor, respectively. It is seen in Chapter 19 that at a given condenser temperature the cooling capacity associated with mass flow rate given by a compressor increases as the evaporator temperature increases. On the other hand, for a given evaporator temperature, the cooling capacity decreases with increase in condenser temperature. These characteristics are shown graphically in Fig.25.2. Evaporator temperature, Te Capacity, Qe T = 30o c C T = 35o c C T = 40o Cc Fig.25.2. Variation of refrigeration capacity of a reciprocating compressor with evaporator and condenser temperatures at a fixed RPM Version 1 ME, IIT Kharagpur 5
  • 6. The following equation may represent the above trends: 2 2 2 2 2 2 Q =a +a +a T +a T +a T +a T T +a T T +a T T +a T TT (25.3)e e e c c e c e c e c e c1 2 3 4 5 6 7 8 9 and Twhere Te c are evaporator and condenser temperatures, respectively. The a to a1 9 are constants which can be determined by curve fitting the experimental or manufacturers’ data using least square method, or by solving nine simultaneous equations of the type (25.3) for the nine constants ai using nine values of Q from given catalogue data for various values of T and Te e c. Similar expression can be obtained for power input to the compressor. 25.3. Condenser performance characteristics: Actual representation of condenser performance can be quite complex as it consists of a de-superheating zone followed by condensing and subcooling zones. The heat transfer coefficient varies continuously along the length of the condenser due to the continuously changing state of the refrigerant. Hence a detailed analysis should include these aspects. However, as discussed in an earlier chapter on condensers, most of the time a simplified procedure is adopted by assuming the temperature to remain constant at a saturated temperature corresponding to the condensing pressure and a constant average condensing heat transfer coefficient is assumed. For air-cooled condensers, it is possible to represent the total heat rejection rate from the condenser as a function of temperature difference and the overall heat transfer coefficient as follows: Q = U A (T - Tc c c c ∞) (25.4) where, T is the ambient temperature and Tc∞ is the condensing temperature of refrigerant. For water-cooled condenser, one has to consider the water flow rate and inlet water temperature as additional parameters. In this case also a single region with constant condenser temperature Tc is considered. The heat transfer rate for a water-cooled condenser is expressed as follows: )TT(Cpm i,wo,www −Q = U A LMTD = (25.5)c c c where is the water flow rate, U is overall heat transfer coefficient, Twm and Tc w,i w,o are the inlet and outlet water temperatures respectively. The log mean temperature difference of condenser LMTD is expressed as follows:c Version 1 ME, IIT Kharagpur 6
  • 7. ⎭ ⎬ ⎫ ⎩ ⎨ ⎧ − − − = o,wc i,wc i,wo,w TT TT ln TT LMTDc (25.6) From Eqns.(25.5) and (25.6) it can easily be shown that: NTUCm AU pww cc −⎟ ⎟ ⎠ ⎞ ⎜ ⎜ ⎝ ⎛ − −−=−−= e)TT(Te)TT(TT i,wcci,wcco,w (25.6) NTU is the Number of Transfer Units equal to ⎟ ⎟ ⎠ ⎞ ⎜ ⎜ ⎝ ⎛ ww . cc Cpm/AU The matching or the determination of balance point requires that its characteristics be represented in the same form as done for compressor, that is, cooling capacity vs. evaporator temperature. The condenser by itself does not give cooling capacity. One finds out the condensation rate of liquid refrigerant from the heat rejection capacity of condenser. The condensate rate multiplied by refrigeration capacity gives the cooling capacity. Hence from the given heat rejection capacity Qc, one finds the condensate rate for the SSS cycle as follows: refm rm = Q /(h – h ) (25.7)c 2 3 The corresponding refrigeration of the condenser is given by, rmQ (h – h= ) (25.8)e 1 4 The condenser characteristics are shown in Fig.25.3 for a fixed value of and Twm w,i. It is observed that for a fixed evaporator temperature the capacity is higher at higher condenser temperature. A higher condenser temperature leads to a larger value of LMTDc, which in turn gives a larger heat transfer rate and a larger condensate rate. Further it is observed that at fixed condenser temperature, the cooling capacity increases with increase in evaporator temperature. The heat rejection ratio decreases with increase in evaporator temperature hence less heat rejection Qc is required per unit cooling capacity, therefore the condensate rate of condenser can give larger cooling capacity. Figure 25.4 shows the effect of entering water temperature Tw,i on cooling capacity for various condenser temperatures. The cooling capacity is zero when the entering water temperature Version 1 ME, IIT Kharagpur 7
  • 8. is equal to condenser temperature. As the inlet water temperature increases for a fixed condenser temperature, the LMTDc decreases, which decreases the cooling capacity. The following algebraic equation representing the curves of Fig. 25.3 at constant inlet temperature and flow rate of water can represent these characteristics. 2 2 2 2 2 2 Q =b +b T +b T +b T +b T +b T T +b T T +b T T +b T T (25.9)e e e c c e c e c e c e c1 2 3 4 5 6 7 8 9 Evaporator temperature, Te Capacity, Qe T = 40o Cc T = 35o Cc T = 30o Cc Fig.25.3. Condenser performance at fixed water inlet temperature and flow rate Version 1 ME, IIT Kharagpur 8
  • 9. The characteristics in Fig. 25.4 are straight lines with almost same slope for all the condenser temperatures. These may be represented by the following equation with a constant G. Qe = G(Tc - Tw,i ) (25.10) Water inlet temperature, o C Capacity, Qe T = 40o C T c = 35o C T c = 30c o C T = 25o c C 40o C35o C30o C25o C 0 Fig.25.4. Condenser performance with water inlet temperature at fixed flow rate Version 1 ME, IIT Kharagpur 9
  • 10. 25.4. Evaporator Performance Evaporator is also a heat exchanger just like condenser. For the sake of illustration, consider an evaporator that is used for chilling a brine. The cooling capacity of brine chiller is shown in Fig. 25.5 as a function of brine flow rate for different values of LMTD of evaporator. The brine side heat transfer coefficient hb increases as the brine flow rate increases as a result, the overall heat transfer coefficient of the evaporator increases. Figure 25.5 shows that the cooling capacity increases with flow rate for fixed LMTD for this reason.e Brine flow rate Capacity, Qe LMTDe = 4o C LMTDe = 7o C LMTDe = 6o C LMTDe = 5o C Fig.25.5: Evaporator performance with brine flow rate and LMTDe One can obtain the data for cooling capacity at various brine inlet temperatures from the characteristics of evaporator as shown in Fig.25.5. For example, if a plot for brine inlet temperature T o of 10b,i C is required, then we may choose an LMTDe of 5o C and read the capacity Qe for the chosen brine flow rate . Then the brine outlet temperature Tbm is obtained from the equation:b,o Q = Cbme pb (T - Tb,i b,o) (25.11) is obtained from the expression for LMTD :Then the evaporator temperature Te e Version 1 ME, IIT Kharagpur 10
  • 11. ⎪⎭ ⎪ ⎬ ⎫ ⎪⎩ ⎪ ⎨ ⎧ − − − = eo,b ei,b o,bi,b e TT TT ln TT LMTD (25.12) The capacity Q and evaporator temperature Te e are determined for different values of LMTDe for a fixed brine flow rate and brine inlet temperature of 10o C. Figure 25.6 shows a plot obtained by this method. In this plot the brine flow rate is constant hence the brine side heat transfer coefficient is constant. If the evaporation heat transfer coefficient was also constant then overall heat transfer coefficient will also be constant and these lines will be straight lines. The evaporation heat transfer coefficient increases with increases in evaporator temperature hence these lines deviate slightly from straight lines. The capacity for these lines may be expressed as follows: 2 Q = c (T -T )+c (T -T )e 0 b,i e 1 b,i e (25.13) Evaporator temperature, Te Capacity, Qe Brine inlet temp.,Tb,i = 15o C Brine inlet temp. ,Tb,i = 10o C Brine inlet temp. ,Tb,i = 5o C 15o C10o C5o C 0 Fig.25.6: Performance characteristics of evaporator at fixed brine flow rate Version 1 ME, IIT Kharagpur 11
  • 12. 25.5. Expansion valve Characteristics: The characteristics of expansion valve play an important role in deciding the conditions achieved by the refrigeration system. It was shown in Chapter 24 that compressor and expansion valve seek an evaporator temperature such that under steady state conditions, the mass flow rate is same through the compressor and expansion valve. This was the result under the constraint that the condenser and evaporator have sufficiently large heat transfer areas and do not influence the performance of expansion device and compressor. In this chapter it is assumed that the expansion valve is capable of providing sufficient mass flow rate at all condenser and evaporator temperatures. This is assumed to simplify the matching problem. A float type of expansion valve or thermostatic expansion valve will meet this requirement. If the analysis is being done by computational method then the valve performance may also be included with some additional computational effort. 25.6.Condensing unit: As mentioned before, if graphical procedure is used to find performance evaluation of various components, then only two components can be considered at a time. In view of this the first sub-system considered is the condensing unit. Condensing unit is a combination of compressor and condenser. This unit draws refrigerant from the evaporator, compresses it in the compressor, condenses it in the condenser and then feeds the condensed liquid refrigerant to the expansion valve. It is available off-the-shelf as a packaged unit from the manufacturer with matched set of compressor, compressor motor and condenser along with reservoir and controls. This may be air-cooled or water-cooled unit which may be installed as an outdoor unit. The performance of condensing unit as function of evaporator temperature is obtained by combining the cooling capacity versus evaporator temperature characteristics of compressor and condenser. First we consider cooling capacity versus evaporator temperature assuming the compressor sped, the temperature and mass flow rate and entering water to condenser to be constant. This matching is obtained by superimposing the compressor performance curve given in Fig.25.2 on the condenser performance given in Fig.25.3 as shown in Fig.25.7. The intersection of compressor and condenser characteristics is at point A for 30o C condenser temperature. The combination of compressor and condenser will achieve a cooling capacity and evaporator temperature corresponding to this point at a condensing temperature of 30o C. Similarly, points B and C are the intersections at condenser temperatures of 35 and 40o C, respectively. These points are called balance points and the line A-B-C is called the performance characteristics of the condensing unit. Version 1 ME, IIT Kharagpur 12
  • 13. Compressor Condenser Balance line Evaporator temperature, Te It is observed that as the evaporator temperature decreases, the condensing temperature for the combination also decreases. This is explained as follows: at lower evaporator temperatures, the volumetric efficiency and the mass flow rate through the compressor decreases. This decreases the load on the condenser. A large condenser heat transfer area is available for small mass flow rate, hence condensation can occur at lower condenser temperature. It is also seen that as the evaporator temperature decreases, the refrigeration capacity of the condensing unit also decreases. This is due to the lower mass flow rate through the compressor due to lower volumetric efficiency and lower vapour density at compressor inlet. Figure 25.8 shows the variation of refrigeration capacity of the condensing unit with variation in inlet water temperature to the condenser. This is obtained by superimposition of compressor characteristics of Fig.25.2 on the variation of condenser performance with inlet water temperature given in Fig.25.4. The two figures are shown side-by-side. At constant evaporator temperature of say, – 5o C and condenser temperature of 30o C, the inlet water temperature corresponding to point D is required to match the two components. Points E and F are the balance points at condenser temperatures of 35 and 40o C respectively. Line DEF is the characteristics of the condensing unit at an evaporator temperature of – 5o C. It is observed that the cooling capacity decreases as the inlet water temperature to condenser increases.temperature to condenser increases. Capacity, Qe Tc=30o C Tc=35o C T =40o Cc C A B At fixed compressor speed, condenser water flow rate and water inlet temperature Fig.25.7: Performance characteristics of a condensing unit as a function of evaporator and condensing temperatures Version 1 ME, IIT Kharagpur 13
  • 14. These characteristics can also be obtained by simultaneous solution of Eqns. (25.3) and (25.9) for constant water temperature at condenser inlet and constant water flow rate. For example, we wish to find the condenser temperature and capacity for a given evaporator temperature of say 10o C. An iterative procedure may be devised as follows: (i) For Te = 10o C assume a condensing temperature Tc = 35o C (ii) Find Qe from Eqn.(25.3) (iii) Substitution of Te = 10o C and Qe in Eqn.(25.9) will yield a quadratic equation for Tc. The value of Tc is found and checked against the assumed value of Tc (35o C being the first iterate) and iteration is continued until the calculated value matches with the assumed value of condenser temperature. 25.7. Performance of complete system - condensing unit and evaporator: In steady state, a balance condition must prevail between all the components, that is, between condensing unit and evaporator assuming that the expansion valve will provide appropriate mass flow rate. This confluence will represent the performance of complete single-stage vapour compression refrigeration system. The combined curves will also give insight into the off- Evaporator temperature, o C Temperature of entering water, o C Qe Qe T =30o C T c c=30o C Tc=35o C T =30o C T c=40o C Tc =35o Cc F D E −5o C Fig.25.8: Performance of the condensing unit as a function of water temperature at condenser inlet Version 1 ME, IIT Kharagpur 14
  • 15. design performance of the system and operational problems. Superimposing Fig.25.6 for the evaporator characteristics and Fig.25.7 for condensing unit characteristics yields the balance point of the system. This is shown in Fig.25.9. The characteristic curve shown in Fig.25.9 is for constant water temperature at condenser inlet, constant flow rate to the condenser, constant compressor speed and constant brine temperature at the inlet to the evaporator. The point of intersection of the two curves gives the refrigeration capacity and the evaporator temperature that the system will achieve. One can study the response of the system in transient state also by this figure. In a transient state, say the evaporator temperature is 5o C. The figure shows that at this point the condensing unit has a capacity corresponding to point B while the evaporator has capacity corresponding to a lower value at C. Hence the condensing unit has excess capacity. The excess capacity will reduce the temperature of refrigerant and the metallic wall of the evaporator. This will continue until the balance point of 3o C is reached at point A. Figure 25.10 shows the effect of brine mass flow rate compared to that at the balance point. If the brine flow rate is increased, it is observed that cooling capacity increases to point D. At higher flow rate the overall heat transfer coefficient increases while (Tb,i-Tb,o) decreases permitting a larger mean temperature difference between refrigerant and brine. Therefore with increase in mass flow rate of brine, the cooling capacity increases. The pump power also Evaporator temperature, Te Capacity, Qe Condensing unit Evaporator (Brine inlet = 10o C) Excess capacity A B C 15o C 5o C Fig.25.9: Performance of the complete system as an intersection of evaporator and condensing unit characteristics at a brine inlet temperature of 10o C 5o C Version 1 ME, IIT Kharagpur 15
  • 16. increases for the increased brine mass flow rate. Hence one has to make a compromise between increased capacity and increased cost of pump power. Figure 25.10 shows the condition for lower brine flow rate when the heat transfer coefficient on brine side decreases and temperature difference (T -Tb,i b,o) increases. This is referred to as starving of evaporator. Evaporator temperature,Te Capacity, Qe Condensing unit Increased brine flow rate Design flow rate Evaporator starving D A Fig.25.10: Influence of brine flow rate on system cooling capacity 25.8. Effect of expansion valve: So far we have considered the balance between compressor, condenser and evaporator assuming that expansion valve can feed sufficient refrigerant to the evaporator so that heat transfer surface of the evaporator is wetted with refrigerant. Thermostatic expansion valve meets this requirement. Automatic expansion valve and capillary tube as observed in Chapter 24, result in a condition where sufficient quantity of refrigerant could not be supplied to evaporator. This condition was referred to as starving of evaporator. Starving reduces the heat transfer coefficient in evaporator since there is not sufficient refrigerant to wet the heat transfer surface consequently the cooling capacity reduces. There are other conditions also which may lead to this situation. These are as follows: Version 1 ME, IIT Kharagpur 16
  • 17. (i) Expansion valve is too small, (ii) Some vapour is present in the liquid entering the expansion valve, and (iii) Pressure difference across the expansion valve is small If the refrigerant charge in the system is small then condition (ii) is likely to occur. Also if the frictional pressure drop in the liquid line is large or the valve is located at higher elevation than condenser then this condition may occur. During winter months the ambient temperature is low hence in air-cooled condenser the condenser pressure is low and the difference between evaporator and condenser pressure is small, as a result the starving condition (iii) is likely to occur. In this condition the expansion valve does not feed sufficient refrigerant to the evaporator since the driving force; the pressure difference across the expansion valve is small. The evaporator pressure also decreases in response to drop in condenser pressure. The evaporator pressure may become so low that mass flow rate through compressor may decrease due to lower volumetric efficiency. Hermetic compressor depends upon the mass flow rate of refrigerant for cooling on motor and compressor. This may be adversely affected under starved condition. 25.9. Conclusion: The methods presented in this chapter are useful when compressor, condenser, evaporator and expansion valve have been selected and the performance of combined system is desired. This analysis may not be useful in selecting the initial equipment. The techniques presented in this chapter are useful in predicting system performance for off-design conditions like a change in ambient temperature, condenser inlet water temperature and brine inlet temperature etc. The power requirement of the compressor has not been given due emphasis in the analysis. In fact, an equation similar to Eqn. (25.3) may be written for this also. This can also be found from known values of condenser and evaporator loads. An important aspect of refrigeration system performance is the sensitivity analysis which deals with % change in, say cooling capacity with % change in capacity of individual components like the compressor size, heat transfer area of evaporator and condenser etc. This can easily be done by mathematical simulation using the performance characteristics of the components given by empirical equations. It has been shown in Stoecker and Jones that compressor capacity has the dominant effect on system capacity and evaporator is next in importance. An increase in compressor capacity by 10% has the effect of 6.3% increase in system capacity. A 10% increase in evaporator gives 2.1% increase in system capacity, while 10% increase in condenser gives 1.3 % increase in system capacity. Such a data along with the relative costs of the components can be used for optimization of the first cost of the system. Table 25.1 taken from Stoecker and Jones illustrates the results of sensitivity analysis. Version 1 ME, IIT Kharagpur 17
  • 18. Ratio of component capacity to base capacity Compressor Condenser Evaporator Refrigeration capacity, TR % increase 1.0 1.0 1.0 95.6 - 1.1 1.0 1.0 101.6 6.3 1.0 1.1 1.0 96.8 1.3 1.0 1.0 1.1 97.6 2.1 1.1 1.1 1.1 1.1 10.0 Table 25.1: Results of sensitivity analysis of a vapour compression refrigeration system (Stoecker and Jones, 1982) Questions and answers: 1. Which of the following statements are TRUE? a) A graphical method generally considers two components at a time for system analysis b) An analytical method can consider more than two components at a time for system analysis c) Use of analytical method requires simultaneous solution of algebraic equations d) All of the above Ans.: d) 2. Which of the following statements are TRUE? a) At a fixed RPM, the cooling capacity of a reciprocating compressor decreases as the evaporator temperature decreases and condensing temperature increases b) At fixed water inlet temperature and flow rate, the capacity of a condenser increases as the condensing temperature and evaporator temperature increase c) At fixed water flow rate and condensing temperature, the capacity of a condenser increases as the water inlet temperature increases d) At fixed water flow rate and cooling capacity, the condensing temperature increases as the water inlet temperature increases Ans.: a), b) and d) 3. Which of the following statements are TRUE? a) At a fixed evaporator LMTD, the cooling capacity of a brine chilling evaporator increases with brine flow rate Version 1 ME, IIT Kharagpur 18
  • 19. b) At a constant brine flow rate and a given evaporator temperature, the cooling capacity of the evaporator increases as the brine temperature at evaporator inlet increases c) At a constant brine flow rate and a given evaporator temperature, the cooling capacity of the evaporator increases as the brine temperature at evaporator inlet decreases d) For constant cooling capacity and brine flow rate, the evaporator temperature has to decrease as the brine temperature at the inlet decreases Ans.: a), b) and d) 4. Which of the following statements are TRUE? a) The performance characteristics of a condensing unit are obtained by matching the characteristics of compressor and condenser b) The performance characteristics of a condensing unit are obtained by matching the characteristics of evaporator and condenser c) The performance characteristics of a condensing unit are obtained by matching the characteristics of expansion valve and condenser d) The performance characteristics of a condensing unit are obtained by matching the characteristics of compressor and evaporator Ans.: a) 5. Which of the following statements are TRUE? a) At constant RPM, cooling water flow rate and inlet temperature, the balance point condensing temperature increases as evaporator temperature increases b) At constant RPM, cooling water flow rate and inlet temperature, the balance point condensing temperature increases as evaporator temperature decreases c) At constant RPM, cooling water flow rate and inlet temperature, the cooling capacity at balance point increases as evaporator temperature increases d) At constant RPM, cooling water flow rate and inlet temperature, the cooling capacity at balance point increases as evaporator temperature decreases Ans.: a) and c) 6. Starving of evaporator followed by reduction cooling capacity occurs when: a) The capacity of expansion valve is larger than required b) The inlet to the expansion valve is in two-phase region c) The expansion valve is located at a higher elevation compared to condenser d) There is a refrigerant leakage in the system Ans.: b), c) and d) Version 1 ME, IIT Kharagpur 19