Influence of Wind Loads on Tall
Buildings
Study Project Report
By
Mukul Yambal (2013A2PS581P)
Study Oriented Project
Under Dr. G. Muthukumar
BITS Pilani
May 2016
2
Contents
ACKNOWLEDGEMENT ................................................................................................................................................. 3
INTRODUCTION.......................................................................................................................................................... 4
INDIAN STANDARD CODE -IS 875: PART3 ................................................................................................................... 9
Basic Wind Speed:.............................................................................................................................................10
Design Wind Speed:..........................................................................................................................................10
Probability factor (risk coefficient) (k1) .......................................................................................................11
Terrain, Height and Structure Size factor (K2) .............................................................................................11
Topography factor (K3) ................................................................................................................................12
Importance Factor for Cyclonic Region (k4).................................................................................................13
Wind Pressure...................................................................................................................................................13
Design Wind Pressure.......................................................................................................................................14
Wind Forces on individual members ................................................................................................................14
Wind Forces on structure..................................................................................................................................15
Dynamic Effects.................................................................................................................................................15
Gust Factor........................................................................................................................................................17
Cross wind Response ........................................................................................................................................19
Difference between IS 875:1987 and 2009 (draft)..............................................................................................20
ASCE-7: Minimum Design Loads for Buildings and Other Structures (American code) (2002) .........................21
Some Basic Concepts ........................................................................................................................................21
1. Basic Wind Speed (V) ...........................................................................................................................21
2. Exposure Category................................................................................................................................22
3. Topographic Factor (KZI) .......................................................................................................................23
4. Gust Factor (G or Gf).............................................................................................................................24
Method 1 - Simplified Procedure......................................................................................................................25
Method 2 - Analytical Procedure......................................................................................................................27
Method 3 - Wind Tunnel Procedure.................................................................................................................28
Example:............................................................................................................................................................29
1. Structural Data .....................................................................................................................................30
2. Properties .............................................................................................................................................31
3. Load Combination factors....................................................................................................................32
4. Auto Load Calculations Using ETABS 2015 ..........................................................................................32
5. Analysis.................................................................................................................................................41
6. Displacements due to Wind Loads.......................................................................................................43
Summary...........................................................................................................................................................45
Conclusion.........................................................................................................................................................47
References ........................................................................................................................................................48
3
ACKNOWLEDGEMENT
I am indebted to my Instructor Dr. G. Muthukumar, Lecturer Civil Engineering
Group, BITS Pilani who introduced me to this work and provided me an opportunity to work
under his supervision. His constantly supported and encouraged me throughout this work. The
discussions with him were so healthy and fruitful that gave me a chance to increase my domain
of knowledge.
4
INTRODUCTION
This Study Project covers some essential study regarding wind loads and related
different codal provisions related to wind and load considered in designing of buildings due to
wind. Study of Indian Standard code (IS 875:1987:- Part 3) as well as (IS 875:2009 part 3-draft)
is explained in this report. American Code for wind loads (ASCE-7:2002 version) and its
comparison with Indian codes is also included in this report.
Some properties and facts related to tall buildings, wind and variation of wind with
respect to its height are introduced below which will give necessity of wind loads on tall
buildings.
TALL BUILDINGS
There is no absolute definition of what constitutes a “tall building” according to
Council of Tall Buildings and Urban Habitat (CTBUH).Height is relative concept, i.e. a building
which should be considered as tall building in country like India may not considered as tall in
case of tall buildings countries like US(Chicago). Measurement of height of Tall Building can
be considered by three methods according to CTBUH. :-
1. Height to Architectural Top
Height is measured from the level of the lowest, significant, open-
air, pedestrian entrance to the architectural top of the building, including spires,
but not including antennae, signage, flagpoles or other functional-technical
equipment.
This measurement is the most widely utilized and is employed to define the Council
on Tall Buildings and Urban Habitat (CTBUH) rankings of the “World’s Tallest
Buildings.”
Some of rankings of world’s tallest buildings are listed below:-
i) Burj Khalifa Dubai (2010) 828m /2,717ft
ii) Shanghai Tower, Shanghai (2015) 632m 2,073ft
iii) Makkah Royal Clock Tower Hotel, Mecca (2012) 601m 1,972ft
v) One World Trade Center, New York City (2014) 541m 1,776ft
5
2. Height to Tip
Height is measured from the level of the lowest, significant, open-
air, pedestrian entrance to the highest point of the building, irrespective of material
or function of the highest element (i.e., including antennae, flagpoles, signage, and
other functional technical equipment).
3. Highest Occupied Floor
Height is measured from the level of the lowest, significant, open-
air, pedestrian entrance to the finished floor level of the highest occupied floor
within the building.
Note: - A building having height more than 15 m is considered as tall building according to
National Building Code 2005 of India is Called Tall building. (High Rise Building).
Building having height more than 18 m (60ft.) is considered as tall building according to
American code ASCE-7: 2002 version. Building having mean roof height more than least
horizontal dimension is also considered as tall building according to this American code.
6
WIND
Wind is air in motion relative to the surface of the earth. Primary
reasons of wind is rotation of earth as well as due to difference in terrestrial radiation.
Over 50 years study of wind and its speed is carried out in different places to find mean
wind speed in different places so that it can be used in further calculations of wind loads
which is listed in IS 875:Part3 -1997 as well as in 2009 draft version. This study is carried
out using anemometers or anemographs which are installed in different meteorological
stations at height of 10 m- 30 m. According to this study India is divided into six different
categories depending upon basic wind speeds in each zone. Average basic speeds as per
IS875 is given in table 1.
Some parts of Jammu and Kashmir as well as Mizoram and Tripura. 55 m/s
Whole eastern Coastal area, Costal part in Gujarat as well as Assam. 50 m/s
Some part of Tamil Nadu and almost Half North India which includes part of Gujarat ,whole
Rajasthan ,Punjab ,part of Madhya Pradesh, Utter Pradesh ,Bihar ,Part of Jharkhand, West
Bengal and Sikkim.
47 m/s
Western coastal area in Maharashtra as well as some inside land near eastern costal area which
is part of Andhra Pradesh ,Maharashtra and Orissa and some eastern part of India , that is ,
Nagaland , Manipur and Mizoram.
44 m/s
Most of the Middle and South India. 39 m/s
Some part of Karnataka, Kerala, Andhra-Pradesh, Telangana and Tamil Nadu which is mostly
land between eastern and western costal area.
33 m/s
Table1-According to IS875:1997 - Part3
In American code, the basic wind speed, V, used in the
determination of design wind loads on buildings and other structures is considered from
a counter curve given in ASCE-7: 2002 version except Special wind regions Estimation of
wind speed from regional data. Data for Special Wind Region is listed below in Table2.
Location V (mph) (m/s)
Hawaii 105 47
Puerto Rico 145 65
Guam 170 76
Virgin Islands 145 65
American Samoa 125 56
Table2-According to ASCE-7:2002: Special Wind Regions
7
WIND AND ITS VARIATION WITH HEIGHT
Wind speeds are generally very low near earth surface due to earth friction.
It increases with height from zero to some value and then it remains almost constant. At
some height wind can be considered as free from
earth’s atmosphere which leads to almost constant
velocity after certain height. This height is known as
Fetch Height or Gradient Height.
Wind is mostly in horizontal direction in
high speeds as compared to its vertical component.
Vertical component of Wind may be neglected in
mostly design cases for wind loads as it is very small,
hence generally horizontal winds are considered.
Gradient Height
8
As per CTBUH, Tall buildings ae also classifies as supertall and mega tall
buildings. Supertall building is a building having height over 300 m (984 feet) while Mega
building is one which has height over 600 m (1968 feet).There were total 91 supertall
buildings and 2 Mega buildings in world till June 2015.Now mostly high populated cities
are coming up with many tall structures. For seismic loads, earthquake loads are usually
known to people but wind loads also plays important role near coastal areas as discussed
above. There are many areas damaged due to cyclones. Wind speed increases with
height from ground surface and hence its impact which eventually leads to Wind as
major factor in consideration for case of tall buildings. Increasing number of tall
structures and unawareness of people regarding wind loads makes this study very
important.
This report will describe about IS 875:1987 –Part 3 which is mainly code used
for designing wind loads in India. Calculation of design wind speeds, design wind
pressure followed by design wind pressure , some Oscillation related phenomenon like
Galloping , flutter ,Ovaling ,Vortex Shedding , etc. according to IS 875:1987 – part 3 as
well as few changes made in IS 875:2009 –Part-3 (draft form) which includes
Interference effect, Dynamic Response Factor ,Cross wind response ,etc.
This report will also describe about American code for Wind Loads, ASCE-
7:2002 version, Wind loading part. Three different methods, i.e. Simplified Procedure,
Analysis Procedure and Wind Tunnel Testing will be described in the report along with
its limitations.
This report will be completed by comparing deformation due to wind loads
which will be calculated by software E-Tabs-2014. A Concrete frame and Steel frame
will be modelled and deformation due to wind will be calculated using IS 875:1987 as
well as ASCE -7:2002 version.
9
INDIAN STANDARD CODE -IS 875: PART3
IS 875 was first published in 1957 for the guidance of civil engineers,
designers and architects associated with the planning and design of buildings which was
included the provisions for the basic design loads (dead loads, live loads, wind loads and seismic
loads) to be assumed in the design of the buildings. In its first revision in 1964, the wind pressure
provisions were modified on the basis of studies of wind phenomenon and its effect on
structures, undertaken by the special committee in consultation with the Indian Meteorological
Department. Similarly in 1987 code many changes carried out which leads to better design of
building for wind loads and continuous studied related wind made another version of this code
in 2009 which is still in its draft form.
Design aspect related to wind loads are mentioned in this Indian
Standard Codes. This code is designed by examining few international codes listed below:-
 BSCP 3:1973 Code of basic data for design of buildings: Chapter 5 –Loading: Part 2: Wind
loads
 AS 117, Part 2 -1983 SAA Loading code Part2 –Wind forces
 NZS 4203-1976 Code of Practice for general structural design loading for buildings
 ANSI A58.1-1972 American Standard Building code requirements for minimum design
loads in buildings and other structures
 Wind resistant design regulations, a world list. Association for Science Documents
Information, Tokyo.
Some points in IS 875 part 3 are listed below:-
i. Basic Wind speed
ii. Design Wind speed
iii. Wind Pressure
iv. Design Wind Pressure
v. Wind Forces on individual members
vi. Wind Forces on structure
vii. Dynamic Effects
viii. Gust Factor
10
Basic Wind Speed:
India is divided in 6 zones according to Basic wind velocity which is
applicable for height about 10 m from mean ground level which is explained in
introduction of wind.
In Appendix A, IS 875: Part3 -1987 (as well as 2009), Basic wind speed
(Vb) for some important cities is listed by studying wind speeds over 50 years.
Cyclonic storms generally extend up to 60 km inland after striking sea
coast. The influence of wind speed off the coast up to the distance of about 200km
may be taken as 1.15 times the value of nearest coast in case of absence of definite
data. This is also known as off shore velocity.
Design Wind Speed:
Design Wind Speed can be determined by estimating Basic Wind
Speed as well as some other factors such as topographical factor, risk factor, terrain
and height factor and Importance Factor for Cyclonic Region. Relation between all
this factors is given by following formulae: -
Vz=K1K2K3Vb - (IS 875:1987 – Part3)
Vz=K1K2K3K4Vb - (IS 875:2009 – Part3)
Where
 Vz = design wind speed at any height z in m/s
 Vb = basic wind speed in m/s
 K1 = Probability factor (risk coefficient)
 K2 = terrain, height and structure size factor
 K3 = topography factor
 K4 = Importance Factor for Cyclonic Region
11
Probability factor (risk coefficient) (k1)
This factor depends on estimated life structure required for a
building. Few of K1 Values are given in IS 875 part -3 and it can be generalized
using following formula:-
K1=
XN,PN
X50,063
=
A−B[ln⁡{−
1
N
ln⁡(1−PN)}]
A+4B
Where,
 N = mean probable design life of the structure in years
 PN = risk level in N consecutive years (probability that the design wind
speed is exceeded at least once in N successive years), nominal value = 0.63
 XN,P = extreme wind speed for given value of N and PN
 X50,0.63 = extreme wind speed for N = 50 years and PN = 0.63
A and B are coefficients depends on different basic wind speed zones.
Terrain, Height and Structure Size factor (K2)
As per its name K2 factor depends on Terrain, Height of
different structures, Size factor that is Class of Buildings. Values of K2 is gives in IS
875 according to above factors. As per IS 875, Terrain is divided into four different
categories and buildings are divided into three types as per its size which is
described below:-
a. Types of Terrain:
Classified in Four different terrains as follows:-
a) CATEGORY 1:- Exposed Open terrain with few or no obstructions.
b) CATEGORY 2:- Open terrain with well scattered obstructions.
c) CATEGORY 3:- Terrain with numerous closely spaced obstructions.
d)CATEGORY 4:- Terrain with numerous large high closely spaced
obstructions
12
b. Classes of Buildings:
Buildings can be classified in three different classes depending upon size
factor:-
a) Class A:-Structure and/or its component having its maximum dimension
less than 20 m.
b) Class B: - Structure and/or its component having its maximum dimension
between 20 m and 50 m.
c) Class C: - Structure and/or its component having its maximum dimension
greater than 50 m
The velocity profile for a given terrain category does not develop to
full height immediately with the commencement of that terrain category but
develop gradually to height ( h, ) which increases with the fetch or upwind distance
(x). The relation between the developed height (h,) and the fetch (x) for wind-flow
over each of the four terrain categories is given in IS 875. For structures of heights
greater than the developed height (h,) the velocity profile may be determined in
accordance with the less or least rough terrain, or another procedure is given in
Appendix B of IS 875:1987-part3
Topography factor (K3)
This is factor for taking local topographic feature like cliffs, hills
valleys, etc. into consideration while calculating design wind speed. This factor is
effective when upwind slop (θ) is greater than 3o. Value of K3 is i) 1 when θ< 3o ii)
1.36 when θ> 17o. And for 3 o < θ < 17 o It can be given by:-
K3 =1 + Cs
Where C and s can be determined by using
Appendix C given in IS 875:1987 –part3
13
Importance Factor for Cyclonic Region (k4)
Cyclonic wind speeds may be higher than basic wind speed. To
consider increase in this velocity during cyclones K4 factor is introduced in IS
875:2009 Part 3. This factor will be mostly useful in cyclonic regions like eastern
coastal areas of India.
The following values of k4 are stipulated, as applicable
according to the importance of the structure:
 Structures of post–cyclone importance 1.30
 Industrial structures 1.15
 All other structures 1.00
This factor is useful for 60 km inland from eastern sea coast and Gujarat sea coast.
Wind Pressure
Wind Pressure due to design velocity can be determined by following
formula given in IS 875:1987 –part3
Pz= 0.6 (𝑉z⁡)2
Where
 𝑃z = wind pressure in N/m2 at height z.
 𝑉z = design wind velocity in m/s at height z.
The coefficient 0’6 (in SI units) in the above formula depends on a number
of factors and mainly on the atmospheric pressure and air temperature. The value
chosen corresponds to the average appropriate Indian atmospheric conditions.
14
Design Wind Pressure
Design Wind pressure according to IS875:1987 –part3 is same as
wind pressure explained above. In IS 875:2009 –part3 few new factors like wind
directionality factor, area averaging factor, Combination factor are introduced to make
design economical, hence design pressure is different than wind pressure which is given
by following formula:-
Pd =⁡Kd.⁡Ka.Kc .Pz
Where
 Pd = design wind pressure in N/m2 at height z.
 Pz = wind pressure in N/m2 at height z.
 Kd = wind directionality factor.
 Ka = area averaging factor.
 Kc = Combination factor.

Wind Forces on individual members
The wind load on individual structural elements such as roofs and
walls, and individual cladding units and their fittings, it is essential to take account
of the pressure difference between opposite faces of such elements or units. For
calculation of wind force on individual cladding units following formula can be
used:-
F = (Cpe − Cpi) A pd
Where
 Pd = design wind pressure in N/m2 at height z.
 Cpe = external pressure coefficient.
 Cpi = internal pressure coefficient.
 A = Surface area of structural element
Internal and external pressure coefficients for different units having different
shapes, structures and slopes are described in IS 875 with figures.
15
Wind Forces on structure
The value of force coefficients apply to a building or
structure as a whole, and when multiplied by the effective frontal area A, of the
building or structure and by design wind pressure, pd gives the total wind load
on that particular building or structure.
F = (Cf) A pd
Where
 Pd = design wind pressure in N/m2 at height z.
 Cf = force coefficient of building.
 A = Surface area of structural element.
Force Coefficient:
Force coefficient can be classified into 3 types as follows:-
i) Frictional force drag coefficient:-In certain buildings of special shape, a force
due to frictional drag shall be taken into account in addition to those loads
specified.
ii) Force Coefficients for Clad Buildings:-values of Cf for different shaped clad
buildings are mentioned in IS 875
iii) Force Coefficients for unclad Buildings:- values of Cf for different shaped
unclad buildings are mentioned in IS 875.
Dynamic Effects
For tall, long span and slender structures, wind Fluctuations
causes fluctuating forces on structure which induces large dynamic motions
including oscillations. Wind loads can induce both along wind Oscillations as well
As crosswind Oscillations (vortex shedding). Along wind Oscillations are
calculated more readily. Estimation of Vortex shedding has been introduced in IS
875: 1987 but is still not developed enough.
Flexible slender structures and structural elements have to
investigate for oscillating effects cause due to wind loadings. Criteria for
examining structure or building need not necessary if buildings and closed
structures having ratio of height to minimum lateral dimension, more than 5
OR natural frequency of buildings and closed structures in first mode is less
than 1Hz.
16
i) Fundamental time period (T):
Fundamental time period (T) can be determined by experimental
methods of similar structures. In absence of such data T can be calculated
as follows:-
 For moment resisting frames without bracings:-
T=0.1n
n=number of storeys including basement storeys
 For all others
T=
.09𝐻
𝑑
o H=Height of building in metres.
o D=maximum base dimension of building in metres in direction
parallel to applied load.
ii) Wind induced Motions (T):
a) Galloping: - Galloping is the self-induced cross-wind oscillations of
flexible structures due to aerodynamic forces that are in-phase with
the motion of the structure. It is characterised by the progressively
increasing amplitude of transverse vibrations with increased wind
speed. Galloping is generally not an issue for buildings.
b) Flutter: - Flutter is unstable oscillatory motion of a structure due to
coupling between aerodynamic force and elastic deformation of the
structure. Flutter can set in at wind speeds much less than those
required for exciting the individual modes of motion. Long span
suspension bridge decks or any member of a structure with large values
of d/t ( where d is the depth of a structure or structural member parallel
to wind stream and t is the least lateral dimension of a member ) are
prone to low speed flutter. Wind tunnel testing is required to.
Determine critical flutter speeds and the likely structural response.
Other types of flutter are single degree of freedom stall flutter, torsional
flutter, etc.
Example of flutter: -The collapse of the original Tacoma Narrows Bridge,
a suspension bridge in the U.S. state of Washington.
17
c) Ovalling: - This walled structures with open
ends at one or both ends such as oil storage
tanks, and natural draught cooling towers in
which the ratio of the diameter of minimum
lateral dimension to the wall thickness is of
the order of 100 or more, are prone to
ovalling oscillations. These oscillations are characterized by periodic
radial deformation of the hollow structure.
iii) Motion due to Vortex Shedding:
For slender structures, ŋ –frequency of Vortex Shedding can be given by
ŋ=
SVd
b
 S=Strouhal number.
 Vd=Design Wind velocity.
 b=breadth of structure or
structural member in
horizontal plane normal to
wind direction.
Circular sections
 S=0.2 for Vz ≤ 7
 S=0.25 for Vz > 7
Rectangular Structures
 S=0.15
Gust Factor
IS 875:1987 allows Gust method for calculation of wind loads some cases .This
method needs Hourly mean wind speed which is equal to basic wind speed. Wind load
can be calculated from Gust factor method by using following formula:-
𝐹 = (𝐶𝑓) 𝐴𝑒 𝑝𝑑𝐺
 Fz = along wind load on the structure at any height z corresponding to strip area Ae
 Cf = force coefficient of building
 Ae = effective frontal area considered for structure at height z
 Pz = design pressure at height z due to hourly mean wind
Ovalling
18
G=Gust factor =
𝑝𝑒𝑎𝑘 𝑙𝑜𝑎𝑑
𝑚𝑒𝑎𝑛 𝑙𝑜𝑎𝑑
G=1+gtr√ 𝐵(1 + ∅)2 +
𝑆𝐸
𝛽
Where
gf = peak factor defined as the ratio of the expected peak value to the
root mean value of a fluctuating load
Y = roughness factor which is dependent on the size of the structure in
relation to the ground roughness.
B = background factor indicating a measure of slowly varying component
of fluctuating wind load
SE
β
=measure of the resonant component of the fluctuating wind load
S = size reduction factor
E = measure of available energy in the wind stream at the natural
frequency of the structure
β = damping coefficient (as a fraction of critical damping) of the structure
ɸ =
𝑔𝑡 × 𝑟√𝛽
4
19
Cross wind Response
This factor is defined in IS 875: 2009 draft version .The equivalent
cross–wind static force per unit height (We) as a function of z in Newton per
meter height, shall be as follows:
We (z) = 0.6 [Vh] 2 d Cdyn
Where,
d = Lateral dimension of the structure parallel to the wind stream, and
Cdyn = 1.5gR
b
𝑑
𝐾𝑚
1+𝑔𝑣𝑙ℎ
(
𝑧
ℎ
)k √(
𝜋𝐶𝑓𝑠
𝛽
)
Where,
Km = mode shape correction factor = 0.76 + 0.24 k
Where
k = mode shape power exponent for the fundamental mode of
vibration
= 1.5 for a uniform cantilever
= 0.5 for a slender framed structure (moment resistant)
= 1.0 for building with central core and moment resisting façade
= 2.3 for a tower decreasing in stiffness with height, or with a large
mass at top
Cfs = cross–wind force spectrum coefficient generalized for a linear
mode shape.
GR = peak factor for resonant response (1 hour period) given by
GR = [2 log (3600f0)] (½)
β = ratio of structural damping to critical damping of Structure
Ih = turbulence intensity, obtained by setting z equal to h
gv = peak factor for the upwind velocity fluctuations, which shall be
taken as 3.5
20
Difference between IS 875:1987 and 2009
(draft)
 For calculation of wind speed K4 factor for cyclone is introduced in 2009 version.
 Design Wind Pressure is same as wind pressure in case of 1987 code but for 2009 version
three new factors are introduced. Design pressure can be obtained by multiplying this
factors by wind pressure. This three factors are
 a)Kd=wind directional factor
 a)Ka=Area averaging factor
 a)Kc=combination factor
 Interference effect is introduced in 2009 code while it was not in 1987. When wind comes
from striking some buildings and original wing may have some phase difference which will
leads to interference effect.
 Dynamic Response Factor will tell you wind pressure at certain height of building. In the
1987 version, the dynamic response factor, Cdyn, was applied to the wind loading due to
hourly mean wind speed, as opposed to the 3second gust speed used in the 2009 version.
 CROSS-WIND RESPONSE is introduced in 2009 draft for determining equivalent static
wind force and base overturning moment in the cross-wind direction for tall enclosed
buildings and towers of rectangular cross-section
 Some parts of the code have been revised from the 1987 version to take into account the
wind incidence angle.
21
ASCE-7: Minimum Design Loads for Buildings
and Other Structures (American code) (2002)
This Code is published by American Society for Civil Engineers. As per name
of code this is made for design of all kinds of loads like dead, live, soil, flood, wind, snow,
rain, ice and earthquake loads. In this report mainly we will focus on wind load designing.
The design wind loads for buildings and other structures, including the main
wind force-resisting system and component and cladding elements thereof, shall be
determined using one of the following procedures: 1) Method 1 - Simplified Procedure
2) Method 2 – Analytical Procedure
3) Method 3 – Wind Tunnel Procedure
Some Basic Concepts
Before going into further details of procedures, some basic concepts should be
introduced as per ASCE-7:2002 Version.
1. Basic Wind Speed (V)
Basic Wind Velocity can be determined by contour map given in code ASCE-
7:2002 version except for special wind regions and it can also be determined using
Regional Climatic Data.
Special Wind Regions: The Basic Wind Speed shall be increased in case the
wind speeds are higher than given in code by record or experience.
Regional Climatic Data: Reginal Climatic Data should be preferred instead
of code data when approved extreme-value statistical analytical procedure have
been employed in reducing the data and all related factors have been taken into
account.
Hurricane-Prone Regions: This code allows basic wind speed from
simulation techniques instead of given in code data when approved simulation or
extreme value statistics analysis procedures are used. (Not allowed along Gulf and
22
Atlantic coasts, the Caribbean or Hawaii). The resulting design speed by this
methods shall not be less than resulting 500 year return period wind speed divided
by √1.5 .
2. Exposure Category
The characteristics of ground roughness and surface irregularities are the
important factors to be considered while designing wind loads. This factors are
included in exposure category which will also take ground variation due to natural
topography and vegetation.
Surface Roughness Category: There are three major categories of surface
roughness as follows
Surface Roughness B: Urban and suburban area, wooded areas or other
terrain with numerous closely spaced obstructions having size of single family
dwelling or larger.
Surface Roughness C: Open terrain with scattered obstructions having
heights generally less than 30ft. (9.1 m). This category also includes flat open
country, grasslands, and all water surfaces in hurricane-prone regions.
Surface Roughness D: Flat, unobstructed and water surfaces outside
hurricane-prone regions. This category also includes smooth mud flats, salt flats,
and unbroken ice.
Exposure Category: There are three different exposure categories defined in
this code along with transition zone explained as follows:
Exposure B: It is mainly for surface category B. Ground surface roughness
conditions prevails in the upwind direction for a distance of at least 2630 ft. (800
m.) or 10 times the height of the building whichever is greater. Upwind distance
can be reduced to 1500 ft. (457 m.), in case of buildings having mean roof height
less than or equal to 30ft. (9.1 m.).
Exposure C: This is for all cases other than where exposure B n exposure
D do not apply.
Exposure D: It is mainly for surface category D. Ground surface roughness
conditions prevails in the upwind direction for a distance of at least 5000 ft. (1524
m.) or 10 times the height of the building whichever is greater. This can extend
23
inland fro the shoreline for a distance of 600 ft. (200 m.) or 10 times the height of
the building whichever is greater.
Transition Zone: For a site located in between any two or more exposure
categories, the category resulting largest wind force should be considered.
Intermediate exposure is permitted in case of rational analysis.
3. Topographic Factor (KZI)
Wind Speed-Up effects over Hills, Ridges, and Escarpments
constituting abrupt changes in the general topography, located in any exposure
category, and should be considered while designing wind loads. Conditions to be
considered while designing are as follows:-
1. The hill, ridge, or escarpment is isolated and unobstructed upwind by other
similar topographic features of comparable height for 100 times the height of the
topographic feature (100 H) or 2 miles (3.22 km), whichever is less. This distance
shall be measured horizontally from the point at which the height H of the hill,
ridge, or escarpment is determined.
2. The hill, ridge, or escarpment protrudes above the height of upwind terrain
features within a 2-mile (3.22-km) radius in any quadrant by a factor of two or
more.
3. The structure is located in the upper half of a hill or ridge or near the crest of an
escarpment.
4. H/LH ≤ 0.2.
5. H is greater than or equal to 15 ft. (4.5 m) for Exposures C and D and 60 ft. (18
m) for Exposure B.
Topographic Factor. The wind speed-up effect shall be included in the calculation
of design wind loads by using the factor Kzt which can be calculated as follows:
Kzt= (1+K1K2K3)2
24
4. Gust Factor (G or Gf)
In this code Gust Factors are given for rigid structures as wells as for
flexible structures as given below:-
For Rigid Structures:-
G = 0.925 ((l + 1.7gQIQ)/ (1 + 1.7gv lz)
lz = c(33/z)1/6
Where,
Iz = Intensity of turbulence at height z.
Z=equivalent height of structure (0.6h) > zmin .
For Flexible Structures:-
Gf = 0.925 ((l + 1.7Iz (gQ
2Q2+gR
2R2)0.5)/ (1 + 1.7gv lz)
25
Method 1 - Simplified Procedure
To design any building or structure by this method, it should satisfy few
conditions mentioned as follows:-
i. For the design of main wind force-resisting systems:-
 The building is a simple diaphragm building, i.e. an enclosed or partially
enclosed building in which wind loads are transmitted through floor and roof
diaphragms to the vertical main wind force-resisting system.
 The building is a low-rise building i.e. enclosed or partially enclosed Buildings
of which mean roof height h jess than or equal to 60 ft. (18 m) or mean roof
height h does not exceed least horizontal dimension.
 The building is enclosed and conforms to the wind borne debris provisions.
 The building is a regular shaped building or structure, i.e. building with no
geometric irregularity in spatial form.
 The building is not classified as a flexible, i.e. Buildings having no natural
frequency less than 1 Hz.
 the building does not have response characteristics making it subject to
across-wind loading, vortex shedding, instability due to galloping or flutter;
and does not have a site location for which channelling effects or buffeting in
the wake of upwind obstructions warrant special consideration.
 The building structure has no expansion joints or separations.
 The building is not subject to the topographic effects i.e., K zt = 1.0.
 The building has an approximately symmetrical cross section in each direction with
either a fiat roof, or a gable or hip roof with θ ≤ 45 degrees.
ii. For the design of components and cladding:-
 The mean roof height h ≤ 60 ft.
 The building is enclosed and conforms to the wind-borne debris provisions
 The building is a regular shaped building.
 The building does not have response characteristics making it subject to
across-wind loading, vortex shedding, instability due to galloping or flutter; and
does not have a site location for which channelling effects or buffeting in the
wake of upwind obstructions warrant special consideration.
 The building is not subject to the topographic effects, i.e., Kzt = 1.0.
 The building has either a flat roof, or a gable roof with θ ≤ 45 degrees, or a hip
roof with θ ≤ 27 degrees.
26
Design Procedure:-
1. Determine Basic Wind Speed, Importance factor I, exposure category, and
exposure adjustment coefficient λ from code.
2. Main Wind Force-Resisting System:-Simplified design wind pressure (ps) can be
given by following formula:
ps = λ Ips30
Where,
λ = adjustment factor for building height and Exposure
I = importance factor
pS30 = simplified design wind pressure for exposure B, at h = 30
ft, and for I = 1.0.
Note:-ps should not be less than 10lb/ft2 (0.48 kN/m2). This force is applied on
horizontal and vertical projections of building surfaces.
3. Component and Cladding:-Net design wind pressure (pnet) can be given by
following formula:
Pnet = λ Ipnet30
Where,
λ = adjustment factor for building height and Exposure
I = importance factor
pnet30 = simplified design wind pressure for exposure B, at h =
30 ft, and for I = 1.0.
Note:-Positive pnet should not be greater than 10lb/ft2 (0.48 kN/m2) and negative
pnet should not be less than -10lb/ft2 (-0.48 kN/m2). This force is applied normal
to each building surfaces.
27
Method 2 - Analytical Procedure
To design any building or structure by this method, it should satisfy few
conditions mentioned as follows:-
 The building or other structure is a regular shaped building or structure.
 The building or other structure does not have response characteristics making
it subject to across-wind loading, vortex shedding, instability due to galloping
or flutter; or does not have a site location for which channelling effects or
buffeting in the wake of upwind obstructions warrant special consideration.
Design Procedure:-
1. The basic wind speed V and wind directionality factor K d, importance
factor I, an exposure category or exposure categories and velocity
pressure exposure coefficient KZ or KH, shall be determined for each
wind direction.
2. A topographic factor KZt, a gust effect factor G or Gf, an enclosure
classification shall be determined.
3. Internal pressure coefficient GCpi as well as external pressure
coefficients Cp or GCpf, or GCf shall be determined.
4. Velocity pressure at height z (qz or qh) can be determined using
following formula:-
qz = 0.00256 Kz KZt Kd V2 I (lb/ft2)
[In SI: qz = 0.613 KzKztKd V2 I (N/m2); V in m/s]
Where,
Kd =Wind directionality factor.
Kz =Velocity pressure exposure coefficient.
KZt = Topographical factor.
5. Design wind load p or F shall be determined by considering formulae
given in code as per required case of building.
28
Method 3 - Wind Tunnel Procedure
Wind Tunnel Testing is used to determine
wind loads on any buildings and structures. This method is
useful in prediction of wind loads and responses of structures,
structural components, and cladding to verify the wind
conditions and hence to design any building or structure.
Problem with this method is its cost, i.e. it is very expensive.
Example of Structure for which wind
tunnel testing is used is World Trade Centre. In this method
experiments are conducted on small model applying same
Surrounding conditions.
Tests for determining fluctuating mean wind pressure or force by Wind Tunnel Testing
should meet following conditions:-
1. The natural atmospheric boundary layer has been modelled to account for the variation
of wind speed with height.
2. The relevant macro length and micro length scales of the longitudinal component of
atmospheric
Turbulence are modelled to approximately the same scale as that used to model the
building or structure
3. The modelled building or other structure and surrounding structures and topography
are geometrically
Similar to their full-scale counterparts, except that, for low--rise buildings.
4. The projected area of the modelled building or other structure and surroundings is less
than 8% of the test section cross-sectional area unless correction is made for blockage.
5. The longitudinal pressure gradient in the wind-tunnel test section is accounted for
6. Reynolds number effects on pressures and forces are minimized
7. Response characteristics of the wind-tunnel instrumentation are consistent with the
required measurements.
World Trade Centre
29
Example:
Reinforced Concrete (RCC) frame with flat roof is designed using ETABS 2015
software having following dimensions:-
Component Length (in m.) Width (in mm.) Depth (in mm.)
Column (Except first floor) 3.2004 600 6000
Column (For first floor) 3.6576 600 600
Beam 6.096 600 6000
Number of Stories =10
Total Length = 24.396 m. (4 Beams in X direction) (Total 5 Gridlines)
Total Breadth = 12.198 m. (2 Beams in Y direction) (Total 3 Gridlines)
Slab Thickness =200 mm.
As shown in figure below:-
Note: - No additional Dead loads and Live Loads are considered as their value is 0 kN/m2.
3D View
30
1. Structural Data
Data related to structure is provided in Table given below:-
a. Story Data:
Elevation and Height of each Floor is given in Table below:-
Table: Elevation and Height
Name Height (mm) Elevation (mm)
Story10 3200.4 32461.2
Story9 3200.4 29260.8
Story8 3200.4 26060.4
Story7 3200.4 22860
Story6 3200.4 19659.6
Story5 3200.4 16459.2
Story4 3200.4 13258.8
Story3 3200.4 10058.4
Story2 3200.4 6858
Story1 3657.6 3657.6
Base 0 0
b. Mass:
Table: Centre of Mass Calculations
Table: Centre of Mass Calculations
Story Diaphragm
Mass X
kg
Mass Y
kg
Mass Moment of Inertia
ton-m²
X Mass Center
m
Y Mass Center
m
Story10 D1 273531.07 273531.07 20590.7181 12.192 6.096
Story9 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story8 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story7 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story6 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story5 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story4 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story3 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story2 D1 294293.59 294293.59 22648.2132 12.192 6.096
Story1 D1 297259.66 297259.66 22942.141 12.192 6.096
Story Diaphragm
Mass X
kg
Mass Y
kg
XCM
m
YCM
m
Cumulative X
kg
Cumulative Y
Kg
XCCM
m
YCCM
m
Story10 D1 273531.07 273531.07 12.192 6.096 273531.07 273531.07 12.192 6.096
Story9 D1 294293.59 294293.59 12.192 6.096 567824.65 567824.65 12.192 6.096
Story8 D1 294293.59 294293.59 12.192 6.096 862118.24 862118.24 12.192 6.096
Story7 D1 294293.59 294293.59 12.192 6.096 1156411.83 1156411.83 12.192 6.096
Story6 D1 294293.59 294293.59 12.192 6.096 1450705.42 1450705.42 12.192 6.096
Story5 D1 294293.59 294293.59 12.192 6.096 1744999.01 1744999.01 12.192 6.096
Story4 D1 294293.59 294293.59 12.192 6.096 2039292.6 2039292.6 12.192 6.096
Story3 D1 294293.59 294293.59 12.192 6.096 2333586.19 2333586.19 12.192 6.096
Story2 D1 294293.59 294293.59 12.192 6.096 2627879.78 2627879.78 12.192 6.096
Story1 D1 297259.66 297259.66 12.192 6.096 2925139.45 2925139.45 12.192 6.096
31
Table: Centre of Mass Calculations
Story
UX
kg
UY
kg
UZ
kg
Story10 273531.07 273531.07 0
Story9 294293.59 294293.59 0
Story8 294293.59 294293.59 0
Story7 294293.59 294293.59 0
Story6 294293.59 294293.59 0
Story5 294293.59 294293.59 0
Story4 294293.59 294293.59 0
Story3 294293.59 294293.59 0
Story2 294293.59 294293.59 0
Story1 297259.66 297259.66 0
Base 23728.6 23728.6 0
2. Properties
a. Materials:
Table: Material Properties
Name Type
E
MPa
ν
Unit Weight
kN/m³
Design Strengths
4000Psi Concrete 24855.58 0.2 23.5631 Fc=27.58 MPa
A615Gr60 Rebar 199947.98 0.3 76.9729
Fy=413.69 MPa, Fu=620.53
MPa
b. Frame Sections:
Table: Frame Sections
Name Material Shape
Concrete Beam 4000Psi Concrete Rectangular
Concrete Column 4000Psi Concrete Rectangular
c. Shell Sections:
Table: Shell Sections
Name Design Type Element Type Material
Total Thickness
mm
Slab1 Slab Shell-Thin 4000Psi 200
d. Reinforcement Sizes:
Table: Reinforcing Bar Sizes
Name
Diameter
mm
Area
mm²
10 10 79
20 20 314
32
3. Load Combination factors
Load combination factors used while analysing are listed below. This factors are taken
for DL+LL+WL combination from IS 456 for Indian case and from ASCE-07:2002 for
American case.
Table: Load Combination Factors from IS456
Name Load Case/Combo Scale Factor Type Auto
DD+LL+WL (Indian) Dead 1.2 Linear Add No
DD+LL+WL (Indian) Live 1.2 No
DD+LL+WL (Indian) Wind Indian 1.2 No
Table: Load Combination Factors from ASCE-07:2002
Name Load Case/Combo Scale Factor Type Auto
DD+LL+WL (American) Dead 1.2 Linear Add No
DD+LL+WL (American) Live 1 No
DD+LL+WL (American) Wind American 1.6 No
4. Auto Load Calculations Using ETABS 2015
a. Indian IS875:1987 Auto Wind Load Calculation:
Assuming frame is located near Orissa, where basic wind speed Vb is 50 ms-1 as per
given in IS875:1987. Other assumed parameters are as follows:-
Table: Factors related to Wind Loads
Structure Class Class B
Terrain Category Category 2
Wind Direction 0;90 degrees
Basic Wind Speed, Vb 50 ms-1
Windward Coefficient, Cp,wind 0.8
Leeward Coefficient, Cp,lee 0.5
Risk Coefficient, k1 1
Topography Factor, k3 1
Table: Calculated Factors
Design Wind Speed, Vz Vz=k1k2k3Vb Vz=50
Design Wind Pressure, pz Pz=0.6Vz
2
Pz=1500
33
Story Elevation(m) X-Dir(kN) Y-Dir(kN)
Story10 32.4612 47.4621 0
Story9 29.2608 93.5974 0
Story8 26.0604 90.9865 0
Story7 22.86 88.311 0
Story6 19.6596 85.5586 0
Story5 16.4592 82.4853 0
Story4 13.2588 78.9015 0
Story3 10.0584 75.5657 0
Story2 6.858 74.8726 0
Story1 3.6576 80.2207 0
Base 0 0 0
Story Elevation(m) X-Dir(kN) Y-Dir(kN)
Story10 32.4612 0 93.7845
Story9 29.2608 0 184.947
Story8 26.0604 0 179.788
Story7 22.86 0 174.5012
Story6 19.6596 0 169.0624
Story5 16.4592 0 162.9897
Story4 13.2588 0 155.9081
Story3 10.0584 0 149.3167
Story2 6.858 0 147.9471
Story1 3.6576 0 158.5148
Base 0 0 0
Case-1
Case-2
34
b. ASCE 7-02 Auto Wind Load Calculations:
Assuming frame is located is in America having same Basic Wind Speed as in Orissa i.e.,
Vb is 50 ms-1 (111.85⁡mph). Other assumed parameters are as follows:-
Table: Factors related to Wind Loads
Structure Class Class B
Terrain Category Category 2
Wind Direction 0 degrees
Basic Wind Speed, Vb 111.85 mph
Windward Coefficient, Cp,wind 0.8
Leeward Coefficient, Cp,lee 0.5
Gradient Height, zg 900
Empirical Exponent, α 9.5
Topographical Factor, Kzt 1
Directionality Factor, Kd 085
Importance Factor, I I = 1
Gust Effect Factor, G G = 0.85
Table: Calculation formulas
Design Wind Pressure, p [ASCE 6.5.12.2.1 Eq. 6-17] 𝐩 = 𝐪𝐆𝐂 𝐩,𝐰𝐢𝐧𝐝 + 𝐪 𝐡(𝐆𝐂 𝐩,𝐥𝐞𝐞)
Velocity Pressure Exposure Coefficient, Kz;
For 15 ft.≤Z≤ Zg For Z < 15 ft.
Kz = 2.01 (z/zg)2/ɑ Kz = 2.0 I (l5/zg)2/ ɑ
Velocity Pressure, qz 𝐪 𝐳 = 𝟎. 𝟎𝟎𝟐𝟓𝟔𝐊 𝐳 𝐊 𝐳𝐭 𝐊 𝐝 𝐕 𝟐
𝐈
35
Story Elevation(m) X-Dir(kN) Y-Dir(kN)
Story10 32.4612 24.447 0
Story9 29.2608 48.1865 0
Story8 26.0604 47.0583 0
Story7 22.86 45.8258 0
Story6 19.6596 44.4622 0
Story5 16.4592 42.928 0
Story4 13.2588 41.1603 0
Story3 10.0584 39.0482 0
Story2 6.858 36.3775 0
Story1 3.6576 36.6011 0
Base 0 0 0
Story Elevation(m) X-Dir(kN) Y-Dir(kN)
Story10 32.4612 0 56.9014
Story9 29.2608 0 112.4047
Story8 26.0604 0 110.1753
Story7 22.86 0 107.7399
Story6 19.6596 0 105.0456
Story5 16.4592 0 102.0141
Story4 13.2588 0 98.521
Story3 10.0584 0 94.3476
Story2 6.858 0 89.0703
Story1 3.6576 0 90.7399
Base 0 0 0
Case-1
36
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 18.3353 0
Story9 29.2608 36.1399 0
Story8 26.0604 35.2937 0
Story7 22.86 34.3693 0
Story6 19.6596 33.3467 0
Story5 16.4592 32.196 0
Story4 13.2588 30.8702 0
Story3 10.0584 29.2862 0
Story2 6.858 27.2831 0
Story1 3.6576 27.4508 0
Base 0 0 0
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 18.3353 0
Story9 29.2608 36.1399 0
Story8 26.0604 35.2937 0
Story7 22.86 34.3693 0
Story6 19.6596 33.3467 0
Story5 16.4592 32.196 0
Story4 13.2588 30.8702 0
Story3 10.0584 29.2862 0
Story2 6.858 27.2831 0
Story1 3.6576 27.4508 0
Base 0 0 0
Case-1
37
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 0 42.676
Story9 29.2608 0 84.3035
Story8 26.0604 0 82.6315
Story7 22.86 0 80.8049
Story6 19.6596 0 78.7842
Story5 16.4592 0 76.5106
Story4 13.2588 0 73.8908
Story3 10.0584 0 70.7607
Story2 6.858 0 66.8027
Story1 3.6576 0 68.0549
Base 0 0 0
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 0 42.676
Story9 29.2608 0 84.3035
Story8 26.0604 0 82.6315
Story7 22.86 0 80.8049
Story6 19.6596 0 78.7842
Story5 16.4592 0 76.5106
Story4 13.2588 0 73.8908
Story3 10.0584 0 70.7607
Story2 6.858 0 66.8027
Story1 3.6576 0 68.0549
Base 0 0 0
Case-2
38
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 18.3353 -36.2302
Story9 29.2608 36.1399 -71.4118
Story8 26.0604 35.2937 -69.7398
Story7 22.86 34.3693 -67.9132
Story6 19.6596 33.3467 -65.8925
Story5 16.4592 32.196 -63.6189
Story4 13.2588 30.8702 -60.9991
Story3 10.0584 29.2862 -57.869
Story2 6.858 27.2831 -53.911
Story1 3.6576 27.4508 -54.2424
Base 0 0 0
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 21.5974 42.676
Story9 29.2608 42.6641 84.3035
Story8 26.0604 41.8179 82.6315
Story7 22.86 40.8935 80.8049
Story6 19.6596 39.8709 78.7842
Story5 16.4592 38.7202 76.5106
Story4 13.2588 37.3944 73.8908
Story3 10.0584 35.8103 70.7607
Story2 6.858 33.8073 66.8027
Story1 3.6576 34.441 68.0549
Base 0 0 0
Case-2
39
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 13.7637 -27.1968
Story9 29.2608 27.129 -53.6065
Story8 26.0604 26.4938 -52.3514
Story7 22.86 25.7999 -50.9802
Story6 19.6596 25.0322 -49.4633
Story5 16.4592 24.1685 -47.7566
Story4 13.2588 23.1732 -45.79
Story3 10.0584 21.9841 -43.4403
Story2 6.858 20.4805 -40.4692
Story1 3.6576 20.6064 -40.7179
Base 0 0 0
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 13.7637 -27.1968
Story9 29.2608 27.129 -53.6065
Story8 26.0604 26.4938 -52.3514
Story7 22.86 25.7999 -50.9802
Story6 19.6596 25.0322 -49.4633
Story5 16.4592 24.1685 -47.7566
Story4 13.2588 23.1732 -45.79
Story3 10.0584 21.9841 -43.4403
Story2 6.858 20.4805 -40.4692
Story1 3.6576 20.6064 -40.7179
Base 0 0 0
Case-3
40
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 16.2124 32.0355
Story9 29.2608 32.0265 63.2838
Story8 26.0604 31.3913 62.0287
Story7 22.86 30.6974 60.6576
Story6 19.6596 29.9297 59.1407
Story5 16.4592 29.066 57.4339
Story4 13.2588 28.0707 55.4673
Story3 10.0584 26.8816 53.1177
Story2 6.858 25.378 50.1466
Story1 3.6576 25.8537 51.0865
Base 0 0 0
Story Elevation X-Dir Y-Dir
m kN kN
Story10 32.4612 16.2124 32.0355
Story9 29.2608 32.0265 63.2838
Story8 26.0604 31.3913 62.0287
Story7 22.86 30.6974 60.6576
Story6 19.6596 29.9297 59.1407
Story5 16.4592 29.066 57.4339
Story4 13.2588 28.0707 55.4673
Story3 10.0584 26.8816 53.1177
Story2 6.858 25.378 50.1466
Story1 3.6576 25.8537 51.0865
Base 0 0 0
Case-4
41
5. Analysis
a. Base Reaction Calculations:
Table: Base reactions
Load Case/Combo FX(kN) FY(kN) FZ(kN) MX(kN-m) MY(kN-m) MZ(kN-m) X(m) Y(m) Z(m)
Dead 0 0 28918.5181 176287.2864 -352575 0 0 0 0
DD+LL+WL (Indian) Max 0 0 34702.2217 245505.1329 -423089 5837.2475 0 0 0
DD+LL+WL (Indian) Min -957.5537 -1892.1115 34702.2217 211544.7437 -440276 -23068.6228 0 0 0
DD+LL+WL (American) Max 0 962.9247 34702.2217 239404.7455 -423089 14710.6433 0 0 0
DD+LL+WL (American) Min -649.7518 -1547.1356 34702.2217 194045.4059 -434897 -18862.6773 0 0 0
b. Story Forces:
i. Shear Diagrams
.
Shear Forces increases from top to bottom for frame.Folowing table shows shear
forces for different cases which are calculated for story 1 :-
Load Case/Combo Location P VX VY T
Dead Top 28453.12 0 0 0
Dead Bottom 28918.52 0 0 0
DD+LL+WL (Indian) Max Top 34143.75 0 0 5837.248
DD+LL+WL (Indian) Max Bottom 34702.22 0 0 5837.248
DD+LL+WL (Indian) Min Top 34143.75 -957.554 -1892.11 -23068.6
DD+LL+WL (Indian) Min Bottom 34702.22 -957.554 -1892.11 -23068.6
DD+LL+WL (American) Max Top 34143.75 0 962.9247 14710.64
DD+LL+WL (American) Max Bottom 34702.22 0 962.9247 14710.64
DD+LL+WL (American) Min Top 34143.75 -649.752 -1547.14 -18862.7
DD+LL+WL (American) Min Bottom 34702.22 -649.752 -1547.14 -18862.7
Dead Load Case DD+LL+WL Indian case DD+LL+WL American case
42
ii. Moment Diagrams
Moments increases from top to bottom for frame.Folowing table shows Moments for different
cases which are calculated for story 1 :-
Story Load Case/Combo Location MX MY
Story1 Dead Top 173450.2 -346900
Story1 Dead Bottom 176287.3 -352575
Story1 DD+LL+WL (Indian) Max Top 235180.1 -416281
Story1 DD+LL+WL (Indian) Max Bottom 245505.1 -423089
Story1 DD+LL+WL (Indian) Min Top 208140.3 -429965
Story1 DD+LL+WL (Indian) Min Bottom 211544.7 -440276
Story1 DD+LL+WL (American) Max Top 230341.5 -416281
Story1 DD+LL+WL (American) Max Bottom 239404.7 -423089
Story1 DD+LL+WL (American) Min Top 194162.9 -425712
Story1 DD+LL+WL (American) Min Bottom 194045.4 -434897
Dead Load Case DD+LL+WL Indian case DD+LL+WL American case
43
6. Displacements due to Wind Loads
Maximum joint displacements for different cases are shown in following table :-
Load Case/Combo
Story
no.
UXmax(mm) UYmax(mm)
UZmax(mm
)
RXmax(rad) RYmax(rad) RZmax(rad)
Dead 10 -2.23E-08 -2.59E-08 -5.43E+00 3.08E-04 2.92E-04 0
DD+LL+WL (Indian) Max 10 1.68E+01 3.79E+01 -6.52E+00 3.70E-04 -2.91E-04 0
DD+LL+WL (Indian) Min 10 -2.77E-08 -3.21E-08 -6.52E+00 -4.87E-03 3.51E-04 0
DD+LL+WL (American) Max 10 3.51E-04 3.32E+01 -6.52E+00 2.90E-03 1.69E-03 8.03E-04
DD+LL+WL (American) Min 10 -5.02E+00 -2.24E+01 -6.52E+00 -4.30E-03 -6.91E-04 -8.03E-04
Dead Load Case DD+LL+WL Indian case DD+LL+WL American case
Deformation Diagrams
-5
0
5
10
15
20
1
15
29
43
57
71
85
99
113
127
141
155
169
183
197
211
225
239
253
267
281
295
309
323
337
351
DisplacementinXdirection(inmm)
Joint numbers (from story10 to story1)
Displacement of joints in X Direction
Dead DD+LL+WL (Indian) DD+LL+WL (American)
44
As Shown in above Graphs, Displacement in all direction is maximum for Indian DD+LL+WL
combination, while it is least is case of X & Y direction for dead loads. For American DD+LL+WL
combination, Displacement is least in Z direction as compared to other cases.
For Z direction displacements, Negative displacement means displacement in downward
direction. Some joints are assumed to be fixed and hence their displacement in z direction is zero
In all three cases, Maximum displacement is found to be for top story, i.e. for story 10. It
decreases with height.
-5
0
5
10
15
20
25
30
35
40
1
15
29
43
57
71
85
99
113
127
141
155
169
183
197
211
225
239
253
267
281
295
309
323
337
351
DisplacementinYdirection(inmm)
Joint numbers (from story10 to story1)
Displacement of joints in Y Direction
Dead DD+LL+WL (Indian) DD+LL+WL (American)
-7
-6
-5
-4
-3
-2
-1
0
1
15
29
43
57
71
85
99
113
127
141
155
169
183
197
211
225
239
253
267
281
295
309
323
337
351
DisplacementinYdirection(inmm)
Joint numbers (from story10 to story1)
Displacement of joints in Z Direction
Dead DD+LL+WL (Indian) DD+LL+WL (American)
45
Summary
 Wind Load increases with increase in height and its direction is horizontal hence it is
important to analyse Tall buildings for wind loads.
 IS 875:1987 Part 3 is Indian Standard Code for design of wind loads. IS 875:2009 part 3 is
in draft version, having few changes in it as compared to IS875:1987 part3.
 ASCE -07 Chapter 6 is meant for design of wind loads. 2002 version of this code is used
in this report while 2005, 2010 versions of this codes are also available.
 For IS 875:1987 and 2009 (part 3) versions, some major points for designing wind loads
are as follows:-
o Determining basic wind speed and hence design wind speed depending upon
height of building, terrain, topography, etc. (in case of 2009, cyclone zone also
considered).
o Determining Wind pressure and Design wind pressure for calculated design
velocity.
o Determining force coefficients and hence wind forces on buildings as well as for
individual members.
o This code is yet to be developed for considering Dynamic effects except vortex
shedding.
 For ASCE-07:2002 version, some major points for designing loads are as follows:-
There are three different methods for this code
o Simplified method:-This is similar to IS 875 method. It needs to determine Basic
Wind Speed, Importance factor I, exposure category, and exposure adjustment
coefficient λ for calculation of wind loads. This is applicable for limited cases of
buildings and structures.
o Analytical method: - in this method some more factors as compared to simplified
method are taken into account. This can be applicable for most of the buildings
and structure.
o Wind Tunnel method: - This is method in which, actual model of building or
structure for which wind loading is to be designed. Wind conditions are applied
considering scale factors and making same environment as that of actual
building. Response of building and its components are observed and building or
structure is designed.
46
 Some Observations from case studied for same conditions using IS875:1987 and ASCE-
7:02
o Wind Load for structure is calculated for 2 time taking only 1 case using IS 875:
part3 while it is calculated for 12 times considering 4 different cases in case of
ASCE-07:2002.
o Base reactions as well as Shear forces in Y directions are zero as per IS 875 but it
have positive value in case of ASCE-07.
o Moments for both codes are almost equal.
o Joint displacements are more in case of IS codes that displacements calculated
as per ASCE: 07.
47
Conclusion
 ASCE:07 allows to use basic wind data by studying and analysing wind data which means more
accurate local conditions can be considered and hence structure may be more economical as
well as more strong. Local weather data study and its analysis should be allowed in Indian
Codes too.
 Gust Factor method in IS 875 which is somewhat similar to analysis method in ASCE-07:2002 is
yet to be developed fully as compared to ASCE code.
 Wind Tunnel procedure allowed in case or American code. Indian codes should also contain
wind tunnel procedure in case of designing tall buildings mostly in metro cities where tall
building can be designed considering all factors which will reduce risk for buildings.
 ASCE-07 consider 4 cases while IS875 consider only two cases to determine design wind
pressure. Indian code should improve for determining wind load taking more cases, as more
cases mean more precision and hence less risk.
 American code is more effective for designing for wind loads as it gives less deformation as
compared to Indian code. Less deformation means less chance for failure.
48
References
1. Council of Tall Building and Habitat (CTBUH) website.
2. Indian Standard Code:-Code of practice for design loads (other
than earthquake) for buildings and structures- IS875:1987 – Part
3
3. Indian Standard Code Draft version- IS 875:2009 –Part 3 draft
version with commentary.
4. American Code: Minimum Design Loads For Buildings and other
structures. (ASCE-7:2002 version)
5. http://www.fluidstructures.com/html/vortex/phenomena.html

More Related Content

What's hot

DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDING
Anjneya Srivastava
 
Guntry girder
Guntry girderGuntry girder
Guntry girder
kajol panchal
 
Steel building design worked example
Steel building design worked exampleSteel building design worked example
Steel building design worked example
Md. Shahadat Hossain
 
Steel in Highrise building : Application
Steel in Highrise building : Application Steel in Highrise building : Application
Steel in Highrise building : Application
Onal Kothari
 
Analysis and design of multystory building
Analysis and design of multystory buildingAnalysis and design of multystory building
Analysis and design of multystory building
Awat Hasan Ra
 
Earthquake resistant building construction
Earthquake resistant building constructionEarthquake resistant building construction
Earthquake resistant building construction
daspriyabrata3
 
Shear Wall
Shear WallShear Wall
Shear Wall
Rutvik Sabhaya
 
Final ppt on staad pro
Final ppt on staad proFinal ppt on staad pro
Final ppt on staad pro
Sakina Faiz
 
Structure analysis and design
Structure analysis and designStructure analysis and design
Structure analysis and design
Kiran Birdi
 
PROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDING
PROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDINGPROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDING
PROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDINGAmritpal Singh
 
Design of footing as per IS 456-2000
Design of footing as per IS 456-2000Design of footing as per IS 456-2000
Design of footing as per IS 456-2000
PraveenKumar Shanmugam
 
Design of multistorey building
Design of multistorey buildingDesign of multistorey building
Design of multistorey building
Sivaji Djpk
 
seismic analysis of multistoryed building by ETABS
 seismic analysis of multistoryed building by ETABS seismic analysis of multistoryed building by ETABS
seismic analysis of multistoryed building by ETABS
vishal maurya
 
Design and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staadDesign and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staad
gopichand's
 
Earth quake failures best
Earth quake failures bestEarth quake failures best
Earth quake failures best
Make Mannan
 
Analysis of g+3 rcc storied building
Analysis of g+3 rcc storied buildingAnalysis of g+3 rcc storied building
Analysis of g+3 rcc storied building
Tarun kumar
 
Long wall and short wall method 2
Long wall and short wall method 2Long wall and short wall method 2
Long wall and short wall method 2
Saiyyed Akbar
 
Architectural And Structural Design Of Blast Resistant Buildings - REPORT
Architectural And Structural Design Of Blast Resistant Buildings - REPORTArchitectural And Structural Design Of Blast Resistant Buildings - REPORT
Architectural And Structural Design Of Blast Resistant Buildings - REPORT
Paul Jomy
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic Analysis
Krishnagnr
 
residential buliding by stadd pro
residential buliding by stadd proresidential buliding by stadd pro
residential buliding by stadd pro
ila vamsi krishna
 

What's hot (20)

DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDING
 
Guntry girder
Guntry girderGuntry girder
Guntry girder
 
Steel building design worked example
Steel building design worked exampleSteel building design worked example
Steel building design worked example
 
Steel in Highrise building : Application
Steel in Highrise building : Application Steel in Highrise building : Application
Steel in Highrise building : Application
 
Analysis and design of multystory building
Analysis and design of multystory buildingAnalysis and design of multystory building
Analysis and design of multystory building
 
Earthquake resistant building construction
Earthquake resistant building constructionEarthquake resistant building construction
Earthquake resistant building construction
 
Shear Wall
Shear WallShear Wall
Shear Wall
 
Final ppt on staad pro
Final ppt on staad proFinal ppt on staad pro
Final ppt on staad pro
 
Structure analysis and design
Structure analysis and designStructure analysis and design
Structure analysis and design
 
PROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDING
PROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDINGPROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDING
PROJECT REPORT ON DESIGN OF A RESIDENTIAL BUILDING
 
Design of footing as per IS 456-2000
Design of footing as per IS 456-2000Design of footing as per IS 456-2000
Design of footing as per IS 456-2000
 
Design of multistorey building
Design of multistorey buildingDesign of multistorey building
Design of multistorey building
 
seismic analysis of multistoryed building by ETABS
 seismic analysis of multistoryed building by ETABS seismic analysis of multistoryed building by ETABS
seismic analysis of multistoryed building by ETABS
 
Design and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staadDesign and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staad
 
Earth quake failures best
Earth quake failures bestEarth quake failures best
Earth quake failures best
 
Analysis of g+3 rcc storied building
Analysis of g+3 rcc storied buildingAnalysis of g+3 rcc storied building
Analysis of g+3 rcc storied building
 
Long wall and short wall method 2
Long wall and short wall method 2Long wall and short wall method 2
Long wall and short wall method 2
 
Architectural And Structural Design Of Blast Resistant Buildings - REPORT
Architectural And Structural Design Of Blast Resistant Buildings - REPORTArchitectural And Structural Design Of Blast Resistant Buildings - REPORT
Architectural And Structural Design Of Blast Resistant Buildings - REPORT
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic Analysis
 
residential buliding by stadd pro
residential buliding by stadd proresidential buliding by stadd pro
residential buliding by stadd pro
 

Viewers also liked

Wind loads
Wind loadsWind loads
Wind loads
Akshay D Nicator
 
Effects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildingsEffects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildings
eSAT Journals
 
S a fe construction practices class X social project , flood, cyclone, disa...
S a fe construction   practices class X social project , flood, cyclone, disa...S a fe construction   practices class X social project , flood, cyclone, disa...
S a fe construction practices class X social project , flood, cyclone, disa...
Anantha Narayanan
 
Seismic Conceptual Design of Buildings
Seismic Conceptual Design of BuildingsSeismic Conceptual Design of Buildings
Seismic Conceptual Design of BuildingsMohd Danish
 
Wind tunnel building test
Wind tunnel building testWind tunnel building test
Wind tunnel building test
Dr.Youssef Hammida
 
sustainable development with building load basics
sustainable development with building load basicssustainable development with building load basics
sustainable development with building load basicssantosh naik
 
(2015)wind induced motion seminar
(2015)wind induced motion seminar(2015)wind induced motion seminar
(2015)wind induced motion seminar
pranavbalkipsb
 
Keangnam towers wind tunnel testing
Keangnam towers wind tunnel testingKeangnam towers wind tunnel testing
Keangnam towers wind tunnel testing
Nguyen Ton Viet
 
Dampers
DampersDampers
Dampers
Krishnagnr
 
Wind loads calculation
Wind loads calculationWind loads calculation
Wind loads calculationHenry Kurniadi
 
101 Engineering Quotes from the Minds of Innovators - WorkflowMax
101 Engineering Quotes from the Minds of Innovators - WorkflowMax101 Engineering Quotes from the Minds of Innovators - WorkflowMax
101 Engineering Quotes from the Minds of Innovators - WorkflowMax
WorkflowMax (A Xero Product)
 
Wind load calculation
Wind load calculationWind load calculation
Wind load calculation
Godfrey James
 
Determinate structures
 Determinate structures Determinate structures
Determinate structuresTarun Gehlot
 
Earthquake resistant structure
Earthquake resistant structureEarthquake resistant structure
Earthquake resistant structure
vikskyn
 
High rise structure & core
High rise  structure & coreHigh rise  structure & core
High rise structure & core
Meer Musabber ali (joyous)
 
Base isolation
Base isolationBase isolation
Base isolation
premsai05
 
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRODESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
Ali Meer
 

Viewers also liked (20)

WIND ISSUES IN THE DESIGN OF TALL BUILDINGS
WIND ISSUES IN THE DESIGN OF TALL BUILDINGSWIND ISSUES IN THE DESIGN OF TALL BUILDINGS
WIND ISSUES IN THE DESIGN OF TALL BUILDINGS
 
Wind loads
Wind loadsWind loads
Wind loads
 
Effects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildingsEffects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildings
 
S a fe construction practices class X social project , flood, cyclone, disa...
S a fe construction   practices class X social project , flood, cyclone, disa...S a fe construction   practices class X social project , flood, cyclone, disa...
S a fe construction practices class X social project , flood, cyclone, disa...
 
Seismic Conceptual Design of Buildings
Seismic Conceptual Design of BuildingsSeismic Conceptual Design of Buildings
Seismic Conceptual Design of Buildings
 
Wind tunnel building test
Wind tunnel building testWind tunnel building test
Wind tunnel building test
 
sustainable development with building load basics
sustainable development with building load basicssustainable development with building load basics
sustainable development with building load basics
 
(2015)wind induced motion seminar
(2015)wind induced motion seminar(2015)wind induced motion seminar
(2015)wind induced motion seminar
 
Keangnam towers wind tunnel testing
Keangnam towers wind tunnel testingKeangnam towers wind tunnel testing
Keangnam towers wind tunnel testing
 
Seismic Design Basics - Superstructure
Seismic Design Basics - SuperstructureSeismic Design Basics - Superstructure
Seismic Design Basics - Superstructure
 
Dampers
DampersDampers
Dampers
 
Wind loads calculation
Wind loads calculationWind loads calculation
Wind loads calculation
 
Is 875 wind load
Is 875   wind loadIs 875   wind load
Is 875 wind load
 
101 Engineering Quotes from the Minds of Innovators - WorkflowMax
101 Engineering Quotes from the Minds of Innovators - WorkflowMax101 Engineering Quotes from the Minds of Innovators - WorkflowMax
101 Engineering Quotes from the Minds of Innovators - WorkflowMax
 
Wind load calculation
Wind load calculationWind load calculation
Wind load calculation
 
Determinate structures
 Determinate structures Determinate structures
Determinate structures
 
Earthquake resistant structure
Earthquake resistant structureEarthquake resistant structure
Earthquake resistant structure
 
High rise structure & core
High rise  structure & coreHigh rise  structure & core
High rise structure & core
 
Base isolation
Base isolationBase isolation
Base isolation
 
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRODESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
 

Similar to Influence of Wind Loads on tall buildings

Non linear analysis of reinforced concrete chimney
Non linear analysis of reinforced concrete chimneyNon linear analysis of reinforced concrete chimney
Non linear analysis of reinforced concrete chimney
IAEME Publication
 
Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...
Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...
Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...
IRJET Journal
 
ANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDING
ANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDINGANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDING
ANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDING
IAEME Publication
 
IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...
IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...
IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...
IRJET Journal
 
IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...
IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...
IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...
IRJET Journal
 
Parametric study on an industrial structure for various dynamic loads
Parametric study on an industrial structure for various dynamic loadsParametric study on an industrial structure for various dynamic loads
Parametric study on an industrial structure for various dynamic loads
eSAT Journals
 
IS 875-3-1987
IS 875-3-1987IS 875-3-1987
IS 875-3-1987
Aseena Latheef
 
CFD simulation for predicting the wind effect on the high rise building: NET ...
CFD simulation for predicting the wind effect on the high rise building: NET ...CFD simulation for predicting the wind effect on the high rise building: NET ...
CFD simulation for predicting the wind effect on the high rise building: NET ...
ikhsan setiawan
 
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
IJMER
 
Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...
Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...
Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...
IRJET Journal
 
Dynamic Wind Analysis of High-Rise Building
Dynamic Wind Analysis of High-Rise BuildingDynamic Wind Analysis of High-Rise Building
Dynamic Wind Analysis of High-Rise Building
IRJET Journal
 
A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...
A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...
A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...
IRJET Journal
 
COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...
COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...
COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...
IRJET Journal
 
IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...
IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...
IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...
IRJET Journal
 
IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...
IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...
IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...
IRJET Journal
 
Analysis of Wind Load on Tall Building of Various Aspect Ratios
Analysis of Wind Load on Tall Building of Various Aspect RatiosAnalysis of Wind Load on Tall Building of Various Aspect Ratios
Analysis of Wind Load on Tall Building of Various Aspect Ratios
IRJET Journal
 
THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...
THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...
THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...
IRJET Journal
 
Summer Engineering Internship Training Report, ADRDE Agra, DRDO
Summer Engineering Internship Training Report, ADRDE Agra, DRDOSummer Engineering Internship Training Report, ADRDE Agra, DRDO
Summer Engineering Internship Training Report, ADRDE Agra, DRDO
Aayush Singhal
 
BEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUE
BEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUEBEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUE
BEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUE
IRJET Journal
 
Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...
Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...
Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...
YogeshIJTSRD
 

Similar to Influence of Wind Loads on tall buildings (20)

Non linear analysis of reinforced concrete chimney
Non linear analysis of reinforced concrete chimneyNon linear analysis of reinforced concrete chimney
Non linear analysis of reinforced concrete chimney
 
Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...
Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...
Study of Comparison Between Static and Dynamic Analysis Subjected to Wind and...
 
ANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDING
ANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDINGANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDING
ANALYSIS OF WIND & EARTHQUAKE LOAD FOR DIFFERENT SHAPES OF HIGH RISE BUILDING
 
IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...
IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...
IRJET- Shape Optimization of Corners having Different Radius of High Rise Bui...
 
IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...
IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...
IRJET- Analysis and Design Of B+G+10 Commercial High-Rise Building under Seis...
 
Parametric study on an industrial structure for various dynamic loads
Parametric study on an industrial structure for various dynamic loadsParametric study on an industrial structure for various dynamic loads
Parametric study on an industrial structure for various dynamic loads
 
IS 875-3-1987
IS 875-3-1987IS 875-3-1987
IS 875-3-1987
 
CFD simulation for predicting the wind effect on the high rise building: NET ...
CFD simulation for predicting the wind effect on the high rise building: NET ...CFD simulation for predicting the wind effect on the high rise building: NET ...
CFD simulation for predicting the wind effect on the high rise building: NET ...
 
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
Parametric Study for Wind Design of Vertical Pressure Vessel as per Indian St...
 
Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...
Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...
Analysis of Wind Load Effects on R.C Structure Resting on Flat and Sloping Gr...
 
Dynamic Wind Analysis of High-Rise Building
Dynamic Wind Analysis of High-Rise BuildingDynamic Wind Analysis of High-Rise Building
Dynamic Wind Analysis of High-Rise Building
 
A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...
A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...
A COMPARATIVE STUDY USING ETABS SOFTWARE ON THE WIND ANALYSIS OF G+10 AND G+1...
 
COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...
COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...
COMPARATIVE STUDY OF WIND ANALYSIS ON STRUCTURAL SHAPE WITH & WITHOUT SHEAR W...
 
IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...
IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...
IRJET - Wind Speed Variation and its Effect on the High-Rise Building due to ...
 
IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...
IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...
IRJET- Optimization of Tall Structures Under Constraints of Wind Loads and Fi...
 
Analysis of Wind Load on Tall Building of Various Aspect Ratios
Analysis of Wind Load on Tall Building of Various Aspect RatiosAnalysis of Wind Load on Tall Building of Various Aspect Ratios
Analysis of Wind Load on Tall Building of Various Aspect Ratios
 
THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...
THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...
THE WIND EFFECT ON G+3 BUILDING ROOF MOUNT WITH SINGLE AXIS TRACKER AND GROUN...
 
Summer Engineering Internship Training Report, ADRDE Agra, DRDO
Summer Engineering Internship Training Report, ADRDE Agra, DRDOSummer Engineering Internship Training Report, ADRDE Agra, DRDO
Summer Engineering Internship Training Report, ADRDE Agra, DRDO
 
BEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUE
BEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUEBEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUE
BEHAVIOR OF TALL MASONRY CHIMNEYS UNDER WIND LOADINGS USING CFD TECHNIQUE
 
Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...
Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...
Seismic and Wind Analysis of Reinforced Concrete Multistory Building under Di...
 

Recently uploaded

在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
obonagu
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
Kerry Sado
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
ssuser7dcef0
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
manasideore6
 
Basic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparelBasic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparel
top1002
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
DfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributionsDfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributions
gestioneergodomus
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTSHeap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Soumen Santra
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
SyedAbiiAzazi1
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdfGoverning Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
WENKENLI1
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
ongomchris
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
ML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptxML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptx
Vijay Dialani, PhD
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 

Recently uploaded (20)

在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
 
Basic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparelBasic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparel
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
DfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributionsDfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributions
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTSHeap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdfGoverning Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
ML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptxML for identifying fraud using open blockchain data.pptx
ML for identifying fraud using open blockchain data.pptx
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 

Influence of Wind Loads on tall buildings

  • 1. 1 Influence of Wind Loads on Tall Buildings Study Project Report By Mukul Yambal (2013A2PS581P) Study Oriented Project Under Dr. G. Muthukumar BITS Pilani May 2016
  • 2. 2 Contents ACKNOWLEDGEMENT ................................................................................................................................................. 3 INTRODUCTION.......................................................................................................................................................... 4 INDIAN STANDARD CODE -IS 875: PART3 ................................................................................................................... 9 Basic Wind Speed:.............................................................................................................................................10 Design Wind Speed:..........................................................................................................................................10 Probability factor (risk coefficient) (k1) .......................................................................................................11 Terrain, Height and Structure Size factor (K2) .............................................................................................11 Topography factor (K3) ................................................................................................................................12 Importance Factor for Cyclonic Region (k4).................................................................................................13 Wind Pressure...................................................................................................................................................13 Design Wind Pressure.......................................................................................................................................14 Wind Forces on individual members ................................................................................................................14 Wind Forces on structure..................................................................................................................................15 Dynamic Effects.................................................................................................................................................15 Gust Factor........................................................................................................................................................17 Cross wind Response ........................................................................................................................................19 Difference between IS 875:1987 and 2009 (draft)..............................................................................................20 ASCE-7: Minimum Design Loads for Buildings and Other Structures (American code) (2002) .........................21 Some Basic Concepts ........................................................................................................................................21 1. Basic Wind Speed (V) ...........................................................................................................................21 2. Exposure Category................................................................................................................................22 3. Topographic Factor (KZI) .......................................................................................................................23 4. Gust Factor (G or Gf).............................................................................................................................24 Method 1 - Simplified Procedure......................................................................................................................25 Method 2 - Analytical Procedure......................................................................................................................27 Method 3 - Wind Tunnel Procedure.................................................................................................................28 Example:............................................................................................................................................................29 1. Structural Data .....................................................................................................................................30 2. Properties .............................................................................................................................................31 3. Load Combination factors....................................................................................................................32 4. Auto Load Calculations Using ETABS 2015 ..........................................................................................32 5. Analysis.................................................................................................................................................41 6. Displacements due to Wind Loads.......................................................................................................43 Summary...........................................................................................................................................................45 Conclusion.........................................................................................................................................................47 References ........................................................................................................................................................48
  • 3. 3 ACKNOWLEDGEMENT I am indebted to my Instructor Dr. G. Muthukumar, Lecturer Civil Engineering Group, BITS Pilani who introduced me to this work and provided me an opportunity to work under his supervision. His constantly supported and encouraged me throughout this work. The discussions with him were so healthy and fruitful that gave me a chance to increase my domain of knowledge.
  • 4. 4 INTRODUCTION This Study Project covers some essential study regarding wind loads and related different codal provisions related to wind and load considered in designing of buildings due to wind. Study of Indian Standard code (IS 875:1987:- Part 3) as well as (IS 875:2009 part 3-draft) is explained in this report. American Code for wind loads (ASCE-7:2002 version) and its comparison with Indian codes is also included in this report. Some properties and facts related to tall buildings, wind and variation of wind with respect to its height are introduced below which will give necessity of wind loads on tall buildings. TALL BUILDINGS There is no absolute definition of what constitutes a “tall building” according to Council of Tall Buildings and Urban Habitat (CTBUH).Height is relative concept, i.e. a building which should be considered as tall building in country like India may not considered as tall in case of tall buildings countries like US(Chicago). Measurement of height of Tall Building can be considered by three methods according to CTBUH. :- 1. Height to Architectural Top Height is measured from the level of the lowest, significant, open- air, pedestrian entrance to the architectural top of the building, including spires, but not including antennae, signage, flagpoles or other functional-technical equipment. This measurement is the most widely utilized and is employed to define the Council on Tall Buildings and Urban Habitat (CTBUH) rankings of the “World’s Tallest Buildings.” Some of rankings of world’s tallest buildings are listed below:- i) Burj Khalifa Dubai (2010) 828m /2,717ft ii) Shanghai Tower, Shanghai (2015) 632m 2,073ft iii) Makkah Royal Clock Tower Hotel, Mecca (2012) 601m 1,972ft v) One World Trade Center, New York City (2014) 541m 1,776ft
  • 5. 5 2. Height to Tip Height is measured from the level of the lowest, significant, open- air, pedestrian entrance to the highest point of the building, irrespective of material or function of the highest element (i.e., including antennae, flagpoles, signage, and other functional technical equipment). 3. Highest Occupied Floor Height is measured from the level of the lowest, significant, open- air, pedestrian entrance to the finished floor level of the highest occupied floor within the building. Note: - A building having height more than 15 m is considered as tall building according to National Building Code 2005 of India is Called Tall building. (High Rise Building). Building having height more than 18 m (60ft.) is considered as tall building according to American code ASCE-7: 2002 version. Building having mean roof height more than least horizontal dimension is also considered as tall building according to this American code.
  • 6. 6 WIND Wind is air in motion relative to the surface of the earth. Primary reasons of wind is rotation of earth as well as due to difference in terrestrial radiation. Over 50 years study of wind and its speed is carried out in different places to find mean wind speed in different places so that it can be used in further calculations of wind loads which is listed in IS 875:Part3 -1997 as well as in 2009 draft version. This study is carried out using anemometers or anemographs which are installed in different meteorological stations at height of 10 m- 30 m. According to this study India is divided into six different categories depending upon basic wind speeds in each zone. Average basic speeds as per IS875 is given in table 1. Some parts of Jammu and Kashmir as well as Mizoram and Tripura. 55 m/s Whole eastern Coastal area, Costal part in Gujarat as well as Assam. 50 m/s Some part of Tamil Nadu and almost Half North India which includes part of Gujarat ,whole Rajasthan ,Punjab ,part of Madhya Pradesh, Utter Pradesh ,Bihar ,Part of Jharkhand, West Bengal and Sikkim. 47 m/s Western coastal area in Maharashtra as well as some inside land near eastern costal area which is part of Andhra Pradesh ,Maharashtra and Orissa and some eastern part of India , that is , Nagaland , Manipur and Mizoram. 44 m/s Most of the Middle and South India. 39 m/s Some part of Karnataka, Kerala, Andhra-Pradesh, Telangana and Tamil Nadu which is mostly land between eastern and western costal area. 33 m/s Table1-According to IS875:1997 - Part3 In American code, the basic wind speed, V, used in the determination of design wind loads on buildings and other structures is considered from a counter curve given in ASCE-7: 2002 version except Special wind regions Estimation of wind speed from regional data. Data for Special Wind Region is listed below in Table2. Location V (mph) (m/s) Hawaii 105 47 Puerto Rico 145 65 Guam 170 76 Virgin Islands 145 65 American Samoa 125 56 Table2-According to ASCE-7:2002: Special Wind Regions
  • 7. 7 WIND AND ITS VARIATION WITH HEIGHT Wind speeds are generally very low near earth surface due to earth friction. It increases with height from zero to some value and then it remains almost constant. At some height wind can be considered as free from earth’s atmosphere which leads to almost constant velocity after certain height. This height is known as Fetch Height or Gradient Height. Wind is mostly in horizontal direction in high speeds as compared to its vertical component. Vertical component of Wind may be neglected in mostly design cases for wind loads as it is very small, hence generally horizontal winds are considered. Gradient Height
  • 8. 8 As per CTBUH, Tall buildings ae also classifies as supertall and mega tall buildings. Supertall building is a building having height over 300 m (984 feet) while Mega building is one which has height over 600 m (1968 feet).There were total 91 supertall buildings and 2 Mega buildings in world till June 2015.Now mostly high populated cities are coming up with many tall structures. For seismic loads, earthquake loads are usually known to people but wind loads also plays important role near coastal areas as discussed above. There are many areas damaged due to cyclones. Wind speed increases with height from ground surface and hence its impact which eventually leads to Wind as major factor in consideration for case of tall buildings. Increasing number of tall structures and unawareness of people regarding wind loads makes this study very important. This report will describe about IS 875:1987 –Part 3 which is mainly code used for designing wind loads in India. Calculation of design wind speeds, design wind pressure followed by design wind pressure , some Oscillation related phenomenon like Galloping , flutter ,Ovaling ,Vortex Shedding , etc. according to IS 875:1987 – part 3 as well as few changes made in IS 875:2009 –Part-3 (draft form) which includes Interference effect, Dynamic Response Factor ,Cross wind response ,etc. This report will also describe about American code for Wind Loads, ASCE- 7:2002 version, Wind loading part. Three different methods, i.e. Simplified Procedure, Analysis Procedure and Wind Tunnel Testing will be described in the report along with its limitations. This report will be completed by comparing deformation due to wind loads which will be calculated by software E-Tabs-2014. A Concrete frame and Steel frame will be modelled and deformation due to wind will be calculated using IS 875:1987 as well as ASCE -7:2002 version.
  • 9. 9 INDIAN STANDARD CODE -IS 875: PART3 IS 875 was first published in 1957 for the guidance of civil engineers, designers and architects associated with the planning and design of buildings which was included the provisions for the basic design loads (dead loads, live loads, wind loads and seismic loads) to be assumed in the design of the buildings. In its first revision in 1964, the wind pressure provisions were modified on the basis of studies of wind phenomenon and its effect on structures, undertaken by the special committee in consultation with the Indian Meteorological Department. Similarly in 1987 code many changes carried out which leads to better design of building for wind loads and continuous studied related wind made another version of this code in 2009 which is still in its draft form. Design aspect related to wind loads are mentioned in this Indian Standard Codes. This code is designed by examining few international codes listed below:-  BSCP 3:1973 Code of basic data for design of buildings: Chapter 5 –Loading: Part 2: Wind loads  AS 117, Part 2 -1983 SAA Loading code Part2 –Wind forces  NZS 4203-1976 Code of Practice for general structural design loading for buildings  ANSI A58.1-1972 American Standard Building code requirements for minimum design loads in buildings and other structures  Wind resistant design regulations, a world list. Association for Science Documents Information, Tokyo. Some points in IS 875 part 3 are listed below:- i. Basic Wind speed ii. Design Wind speed iii. Wind Pressure iv. Design Wind Pressure v. Wind Forces on individual members vi. Wind Forces on structure vii. Dynamic Effects viii. Gust Factor
  • 10. 10 Basic Wind Speed: India is divided in 6 zones according to Basic wind velocity which is applicable for height about 10 m from mean ground level which is explained in introduction of wind. In Appendix A, IS 875: Part3 -1987 (as well as 2009), Basic wind speed (Vb) for some important cities is listed by studying wind speeds over 50 years. Cyclonic storms generally extend up to 60 km inland after striking sea coast. The influence of wind speed off the coast up to the distance of about 200km may be taken as 1.15 times the value of nearest coast in case of absence of definite data. This is also known as off shore velocity. Design Wind Speed: Design Wind Speed can be determined by estimating Basic Wind Speed as well as some other factors such as topographical factor, risk factor, terrain and height factor and Importance Factor for Cyclonic Region. Relation between all this factors is given by following formulae: - Vz=K1K2K3Vb - (IS 875:1987 – Part3) Vz=K1K2K3K4Vb - (IS 875:2009 – Part3) Where  Vz = design wind speed at any height z in m/s  Vb = basic wind speed in m/s  K1 = Probability factor (risk coefficient)  K2 = terrain, height and structure size factor  K3 = topography factor  K4 = Importance Factor for Cyclonic Region
  • 11. 11 Probability factor (risk coefficient) (k1) This factor depends on estimated life structure required for a building. Few of K1 Values are given in IS 875 part -3 and it can be generalized using following formula:- K1= XN,PN X50,063 = A−B[ln⁡{− 1 N ln⁡(1−PN)}] A+4B Where,  N = mean probable design life of the structure in years  PN = risk level in N consecutive years (probability that the design wind speed is exceeded at least once in N successive years), nominal value = 0.63  XN,P = extreme wind speed for given value of N and PN  X50,0.63 = extreme wind speed for N = 50 years and PN = 0.63 A and B are coefficients depends on different basic wind speed zones. Terrain, Height and Structure Size factor (K2) As per its name K2 factor depends on Terrain, Height of different structures, Size factor that is Class of Buildings. Values of K2 is gives in IS 875 according to above factors. As per IS 875, Terrain is divided into four different categories and buildings are divided into three types as per its size which is described below:- a. Types of Terrain: Classified in Four different terrains as follows:- a) CATEGORY 1:- Exposed Open terrain with few or no obstructions. b) CATEGORY 2:- Open terrain with well scattered obstructions. c) CATEGORY 3:- Terrain with numerous closely spaced obstructions. d)CATEGORY 4:- Terrain with numerous large high closely spaced obstructions
  • 12. 12 b. Classes of Buildings: Buildings can be classified in three different classes depending upon size factor:- a) Class A:-Structure and/or its component having its maximum dimension less than 20 m. b) Class B: - Structure and/or its component having its maximum dimension between 20 m and 50 m. c) Class C: - Structure and/or its component having its maximum dimension greater than 50 m The velocity profile for a given terrain category does not develop to full height immediately with the commencement of that terrain category but develop gradually to height ( h, ) which increases with the fetch or upwind distance (x). The relation between the developed height (h,) and the fetch (x) for wind-flow over each of the four terrain categories is given in IS 875. For structures of heights greater than the developed height (h,) the velocity profile may be determined in accordance with the less or least rough terrain, or another procedure is given in Appendix B of IS 875:1987-part3 Topography factor (K3) This is factor for taking local topographic feature like cliffs, hills valleys, etc. into consideration while calculating design wind speed. This factor is effective when upwind slop (θ) is greater than 3o. Value of K3 is i) 1 when θ< 3o ii) 1.36 when θ> 17o. And for 3 o < θ < 17 o It can be given by:- K3 =1 + Cs Where C and s can be determined by using Appendix C given in IS 875:1987 –part3
  • 13. 13 Importance Factor for Cyclonic Region (k4) Cyclonic wind speeds may be higher than basic wind speed. To consider increase in this velocity during cyclones K4 factor is introduced in IS 875:2009 Part 3. This factor will be mostly useful in cyclonic regions like eastern coastal areas of India. The following values of k4 are stipulated, as applicable according to the importance of the structure:  Structures of post–cyclone importance 1.30  Industrial structures 1.15  All other structures 1.00 This factor is useful for 60 km inland from eastern sea coast and Gujarat sea coast. Wind Pressure Wind Pressure due to design velocity can be determined by following formula given in IS 875:1987 –part3 Pz= 0.6 (𝑉z⁡)2 Where  𝑃z = wind pressure in N/m2 at height z.  𝑉z = design wind velocity in m/s at height z. The coefficient 0’6 (in SI units) in the above formula depends on a number of factors and mainly on the atmospheric pressure and air temperature. The value chosen corresponds to the average appropriate Indian atmospheric conditions.
  • 14. 14 Design Wind Pressure Design Wind pressure according to IS875:1987 –part3 is same as wind pressure explained above. In IS 875:2009 –part3 few new factors like wind directionality factor, area averaging factor, Combination factor are introduced to make design economical, hence design pressure is different than wind pressure which is given by following formula:- Pd =⁡Kd.⁡Ka.Kc .Pz Where  Pd = design wind pressure in N/m2 at height z.  Pz = wind pressure in N/m2 at height z.  Kd = wind directionality factor.  Ka = area averaging factor.  Kc = Combination factor.  Wind Forces on individual members The wind load on individual structural elements such as roofs and walls, and individual cladding units and their fittings, it is essential to take account of the pressure difference between opposite faces of such elements or units. For calculation of wind force on individual cladding units following formula can be used:- F = (Cpe − Cpi) A pd Where  Pd = design wind pressure in N/m2 at height z.  Cpe = external pressure coefficient.  Cpi = internal pressure coefficient.  A = Surface area of structural element Internal and external pressure coefficients for different units having different shapes, structures and slopes are described in IS 875 with figures.
  • 15. 15 Wind Forces on structure The value of force coefficients apply to a building or structure as a whole, and when multiplied by the effective frontal area A, of the building or structure and by design wind pressure, pd gives the total wind load on that particular building or structure. F = (Cf) A pd Where  Pd = design wind pressure in N/m2 at height z.  Cf = force coefficient of building.  A = Surface area of structural element. Force Coefficient: Force coefficient can be classified into 3 types as follows:- i) Frictional force drag coefficient:-In certain buildings of special shape, a force due to frictional drag shall be taken into account in addition to those loads specified. ii) Force Coefficients for Clad Buildings:-values of Cf for different shaped clad buildings are mentioned in IS 875 iii) Force Coefficients for unclad Buildings:- values of Cf for different shaped unclad buildings are mentioned in IS 875. Dynamic Effects For tall, long span and slender structures, wind Fluctuations causes fluctuating forces on structure which induces large dynamic motions including oscillations. Wind loads can induce both along wind Oscillations as well As crosswind Oscillations (vortex shedding). Along wind Oscillations are calculated more readily. Estimation of Vortex shedding has been introduced in IS 875: 1987 but is still not developed enough. Flexible slender structures and structural elements have to investigate for oscillating effects cause due to wind loadings. Criteria for examining structure or building need not necessary if buildings and closed structures having ratio of height to minimum lateral dimension, more than 5 OR natural frequency of buildings and closed structures in first mode is less than 1Hz.
  • 16. 16 i) Fundamental time period (T): Fundamental time period (T) can be determined by experimental methods of similar structures. In absence of such data T can be calculated as follows:-  For moment resisting frames without bracings:- T=0.1n n=number of storeys including basement storeys  For all others T= .09𝐻 𝑑 o H=Height of building in metres. o D=maximum base dimension of building in metres in direction parallel to applied load. ii) Wind induced Motions (T): a) Galloping: - Galloping is the self-induced cross-wind oscillations of flexible structures due to aerodynamic forces that are in-phase with the motion of the structure. It is characterised by the progressively increasing amplitude of transverse vibrations with increased wind speed. Galloping is generally not an issue for buildings. b) Flutter: - Flutter is unstable oscillatory motion of a structure due to coupling between aerodynamic force and elastic deformation of the structure. Flutter can set in at wind speeds much less than those required for exciting the individual modes of motion. Long span suspension bridge decks or any member of a structure with large values of d/t ( where d is the depth of a structure or structural member parallel to wind stream and t is the least lateral dimension of a member ) are prone to low speed flutter. Wind tunnel testing is required to. Determine critical flutter speeds and the likely structural response. Other types of flutter are single degree of freedom stall flutter, torsional flutter, etc. Example of flutter: -The collapse of the original Tacoma Narrows Bridge, a suspension bridge in the U.S. state of Washington.
  • 17. 17 c) Ovalling: - This walled structures with open ends at one or both ends such as oil storage tanks, and natural draught cooling towers in which the ratio of the diameter of minimum lateral dimension to the wall thickness is of the order of 100 or more, are prone to ovalling oscillations. These oscillations are characterized by periodic radial deformation of the hollow structure. iii) Motion due to Vortex Shedding: For slender structures, ŋ –frequency of Vortex Shedding can be given by ŋ= SVd b  S=Strouhal number.  Vd=Design Wind velocity.  b=breadth of structure or structural member in horizontal plane normal to wind direction. Circular sections  S=0.2 for Vz ≤ 7  S=0.25 for Vz > 7 Rectangular Structures  S=0.15 Gust Factor IS 875:1987 allows Gust method for calculation of wind loads some cases .This method needs Hourly mean wind speed which is equal to basic wind speed. Wind load can be calculated from Gust factor method by using following formula:- 𝐹 = (𝐶𝑓) 𝐴𝑒 𝑝𝑑𝐺  Fz = along wind load on the structure at any height z corresponding to strip area Ae  Cf = force coefficient of building  Ae = effective frontal area considered for structure at height z  Pz = design pressure at height z due to hourly mean wind Ovalling
  • 18. 18 G=Gust factor = 𝑝𝑒𝑎𝑘 𝑙𝑜𝑎𝑑 𝑚𝑒𝑎𝑛 𝑙𝑜𝑎𝑑 G=1+gtr√ 𝐵(1 + ∅)2 + 𝑆𝐸 𝛽 Where gf = peak factor defined as the ratio of the expected peak value to the root mean value of a fluctuating load Y = roughness factor which is dependent on the size of the structure in relation to the ground roughness. B = background factor indicating a measure of slowly varying component of fluctuating wind load SE β =measure of the resonant component of the fluctuating wind load S = size reduction factor E = measure of available energy in the wind stream at the natural frequency of the structure β = damping coefficient (as a fraction of critical damping) of the structure ɸ = 𝑔𝑡 × 𝑟√𝛽 4
  • 19. 19 Cross wind Response This factor is defined in IS 875: 2009 draft version .The equivalent cross–wind static force per unit height (We) as a function of z in Newton per meter height, shall be as follows: We (z) = 0.6 [Vh] 2 d Cdyn Where, d = Lateral dimension of the structure parallel to the wind stream, and Cdyn = 1.5gR b 𝑑 𝐾𝑚 1+𝑔𝑣𝑙ℎ ( 𝑧 ℎ )k √( 𝜋𝐶𝑓𝑠 𝛽 ) Where, Km = mode shape correction factor = 0.76 + 0.24 k Where k = mode shape power exponent for the fundamental mode of vibration = 1.5 for a uniform cantilever = 0.5 for a slender framed structure (moment resistant) = 1.0 for building with central core and moment resisting façade = 2.3 for a tower decreasing in stiffness with height, or with a large mass at top Cfs = cross–wind force spectrum coefficient generalized for a linear mode shape. GR = peak factor for resonant response (1 hour period) given by GR = [2 log (3600f0)] (½) β = ratio of structural damping to critical damping of Structure Ih = turbulence intensity, obtained by setting z equal to h gv = peak factor for the upwind velocity fluctuations, which shall be taken as 3.5
  • 20. 20 Difference between IS 875:1987 and 2009 (draft)  For calculation of wind speed K4 factor for cyclone is introduced in 2009 version.  Design Wind Pressure is same as wind pressure in case of 1987 code but for 2009 version three new factors are introduced. Design pressure can be obtained by multiplying this factors by wind pressure. This three factors are  a)Kd=wind directional factor  a)Ka=Area averaging factor  a)Kc=combination factor  Interference effect is introduced in 2009 code while it was not in 1987. When wind comes from striking some buildings and original wing may have some phase difference which will leads to interference effect.  Dynamic Response Factor will tell you wind pressure at certain height of building. In the 1987 version, the dynamic response factor, Cdyn, was applied to the wind loading due to hourly mean wind speed, as opposed to the 3second gust speed used in the 2009 version.  CROSS-WIND RESPONSE is introduced in 2009 draft for determining equivalent static wind force and base overturning moment in the cross-wind direction for tall enclosed buildings and towers of rectangular cross-section  Some parts of the code have been revised from the 1987 version to take into account the wind incidence angle.
  • 21. 21 ASCE-7: Minimum Design Loads for Buildings and Other Structures (American code) (2002) This Code is published by American Society for Civil Engineers. As per name of code this is made for design of all kinds of loads like dead, live, soil, flood, wind, snow, rain, ice and earthquake loads. In this report mainly we will focus on wind load designing. The design wind loads for buildings and other structures, including the main wind force-resisting system and component and cladding elements thereof, shall be determined using one of the following procedures: 1) Method 1 - Simplified Procedure 2) Method 2 – Analytical Procedure 3) Method 3 – Wind Tunnel Procedure Some Basic Concepts Before going into further details of procedures, some basic concepts should be introduced as per ASCE-7:2002 Version. 1. Basic Wind Speed (V) Basic Wind Velocity can be determined by contour map given in code ASCE- 7:2002 version except for special wind regions and it can also be determined using Regional Climatic Data. Special Wind Regions: The Basic Wind Speed shall be increased in case the wind speeds are higher than given in code by record or experience. Regional Climatic Data: Reginal Climatic Data should be preferred instead of code data when approved extreme-value statistical analytical procedure have been employed in reducing the data and all related factors have been taken into account. Hurricane-Prone Regions: This code allows basic wind speed from simulation techniques instead of given in code data when approved simulation or extreme value statistics analysis procedures are used. (Not allowed along Gulf and
  • 22. 22 Atlantic coasts, the Caribbean or Hawaii). The resulting design speed by this methods shall not be less than resulting 500 year return period wind speed divided by √1.5 . 2. Exposure Category The characteristics of ground roughness and surface irregularities are the important factors to be considered while designing wind loads. This factors are included in exposure category which will also take ground variation due to natural topography and vegetation. Surface Roughness Category: There are three major categories of surface roughness as follows Surface Roughness B: Urban and suburban area, wooded areas or other terrain with numerous closely spaced obstructions having size of single family dwelling or larger. Surface Roughness C: Open terrain with scattered obstructions having heights generally less than 30ft. (9.1 m). This category also includes flat open country, grasslands, and all water surfaces in hurricane-prone regions. Surface Roughness D: Flat, unobstructed and water surfaces outside hurricane-prone regions. This category also includes smooth mud flats, salt flats, and unbroken ice. Exposure Category: There are three different exposure categories defined in this code along with transition zone explained as follows: Exposure B: It is mainly for surface category B. Ground surface roughness conditions prevails in the upwind direction for a distance of at least 2630 ft. (800 m.) or 10 times the height of the building whichever is greater. Upwind distance can be reduced to 1500 ft. (457 m.), in case of buildings having mean roof height less than or equal to 30ft. (9.1 m.). Exposure C: This is for all cases other than where exposure B n exposure D do not apply. Exposure D: It is mainly for surface category D. Ground surface roughness conditions prevails in the upwind direction for a distance of at least 5000 ft. (1524 m.) or 10 times the height of the building whichever is greater. This can extend
  • 23. 23 inland fro the shoreline for a distance of 600 ft. (200 m.) or 10 times the height of the building whichever is greater. Transition Zone: For a site located in between any two or more exposure categories, the category resulting largest wind force should be considered. Intermediate exposure is permitted in case of rational analysis. 3. Topographic Factor (KZI) Wind Speed-Up effects over Hills, Ridges, and Escarpments constituting abrupt changes in the general topography, located in any exposure category, and should be considered while designing wind loads. Conditions to be considered while designing are as follows:- 1. The hill, ridge, or escarpment is isolated and unobstructed upwind by other similar topographic features of comparable height for 100 times the height of the topographic feature (100 H) or 2 miles (3.22 km), whichever is less. This distance shall be measured horizontally from the point at which the height H of the hill, ridge, or escarpment is determined. 2. The hill, ridge, or escarpment protrudes above the height of upwind terrain features within a 2-mile (3.22-km) radius in any quadrant by a factor of two or more. 3. The structure is located in the upper half of a hill or ridge or near the crest of an escarpment. 4. H/LH ≤ 0.2. 5. H is greater than or equal to 15 ft. (4.5 m) for Exposures C and D and 60 ft. (18 m) for Exposure B. Topographic Factor. The wind speed-up effect shall be included in the calculation of design wind loads by using the factor Kzt which can be calculated as follows: Kzt= (1+K1K2K3)2
  • 24. 24 4. Gust Factor (G or Gf) In this code Gust Factors are given for rigid structures as wells as for flexible structures as given below:- For Rigid Structures:- G = 0.925 ((l + 1.7gQIQ)/ (1 + 1.7gv lz) lz = c(33/z)1/6 Where, Iz = Intensity of turbulence at height z. Z=equivalent height of structure (0.6h) > zmin . For Flexible Structures:- Gf = 0.925 ((l + 1.7Iz (gQ 2Q2+gR 2R2)0.5)/ (1 + 1.7gv lz)
  • 25. 25 Method 1 - Simplified Procedure To design any building or structure by this method, it should satisfy few conditions mentioned as follows:- i. For the design of main wind force-resisting systems:-  The building is a simple diaphragm building, i.e. an enclosed or partially enclosed building in which wind loads are transmitted through floor and roof diaphragms to the vertical main wind force-resisting system.  The building is a low-rise building i.e. enclosed or partially enclosed Buildings of which mean roof height h jess than or equal to 60 ft. (18 m) or mean roof height h does not exceed least horizontal dimension.  The building is enclosed and conforms to the wind borne debris provisions.  The building is a regular shaped building or structure, i.e. building with no geometric irregularity in spatial form.  The building is not classified as a flexible, i.e. Buildings having no natural frequency less than 1 Hz.  the building does not have response characteristics making it subject to across-wind loading, vortex shedding, instability due to galloping or flutter; and does not have a site location for which channelling effects or buffeting in the wake of upwind obstructions warrant special consideration.  The building structure has no expansion joints or separations.  The building is not subject to the topographic effects i.e., K zt = 1.0.  The building has an approximately symmetrical cross section in each direction with either a fiat roof, or a gable or hip roof with θ ≤ 45 degrees. ii. For the design of components and cladding:-  The mean roof height h ≤ 60 ft.  The building is enclosed and conforms to the wind-borne debris provisions  The building is a regular shaped building.  The building does not have response characteristics making it subject to across-wind loading, vortex shedding, instability due to galloping or flutter; and does not have a site location for which channelling effects or buffeting in the wake of upwind obstructions warrant special consideration.  The building is not subject to the topographic effects, i.e., Kzt = 1.0.  The building has either a flat roof, or a gable roof with θ ≤ 45 degrees, or a hip roof with θ ≤ 27 degrees.
  • 26. 26 Design Procedure:- 1. Determine Basic Wind Speed, Importance factor I, exposure category, and exposure adjustment coefficient λ from code. 2. Main Wind Force-Resisting System:-Simplified design wind pressure (ps) can be given by following formula: ps = λ Ips30 Where, λ = adjustment factor for building height and Exposure I = importance factor pS30 = simplified design wind pressure for exposure B, at h = 30 ft, and for I = 1.0. Note:-ps should not be less than 10lb/ft2 (0.48 kN/m2). This force is applied on horizontal and vertical projections of building surfaces. 3. Component and Cladding:-Net design wind pressure (pnet) can be given by following formula: Pnet = λ Ipnet30 Where, λ = adjustment factor for building height and Exposure I = importance factor pnet30 = simplified design wind pressure for exposure B, at h = 30 ft, and for I = 1.0. Note:-Positive pnet should not be greater than 10lb/ft2 (0.48 kN/m2) and negative pnet should not be less than -10lb/ft2 (-0.48 kN/m2). This force is applied normal to each building surfaces.
  • 27. 27 Method 2 - Analytical Procedure To design any building or structure by this method, it should satisfy few conditions mentioned as follows:-  The building or other structure is a regular shaped building or structure.  The building or other structure does not have response characteristics making it subject to across-wind loading, vortex shedding, instability due to galloping or flutter; or does not have a site location for which channelling effects or buffeting in the wake of upwind obstructions warrant special consideration. Design Procedure:- 1. The basic wind speed V and wind directionality factor K d, importance factor I, an exposure category or exposure categories and velocity pressure exposure coefficient KZ or KH, shall be determined for each wind direction. 2. A topographic factor KZt, a gust effect factor G or Gf, an enclosure classification shall be determined. 3. Internal pressure coefficient GCpi as well as external pressure coefficients Cp or GCpf, or GCf shall be determined. 4. Velocity pressure at height z (qz or qh) can be determined using following formula:- qz = 0.00256 Kz KZt Kd V2 I (lb/ft2) [In SI: qz = 0.613 KzKztKd V2 I (N/m2); V in m/s] Where, Kd =Wind directionality factor. Kz =Velocity pressure exposure coefficient. KZt = Topographical factor. 5. Design wind load p or F shall be determined by considering formulae given in code as per required case of building.
  • 28. 28 Method 3 - Wind Tunnel Procedure Wind Tunnel Testing is used to determine wind loads on any buildings and structures. This method is useful in prediction of wind loads and responses of structures, structural components, and cladding to verify the wind conditions and hence to design any building or structure. Problem with this method is its cost, i.e. it is very expensive. Example of Structure for which wind tunnel testing is used is World Trade Centre. In this method experiments are conducted on small model applying same Surrounding conditions. Tests for determining fluctuating mean wind pressure or force by Wind Tunnel Testing should meet following conditions:- 1. The natural atmospheric boundary layer has been modelled to account for the variation of wind speed with height. 2. The relevant macro length and micro length scales of the longitudinal component of atmospheric Turbulence are modelled to approximately the same scale as that used to model the building or structure 3. The modelled building or other structure and surrounding structures and topography are geometrically Similar to their full-scale counterparts, except that, for low--rise buildings. 4. The projected area of the modelled building or other structure and surroundings is less than 8% of the test section cross-sectional area unless correction is made for blockage. 5. The longitudinal pressure gradient in the wind-tunnel test section is accounted for 6. Reynolds number effects on pressures and forces are minimized 7. Response characteristics of the wind-tunnel instrumentation are consistent with the required measurements. World Trade Centre
  • 29. 29 Example: Reinforced Concrete (RCC) frame with flat roof is designed using ETABS 2015 software having following dimensions:- Component Length (in m.) Width (in mm.) Depth (in mm.) Column (Except first floor) 3.2004 600 6000 Column (For first floor) 3.6576 600 600 Beam 6.096 600 6000 Number of Stories =10 Total Length = 24.396 m. (4 Beams in X direction) (Total 5 Gridlines) Total Breadth = 12.198 m. (2 Beams in Y direction) (Total 3 Gridlines) Slab Thickness =200 mm. As shown in figure below:- Note: - No additional Dead loads and Live Loads are considered as their value is 0 kN/m2. 3D View
  • 30. 30 1. Structural Data Data related to structure is provided in Table given below:- a. Story Data: Elevation and Height of each Floor is given in Table below:- Table: Elevation and Height Name Height (mm) Elevation (mm) Story10 3200.4 32461.2 Story9 3200.4 29260.8 Story8 3200.4 26060.4 Story7 3200.4 22860 Story6 3200.4 19659.6 Story5 3200.4 16459.2 Story4 3200.4 13258.8 Story3 3200.4 10058.4 Story2 3200.4 6858 Story1 3657.6 3657.6 Base 0 0 b. Mass: Table: Centre of Mass Calculations Table: Centre of Mass Calculations Story Diaphragm Mass X kg Mass Y kg Mass Moment of Inertia ton-m² X Mass Center m Y Mass Center m Story10 D1 273531.07 273531.07 20590.7181 12.192 6.096 Story9 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story8 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story7 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story6 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story5 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story4 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story3 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story2 D1 294293.59 294293.59 22648.2132 12.192 6.096 Story1 D1 297259.66 297259.66 22942.141 12.192 6.096 Story Diaphragm Mass X kg Mass Y kg XCM m YCM m Cumulative X kg Cumulative Y Kg XCCM m YCCM m Story10 D1 273531.07 273531.07 12.192 6.096 273531.07 273531.07 12.192 6.096 Story9 D1 294293.59 294293.59 12.192 6.096 567824.65 567824.65 12.192 6.096 Story8 D1 294293.59 294293.59 12.192 6.096 862118.24 862118.24 12.192 6.096 Story7 D1 294293.59 294293.59 12.192 6.096 1156411.83 1156411.83 12.192 6.096 Story6 D1 294293.59 294293.59 12.192 6.096 1450705.42 1450705.42 12.192 6.096 Story5 D1 294293.59 294293.59 12.192 6.096 1744999.01 1744999.01 12.192 6.096 Story4 D1 294293.59 294293.59 12.192 6.096 2039292.6 2039292.6 12.192 6.096 Story3 D1 294293.59 294293.59 12.192 6.096 2333586.19 2333586.19 12.192 6.096 Story2 D1 294293.59 294293.59 12.192 6.096 2627879.78 2627879.78 12.192 6.096 Story1 D1 297259.66 297259.66 12.192 6.096 2925139.45 2925139.45 12.192 6.096
  • 31. 31 Table: Centre of Mass Calculations Story UX kg UY kg UZ kg Story10 273531.07 273531.07 0 Story9 294293.59 294293.59 0 Story8 294293.59 294293.59 0 Story7 294293.59 294293.59 0 Story6 294293.59 294293.59 0 Story5 294293.59 294293.59 0 Story4 294293.59 294293.59 0 Story3 294293.59 294293.59 0 Story2 294293.59 294293.59 0 Story1 297259.66 297259.66 0 Base 23728.6 23728.6 0 2. Properties a. Materials: Table: Material Properties Name Type E MPa ν Unit Weight kN/m³ Design Strengths 4000Psi Concrete 24855.58 0.2 23.5631 Fc=27.58 MPa A615Gr60 Rebar 199947.98 0.3 76.9729 Fy=413.69 MPa, Fu=620.53 MPa b. Frame Sections: Table: Frame Sections Name Material Shape Concrete Beam 4000Psi Concrete Rectangular Concrete Column 4000Psi Concrete Rectangular c. Shell Sections: Table: Shell Sections Name Design Type Element Type Material Total Thickness mm Slab1 Slab Shell-Thin 4000Psi 200 d. Reinforcement Sizes: Table: Reinforcing Bar Sizes Name Diameter mm Area mm² 10 10 79 20 20 314
  • 32. 32 3. Load Combination factors Load combination factors used while analysing are listed below. This factors are taken for DL+LL+WL combination from IS 456 for Indian case and from ASCE-07:2002 for American case. Table: Load Combination Factors from IS456 Name Load Case/Combo Scale Factor Type Auto DD+LL+WL (Indian) Dead 1.2 Linear Add No DD+LL+WL (Indian) Live 1.2 No DD+LL+WL (Indian) Wind Indian 1.2 No Table: Load Combination Factors from ASCE-07:2002 Name Load Case/Combo Scale Factor Type Auto DD+LL+WL (American) Dead 1.2 Linear Add No DD+LL+WL (American) Live 1 No DD+LL+WL (American) Wind American 1.6 No 4. Auto Load Calculations Using ETABS 2015 a. Indian IS875:1987 Auto Wind Load Calculation: Assuming frame is located near Orissa, where basic wind speed Vb is 50 ms-1 as per given in IS875:1987. Other assumed parameters are as follows:- Table: Factors related to Wind Loads Structure Class Class B Terrain Category Category 2 Wind Direction 0;90 degrees Basic Wind Speed, Vb 50 ms-1 Windward Coefficient, Cp,wind 0.8 Leeward Coefficient, Cp,lee 0.5 Risk Coefficient, k1 1 Topography Factor, k3 1 Table: Calculated Factors Design Wind Speed, Vz Vz=k1k2k3Vb Vz=50 Design Wind Pressure, pz Pz=0.6Vz 2 Pz=1500
  • 33. 33 Story Elevation(m) X-Dir(kN) Y-Dir(kN) Story10 32.4612 47.4621 0 Story9 29.2608 93.5974 0 Story8 26.0604 90.9865 0 Story7 22.86 88.311 0 Story6 19.6596 85.5586 0 Story5 16.4592 82.4853 0 Story4 13.2588 78.9015 0 Story3 10.0584 75.5657 0 Story2 6.858 74.8726 0 Story1 3.6576 80.2207 0 Base 0 0 0 Story Elevation(m) X-Dir(kN) Y-Dir(kN) Story10 32.4612 0 93.7845 Story9 29.2608 0 184.947 Story8 26.0604 0 179.788 Story7 22.86 0 174.5012 Story6 19.6596 0 169.0624 Story5 16.4592 0 162.9897 Story4 13.2588 0 155.9081 Story3 10.0584 0 149.3167 Story2 6.858 0 147.9471 Story1 3.6576 0 158.5148 Base 0 0 0 Case-1 Case-2
  • 34. 34 b. ASCE 7-02 Auto Wind Load Calculations: Assuming frame is located is in America having same Basic Wind Speed as in Orissa i.e., Vb is 50 ms-1 (111.85⁡mph). Other assumed parameters are as follows:- Table: Factors related to Wind Loads Structure Class Class B Terrain Category Category 2 Wind Direction 0 degrees Basic Wind Speed, Vb 111.85 mph Windward Coefficient, Cp,wind 0.8 Leeward Coefficient, Cp,lee 0.5 Gradient Height, zg 900 Empirical Exponent, α 9.5 Topographical Factor, Kzt 1 Directionality Factor, Kd 085 Importance Factor, I I = 1 Gust Effect Factor, G G = 0.85 Table: Calculation formulas Design Wind Pressure, p [ASCE 6.5.12.2.1 Eq. 6-17] 𝐩 = 𝐪𝐆𝐂 𝐩,𝐰𝐢𝐧𝐝 + 𝐪 𝐡(𝐆𝐂 𝐩,𝐥𝐞𝐞) Velocity Pressure Exposure Coefficient, Kz; For 15 ft.≤Z≤ Zg For Z < 15 ft. Kz = 2.01 (z/zg)2/ɑ Kz = 2.0 I (l5/zg)2/ ɑ Velocity Pressure, qz 𝐪 𝐳 = 𝟎. 𝟎𝟎𝟐𝟓𝟔𝐊 𝐳 𝐊 𝐳𝐭 𝐊 𝐝 𝐕 𝟐 𝐈
  • 35. 35 Story Elevation(m) X-Dir(kN) Y-Dir(kN) Story10 32.4612 24.447 0 Story9 29.2608 48.1865 0 Story8 26.0604 47.0583 0 Story7 22.86 45.8258 0 Story6 19.6596 44.4622 0 Story5 16.4592 42.928 0 Story4 13.2588 41.1603 0 Story3 10.0584 39.0482 0 Story2 6.858 36.3775 0 Story1 3.6576 36.6011 0 Base 0 0 0 Story Elevation(m) X-Dir(kN) Y-Dir(kN) Story10 32.4612 0 56.9014 Story9 29.2608 0 112.4047 Story8 26.0604 0 110.1753 Story7 22.86 0 107.7399 Story6 19.6596 0 105.0456 Story5 16.4592 0 102.0141 Story4 13.2588 0 98.521 Story3 10.0584 0 94.3476 Story2 6.858 0 89.0703 Story1 3.6576 0 90.7399 Base 0 0 0 Case-1
  • 36. 36 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 18.3353 0 Story9 29.2608 36.1399 0 Story8 26.0604 35.2937 0 Story7 22.86 34.3693 0 Story6 19.6596 33.3467 0 Story5 16.4592 32.196 0 Story4 13.2588 30.8702 0 Story3 10.0584 29.2862 0 Story2 6.858 27.2831 0 Story1 3.6576 27.4508 0 Base 0 0 0 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 18.3353 0 Story9 29.2608 36.1399 0 Story8 26.0604 35.2937 0 Story7 22.86 34.3693 0 Story6 19.6596 33.3467 0 Story5 16.4592 32.196 0 Story4 13.2588 30.8702 0 Story3 10.0584 29.2862 0 Story2 6.858 27.2831 0 Story1 3.6576 27.4508 0 Base 0 0 0 Case-1
  • 37. 37 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 0 42.676 Story9 29.2608 0 84.3035 Story8 26.0604 0 82.6315 Story7 22.86 0 80.8049 Story6 19.6596 0 78.7842 Story5 16.4592 0 76.5106 Story4 13.2588 0 73.8908 Story3 10.0584 0 70.7607 Story2 6.858 0 66.8027 Story1 3.6576 0 68.0549 Base 0 0 0 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 0 42.676 Story9 29.2608 0 84.3035 Story8 26.0604 0 82.6315 Story7 22.86 0 80.8049 Story6 19.6596 0 78.7842 Story5 16.4592 0 76.5106 Story4 13.2588 0 73.8908 Story3 10.0584 0 70.7607 Story2 6.858 0 66.8027 Story1 3.6576 0 68.0549 Base 0 0 0 Case-2
  • 38. 38 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 18.3353 -36.2302 Story9 29.2608 36.1399 -71.4118 Story8 26.0604 35.2937 -69.7398 Story7 22.86 34.3693 -67.9132 Story6 19.6596 33.3467 -65.8925 Story5 16.4592 32.196 -63.6189 Story4 13.2588 30.8702 -60.9991 Story3 10.0584 29.2862 -57.869 Story2 6.858 27.2831 -53.911 Story1 3.6576 27.4508 -54.2424 Base 0 0 0 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 21.5974 42.676 Story9 29.2608 42.6641 84.3035 Story8 26.0604 41.8179 82.6315 Story7 22.86 40.8935 80.8049 Story6 19.6596 39.8709 78.7842 Story5 16.4592 38.7202 76.5106 Story4 13.2588 37.3944 73.8908 Story3 10.0584 35.8103 70.7607 Story2 6.858 33.8073 66.8027 Story1 3.6576 34.441 68.0549 Base 0 0 0 Case-2
  • 39. 39 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 13.7637 -27.1968 Story9 29.2608 27.129 -53.6065 Story8 26.0604 26.4938 -52.3514 Story7 22.86 25.7999 -50.9802 Story6 19.6596 25.0322 -49.4633 Story5 16.4592 24.1685 -47.7566 Story4 13.2588 23.1732 -45.79 Story3 10.0584 21.9841 -43.4403 Story2 6.858 20.4805 -40.4692 Story1 3.6576 20.6064 -40.7179 Base 0 0 0 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 13.7637 -27.1968 Story9 29.2608 27.129 -53.6065 Story8 26.0604 26.4938 -52.3514 Story7 22.86 25.7999 -50.9802 Story6 19.6596 25.0322 -49.4633 Story5 16.4592 24.1685 -47.7566 Story4 13.2588 23.1732 -45.79 Story3 10.0584 21.9841 -43.4403 Story2 6.858 20.4805 -40.4692 Story1 3.6576 20.6064 -40.7179 Base 0 0 0 Case-3
  • 40. 40 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 16.2124 32.0355 Story9 29.2608 32.0265 63.2838 Story8 26.0604 31.3913 62.0287 Story7 22.86 30.6974 60.6576 Story6 19.6596 29.9297 59.1407 Story5 16.4592 29.066 57.4339 Story4 13.2588 28.0707 55.4673 Story3 10.0584 26.8816 53.1177 Story2 6.858 25.378 50.1466 Story1 3.6576 25.8537 51.0865 Base 0 0 0 Story Elevation X-Dir Y-Dir m kN kN Story10 32.4612 16.2124 32.0355 Story9 29.2608 32.0265 63.2838 Story8 26.0604 31.3913 62.0287 Story7 22.86 30.6974 60.6576 Story6 19.6596 29.9297 59.1407 Story5 16.4592 29.066 57.4339 Story4 13.2588 28.0707 55.4673 Story3 10.0584 26.8816 53.1177 Story2 6.858 25.378 50.1466 Story1 3.6576 25.8537 51.0865 Base 0 0 0 Case-4
  • 41. 41 5. Analysis a. Base Reaction Calculations: Table: Base reactions Load Case/Combo FX(kN) FY(kN) FZ(kN) MX(kN-m) MY(kN-m) MZ(kN-m) X(m) Y(m) Z(m) Dead 0 0 28918.5181 176287.2864 -352575 0 0 0 0 DD+LL+WL (Indian) Max 0 0 34702.2217 245505.1329 -423089 5837.2475 0 0 0 DD+LL+WL (Indian) Min -957.5537 -1892.1115 34702.2217 211544.7437 -440276 -23068.6228 0 0 0 DD+LL+WL (American) Max 0 962.9247 34702.2217 239404.7455 -423089 14710.6433 0 0 0 DD+LL+WL (American) Min -649.7518 -1547.1356 34702.2217 194045.4059 -434897 -18862.6773 0 0 0 b. Story Forces: i. Shear Diagrams . Shear Forces increases from top to bottom for frame.Folowing table shows shear forces for different cases which are calculated for story 1 :- Load Case/Combo Location P VX VY T Dead Top 28453.12 0 0 0 Dead Bottom 28918.52 0 0 0 DD+LL+WL (Indian) Max Top 34143.75 0 0 5837.248 DD+LL+WL (Indian) Max Bottom 34702.22 0 0 5837.248 DD+LL+WL (Indian) Min Top 34143.75 -957.554 -1892.11 -23068.6 DD+LL+WL (Indian) Min Bottom 34702.22 -957.554 -1892.11 -23068.6 DD+LL+WL (American) Max Top 34143.75 0 962.9247 14710.64 DD+LL+WL (American) Max Bottom 34702.22 0 962.9247 14710.64 DD+LL+WL (American) Min Top 34143.75 -649.752 -1547.14 -18862.7 DD+LL+WL (American) Min Bottom 34702.22 -649.752 -1547.14 -18862.7 Dead Load Case DD+LL+WL Indian case DD+LL+WL American case
  • 42. 42 ii. Moment Diagrams Moments increases from top to bottom for frame.Folowing table shows Moments for different cases which are calculated for story 1 :- Story Load Case/Combo Location MX MY Story1 Dead Top 173450.2 -346900 Story1 Dead Bottom 176287.3 -352575 Story1 DD+LL+WL (Indian) Max Top 235180.1 -416281 Story1 DD+LL+WL (Indian) Max Bottom 245505.1 -423089 Story1 DD+LL+WL (Indian) Min Top 208140.3 -429965 Story1 DD+LL+WL (Indian) Min Bottom 211544.7 -440276 Story1 DD+LL+WL (American) Max Top 230341.5 -416281 Story1 DD+LL+WL (American) Max Bottom 239404.7 -423089 Story1 DD+LL+WL (American) Min Top 194162.9 -425712 Story1 DD+LL+WL (American) Min Bottom 194045.4 -434897 Dead Load Case DD+LL+WL Indian case DD+LL+WL American case
  • 43. 43 6. Displacements due to Wind Loads Maximum joint displacements for different cases are shown in following table :- Load Case/Combo Story no. UXmax(mm) UYmax(mm) UZmax(mm ) RXmax(rad) RYmax(rad) RZmax(rad) Dead 10 -2.23E-08 -2.59E-08 -5.43E+00 3.08E-04 2.92E-04 0 DD+LL+WL (Indian) Max 10 1.68E+01 3.79E+01 -6.52E+00 3.70E-04 -2.91E-04 0 DD+LL+WL (Indian) Min 10 -2.77E-08 -3.21E-08 -6.52E+00 -4.87E-03 3.51E-04 0 DD+LL+WL (American) Max 10 3.51E-04 3.32E+01 -6.52E+00 2.90E-03 1.69E-03 8.03E-04 DD+LL+WL (American) Min 10 -5.02E+00 -2.24E+01 -6.52E+00 -4.30E-03 -6.91E-04 -8.03E-04 Dead Load Case DD+LL+WL Indian case DD+LL+WL American case Deformation Diagrams -5 0 5 10 15 20 1 15 29 43 57 71 85 99 113 127 141 155 169 183 197 211 225 239 253 267 281 295 309 323 337 351 DisplacementinXdirection(inmm) Joint numbers (from story10 to story1) Displacement of joints in X Direction Dead DD+LL+WL (Indian) DD+LL+WL (American)
  • 44. 44 As Shown in above Graphs, Displacement in all direction is maximum for Indian DD+LL+WL combination, while it is least is case of X & Y direction for dead loads. For American DD+LL+WL combination, Displacement is least in Z direction as compared to other cases. For Z direction displacements, Negative displacement means displacement in downward direction. Some joints are assumed to be fixed and hence their displacement in z direction is zero In all three cases, Maximum displacement is found to be for top story, i.e. for story 10. It decreases with height. -5 0 5 10 15 20 25 30 35 40 1 15 29 43 57 71 85 99 113 127 141 155 169 183 197 211 225 239 253 267 281 295 309 323 337 351 DisplacementinYdirection(inmm) Joint numbers (from story10 to story1) Displacement of joints in Y Direction Dead DD+LL+WL (Indian) DD+LL+WL (American) -7 -6 -5 -4 -3 -2 -1 0 1 15 29 43 57 71 85 99 113 127 141 155 169 183 197 211 225 239 253 267 281 295 309 323 337 351 DisplacementinYdirection(inmm) Joint numbers (from story10 to story1) Displacement of joints in Z Direction Dead DD+LL+WL (Indian) DD+LL+WL (American)
  • 45. 45 Summary  Wind Load increases with increase in height and its direction is horizontal hence it is important to analyse Tall buildings for wind loads.  IS 875:1987 Part 3 is Indian Standard Code for design of wind loads. IS 875:2009 part 3 is in draft version, having few changes in it as compared to IS875:1987 part3.  ASCE -07 Chapter 6 is meant for design of wind loads. 2002 version of this code is used in this report while 2005, 2010 versions of this codes are also available.  For IS 875:1987 and 2009 (part 3) versions, some major points for designing wind loads are as follows:- o Determining basic wind speed and hence design wind speed depending upon height of building, terrain, topography, etc. (in case of 2009, cyclone zone also considered). o Determining Wind pressure and Design wind pressure for calculated design velocity. o Determining force coefficients and hence wind forces on buildings as well as for individual members. o This code is yet to be developed for considering Dynamic effects except vortex shedding.  For ASCE-07:2002 version, some major points for designing loads are as follows:- There are three different methods for this code o Simplified method:-This is similar to IS 875 method. It needs to determine Basic Wind Speed, Importance factor I, exposure category, and exposure adjustment coefficient λ for calculation of wind loads. This is applicable for limited cases of buildings and structures. o Analytical method: - in this method some more factors as compared to simplified method are taken into account. This can be applicable for most of the buildings and structure. o Wind Tunnel method: - This is method in which, actual model of building or structure for which wind loading is to be designed. Wind conditions are applied considering scale factors and making same environment as that of actual building. Response of building and its components are observed and building or structure is designed.
  • 46. 46  Some Observations from case studied for same conditions using IS875:1987 and ASCE- 7:02 o Wind Load for structure is calculated for 2 time taking only 1 case using IS 875: part3 while it is calculated for 12 times considering 4 different cases in case of ASCE-07:2002. o Base reactions as well as Shear forces in Y directions are zero as per IS 875 but it have positive value in case of ASCE-07. o Moments for both codes are almost equal. o Joint displacements are more in case of IS codes that displacements calculated as per ASCE: 07.
  • 47. 47 Conclusion  ASCE:07 allows to use basic wind data by studying and analysing wind data which means more accurate local conditions can be considered and hence structure may be more economical as well as more strong. Local weather data study and its analysis should be allowed in Indian Codes too.  Gust Factor method in IS 875 which is somewhat similar to analysis method in ASCE-07:2002 is yet to be developed fully as compared to ASCE code.  Wind Tunnel procedure allowed in case or American code. Indian codes should also contain wind tunnel procedure in case of designing tall buildings mostly in metro cities where tall building can be designed considering all factors which will reduce risk for buildings.  ASCE-07 consider 4 cases while IS875 consider only two cases to determine design wind pressure. Indian code should improve for determining wind load taking more cases, as more cases mean more precision and hence less risk.  American code is more effective for designing for wind loads as it gives less deformation as compared to Indian code. Less deformation means less chance for failure.
  • 48. 48 References 1. Council of Tall Building and Habitat (CTBUH) website. 2. Indian Standard Code:-Code of practice for design loads (other than earthquake) for buildings and structures- IS875:1987 – Part 3 3. Indian Standard Code Draft version- IS 875:2009 –Part 3 draft version with commentary. 4. American Code: Minimum Design Loads For Buildings and other structures. (ASCE-7:2002 version) 5. http://www.fluidstructures.com/html/vortex/phenomena.html