International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – Apr 2016
ISSN: 2395-1303 http://www.ijetjournal.org Page 156
66kV & 220kV Substation Protection From Lightning by Fixed
Angle, Rolling Sphere and Early Streamer Method
Pruthak C. Chauhan.1
, Rinkesh S. Kansara2
, Mukesh P. Patel 3
, Anil L. Parmar 4
, Swati
Pimplekar5
1,2,3,4
Department of Electrical Engineering, Shroff S.R. Rotary Institute of Chemical Technology, Vataria,
5
Department of Electrical Engineering, Takalkar Power Engineers and consultants Pvt. Ltd., Vadodara,
I INTRODUCTION
Direct stroke on the transmission line or the substation
will cause major damage to the substation equipment. The
characteristics of this will be depend on range to region.
According to IEEE the stroke happens in two stages, (i)
return stroke, (ii) ionization of air encompassing the center
and the advancement of stepped leaders. So, to overcome this
cause we have to provide protection. The protection is done
by providing lightning mast at different intervals &
connecting Earth wire tower to tower. The methods which are
explained here are Rolling sphere method by simple rod,
Fixed angle method and Early streamer method.
There are some methods for direct stroke lightning protection
on 66kV and 220kV substation .
1) Empirical design method
This method includes two methods.
i) Empirical curves
ii) fixed angles
Fixed angle method is widely used for 66kV voltage level
substation.
2) The electrogeometrical method (EGM)
This method incudes Rolling sphere method.
Meanwhile, for the EGM, the ‘Protection zone of a lightning
protection system may be defined as the area of space inside
which an termination provides protection against a direct
stroke by attracting the stroke to itself”.[2]
we will also apply Early streamer method.
II ROLLING SPHERE METHOD BY ROD
It is one type of EGM model method. This method
builds on basic principal and theories of Whitehead. An
imaginary sphere of radius S rolls over the surface of
substation which rolls up on the LM, LCLM, earth wire and
shield wire which provides lightning shielding.
Fig-1: protected area of shield wires at equal height
The equipment is below the curved surface of sphere
then said to be protected and the portion which remains
RESEARCH ARTICLE OPEN ACCESS
Abstract:
Lightning strokes are most effective in electrical engineering. Charge formation in cloud produces
the lightning stroke. Substation equipment and auxiliaries also can be get damaged by the lightning
strokes. This paper shows some methods to reduce the effect of lightning stroke on the substation. There
are conventional and non-conventional methods for this. This paper describes some of that methods
briefly.
Keywords –Direct stroke lightning protection, Rolling Sphere Method by simple rod, Fixed angle
method , Early streamer method.
International Journal of Engineering and
ISSN: 2395-1303
unprotected is remains below the curved surface. Twin moose
conductor is used over here.
Now we apply this method on substation having 220kV
voltage, calculation is shown below,
Calculation of one section is shown.
For finding the equivalent radius
Rcx ln{(2 x h )/ Rc} - (Vc / E0 ) = 0
Where,
h = height of tower from GL
Eo= Limiting corona
Vc = Rated lightening impulse withstand voltage
Gradient
By solving this equation
Rc = 0.121 m
In the case of twin conductor the radius is given by,
R0 = (r x l)0.5
So, R0 = 0.0235 m
Now the radius of corona is in case of twin conductor,
R'c = R0 + Rc
So, R'c= 0.145 m
The surge impedance if corona is ,
Zc = 60 x { ln (((2 x h ) / R'c) x ((2 x h ) / r ))}0.5
Where,
r = Radious of conductor (in m)
So, Zc= 238.168 m
Fig-2: principal of rolling sphere [1]
The allowable stroke current is
International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar –
http://www.ijetjournal.org
unprotected is remains below the curved surface. Twin moose
Now we apply this method on substation having 220kV
= Rated lightening impulse withstand voltage
In the case of twin conductor the radius is given by,
conductor,
0.5
Is = (2.2 x BIL )/ Zc
Where,
BIL = Rated lightening impulse withstand
voltage ( For 220kV BIL is 1050 kV/m & For
66kV BIL is 450 kV/m )
Is = 9.699 kA
Now, the allowable strike distance is….
S = 8 x k x Is
Where,
k = Strikes on shield wire (value for mast is 1.2 & for earthig
wire is 1)
S = 29.898 m
H = Height of equipment is
H = 12.495m
A = Height of object to be protected
A = 20.00m
D = Elevation difference between Height of equipment &
Object to be Protected
D = 7.500m
E = Elevation Difference between Origin of the rolling sphere
& equipment
E = 22.398m
L = Horizontal difference between Origin of the rolling sphere
& equipment
L = 19.804m
X = Maximum allowable Horizontal separation of the shield
wires ensuring protection of object at height A
X = 39.609m
Here the value of X has not to be more than the diameter the
imaginary sphere(S).
Same calculations can be done for the remaining sections of
the sub-station.
In this method of protection we have used earth wire
and 3No’s lightning masts. Under green curve the whole
portion is protected by the masts and earth wires.
– Apr 2016
Page 157
BIL = Rated lightening impulse withstand
voltage ( For 220kV BIL is 1050 kV/m & For
strike distance is….
k = Strikes on shield wire (value for mast is 1.2 & for earthig
Height of equipment &
E = Elevation Difference between Origin of the rolling sphere
L = Horizontal difference between Origin of the rolling sphere
ontal separation of the shield
wires ensuring protection of object at height A
Here the value of X has not to be more than the diameter the
Same calculations can be done for the remaining sections of
s method of protection we have used earth wire
and 3No’s lightning masts. Under green curve the whole
portion is protected by the masts and earth wires.
International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – Apr 2016
ISSN: 2395-1303 http://www.ijetjournal.org Page 158
Fig-3: protected layout of 220kV rolling sphere by simple rod
III FIXED ANGLE METHOD
This method comes in the empirical design method.
This method was mainly used by designers as a easy boundary
of protection against stroke.
The fixed-angle design method uses parallel angles
to determine the number, position, and height of shielding
wires or LM. Figure illustrates the method for shielding
wires.[1]
Fig-4: fixed angle method for shielding wire [1]
Area protected by fixed angle method is shown by cross lines.
The layout of 66kv substation is shown here in which
we used 1 Lightning Mast and earth wire tower on pick of
tower.
Fig-5: layout of 66kV substation
Now equations for solving this problem is shown here,
For earth wire , measure the height of tower (in m)
and the height of equipment (in m), then H the difference
between them (in m) is calculated for inner side and outer side
radius of protection is Rx..
To reduce shielding angles designers uses fixed angle
method as the structure height increases to maintain a low
failure rate.
For inner side the degree of protection is 45°(α) and for outer
side 60°(β). The equation is,
tanθ =
Fig-6: fixed angle method for masts [1]
For lightning mast the degree of protection is always 45°.
tan 45 =
So, the solution is above design is calculated and the protected
layout is,
Fig-7: protected layout of 66kV substation
Where the purple line shows the area protected by
this method. But the limitation of this method is that it can be
suitable only for 66kV or below 66kV substation above 66kv
it will not reliable so, by rolling sphere method we have
calculate the 220kv substation layout by rolling sphere method
by simple rod.
IV EARLY STREAMER METHOD
This is not method but it is one type of equipment
which is place over a simple lightning rod which is called as
early streamer emission air terminal (OPR).
The OPR efficiency (ΔT):
Lightning is one of the most spectacular
meteorological phenomena. Generated by the interaction of
clouds elements (water and ice), it can kill, injure and damage.
The unique efficiency of the OPR Early streamer emission is
International Journal of Engineering and
ISSN: 2395-1303
based on the difference (ΔT), measured in a laboratory, in
between the emission time of the OPR and the one from a
simple rod. The OPR ESE air terminal is composed of a
striking point connected to a down conductor to conduct the
lightning to the ground.
Complete autonomy:
During a storm the ambient electric field may rise
from 600 V to 10-20 kV/m. When the electric field reach this
level representing a minimum risk for a lightning, the OPR
begins to get activated and generates high voltage puls
helping to create and propagating an upward leader.
After a strike on the OPR, the lightning current is
driven to ground by the down conductor to the earth
termination system.
Fig 8-without using OPR
Fig-9: using OPR
Radius of protection:
The radius of protection (Rp) of the OPR is
calculated according to the NF C 17‑102 (edition 2011). It
depends on the OPR efficiency (ΔT) expressed in micro
seconds. The maximum value for ΔT is 60 μs. The risk
assessment shall be calculated according to the NF
IEC 62305-2 and will define the protection level (LPL I, II, III
or IV) which will be used in the determination of the OPR
radius of protection.
Now,
Rp(h) : Protection radius at a given height (h)
Rp(h) = √ 2rh - h2 + Δ(2r + Δ) (for h ≥ 5 m) For h < 5 m,
refer to the table below
h : Height of the OPR tip above the surface(s) to be protected
r(m) : Standardized striking distance
International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar –
http://www.ijetjournal.org
based on the difference (ΔT), measured in a laboratory, in
between the emission time of the OPR and the one from a
simple rod. The OPR ESE air terminal is composed of a
striking point connected to a down conductor to conduct the
During a storm the ambient electric field may rise
20 kV/m. When the electric field reach this
level representing a minimum risk for a lightning, the OPR
begins to get activated and generates high voltage pulses,
helping to create and propagating an upward leader.
After a strike on the OPR, the lightning current is
driven to ground by the down conductor to the earth
radius of protection (Rp) of the OPR is
102 (edition 2011). It
depends on the OPR efficiency (ΔT) expressed in micro-
seconds. The maximum value for ΔT is 60 μs. The risk
assessment shall be calculated according to the NF C 17‑102.
2 and will define the protection level (LPL I, II, III
or IV) which will be used in the determination of the OPR
For h < 5 m,
: Height of the OPR tip above the surface(s) to be protected
∆(m) = 106 .ΔT (OPR efficiency)
According to the customers demand this can be
designed but the cost of this equipment is too much high but
the surety of the protection is also too much high as the cost
and the plus point of this is the number of this will be so less
as compared to simple lightning rod.
TABLE -1 OPR radius Protection Table
Protection
level
I(r = 20m)
OPR 30 45
h(m) Radius of Protection Rp (m)
2 19 25
3 29 38
4 38 51
5 48 63
6 48 63
8 49 64
10 49 64
15 50 65
20 50 65
45 43 65
50 40 65
55 36 65
60 30 65
By this table first we have to choose
OPR then height of OPR and according to that we have to
choose OPR which will give the radius of protection by the
OPR over the substation.
Here, we have taken protection level I(r = 20m), OPR 60 and
Height of OPR is 20m.
So the radius of protection will be 80m. This same height can
also be calculated by the equation which is mentioned above.
V CONCLUSION
This paper study the DSLP scheme for 66 & 220 kV
substation.
Form we conclude as follows,
1) Fixed angle method is only suitable
substation; for above 66kV we have to apply EGM
method and early streamer method.
2) By applying advanced method of protection total cost
of substation will become less
ACKNOWLEDGEMENT
We gratefully acknowledge Miss Swati Pimplekar,
Takalkar Power Engineers and Consultants Pvt. Ltd,
Vadodara and Mr. Anil Parmar, assistant professor at SRICT,
– Apr 2016
Page 159
According to the customers demand this can be
pment is too much high but
the surety of the protection is also too much high as the cost
and the plus point of this is the number of this will be so less
1 OPR radius Protection Table
60
Radius of Protection Rp (m)
31
47
63
79
79
79
79
80
80
76
74
72
69
By this table first we have to choose protection level then
OPR then height of OPR and according to that we have to
choose OPR which will give the radius of protection by the
Here, we have taken protection level I(r = 20m), OPR 60 and
ius of protection will be 80m. This same height can
also be calculated by the equation which is mentioned above.
This paper study the DSLP scheme for 66 & 220 kV
Fixed angle method is only suitable for 66kV
substation; for above 66kV we have to apply EGM
method and early streamer method.
By applying advanced method of protection total cost
of substation will become less
We gratefully acknowledge Miss Swati Pimplekar,
Engineers and Consultants Pvt. Ltd,
Vadodara and Mr. Anil Parmar, assistant professor at SRICT,
International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – Apr 2016
ISSN: 2395-1303 http://www.ijetjournal.org Page 160
Ankleshwar for their comments and contribution & many of
which have helped us to improve knowledge and paper.
REFERENCES
[1] IEEE 998-2012 Guide for Direct Lightning
Stroke Shielding of Substations.
[2] Comparative Study on Substation Shielding Due
to Direct Lightning Strokes, By Ab Halim Abu
Bakar Date of publish – December 2013 Email:
a.halim@um.edu.my
[3] Lightning Protection Systems Design for
Substations by Using Masts and Matlab, By Le Viet
Dung and K. Petcharaks.
[4] Understanding direct lightning stroke shielding
of substations, By P. K. Sen.
[5] AIEE Committee Report, “A Method of
Estimating Lightning Performance of Transmission
Lines,” AIEE Transactions, vol. 69, no.2, pp. 1187–
1196, Jan. 1950.
[6] Anderson, J. G., “Monte Carlo Computer
Calculation of Transmission-Line Lightning
Performance,” AIEE Transactions, vol. 80, no. 3,
pp. 414–420, Aug. 1961.
[7] Anderson, R. B., and A. J. Eriksson, “Lightning
Parameters for Engineering Application,” Electra,
no. 69, pp. 65–102, Mar. 1980.
[8] Eriksson, A. J., “The Lightning Round Flash—
an Engineering Study,” PhD thesis, University of
Natal, Pretoria, South Africa, Dec. 1979.

More Related Content

What's hot

Conductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersConductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arresters
Gilberto Mejía
 
Earthing Arrangements
Earthing  ArrangementsEarthing  Arrangements
Earthing ArrangementsPaul Holden
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
johny renoald
 
study of lightning arrester
study of lightning arresterstudy of lightning arrester
study of lightning arrester
Malikasad thaheem
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
MuhammedArifTanoli
 
Bil and insulation coordination ppt
Bil and insulation coordination pptBil and insulation coordination ppt
Bil and insulation coordination ppt
BILAL ALAM
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
Jaydeep Chauhan
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection Devices
Jason Koffler
 
**Lightning Arrester Presentation**
**Lightning Arrester Presentation****Lightning Arrester Presentation**
**Lightning Arrester Presentation**SKPAMB
 
Surge Arresters construction and working
Surge Arresters construction and workingSurge Arresters construction and working
Surge Arresters construction and working
Muhammad Faisal Ikram
 
Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & Types
Power System Operation
 
Using High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash HazardsUsing High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash Hazards
michaeljmack
 
surge arrester
surge arrestersurge arrester
surge arrester
shubham kumar
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination design
Naresh Surisetti
 
Problems in overhead transmission line
Problems in overhead transmission lineProblems in overhead transmission line
Problems in overhead transmission line
Dr. Bibhu Prasad Ganthia
 
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Thorne & Derrick International
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
Dr. Rohit Babu
 
Lightning Arrestar
Lightning ArrestarLightning Arrestar
Lightning Arrestar
younistanzeela
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
Pratik Rasam
 

What's hot (20)

Conductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersConductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arresters
 
Earthing Arrangements
Earthing  ArrangementsEarthing  Arrangements
Earthing Arrangements
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
study of lightning arrester
study of lightning arresterstudy of lightning arrester
study of lightning arrester
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
Bil and insulation coordination ppt
Bil and insulation coordination pptBil and insulation coordination ppt
Bil and insulation coordination ppt
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection Devices
 
**Lightning Arrester Presentation**
**Lightning Arrester Presentation****Lightning Arrester Presentation**
**Lightning Arrester Presentation**
 
Surge Arresters construction and working
Surge Arresters construction and workingSurge Arresters construction and working
Surge Arresters construction and working
 
Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & Types
 
Lighting arrester
Lighting arresterLighting arrester
Lighting arrester
 
Using High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash HazardsUsing High Resistance Grounding to Mitigate Arc Flash Hazards
Using High Resistance Grounding to Mitigate Arc Flash Hazards
 
surge arrester
surge arrestersurge arrester
surge arrester
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination design
 
Problems in overhead transmission line
Problems in overhead transmission lineProblems in overhead transmission line
Problems in overhead transmission line
 
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
Wind Farm Earthing, Lightning & Overvoltage Protection - Wind Turbines Earthi...
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
Lightning Arrestar
Lightning ArrestarLightning Arrestar
Lightning Arrestar
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
 

Viewers also liked

Dr. Lightning's Guide to the Science of Lightning
Dr. Lightning's Guide to the Science of LightningDr. Lightning's Guide to the Science of Lightning
Dr. Lightning's Guide to the Science of Lightning
Laurie K. Blandford
 
Electrical injuries
Electrical injuriesElectrical injuries
Electrical injuries
Sudhir Dev
 
Energy crisis and conservation
Energy crisis and conservationEnergy crisis and conservation
Energy crisis and conservationKrunal Gaigole
 
Lightning protection
Lightning protectionLightning protection
Lightning protection
Vincent Wedelich, PE MBA
 
German CakePHP Meetup #3 - Berlin
German CakePHP Meetup #3 - BerlinGerman CakePHP Meetup #3 - Berlin
German CakePHP Meetup #3 - Berlin
Mark Scherer
 

Viewers also liked (7)

Cakephp
CakephpCakephp
Cakephp
 
Dr. Lightning's Guide to the Science of Lightning
Dr. Lightning's Guide to the Science of LightningDr. Lightning's Guide to the Science of Lightning
Dr. Lightning's Guide to the Science of Lightning
 
Electrical injuries
Electrical injuriesElectrical injuries
Electrical injuries
 
Energy crisis and conservation
Energy crisis and conservationEnergy crisis and conservation
Energy crisis and conservation
 
Lightning arresters
Lightning arrestersLightning arresters
Lightning arresters
 
Lightning protection
Lightning protectionLightning protection
Lightning protection
 
German CakePHP Meetup #3 - Berlin
German CakePHP Meetup #3 - BerlinGerman CakePHP Meetup #3 - Berlin
German CakePHP Meetup #3 - Berlin
 

Similar to [IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Patel , Anil L. Parmar , Swati Pimplekar

Ce31533536
Ce31533536Ce31533536
Ce31533536
IJERA Editor
 
Case Study - Lightning Protection
Case Study - Lightning ProtectionCase Study - Lightning Protection
Case Study - Lightning Protection
SuganthanSuga
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
Mohammad Ahmad
 
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
IJERA Editor
 
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  AntennaAnalysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
IJMER
 
S ag calc
S ag calcS ag calc
S ag calc
anurag pugalia
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
IJAPEJOURNAL
 
Schneider electric : Neutral Earthing
Schneider electric : Neutral EarthingSchneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
Eduardo Higino
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
IJERA Editor
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
IJERA Editor
 
Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.
Milton Sarker
 
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
IRJET Journal
 
Dq31551563
Dq31551563Dq31551563
Dq31551563IJMER
 
How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?
Fang Sam
 
IRJET- Design of Microstrip Patch Antenna for Smart Antenna Applications
IRJET-  	  Design of Microstrip Patch Antenna for Smart Antenna ApplicationsIRJET-  	  Design of Microstrip Patch Antenna for Smart Antenna Applications
IRJET- Design of Microstrip Patch Antenna for Smart Antenna Applications
IRJET Journal
 
1 txh000247c0202 opr_lightning_protection_systems
1 txh000247c0202 opr_lightning_protection_systems1 txh000247c0202 opr_lightning_protection_systems
1 txh000247c0202 opr_lightning_protection_systems
Tra Thanh
 
Microstrip_patch_antenna_design.ppt
Microstrip_patch_antenna_design.pptMicrostrip_patch_antenna_design.ppt
Microstrip_patch_antenna_design.ppt
PSOMESWARPATRO
 
H010526975
H010526975H010526975
H010526975
IOSR Journals
 

Similar to [IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Patel , Anil L. Parmar , Swati Pimplekar (20)

Ce31533536
Ce31533536Ce31533536
Ce31533536
 
Case Study - Lightning Protection
Case Study - Lightning ProtectionCase Study - Lightning Protection
Case Study - Lightning Protection
 
Arrester
ArresterArrester
Arrester
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
 
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...A Study on Protection of Cables by Solkor Differential Protection Relay with ...
A Study on Protection of Cables by Solkor Differential Protection Relay with ...
 
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  AntennaAnalysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
 
Hx2615541560
Hx2615541560Hx2615541560
Hx2615541560
 
S ag calc
S ag calcS ag calc
S ag calc
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Schneider electric : Neutral Earthing
Schneider electric : Neutral EarthingSchneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
 
Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.
 
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
 
Dq31551563
Dq31551563Dq31551563
Dq31551563
 
How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?
 
IRJET- Design of Microstrip Patch Antenna for Smart Antenna Applications
IRJET-  	  Design of Microstrip Patch Antenna for Smart Antenna ApplicationsIRJET-  	  Design of Microstrip Patch Antenna for Smart Antenna Applications
IRJET- Design of Microstrip Patch Antenna for Smart Antenna Applications
 
1 txh000247c0202 opr_lightning_protection_systems
1 txh000247c0202 opr_lightning_protection_systems1 txh000247c0202 opr_lightning_protection_systems
1 txh000247c0202 opr_lightning_protection_systems
 
Microstrip_patch_antenna_design.ppt
Microstrip_patch_antenna_design.pptMicrostrip_patch_antenna_design.ppt
Microstrip_patch_antenna_design.ppt
 
H010526975
H010526975H010526975
H010526975
 

More from IJET - International Journal of Engineering and Techniques

healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...
IJET - International Journal of Engineering and Techniques
 
verifiable and multi-keyword searchable attribute-based encryption scheme for...
verifiable and multi-keyword searchable attribute-based encryption scheme for...verifiable and multi-keyword searchable attribute-based encryption scheme for...
verifiable and multi-keyword searchable attribute-based encryption scheme for...
IJET - International Journal of Engineering and Techniques
 
Ijet v5 i6p16
Ijet v5 i6p16Ijet v5 i6p16
Ijet v5 i6p15
Ijet v5 i6p15Ijet v5 i6p15
Ijet v5 i6p14
Ijet v5 i6p14Ijet v5 i6p14
Ijet v5 i6p12
Ijet v5 i6p12Ijet v5 i6p12
Ijet v5 i6p11
Ijet v5 i6p11Ijet v5 i6p11
Ijet v5 i6p2
Ijet v5 i6p2Ijet v5 i6p2
IJET-V3I2P24
IJET-V3I2P24IJET-V3I2P24
IJET-V3I2P23
IJET-V3I2P23IJET-V3I2P23
IJET-V3I2P22
IJET-V3I2P22IJET-V3I2P22
IJET-V3I2P21
IJET-V3I2P21IJET-V3I2P21
IJET-V3I2P20
IJET-V3I2P20IJET-V3I2P20
IJET-V3I2P19
IJET-V3I2P19IJET-V3I2P19
IJET-V3I2P18
IJET-V3I2P18IJET-V3I2P18
IJET-V3I2P17
IJET-V3I2P17IJET-V3I2P17

More from IJET - International Journal of Engineering and Techniques (20)

healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...healthcare supervising system to monitor heart rate to diagonize and alert he...
healthcare supervising system to monitor heart rate to diagonize and alert he...
 
verifiable and multi-keyword searchable attribute-based encryption scheme for...
verifiable and multi-keyword searchable attribute-based encryption scheme for...verifiable and multi-keyword searchable attribute-based encryption scheme for...
verifiable and multi-keyword searchable attribute-based encryption scheme for...
 
Ijet v5 i6p18
Ijet v5 i6p18Ijet v5 i6p18
Ijet v5 i6p18
 
Ijet v5 i6p17
Ijet v5 i6p17Ijet v5 i6p17
Ijet v5 i6p17
 
Ijet v5 i6p16
Ijet v5 i6p16Ijet v5 i6p16
Ijet v5 i6p16
 
Ijet v5 i6p15
Ijet v5 i6p15Ijet v5 i6p15
Ijet v5 i6p15
 
Ijet v5 i6p14
Ijet v5 i6p14Ijet v5 i6p14
Ijet v5 i6p14
 
Ijet v5 i6p13
Ijet v5 i6p13Ijet v5 i6p13
Ijet v5 i6p13
 
Ijet v5 i6p12
Ijet v5 i6p12Ijet v5 i6p12
Ijet v5 i6p12
 
Ijet v5 i6p11
Ijet v5 i6p11Ijet v5 i6p11
Ijet v5 i6p11
 
Ijet v5 i6p10
Ijet v5 i6p10Ijet v5 i6p10
Ijet v5 i6p10
 
Ijet v5 i6p2
Ijet v5 i6p2Ijet v5 i6p2
Ijet v5 i6p2
 
IJET-V3I2P24
IJET-V3I2P24IJET-V3I2P24
IJET-V3I2P24
 
IJET-V3I2P23
IJET-V3I2P23IJET-V3I2P23
IJET-V3I2P23
 
IJET-V3I2P22
IJET-V3I2P22IJET-V3I2P22
IJET-V3I2P22
 
IJET-V3I2P21
IJET-V3I2P21IJET-V3I2P21
IJET-V3I2P21
 
IJET-V3I2P20
IJET-V3I2P20IJET-V3I2P20
IJET-V3I2P20
 
IJET-V3I2P19
IJET-V3I2P19IJET-V3I2P19
IJET-V3I2P19
 
IJET-V3I2P18
IJET-V3I2P18IJET-V3I2P18
IJET-V3I2P18
 
IJET-V3I2P17
IJET-V3I2P17IJET-V3I2P17
IJET-V3I2P17
 

Recently uploaded

Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
ydteq
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
Kerry Sado
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
Investor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptxInvestor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptx
AmarGB2
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
zwunae
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
Kamal Acharya
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
Jayaprasanna4
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
fxintegritypublishin
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
Osamah Alsalih
 
English lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdfEnglish lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdf
BrazilAccount1
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
ongomchris
 

Recently uploaded (20)

Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
Investor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptxInvestor-Presentation-Q1FY2024 investor presentation document.pptx
Investor-Presentation-Q1FY2024 investor presentation document.pptx
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
MCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdfMCQ Soil mechanics questions (Soil shear strength).pdf
MCQ Soil mechanics questions (Soil shear strength).pdf
 
English lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdfEnglish lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdf
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
 

[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Patel , Anil L. Parmar , Swati Pimplekar

  • 1. International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – Apr 2016 ISSN: 2395-1303 http://www.ijetjournal.org Page 156 66kV & 220kV Substation Protection From Lightning by Fixed Angle, Rolling Sphere and Early Streamer Method Pruthak C. Chauhan.1 , Rinkesh S. Kansara2 , Mukesh P. Patel 3 , Anil L. Parmar 4 , Swati Pimplekar5 1,2,3,4 Department of Electrical Engineering, Shroff S.R. Rotary Institute of Chemical Technology, Vataria, 5 Department of Electrical Engineering, Takalkar Power Engineers and consultants Pvt. Ltd., Vadodara, I INTRODUCTION Direct stroke on the transmission line or the substation will cause major damage to the substation equipment. The characteristics of this will be depend on range to region. According to IEEE the stroke happens in two stages, (i) return stroke, (ii) ionization of air encompassing the center and the advancement of stepped leaders. So, to overcome this cause we have to provide protection. The protection is done by providing lightning mast at different intervals & connecting Earth wire tower to tower. The methods which are explained here are Rolling sphere method by simple rod, Fixed angle method and Early streamer method. There are some methods for direct stroke lightning protection on 66kV and 220kV substation . 1) Empirical design method This method includes two methods. i) Empirical curves ii) fixed angles Fixed angle method is widely used for 66kV voltage level substation. 2) The electrogeometrical method (EGM) This method incudes Rolling sphere method. Meanwhile, for the EGM, the ‘Protection zone of a lightning protection system may be defined as the area of space inside which an termination provides protection against a direct stroke by attracting the stroke to itself”.[2] we will also apply Early streamer method. II ROLLING SPHERE METHOD BY ROD It is one type of EGM model method. This method builds on basic principal and theories of Whitehead. An imaginary sphere of radius S rolls over the surface of substation which rolls up on the LM, LCLM, earth wire and shield wire which provides lightning shielding. Fig-1: protected area of shield wires at equal height The equipment is below the curved surface of sphere then said to be protected and the portion which remains RESEARCH ARTICLE OPEN ACCESS Abstract: Lightning strokes are most effective in electrical engineering. Charge formation in cloud produces the lightning stroke. Substation equipment and auxiliaries also can be get damaged by the lightning strokes. This paper shows some methods to reduce the effect of lightning stroke on the substation. There are conventional and non-conventional methods for this. This paper describes some of that methods briefly. Keywords –Direct stroke lightning protection, Rolling Sphere Method by simple rod, Fixed angle method , Early streamer method.
  • 2. International Journal of Engineering and ISSN: 2395-1303 unprotected is remains below the curved surface. Twin moose conductor is used over here. Now we apply this method on substation having 220kV voltage, calculation is shown below, Calculation of one section is shown. For finding the equivalent radius Rcx ln{(2 x h )/ Rc} - (Vc / E0 ) = 0 Where, h = height of tower from GL Eo= Limiting corona Vc = Rated lightening impulse withstand voltage Gradient By solving this equation Rc = 0.121 m In the case of twin conductor the radius is given by, R0 = (r x l)0.5 So, R0 = 0.0235 m Now the radius of corona is in case of twin conductor, R'c = R0 + Rc So, R'c= 0.145 m The surge impedance if corona is , Zc = 60 x { ln (((2 x h ) / R'c) x ((2 x h ) / r ))}0.5 Where, r = Radious of conductor (in m) So, Zc= 238.168 m Fig-2: principal of rolling sphere [1] The allowable stroke current is International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – http://www.ijetjournal.org unprotected is remains below the curved surface. Twin moose Now we apply this method on substation having 220kV = Rated lightening impulse withstand voltage In the case of twin conductor the radius is given by, conductor, 0.5 Is = (2.2 x BIL )/ Zc Where, BIL = Rated lightening impulse withstand voltage ( For 220kV BIL is 1050 kV/m & For 66kV BIL is 450 kV/m ) Is = 9.699 kA Now, the allowable strike distance is…. S = 8 x k x Is Where, k = Strikes on shield wire (value for mast is 1.2 & for earthig wire is 1) S = 29.898 m H = Height of equipment is H = 12.495m A = Height of object to be protected A = 20.00m D = Elevation difference between Height of equipment & Object to be Protected D = 7.500m E = Elevation Difference between Origin of the rolling sphere & equipment E = 22.398m L = Horizontal difference between Origin of the rolling sphere & equipment L = 19.804m X = Maximum allowable Horizontal separation of the shield wires ensuring protection of object at height A X = 39.609m Here the value of X has not to be more than the diameter the imaginary sphere(S). Same calculations can be done for the remaining sections of the sub-station. In this method of protection we have used earth wire and 3No’s lightning masts. Under green curve the whole portion is protected by the masts and earth wires. – Apr 2016 Page 157 BIL = Rated lightening impulse withstand voltage ( For 220kV BIL is 1050 kV/m & For strike distance is…. k = Strikes on shield wire (value for mast is 1.2 & for earthig Height of equipment & E = Elevation Difference between Origin of the rolling sphere L = Horizontal difference between Origin of the rolling sphere ontal separation of the shield wires ensuring protection of object at height A Here the value of X has not to be more than the diameter the Same calculations can be done for the remaining sections of s method of protection we have used earth wire and 3No’s lightning masts. Under green curve the whole portion is protected by the masts and earth wires.
  • 3. International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – Apr 2016 ISSN: 2395-1303 http://www.ijetjournal.org Page 158 Fig-3: protected layout of 220kV rolling sphere by simple rod III FIXED ANGLE METHOD This method comes in the empirical design method. This method was mainly used by designers as a easy boundary of protection against stroke. The fixed-angle design method uses parallel angles to determine the number, position, and height of shielding wires or LM. Figure illustrates the method for shielding wires.[1] Fig-4: fixed angle method for shielding wire [1] Area protected by fixed angle method is shown by cross lines. The layout of 66kv substation is shown here in which we used 1 Lightning Mast and earth wire tower on pick of tower. Fig-5: layout of 66kV substation Now equations for solving this problem is shown here, For earth wire , measure the height of tower (in m) and the height of equipment (in m), then H the difference between them (in m) is calculated for inner side and outer side radius of protection is Rx.. To reduce shielding angles designers uses fixed angle method as the structure height increases to maintain a low failure rate. For inner side the degree of protection is 45°(α) and for outer side 60°(β). The equation is, tanθ = Fig-6: fixed angle method for masts [1] For lightning mast the degree of protection is always 45°. tan 45 = So, the solution is above design is calculated and the protected layout is, Fig-7: protected layout of 66kV substation Where the purple line shows the area protected by this method. But the limitation of this method is that it can be suitable only for 66kV or below 66kV substation above 66kv it will not reliable so, by rolling sphere method we have calculate the 220kv substation layout by rolling sphere method by simple rod. IV EARLY STREAMER METHOD This is not method but it is one type of equipment which is place over a simple lightning rod which is called as early streamer emission air terminal (OPR). The OPR efficiency (ΔT): Lightning is one of the most spectacular meteorological phenomena. Generated by the interaction of clouds elements (water and ice), it can kill, injure and damage. The unique efficiency of the OPR Early streamer emission is
  • 4. International Journal of Engineering and ISSN: 2395-1303 based on the difference (ΔT), measured in a laboratory, in between the emission time of the OPR and the one from a simple rod. The OPR ESE air terminal is composed of a striking point connected to a down conductor to conduct the lightning to the ground. Complete autonomy: During a storm the ambient electric field may rise from 600 V to 10-20 kV/m. When the electric field reach this level representing a minimum risk for a lightning, the OPR begins to get activated and generates high voltage puls helping to create and propagating an upward leader. After a strike on the OPR, the lightning current is driven to ground by the down conductor to the earth termination system. Fig 8-without using OPR Fig-9: using OPR Radius of protection: The radius of protection (Rp) of the OPR is calculated according to the NF C 17‑102 (edition 2011). It depends on the OPR efficiency (ΔT) expressed in micro seconds. The maximum value for ΔT is 60 μs. The risk assessment shall be calculated according to the NF IEC 62305-2 and will define the protection level (LPL I, II, III or IV) which will be used in the determination of the OPR radius of protection. Now, Rp(h) : Protection radius at a given height (h) Rp(h) = √ 2rh - h2 + Δ(2r + Δ) (for h ≥ 5 m) For h < 5 m, refer to the table below h : Height of the OPR tip above the surface(s) to be protected r(m) : Standardized striking distance International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – http://www.ijetjournal.org based on the difference (ΔT), measured in a laboratory, in between the emission time of the OPR and the one from a simple rod. The OPR ESE air terminal is composed of a striking point connected to a down conductor to conduct the During a storm the ambient electric field may rise 20 kV/m. When the electric field reach this level representing a minimum risk for a lightning, the OPR begins to get activated and generates high voltage pulses, helping to create and propagating an upward leader. After a strike on the OPR, the lightning current is driven to ground by the down conductor to the earth radius of protection (Rp) of the OPR is 102 (edition 2011). It depends on the OPR efficiency (ΔT) expressed in micro- seconds. The maximum value for ΔT is 60 μs. The risk assessment shall be calculated according to the NF C 17‑102. 2 and will define the protection level (LPL I, II, III or IV) which will be used in the determination of the OPR For h < 5 m, : Height of the OPR tip above the surface(s) to be protected ∆(m) = 106 .ΔT (OPR efficiency) According to the customers demand this can be designed but the cost of this equipment is too much high but the surety of the protection is also too much high as the cost and the plus point of this is the number of this will be so less as compared to simple lightning rod. TABLE -1 OPR radius Protection Table Protection level I(r = 20m) OPR 30 45 h(m) Radius of Protection Rp (m) 2 19 25 3 29 38 4 38 51 5 48 63 6 48 63 8 49 64 10 49 64 15 50 65 20 50 65 45 43 65 50 40 65 55 36 65 60 30 65 By this table first we have to choose OPR then height of OPR and according to that we have to choose OPR which will give the radius of protection by the OPR over the substation. Here, we have taken protection level I(r = 20m), OPR 60 and Height of OPR is 20m. So the radius of protection will be 80m. This same height can also be calculated by the equation which is mentioned above. V CONCLUSION This paper study the DSLP scheme for 66 & 220 kV substation. Form we conclude as follows, 1) Fixed angle method is only suitable substation; for above 66kV we have to apply EGM method and early streamer method. 2) By applying advanced method of protection total cost of substation will become less ACKNOWLEDGEMENT We gratefully acknowledge Miss Swati Pimplekar, Takalkar Power Engineers and Consultants Pvt. Ltd, Vadodara and Mr. Anil Parmar, assistant professor at SRICT, – Apr 2016 Page 159 According to the customers demand this can be pment is too much high but the surety of the protection is also too much high as the cost and the plus point of this is the number of this will be so less 1 OPR radius Protection Table 60 Radius of Protection Rp (m) 31 47 63 79 79 79 79 80 80 76 74 72 69 By this table first we have to choose protection level then OPR then height of OPR and according to that we have to choose OPR which will give the radius of protection by the Here, we have taken protection level I(r = 20m), OPR 60 and ius of protection will be 80m. This same height can also be calculated by the equation which is mentioned above. This paper study the DSLP scheme for 66 & 220 kV Fixed angle method is only suitable for 66kV substation; for above 66kV we have to apply EGM method and early streamer method. By applying advanced method of protection total cost of substation will become less We gratefully acknowledge Miss Swati Pimplekar, Engineers and Consultants Pvt. Ltd, Vadodara and Mr. Anil Parmar, assistant professor at SRICT,
  • 5. International Journal of Engineering and Techniques - Volume 2 Issue 2, Mar – Apr 2016 ISSN: 2395-1303 http://www.ijetjournal.org Page 160 Ankleshwar for their comments and contribution & many of which have helped us to improve knowledge and paper. REFERENCES [1] IEEE 998-2012 Guide for Direct Lightning Stroke Shielding of Substations. [2] Comparative Study on Substation Shielding Due to Direct Lightning Strokes, By Ab Halim Abu Bakar Date of publish – December 2013 Email: a.halim@um.edu.my [3] Lightning Protection Systems Design for Substations by Using Masts and Matlab, By Le Viet Dung and K. Petcharaks. [4] Understanding direct lightning stroke shielding of substations, By P. K. Sen. [5] AIEE Committee Report, “A Method of Estimating Lightning Performance of Transmission Lines,” AIEE Transactions, vol. 69, no.2, pp. 1187– 1196, Jan. 1950. [6] Anderson, J. G., “Monte Carlo Computer Calculation of Transmission-Line Lightning Performance,” AIEE Transactions, vol. 80, no. 3, pp. 414–420, Aug. 1961. [7] Anderson, R. B., and A. J. Eriksson, “Lightning Parameters for Engineering Application,” Electra, no. 69, pp. 65–102, Mar. 1980. [8] Eriksson, A. J., “The Lightning Round Flash— an Engineering Study,” PhD thesis, University of Natal, Pretoria, South Africa, Dec. 1979.