HV electrical networks can be earthed in different ways, each with advantages and disadvantages. This document analyzes the constraints imposed by overvoltages, network characteristics, and equipment requirements to determine the suitable earthing method. Different earthing options are described such as direct earthing, earthing through a reactor, and earthing through a resistor. Fault currents are calculated using a simplified method to determine protection settings and ensure selectivity.
Transformer Diagnostics | Sweep Frequency Response AnalysisHamedPasha1
Proper commissioning and periodic testing of high voltage equipment is vital to the longevity of your valuable assets. Research shows that improper commissioning along with “set-and-forget” mentality has been the leading causes of premature failures.
Sweep frequency response analysis (SFRA) is one of the most powerful diagnostic tools for assessing mechanical damage to a transformer winding. Analysis of the results, which are in the form of frequency response traces can, however, be daunting to new users.
Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System
Power System protection and Metering,Types of Faults and effects,Symmetrical faults,Unsymmetrical faults,Fault Statics,Components of power System protection,Relay,Classification of Relay,Induction relay,thermal relay,Static Relay,Numerical Relay
Transformer Diagnostics | Sweep Frequency Response AnalysisHamedPasha1
Proper commissioning and periodic testing of high voltage equipment is vital to the longevity of your valuable assets. Research shows that improper commissioning along with “set-and-forget” mentality has been the leading causes of premature failures.
Sweep frequency response analysis (SFRA) is one of the most powerful diagnostic tools for assessing mechanical damage to a transformer winding. Analysis of the results, which are in the form of frequency response traces can, however, be daunting to new users.
Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System Staggering in Power System
Power System protection and Metering,Types of Faults and effects,Symmetrical faults,Unsymmetrical faults,Fault Statics,Components of power System protection,Relay,Classification of Relay,Induction relay,thermal relay,Static Relay,Numerical Relay
Earthing systems: fundamentals of calculation and designLeonardo ENERGY
This application note discusses the principles of earthing electrode design with particular emphasis on earth potential distribution of various electrode geometries.
The electrical properties of the ground and variations according to type and moisture content are discussed. The equation for calculation of the earthing resistance and potential distribution for an idealized hemispherical earth electrode is derived. The concepts of step and touch voltages are discussed and the effect of earthing electrode geometry shown.
The concepts developed in this application note are the basis for the practical guidance given in Earthing systems: basic constructional aspects.
Tutorial on Distance and Over Current ProtectionSARAVANAN A
Contents
• Protection Philosophy of ERPC
• Computation of Distance Relay Setting
• System Study to Understand Distance Relay
Behaviour
• DOC and DEF for EHV system
A fuse is a short piece of metal, inserted in the circuit, which melts when excessive current flows through it and thus breaks the circuit. The fuse element is generally made of materials having low melting point, high conductivity and least deterioration due to oxidation e.g., silver, copper etc. It is inserted in series with the circuit to be protected. Under normal operating conditions, the fuse element is at a temperature below its melting point. Therefore, it carries the normal current without overheating. However, when a short-circuit or overload occurs, the current through the fuse increases beyond its rated value. This raises the temperature and fuse element melts (or blows out), disconnecting the circuit protected by it. In this way, a fuse protects the machines and equipment from damage due to excessive currents.
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
Testing and condition monitoring of substation equipments,Transformer specifications,Monitoring of Transformer,On-load Tap changer,Overhauling,Tan delta and capacitance,Thermal imaging,Sweep frequency response analysis,Oil analysis of Switchgear elements containing oil,tests on insulating oil,Breaker monitoring,Condition monitoring of CT,Condition monitoring of CVT,Surge Arresters,Condition monitoring of relays.
Earthing systems: fundamentals of calculation and designLeonardo ENERGY
This application note discusses the principles of earthing electrode design with particular emphasis on earth potential distribution of various electrode geometries.
The electrical properties of the ground and variations according to type and moisture content are discussed. The equation for calculation of the earthing resistance and potential distribution for an idealized hemispherical earth electrode is derived. The concepts of step and touch voltages are discussed and the effect of earthing electrode geometry shown.
The concepts developed in this application note are the basis for the practical guidance given in Earthing systems: basic constructional aspects.
Tutorial on Distance and Over Current ProtectionSARAVANAN A
Contents
• Protection Philosophy of ERPC
• Computation of Distance Relay Setting
• System Study to Understand Distance Relay
Behaviour
• DOC and DEF for EHV system
A fuse is a short piece of metal, inserted in the circuit, which melts when excessive current flows through it and thus breaks the circuit. The fuse element is generally made of materials having low melting point, high conductivity and least deterioration due to oxidation e.g., silver, copper etc. It is inserted in series with the circuit to be protected. Under normal operating conditions, the fuse element is at a temperature below its melting point. Therefore, it carries the normal current without overheating. However, when a short-circuit or overload occurs, the current through the fuse increases beyond its rated value. This raises the temperature and fuse element melts (or blows out), disconnecting the circuit protected by it. In this way, a fuse protects the machines and equipment from damage due to excessive currents.
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
Testing and condition monitoring of substation equipments,Transformer specifications,Monitoring of Transformer,On-load Tap changer,Overhauling,Tan delta and capacitance,Thermal imaging,Sweep frequency response analysis,Oil analysis of Switchgear elements containing oil,tests on insulating oil,Breaker monitoring,Condition monitoring of CT,Condition monitoring of CVT,Surge Arresters,Condition monitoring of relays.
The purpose of this IEEE 1692 Abstract is to familiarize the reader with the faults that are accountable for most of the
unexplained lightning related damage, and explain the advantages of blocking technologies that can effectively isolate
and protect communications and other equipment.
This presentation represents Power system Protection & Transient Stability introduction.
Protection systems must be designed with both primary protection and backup protection in case primary protection devices fail
There are several common protection schemes; multiple overlapping schemes are usually used
To avoid inadvertent tripping for faults on other transmission lines, impedance relays usually have several zones of protectionIn order to study the transient response of a power system we need to develop models for the generator valid during the transient time frame of several seconds following a system disturbance
Review of Reduction of Leakage Current in Cascaded Multilevel InverterIJRST Journal
Multilevel inverters are a source of high power, often used in industrial applications and can use either sine or modified sine waves. A multilevel inverter uses a series of semiconductor power converters (usually two to three) thus generating higher voltage. Reverse leakage current in a semiconductor device is the current from that semiconductor device when the device is reverse biased. In earlier method transformer is used for generating multilevel output and grid synchronization. Transformer increases the leakage current. Now transformerless method and sine modulation techniques are presented to reduce the leakage current.
lightning stroke. Substation equipment and auxiliaries also can be get damaged by the lightning
strokes. This paper shows some methods to reduce the effect of lightning stroke on the substation. There
are conventional and non-conventional methods for this. This paper describes some of that methods
briefly.
Successful operation of entire power system depends to a considerable extent on efficient and satisfactory performance of substations. Hence substations in general can be considered as heart of overall power system. In any substation, a well-designed grounding plays an important role. Since absence of safe and effective grounding system can result in mal-operation or non-operation of control and protective devices, grounding system design deserves considerable attention for all the substations. There are two primary functions of a safe earthing system. Firstly, ensure that a person who is in the vicinity of earthed facilities during a fault is not exposed to the possibility of a fatal electrical shock. Secondly, provide a low impedance path to earth for currents occurring under normal and fault conditions.The earthing conductors, composing the grid and connections to all equipment and structures, must possess sufficient thermal capacity to pass the highest fault current for the required time
Explore the innovative world of trenchless pipe repair with our comprehensive guide, "The Benefits and Techniques of Trenchless Pipe Repair." This document delves into the modern methods of repairing underground pipes without the need for extensive excavation, highlighting the numerous advantages and the latest techniques used in the industry.
Learn about the cost savings, reduced environmental impact, and minimal disruption associated with trenchless technology. Discover detailed explanations of popular techniques such as pipe bursting, cured-in-place pipe (CIPP) lining, and directional drilling. Understand how these methods can be applied to various types of infrastructure, from residential plumbing to large-scale municipal systems.
Ideal for homeowners, contractors, engineers, and anyone interested in modern plumbing solutions, this guide provides valuable insights into why trenchless pipe repair is becoming the preferred choice for pipe rehabilitation. Stay informed about the latest advancements and best practices in the field.
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
Vaccine management system project report documentation..pdfKamal Acharya
The Division of Vaccine and Immunization is facing increasing difficulty monitoring vaccines and other commodities distribution once they have been distributed from the national stores. With the introduction of new vaccines, more challenges have been anticipated with this additions posing serious threat to the already over strained vaccine supply chain system in Kenya.
Democratizing Fuzzing at Scale by Abhishek Aryaabh.arya
Presented at NUS: Fuzzing and Software Security Summer School 2024
This keynote talks about the democratization of fuzzing at scale, highlighting the collaboration between open source communities, academia, and industry to advance the field of fuzzing. It delves into the history of fuzzing, the development of scalable fuzzing platforms, and the empowerment of community-driven research. The talk will further discuss recent advancements leveraging AI/ML and offer insights into the future evolution of the fuzzing landscape.
Saudi Arabia stands as a titan in the global energy landscape, renowned for its abundant oil and gas resources. It's the largest exporter of petroleum and holds some of the world's most significant reserves. Let's delve into the top 10 oil and gas projects shaping Saudi Arabia's energy future in 2024.
Welcome to WIPAC Monthly the magazine brought to you by the LinkedIn Group Water Industry Process Automation & Control.
In this month's edition, along with this month's industry news to celebrate the 13 years since the group was created we have articles including
A case study of the used of Advanced Process Control at the Wastewater Treatment works at Lleida in Spain
A look back on an article on smart wastewater networks in order to see how the industry has measured up in the interim around the adoption of Digital Transformation in the Water Industry.
About
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
Technical Specifications
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
Key Features
Indigenized remote control interface card suitable for MAFI system CCR equipment. Compatible for IDM8000 CCR. Backplane mounted serial and TCP/Ethernet communication module for CCR remote access. IDM 8000 CCR remote control on serial and TCP protocol.
• Remote control: Parallel or serial interface
• Compatible with MAFI CCR system
• Copatiable with IDM8000 CCR
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
Application
• Remote control: Parallel or serial interface.
• Compatible with MAFI CCR system.
• Compatible with IDM8000 CCR.
• Compatible with Backplane mount serial communication.
• Compatible with commercial and Defence aviation CCR system.
• Remote control system for accessing CCR and allied system over serial or TCP.
• Indigenized local Support/presence in India.
• Easy in configuration using DIP switches.
1. n°62
Neutral earthing in
an industrial HV
network
photographie
François Sautriau
Having graduated from the Ecole
Supérieure d'Electricité in 1968, he
joined Merlin Gerin in 1970. After
working on the design of networks
and protective devices, he was head
of the design office for industrial
projects and then for naval
equipment projects.
He is now, consultant in the
Marketing Division of the Protection
and Control Department
E/CT 62 up dated April 1996
3. Merlin Gerin Technical Specification n° 62 / p.3
neutral earthing in an industrial HV network
contents
1. Introduction p. 4
2. Earthing Direct earthing p. 4
Earthing through a reactor p. 4
Earthing through a resistor p. 4
3. Requirements imposed by Earthing through a current p. 5
overvoltages limiting reactor
Earthing through a resistor p. 4
4. Requirements imposed by networks p. 5
5. Requirements imposed by receivers p. 6
6. Calculating fault currents p. 6
7. Earth protection mode Earth protection adjustment p. 7
Earthing with accessible neutral p. 8
Earthing with an artificial neutral p. 8
Appendix 1: Comments on determining p. 10
network capacitance values
Appendix: Bibliography p. 11
HV electrical networks can be earthed
in different ways. This document
analyzes the constraints imposed by
the different parameters of the
installation (overvoltages, network,
receivers) and calculates the fault
currents.
Different protection modes are
described along with the settings and
adjustments suggested according to
the requirements.
4. Merlin Gerin Technical Specification n° 62 / p.4
1. introduction
[1] See bibliography
When designing an industrial HV
network, a suitable neutral earth
arrangement must be selected: the
neutral can either be insulated, or it can
be connected to earth. The use of an
insulated neutral in an HV network has
the advantage of ensuring operational
continuity since it does not trip on the
first fault, however the network
capacitance must be such that an earth
fault current is not likely to endanger
personnel or damage equipment.
On the other hand, an insulated neutral
2. earthing
neutral generally implies mandatory
tripping on the first fault, however:
s it reduces overvoltages,
s it provides a simple, reliable,
selective means of protection,
s it allows the use of equipment, and in
particular cables, with lower insulation
levels than for an insulated neutral.
implies the following:
s the risk of high overvoltages likely to
favourize multiple faults,
s the use of superinsulated equipment,
s compulsory monitoring of the
insulation,
s protection against overvoltages,
which will become compulsory in the
near future,
s the need for complex, selective
protection against earth faults which
cannot usually be ensured by simple
current-measuring relays. An earthed
earthing through a resistor
This is often the most satisfactory
solution.
A study is necessary to choose
between these two earthing, (through a
reactor or through a resistor) :
accurate determining of these earthing
modes depends on the voltage level,
the size of the network and the type of
receivers.
Depending on the earthing mode, a
criterion then determines a maximum
impedance value corresponding to the
overvoltage problem.
Next, it is necessary to check its
compatibility with the requirements of
the network and the receivers.
However, in the event of an earth fault,
the current is not limited, damage and
interference occur and there is
considerable danger for the personnel
during the time the fault persists.
This solution is not used for HV
distribution.
earthing through a reactor
Tuned reactor (Petersen coil)
This solution is sometimes used for
public HV networks. It is rarely used for
industrial distribution.
Protective relays sensitive to the active
component of the residual current must
be used to obtain selectivity.
Current limiting reactor
This solution can result in serious
overvoltages, as demonstrated by Le
Verre (the Research and Development
division of the E.D.F.) [1]. It can be
used only where there are low limiting
impedances.
The purpose of this study is not to
compare the different neutral earth
arrangements, but rather, once the
neutral earth solution has been
adopted, to determine the earthing
mode by finding a compromise
between three often contradictory
requirements:
s to sufficiently damp overvoltages,
s to limit damage and disturbances
caused by an earth fault,
s to provide simple, selective protective
devices.
Earthing can be of different types:
s direct (without impedance-dependent
current limiting),
s through a reactor,
s through a resistor.
direct earthing
This type of earthing is the most
efficient in limiting overvoltages;
protection selectivity presents no
difficulties.
5. Merlin Gerin Technical Specification n° 62 / p.5
3. requirements imposed by overvoltages
4. requirements imposed by networks
its path and in particular to the cable
shields. The maximum current
withstood by the cable shields may be
specified by the constructors. As a
general rule, the value used is between
500 and 3 000 A for 1 second.
The above criterion is used to define
the lower limit of the phase to earth
fault current.
To determine the upper limit, it is
necessary to check that the fault
current does not cause damage along
fig. 1 : a zigzag or neutral point coil provides
an earth fault current limiting reactor.
current IC in the event of an earth fault.
Hence the relation IL ≥ 2 IC.
Determination of the cable capacitance
values depends on their design (see
appendix for this calculation).
earthing through a current
limiting reactor
(see fig. 1)
The study of overvoltages that occur
when short-circuits are eliminated from
networks with the neutral earthed
through a reactor gives the following
results:
s let, I0ω be the earth fault current
limiting reactance,
s and Lω the network three-phase
short-circuit reactance.
The neutral-to-earth overvoltage
occurring when short-circuits are
eliminated is:
∆V
V
=
1
2
I0
L
for a radial field cable
network,
∆V
V
=
1
2
I0
L
for all other cases.
In practise, the earth fault current is
limited to at most 10 % of the three-
phase short-circuit current, as applied
by the EDF to its HV power distribution
network.
s
U
3 r
is the value of the earth fault
current IL in the earthing connection,
s 3 C ω
U
3
is the network capacitive
earthing through a resistor
As recommended by EDF for
hydroelectric power networks. The
resistance value r is détermined in
order to obtain a total active power
loss :
U
2
3 r
equal to or greater than the
capacitive power 2 C ω U
2
in the event
of a phase-earth fault, i.e.:
U
2
3 r
≥ 2 C ω U
2
.
When dividing by
U
3
, this become
U
3 r
≥ 2 . 3 C ω
U
3
where:
6. Merlin Gerin Technical Specification n° 62 / p.6
5. requirements imposed by receivers
between 3 kV and 15 kV, most
frequently 5.5 kV in France; the earth
fault current should not exceed 20 A in
order to avoid damage to the steel
plating of the machines, for if reworking
a winding is a regular repair, repairing a
machine when the metal plating is
damaged is much more time
consuming and more costly.
6. calculating fault currents
The currents in the different circuits are
easily calculated using a simple
approximative method.
This consists in ignoring the short-
circuit impedance of the source and the
coupled impedances with respect to the
neutral earth impedance and the
network capacitances. In other words,
we consider that earth fault currents are
much lower than three-phase short-
circuit currents (see fig. 2).
To calculate the neutral-to-earth
potential, the sum of the currents
flowing to earth is considered to be
zero (see diagram).
IN + IrD + Σ IrS = 0
0 = g VN + [G + jω C] (VN + E)
+ jωC (VN + a2
E) + jωC (VN + aE)
0 = VN [g + G + 3jωC] + GE
+ jω CE (1 + a2
+ a)
Since 1 + a
2
+ a = 0
This gives:
VN =
− GE
g + G + 3j ω C
where VN =
− zE
z + Z + 3 j ω C z Z
fig. 2: Earth fault current calculation parameters.
In HV networks, receivers are
transformers which have no particular
requirements as concerns the neutral
earthing in a power supply network.
However, industrial HV networks can
supply rotating machines with voltages
z =
1
g
Z=
1
G
Neutral earth impedance
Phase to earth fault impedance
CD Phase to earth capacitanc e of the faulty outgoing
feeder
CS Phase to earth capacitance of a sound outgoing
feeder
C = Σ CS Total phase to earth capacitance of the network
E Network phase voltage
VN Neutral point to earth potential
IN Neutral to earth current
ID Fault current
IrD Residual current of the faulty outgoing feeder
IrS Residual current of a sound outgoing feeder
EVN
3
2
1
g =
1
z
IN
G =
1
Z CD
I r D I r S
CS
ID
aE
a E
2
7. Merlin Gerin Technical Specification n° 62 / p.7
In the event of a short-circuit Z = 0, the
above formulae become:
s
s
s
s
s
s
Since we know VN, the different
currents (IN neutral to earth current, ID
fault current, IrD and IrS residual currents
in outgoing feeders) are calculated as
shown below:
s
s
I N =
−E
z
7. earth protection mode
The neutral earthing impedance affects
the required method of protection
against phase to earth faults.
As a general rule, the higher the fault
currents, the easier they are to detect;
the lower they are, the harder they are
to detect .
Moreover, it is advisable, even
essential, to ensure protection not at
one single point, but in all branches of
the network, since the relays operate
selectively.
Phase to earth protection is provided by
overcurrent relays supplied by the earth
current.
This current can be measured as
follows:
s either by a core balance transformer
around the three phase conductors and
which directly detects the sum of their
currents (zero if no earth fault) ;
s or by three current transformers the
secondary windings of which are
connected to form a neutral conductor
through which the sum of the three
currents flows.
The core balance transformer solution
is the most accurate, however it can
only be installed on cables, not on
busbars or overhead lines. The
3 current transformers solution is often
used, in particular when these
3 transformers are already required for
another application. But the
measurement obtained is degraded by
the inaccuracies of all three
transformers, in particular in the event
of transient overcurrents when the
transformers become saturated.
earth protection setting
This must be adjusted according to the
measurement accuracy. It must ensure
maximum protection and authorize
selectivity.
If the measurement is carried out using
the sum of the secondary currents of
the three transformers, it will be
degraded by the dispersion of the
transformers. In particular, a residual
current is measured if there is no earth
fault when the transformers become
saturated.
Saturation is caused by excessive
amplitude of the phase current, but
more specifically by the DC component
induced in a short-circuit or unbalanced
inrush current.
Note that, in transient conditions, the
DC component can induce saturation of
the transformers even though the peak
value of the transient current is around
10 times less than the saturation value
for a steady-state balanced current. An
earth protection device supplied by
3 transformers must therefore include a
time delay in order to avoid spurious
triggering resulting from transients. The
current setting must not be lower than
6 % of the transformer rating at best, or
15 or 20 % of the transformer ratings in
the most unfavourable cases.
Moreover, if an earth fault occurs in a
star winding near a neutral point, the
maximum fault current is only a small
part of the maximum fault current which
is limited by the neutral earth
impedance. For this reason, the current
setting is usually 20% of the maximum
current limited by the neutral earth in
order to protect 80% of the windings.
But, as the calculation shows, in the
event of a fault, a residual capacitive
current flows through the sound parts of
the network. So, to prevent the
protective device of a sound line from
tripping spuriously, the threshold must
be set to 30% higher than the
capacitive current flowing through this
sound line when a phase to earth short-
circuit affects the network.
Moreover, we must take into account
the possible presence of voltage
harmonics likely to produce currents
IrD = ID + 3jωC D VN
=
g + 3 jω C − CD( )
g+G+3jωC
GE
=
1+ 3jω C − CD( )z
Z + z + 3jωCzZ
E
IrD =
1
z
+ 3jω C − CD( )
E
ID =
1
z
+3jωC
E
IrS = − 3jω CS E
IN = gVN
−gGE
g + G + 3jωC
=
−E
Z +z + 3jωCzZ
ID = G VN +E( )=
g + 3jωC
g + G + 3jωC
GE
1+ 3jωCz
Z + z + 3jωCzZ
IrS = 3jωC S VN
=
− 3jωC S
g + G + 3jωC
GE
=
1− 3jωC S z
Z +z + 3jωCzZ
E
VN = − E
8. Merlin Gerin Technical Specification n° 62 / p.8
which increase as the order of the
harmonics increases. Note that 3rd
harmonics and multiples of 3 exist even
in steady-state conditions. Finally, the
neutral earth impedance characteristics
must be coordinated with the protective
devices so that this impedance itself is
not degraded by the fault current before
it is eliminated.
Note: that this concerns circuit
protection and not personnel protection.
Conclusion: when the earthed neutral
solution is selected for a medium
voltage network, it is advisable to use
earthing through a resistor rather than
other systems.
Calculating r and IL
This resistance r and the maximum
current IL =
U
3 r
are determined
taking the following requirements into
account:
s the current IL must be greater (or
equal) to twice the network capacitive
current in the event of an earth fault
IL ≥ 2 LC in order to limit overvoltages,
s the current IL must be less than the
maximum overcurrent that can be
withstood by the cable shields, normally
between 500 and 3 000 A, depending
on the cable cross section,
s in a network containing HV motors, it
is preferable to respect the relation:
5 A ≤ IL ≤ 20 A but, if this is
incompatible with the first condition, IL
can be up to 50 A,
s in order to ensure correct protection
of receivers, the Ir threshold settings
should not exceed 0,2 IL, i.e. Ir ≤ 0,2 IL,
s in order to ensure selectivity with
regard to sound connections, the
relation Ir ≥ 1,3 IC, must be respected,
where IC is the capacitive current of the
line when a phase to earth fault occurs,
s if the earth current is measured by
3 transformers of rating In , then Ir must
be ≥ 0,06 In,
s the thermal withstand of resistor r
must allow for current IL to flow during
the maximum fault clearing time
required (1 to 1.5 s) or, conversely, the
earth fault must be cleared sufficiently
rapidly to avoid damaging the resistor.
earthing with accessible
neutral
The resistor is connected to the neutral
output terminal and to the earthing
system, either directly, or through a
single-phase transformer the secondary
winding of which is loaded by an
equivalent resistance, as is used in
networks supplied through a
transformer which has a star-connected
secondary winding with accesible
neutral and for AC generators with
accessible neutral (see fig. 3).
If the network is supplied through
several transformers or AC generators,
it is advisable to have one single
neutral earth connection to prevent the
maximum earth fault current from
varying with the number of sources in
service.
a) b)
R r
fig. 3: neutral earthing at the secondary
winding of a star-coupled transformer,
through a resistor either connected directly
(a) or connected through a single-phase
transformer (b).
earthing with an artificial
neutral
If the neutral of the source is
inaccessible (as for delta-connected
windings), or if there are several
parallel-connected sources, earthing
can be ensured by an artificial neutral
(see figs. 4 and 5) (or earthing
transformer)
fig. 4: earthing a network neutral by means
of a star-delta transformer associated to:
a) a resistor connected to the HV side; in
this case the transformer secondary winding
can supply the auxiliaries;
b) a resistor series-connected to the
secondary winding.
r
b)
I ∆
R
a)
I ∆
9. Merlin Gerin Technical Specification n° 62 / p.9
Several solutions are possible:
s a star/delta transformer with a
resistor;
s a zigzag coil (see figs. 1 and 6): this
is used in cases where the maximum
earth fault current is limited to values
over 100 A;
s or, a special transformer, since to set
up an artificial neutral it may be more
economical to use the transformer
which supplies the substation LV
auxiliaries (see figs. 7 and 8).
The resulting impedance :
ro + jIoω appears as a resistance
if ro ≥ 2Ioω,
with ro and Io referenced to the same
voltage.
r
I ∆
fig. 7: neutral earthing by means of a
double-star transformer with compensating
delta windings around a resistor.
fig. 8: neutral earthing by means of a zigzag
transformer.
fig. 5: special transformer for neutral earting
R
I ∆
fig. 6: neutral earthing by means of a zigzag
coil.
R
I ∆
10. Merlin Gerin Technical Specification n° 62 / p.10
appendix 1:how to determine the capacitance values of a network
The capacitance of the cables depends
on their design:
s single-pole cable
The conductor is surrounded by a
shield and the capacitance C is that
measured between the conductor and
the earthed shield.
s three-pole radial field cable
Each conductor is surrounded by a
shield and the capacitance C is that
measured between each conductor and
its earthed shield.
s three-pole belted type cable
A single shield surrounds the three
conductors. There is a capacitance K
between conductors and a capacitance
C between each conductor and the
earthed shield.
be known is therefore:
Ic = 3 Cω V
which only takes into account the
capacitance C regardless of the cable
type.
In practise, cable manufacturers use
the term star connection capacitance,
for which they indicate the following:
s the value of C for radial field cables,
s the value of 3 K + C for belted type
cables.
They do not normally give this C
capacitance value for belted type
cables. On request, they give three
measurement results for these cables:
s the capacitance C1 measured
between a conducting core and the
other cores connected to the metal
sheathing; this gives the relation
C1 = 2 K + C,
s the capacitance C2 measured
between the three conducting cores
bound together and the metal
sheathing; this gives the relation:
C2 = 3 C,
s the capacitance C3 measured
between two conducting cores, with the
third connected to the metal sheathing;
this gives the relation:
C3 =
3 K + C
2
Thus, capacitance C2 must be known in
order to directly obtain the value of:
C =
C2
3
C C
C
K K
K
For the single-pole cable and the
three-pole radial field cable, there is
no ambiguity since there is only one
capacitance, C which is a phase-to-
earth capacitance. If there is no fault
and in three-phase steady-state
operating conditions, a capacitive
current ic flows through each phase
and is absorbed by the cable
capacitance C under the phase
voltage V, flowing from phase to earth,
at the network frequency:
ic = CωV = Cω
U
3
Since this capacitive load is three-
phased and balanced, it does not
disturb the network and does not affect
the protection operation.
On the other hand, if an earth fault
occurs in the network, in other words
when a phase is earthed, the cable
capacitance is equivalent to an
unbalanced load composed of the
capacitance C between the two sound
phases and the earth under phase to
phase voltage U.
The two currents CωU which are out of
phase by 60° flow through the two
sound phases; the sum of these two
currents is known as the capacitive
current IC of the network in the event of
an earth fault.
i.e. IC
= 3 CωV.
For the three-pole belted type cable,
if there is no fault, current ic
flowing in
balanced conditions is:
ic = 3 Kω U + CωV = 3 Kω V + CωV
i.e. ic = (3 K + C) ω V per phase, and
the sum of the currents of the three
phases is zero
Cable manufacturers generally give
this 3 K + C capacitance value for
belted-type cables.
On the other hand, if there is an earth
fault in the network, in other words if a
phase is earthed, the capacitive load
includes:
s the three K capacitance values under
the phase to phase voltage which form
a balanced load;
s the three C capacitance values, two
of which are under phase to phase
voltages and are out of phase by 60°;
the third under a zero voltage.
The sum of these currents (ic per
phase), known as the capacitive current
Ic of the network in the event of an
earth fault is:
ic = 2 CωV cos
π
6
= 3 CωU
i.e. Ic = 3 Cω V.
Conclusion: when determining the
resistance of an earth connection or the
adjustment of an earth protection
device, the capacitive current that must
Ic = 2Cω V cos
π
6
3 CωU
11. Merlin Gerin Technical Specification n° 62 / p.11
[1] Le Verre: «Overvoltages occurring
when elimining short-circuits in
networks with the neutral earthed
through a resistor». Société Française
des Electriciens (French Electricians'
Guild) Bulletin, 8th series, Volume 1,
No. 4 (April, 1960).
[2] E.D.F.: Memo on protection of
hydraulic power generators. NP 69 03.
appendix 2:bibliography