SlideShare a Scribd company logo
n°62
Neutral earthing in
an industrial HV
network
photographie
François Sautriau
Having graduated from the Ecole
Supérieure d'Electricité in 1968, he
joined Merlin Gerin in 1970. After
working on the design of networks
and protective devices, he was head
of the design office for industrial
projects and then for naval
equipment projects.
He is now, consultant in the
Marketing Division of the Protection
and Control Department
E/CT 62 up dated April 1996
Merlin Gerin Technical Specification n° 62 / p.2
Merlin Gerin Technical Specification n° 62 / p.3
neutral earthing in an industrial HV network
contents
1. Introduction p. 4
2. Earthing Direct earthing p. 4
Earthing through a reactor p. 4
Earthing through a resistor p. 4
3. Requirements imposed by Earthing through a current p. 5
overvoltages limiting reactor
Earthing through a resistor p. 4
4. Requirements imposed by networks p. 5
5. Requirements imposed by receivers p. 6
6. Calculating fault currents p. 6
7. Earth protection mode Earth protection adjustment p. 7
Earthing with accessible neutral p. 8
Earthing with an artificial neutral p. 8
Appendix 1: Comments on determining p. 10
network capacitance values
Appendix: Bibliography p. 11
HV electrical networks can be earthed
in different ways. This document
analyzes the constraints imposed by
the different parameters of the
installation (overvoltages, network,
receivers) and calculates the fault
currents.
Different protection modes are
described along with the settings and
adjustments suggested according to
the requirements.
Merlin Gerin Technical Specification n° 62 / p.4
1. introduction
[1] See bibliography
When designing an industrial HV
network, a suitable neutral earth
arrangement must be selected: the
neutral can either be insulated, or it can
be connected to earth. The use of an
insulated neutral in an HV network has
the advantage of ensuring operational
continuity since it does not trip on the
first fault, however the network
capacitance must be such that an earth
fault current is not likely to endanger
personnel or damage equipment.
On the other hand, an insulated neutral
2. earthing
neutral generally implies mandatory
tripping on the first fault, however:
s it reduces overvoltages,
s it provides a simple, reliable,
selective means of protection,
s it allows the use of equipment, and in
particular cables, with lower insulation
levels than for an insulated neutral.
implies the following:
s the risk of high overvoltages likely to
favourize multiple faults,
s the use of superinsulated equipment,
s compulsory monitoring of the
insulation,
s protection against overvoltages,
which will become compulsory in the
near future,
s the need for complex, selective
protection against earth faults which
cannot usually be ensured by simple
current-measuring relays. An earthed
earthing through a resistor
This is often the most satisfactory
solution.
A study is necessary to choose
between these two earthing, (through a
reactor or through a resistor) :
accurate determining of these earthing
modes depends on the voltage level,
the size of the network and the type of
receivers.
Depending on the earthing mode, a
criterion then determines a maximum
impedance value corresponding to the
overvoltage problem.
Next, it is necessary to check its
compatibility with the requirements of
the network and the receivers.
However, in the event of an earth fault,
the current is not limited, damage and
interference occur and there is
considerable danger for the personnel
during the time the fault persists.
This solution is not used for HV
distribution.
earthing through a reactor
Tuned reactor (Petersen coil)
This solution is sometimes used for
public HV networks. It is rarely used for
industrial distribution.
Protective relays sensitive to the active
component of the residual current must
be used to obtain selectivity.
Current limiting reactor
This solution can result in serious
overvoltages, as demonstrated by Le
Verre (the Research and Development
division of the E.D.F.) [1]. It can be
used only where there are low limiting
impedances.
The purpose of this study is not to
compare the different neutral earth
arrangements, but rather, once the
neutral earth solution has been
adopted, to determine the earthing
mode by finding a compromise
between three often contradictory
requirements:
s to sufficiently damp overvoltages,
s to limit damage and disturbances
caused by an earth fault,
s to provide simple, selective protective
devices.
Earthing can be of different types:
s direct (without impedance-dependent
current limiting),
s through a reactor,
s through a resistor.
direct earthing
This type of earthing is the most
efficient in limiting overvoltages;
protection selectivity presents no
difficulties.
Merlin Gerin Technical Specification n° 62 / p.5
3. requirements imposed by overvoltages
4. requirements imposed by networks
its path and in particular to the cable
shields. The maximum current
withstood by the cable shields may be
specified by the constructors. As a
general rule, the value used is between
500 and 3 000 A for 1 second.
The above criterion is used to define
the lower limit of the phase to earth
fault current.
To determine the upper limit, it is
necessary to check that the fault
current does not cause damage along
fig. 1 : a zigzag or neutral point coil provides
an earth fault current limiting reactor.
current IC in the event of an earth fault.
Hence the relation IL ≥ 2 IC.
Determination of the cable capacitance
values depends on their design (see
appendix for this calculation).
earthing through a current
limiting reactor
(see fig. 1)
The study of overvoltages that occur
when short-circuits are eliminated from
networks with the neutral earthed
through a reactor gives the following
results:
s let, I0ω be the earth fault current
limiting reactance,
s and Lω the network three-phase
short-circuit reactance.
The neutral-to-earth overvoltage
occurring when short-circuits are
eliminated is:
∆V
V
=
1
2
I0
L
for a radial field cable
network,
∆V
V
=
1
2
I0
L
for all other cases.
In practise, the earth fault current is
limited to at most 10 % of the three-
phase short-circuit current, as applied
by the EDF to its HV power distribution
network.
s
U
3 r
is the value of the earth fault
current IL in the earthing connection,
s 3 C ω
U
3
is the network capacitive
earthing through a resistor
As recommended by EDF for
hydroelectric power networks. The
resistance value r is détermined in
order to obtain a total active power
loss :
U
2
3 r
equal to or greater than the
capacitive power 2 C ω U
2
in the event
of a phase-earth fault, i.e.:
U
2
3 r
≥ 2 C ω U
2
.
When dividing by
U
3
, this become
U
3 r
≥ 2 . 3 C ω
U
3
where:
Merlin Gerin Technical Specification n° 62 / p.6
5. requirements imposed by receivers
between 3 kV and 15 kV, most
frequently 5.5 kV in France; the earth
fault current should not exceed 20 A in
order to avoid damage to the steel
plating of the machines, for if reworking
a winding is a regular repair, repairing a
machine when the metal plating is
damaged is much more time
consuming and more costly.
6. calculating fault currents
The currents in the different circuits are
easily calculated using a simple
approximative method.
This consists in ignoring the short-
circuit impedance of the source and the
coupled impedances with respect to the
neutral earth impedance and the
network capacitances. In other words,
we consider that earth fault currents are
much lower than three-phase short-
circuit currents (see fig. 2).
To calculate the neutral-to-earth
potential, the sum of the currents
flowing to earth is considered to be
zero (see diagram).
IN + IrD + Σ IrS = 0
0 = g VN + [G + jω C] (VN + E)
+ jωC (VN + a2
E) + jωC (VN + aE)
0 = VN [g + G + 3jωC] + GE
+ jω CE (1 + a2
+ a)
Since 1 + a
2
+ a = 0
This gives:
VN =
− GE
g + G + 3j ω C
where VN =
− zE
z + Z + 3 j ω C z Z
fig. 2: Earth fault current calculation parameters.
In HV networks, receivers are
transformers which have no particular
requirements as concerns the neutral
earthing in a power supply network.
However, industrial HV networks can
supply rotating machines with voltages
z =
1
g
Z=
1
G
Neutral earth impedance
Phase to earth fault impedance
CD Phase to earth capacitanc e of the faulty outgoing
feeder
CS Phase to earth capacitance of a sound outgoing
feeder
C = Σ CS Total phase to earth capacitance of the network
E Network phase voltage
VN Neutral point to earth potential
IN Neutral to earth current
ID Fault current
IrD Residual current of the faulty outgoing feeder
IrS Residual current of a sound outgoing feeder
EVN
3
2
1
g =
1
z
IN
G =
1
Z CD
I r D I r S
CS
ID
aE
a E
2
Merlin Gerin Technical Specification n° 62 / p.7
In the event of a short-circuit Z = 0, the
above formulae become:
s
s
s
s
s
s
Since we know VN, the different
currents (IN neutral to earth current, ID
fault current, IrD and IrS residual currents
in outgoing feeders) are calculated as
shown below:
s
s
I N =
−E
z
7. earth protection mode
The neutral earthing impedance affects
the required method of protection
against phase to earth faults.
As a general rule, the higher the fault
currents, the easier they are to detect;
the lower they are, the harder they are
to detect .
Moreover, it is advisable, even
essential, to ensure protection not at
one single point, but in all branches of
the network, since the relays operate
selectively.
Phase to earth protection is provided by
overcurrent relays supplied by the earth
current.
This current can be measured as
follows:
s either by a core balance transformer
around the three phase conductors and
which directly detects the sum of their
currents (zero if no earth fault) ;
s or by three current transformers the
secondary windings of which are
connected to form a neutral conductor
through which the sum of the three
currents flows.
The core balance transformer solution
is the most accurate, however it can
only be installed on cables, not on
busbars or overhead lines. The
3 current transformers solution is often
used, in particular when these
3 transformers are already required for
another application. But the
measurement obtained is degraded by
the inaccuracies of all three
transformers, in particular in the event
of transient overcurrents when the
transformers become saturated.
earth protection setting
This must be adjusted according to the
measurement accuracy. It must ensure
maximum protection and authorize
selectivity.
If the measurement is carried out using
the sum of the secondary currents of
the three transformers, it will be
degraded by the dispersion of the
transformers. In particular, a residual
current is measured if there is no earth
fault when the transformers become
saturated.
Saturation is caused by excessive
amplitude of the phase current, but
more specifically by the DC component
induced in a short-circuit or unbalanced
inrush current.
Note that, in transient conditions, the
DC component can induce saturation of
the transformers even though the peak
value of the transient current is around
10 times less than the saturation value
for a steady-state balanced current. An
earth protection device supplied by
3 transformers must therefore include a
time delay in order to avoid spurious
triggering resulting from transients. The
current setting must not be lower than
6 % of the transformer rating at best, or
15 or 20 % of the transformer ratings in
the most unfavourable cases.
Moreover, if an earth fault occurs in a
star winding near a neutral point, the
maximum fault current is only a small
part of the maximum fault current which
is limited by the neutral earth
impedance. For this reason, the current
setting is usually 20% of the maximum
current limited by the neutral earth in
order to protect 80% of the windings.
But, as the calculation shows, in the
event of a fault, a residual capacitive
current flows through the sound parts of
the network. So, to prevent the
protective device of a sound line from
tripping spuriously, the threshold must
be set to 30% higher than the
capacitive current flowing through this
sound line when a phase to earth short-
circuit affects the network.
Moreover, we must take into account
the possible presence of voltage
harmonics likely to produce currents
IrD = ID + 3jωC D VN
=
g + 3 jω C − CD( )
g+G+3jωC
GE
=
1+ 3jω C − CD( )z
Z + z + 3jωCzZ
E
IrD =
1
z
+ 3jω C − CD( )


 E
ID =
1
z
+3jωC


 E
IrS = − 3jω CS E
IN = gVN
−gGE
g + G + 3jωC
=
−E
Z +z + 3jωCzZ
ID = G VN +E( )=
g + 3jωC
g + G + 3jωC
GE
1+ 3jωCz
Z + z + 3jωCzZ
IrS = 3jωC S VN
=
− 3jωC S
g + G + 3jωC
GE
=
1− 3jωC S z
Z +z + 3jωCzZ
E
VN = − E
Merlin Gerin Technical Specification n° 62 / p.8
which increase as the order of the
harmonics increases. Note that 3rd
harmonics and multiples of 3 exist even
in steady-state conditions. Finally, the
neutral earth impedance characteristics
must be coordinated with the protective
devices so that this impedance itself is
not degraded by the fault current before
it is eliminated.
Note: that this concerns circuit
protection and not personnel protection.
Conclusion: when the earthed neutral
solution is selected for a medium
voltage network, it is advisable to use
earthing through a resistor rather than
other systems.
Calculating r and IL
This resistance r and the maximum
current IL =
U
3 r
are determined
taking the following requirements into
account:
s the current IL must be greater (or
equal) to twice the network capacitive
current in the event of an earth fault
IL ≥ 2 LC in order to limit overvoltages,
s the current IL must be less than the
maximum overcurrent that can be
withstood by the cable shields, normally
between 500 and 3 000 A, depending
on the cable cross section,
s in a network containing HV motors, it
is preferable to respect the relation:
5 A ≤ IL ≤ 20 A but, if this is
incompatible with the first condition, IL
can be up to 50 A,
s in order to ensure correct protection
of receivers, the Ir threshold settings
should not exceed 0,2 IL, i.e. Ir ≤ 0,2 IL,
s in order to ensure selectivity with
regard to sound connections, the
relation Ir ≥ 1,3 IC, must be respected,
where IC is the capacitive current of the
line when a phase to earth fault occurs,
s if the earth current is measured by
3 transformers of rating In , then Ir must
be ≥ 0,06 In,
s the thermal withstand of resistor r
must allow for current IL to flow during
the maximum fault clearing time
required (1 to 1.5 s) or, conversely, the
earth fault must be cleared sufficiently
rapidly to avoid damaging the resistor.
earthing with accessible
neutral
The resistor is connected to the neutral
output terminal and to the earthing
system, either directly, or through a
single-phase transformer the secondary
winding of which is loaded by an
equivalent resistance, as is used in
networks supplied through a
transformer which has a star-connected
secondary winding with accesible
neutral and for AC generators with
accessible neutral (see fig. 3).
If the network is supplied through
several transformers or AC generators,
it is advisable to have one single
neutral earth connection to prevent the
maximum earth fault current from
varying with the number of sources in
service.
a) b)
R r
fig. 3: neutral earthing at the secondary
winding of a star-coupled transformer,
through a resistor either connected directly
(a) or connected through a single-phase
transformer (b).
earthing with an artificial
neutral
If the neutral of the source is
inaccessible (as for delta-connected
windings), or if there are several
parallel-connected sources, earthing
can be ensured by an artificial neutral
(see figs. 4 and 5) (or earthing
transformer)
fig. 4: earthing a network neutral by means
of a star-delta transformer associated to:
a) a resistor connected to the HV side; in
this case the transformer secondary winding
can supply the auxiliaries;
b) a resistor series-connected to the
secondary winding.
r
b)
I ∆
R
a)
I ∆
Merlin Gerin Technical Specification n° 62 / p.9
Several solutions are possible:
s a star/delta transformer with a
resistor;
s a zigzag coil (see figs. 1 and 6): this
is used in cases where the maximum
earth fault current is limited to values
over 100 A;
s or, a special transformer, since to set
up an artificial neutral it may be more
economical to use the transformer
which supplies the substation LV
auxiliaries (see figs. 7 and 8).
The resulting impedance :
ro + jIoω appears as a resistance
if ro ≥ 2Ioω,
with ro and Io referenced to the same
voltage.
r
I ∆
fig. 7: neutral earthing by means of a
double-star transformer with compensating
delta windings around a resistor.
fig. 8: neutral earthing by means of a zigzag
transformer.
fig. 5: special transformer for neutral earting
R
I ∆
fig. 6: neutral earthing by means of a zigzag
coil.
R
I ∆
Merlin Gerin Technical Specification n° 62 / p.10
appendix 1:how to determine the capacitance values of a network
The capacitance of the cables depends
on their design:
s single-pole cable
The conductor is surrounded by a
shield and the capacitance C is that
measured between the conductor and
the earthed shield.
s three-pole radial field cable
Each conductor is surrounded by a
shield and the capacitance C is that
measured between each conductor and
its earthed shield.
s three-pole belted type cable
A single shield surrounds the three
conductors. There is a capacitance K
between conductors and a capacitance
C between each conductor and the
earthed shield.
be known is therefore:
Ic = 3 Cω V
which only takes into account the
capacitance C regardless of the cable
type.
In practise, cable manufacturers use
the term star connection capacitance,
for which they indicate the following:
s the value of C for radial field cables,
s the value of 3 K + C for belted type
cables.
They do not normally give this C
capacitance value for belted type
cables. On request, they give three
measurement results for these cables:
s the capacitance C1 measured
between a conducting core and the
other cores connected to the metal
sheathing; this gives the relation
C1 = 2 K + C,
s the capacitance C2 measured
between the three conducting cores
bound together and the metal
sheathing; this gives the relation:
C2 = 3 C,
s the capacitance C3 measured
between two conducting cores, with the
third connected to the metal sheathing;
this gives the relation:
C3 =
3 K + C
2
Thus, capacitance C2 must be known in
order to directly obtain the value of:
C =
C2
3
C C
C
K K
K
For the single-pole cable and the
three-pole radial field cable, there is
no ambiguity since there is only one
capacitance, C which is a phase-to-
earth capacitance. If there is no fault
and in three-phase steady-state
operating conditions, a capacitive
current ic flows through each phase
and is absorbed by the cable
capacitance C under the phase
voltage V, flowing from phase to earth,
at the network frequency:
ic = CωV = Cω
U
3
Since this capacitive load is three-
phased and balanced, it does not
disturb the network and does not affect
the protection operation.
On the other hand, if an earth fault
occurs in the network, in other words
when a phase is earthed, the cable
capacitance is equivalent to an
unbalanced load composed of the
capacitance C between the two sound
phases and the earth under phase to
phase voltage U.
The two currents CωU which are out of
phase by 60° flow through the two
sound phases; the sum of these two
currents is known as the capacitive
current IC of the network in the event of
an earth fault.
i.e. IC
= 3 CωV.
For the three-pole belted type cable,
if there is no fault, current ic
flowing in
balanced conditions is:
ic = 3 Kω U + CωV = 3 Kω V + CωV
i.e. ic = (3 K + C) ω V per phase, and
the sum of the currents of the three
phases is zero
Cable manufacturers generally give
this 3 K + C capacitance value for
belted-type cables.
On the other hand, if there is an earth
fault in the network, in other words if a
phase is earthed, the capacitive load
includes:
s the three K capacitance values under
the phase to phase voltage which form
a balanced load;
s the three C capacitance values, two
of which are under phase to phase
voltages and are out of phase by 60°;
the third under a zero voltage.
The sum of these currents (ic per
phase), known as the capacitive current
Ic of the network in the event of an
earth fault is:
ic = 2 CωV cos
π
6
= 3 CωU
i.e. Ic = 3 Cω V.
Conclusion: when determining the
resistance of an earth connection or the
adjustment of an earth protection
device, the capacitive current that must
Ic = 2Cω V cos
π
6
3 CωU
Merlin Gerin Technical Specification n° 62 / p.11
[1] Le Verre: «Overvoltages occurring
when elimining short-circuits in
networks with the neutral earthed
through a resistor». Société Française
des Electriciens (French Electricians'
Guild) Bulletin, 8th series, Volume 1,
No. 4 (April, 1960).
[2] E.D.F.: Memo on protection of
hydraulic power generators. NP 69 03.
appendix 2:bibliography
Merlin Gerin Technical Specification n° 62 / p.12
Réal. DTE - Photo IPV
DTE -05-96 - 1500 - Printing:Clerc

More Related Content

What's hot

Earthing Syatem
Earthing SyatemEarthing Syatem
Earthing SyatemNoman Khan
 
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1 INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
MayankSunhare
 
Protection basic
Protection basicProtection basic
Protection basic
BHAGWAN PRASAD
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
vkmalik
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systems
michaeljmack
 
Earthing systems: fundamentals of calculation and design
Earthing systems: fundamentals of calculation and designEarthing systems: fundamentals of calculation and design
Earthing systems: fundamentals of calculation and design
Leonardo ENERGY
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
Salim Palayi
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
Himansu Pradhan
 
Testing of Transformer (AREVA)
Testing of Transformer (AREVA)Testing of Transformer (AREVA)
Testing of Transformer (AREVA)
AHMED MOHAMED HEGAB
 
MV MetalClad Switchgear
MV MetalClad SwitchgearMV MetalClad Switchgear
MV MetalClad Switchgear
michaeljmack
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
SARAVANAN A
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
siddharam kantoli
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
Rahul Aman
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
RAGHVENDRA KUMAR PANDIT
 
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptx
SuhailAbdul2
 
Fuses(The power system protection)
Fuses(The power system protection)Fuses(The power system protection)
Fuses(The power system protection)
Md Abdullah Al Mayin
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
Sumeet Ratnawat
 
www.srecabletray.com
 www.srecabletray.com www.srecabletray.com
www.srecabletray.com
S.R.ELECTRICAL CO. BEAWAR
 
Differential protection
Differential protectionDifferential protection
Differential protection
Rishi Tandon
 

What's hot (20)

Earthing Syatem
Earthing SyatemEarthing Syatem
Earthing Syatem
 
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1 INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
 
Protection basic
Protection basicProtection basic
Protection basic
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
 
13
1313
13
 
Digital transformer protection systems
Digital transformer protection systemsDigital transformer protection systems
Digital transformer protection systems
 
Earthing systems: fundamentals of calculation and design
Earthing systems: fundamentals of calculation and designEarthing systems: fundamentals of calculation and design
Earthing systems: fundamentals of calculation and design
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Testing of Transformer (AREVA)
Testing of Transformer (AREVA)Testing of Transformer (AREVA)
Testing of Transformer (AREVA)
 
MV MetalClad Switchgear
MV MetalClad SwitchgearMV MetalClad Switchgear
MV MetalClad Switchgear
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptx
 
Fuses(The power system protection)
Fuses(The power system protection)Fuses(The power system protection)
Fuses(The power system protection)
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
www.srecabletray.com
 www.srecabletray.com www.srecabletray.com
www.srecabletray.com
 
Differential protection
Differential protectionDifferential protection
Differential protection
 

Similar to Schneider electric : Neutral Earthing

تأريض2
تأريض2تأريض2
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
Sy Thinhbk
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
Sy Thinhbk
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault Relay
IJSRED
 
Lightning Protection Considerations for Wired Systems
Lightning Protection Considerations for Wired SystemsLightning Protection Considerations for Wired Systems
Lightning Protection Considerations for Wired Systems
Analynk Wireless, LLC
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
Mahesh Chandra Manav
 
Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
Mahesh Chandra Manav
 
unit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.pptunit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.ppt
VijayHiremath26
 
Earthing Arrangements
Earthing  ArrangementsEarthing  Arrangements
Earthing ArrangementsPaul Holden
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
Mohammad Ahmad
 
Emi unit iv ppt
Emi unit iv pptEmi unit iv ppt
Emi unit iv ppt
SIVA NAGENDRA REDDY
 
ECE4762011_Lect22.ppt
ECE4762011_Lect22.pptECE4762011_Lect22.ppt
ECE4762011_Lect22.ppt
Sekar80689
 
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel InverterReview of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
IJRST Journal
 
Earthing Arrangements 17th
Earthing  Arrangements 17thEarthing  Arrangements 17th
Earthing Arrangements 17thPaul Holden
 
Clase 02, puesta a tierra
Clase 02, puesta a tierra Clase 02, puesta a tierra
Clase 02, puesta a tierra
1000028858888
 
E1103032933
E1103032933E1103032933
E1103032933
IOSR Journals
 
[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...
[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...
[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...
IJET - International Journal of Engineering and Techniques
 
Substation Earthing Design
Substation Earthing DesignSubstation Earthing Design
Substation Earthing Design
IOSRJEEE
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using Arduino
IRJET Journal
 

Similar to Schneider electric : Neutral Earthing (20)

تأريض2
تأريض2تأريض2
تأريض2
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault Relay
 
Lightning Protection Considerations for Wired Systems
Lightning Protection Considerations for Wired SystemsLightning Protection Considerations for Wired Systems
Lightning Protection Considerations for Wired Systems
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
 
Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
 
unit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.pptunit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.ppt
 
Earthing Arrangements
Earthing  ArrangementsEarthing  Arrangements
Earthing Arrangements
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
 
Emi unit iv ppt
Emi unit iv pptEmi unit iv ppt
Emi unit iv ppt
 
ECE4762011_Lect22.ppt
ECE4762011_Lect22.pptECE4762011_Lect22.ppt
ECE4762011_Lect22.ppt
 
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel InverterReview of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
 
Earthing Arrangements 17th
Earthing  Arrangements 17thEarthing  Arrangements 17th
Earthing Arrangements 17th
 
Clase 02, puesta a tierra
Clase 02, puesta a tierra Clase 02, puesta a tierra
Clase 02, puesta a tierra
 
K046016266
K046016266K046016266
K046016266
 
E1103032933
E1103032933E1103032933
E1103032933
 
[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...
[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...
[IJET V2I2P26] Authors: Pruthak C. Chauhan., Rinkesh S. Kansara, Mukesh P. Pa...
 
Substation Earthing Design
Substation Earthing DesignSubstation Earthing Design
Substation Earthing Design
 
Underground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using ArduinoUnderground Cable Fault Detection Using Arduino
Underground Cable Fault Detection Using Arduino
 

Recently uploaded

The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
Vaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdfVaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdf
Kamal Acharya
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
Jayaprasanna4
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
abh.arya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
ankuprajapati0525
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
ssuser9bd3ba
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
ViniHema
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 

Recently uploaded (20)

The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
Vaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdfVaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdf
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
H.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdfH.Seo,  ICLR 2024, MLILAB,  KAIST AI.pdf
H.Seo, ICLR 2024, MLILAB, KAIST AI.pdf
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 

Schneider electric : Neutral Earthing

  • 1. n°62 Neutral earthing in an industrial HV network photographie François Sautriau Having graduated from the Ecole Supérieure d'Electricité in 1968, he joined Merlin Gerin in 1970. After working on the design of networks and protective devices, he was head of the design office for industrial projects and then for naval equipment projects. He is now, consultant in the Marketing Division of the Protection and Control Department E/CT 62 up dated April 1996
  • 2. Merlin Gerin Technical Specification n° 62 / p.2
  • 3. Merlin Gerin Technical Specification n° 62 / p.3 neutral earthing in an industrial HV network contents 1. Introduction p. 4 2. Earthing Direct earthing p. 4 Earthing through a reactor p. 4 Earthing through a resistor p. 4 3. Requirements imposed by Earthing through a current p. 5 overvoltages limiting reactor Earthing through a resistor p. 4 4. Requirements imposed by networks p. 5 5. Requirements imposed by receivers p. 6 6. Calculating fault currents p. 6 7. Earth protection mode Earth protection adjustment p. 7 Earthing with accessible neutral p. 8 Earthing with an artificial neutral p. 8 Appendix 1: Comments on determining p. 10 network capacitance values Appendix: Bibliography p. 11 HV electrical networks can be earthed in different ways. This document analyzes the constraints imposed by the different parameters of the installation (overvoltages, network, receivers) and calculates the fault currents. Different protection modes are described along with the settings and adjustments suggested according to the requirements.
  • 4. Merlin Gerin Technical Specification n° 62 / p.4 1. introduction [1] See bibliography When designing an industrial HV network, a suitable neutral earth arrangement must be selected: the neutral can either be insulated, or it can be connected to earth. The use of an insulated neutral in an HV network has the advantage of ensuring operational continuity since it does not trip on the first fault, however the network capacitance must be such that an earth fault current is not likely to endanger personnel or damage equipment. On the other hand, an insulated neutral 2. earthing neutral generally implies mandatory tripping on the first fault, however: s it reduces overvoltages, s it provides a simple, reliable, selective means of protection, s it allows the use of equipment, and in particular cables, with lower insulation levels than for an insulated neutral. implies the following: s the risk of high overvoltages likely to favourize multiple faults, s the use of superinsulated equipment, s compulsory monitoring of the insulation, s protection against overvoltages, which will become compulsory in the near future, s the need for complex, selective protection against earth faults which cannot usually be ensured by simple current-measuring relays. An earthed earthing through a resistor This is often the most satisfactory solution. A study is necessary to choose between these two earthing, (through a reactor or through a resistor) : accurate determining of these earthing modes depends on the voltage level, the size of the network and the type of receivers. Depending on the earthing mode, a criterion then determines a maximum impedance value corresponding to the overvoltage problem. Next, it is necessary to check its compatibility with the requirements of the network and the receivers. However, in the event of an earth fault, the current is not limited, damage and interference occur and there is considerable danger for the personnel during the time the fault persists. This solution is not used for HV distribution. earthing through a reactor Tuned reactor (Petersen coil) This solution is sometimes used for public HV networks. It is rarely used for industrial distribution. Protective relays sensitive to the active component of the residual current must be used to obtain selectivity. Current limiting reactor This solution can result in serious overvoltages, as demonstrated by Le Verre (the Research and Development division of the E.D.F.) [1]. It can be used only where there are low limiting impedances. The purpose of this study is not to compare the different neutral earth arrangements, but rather, once the neutral earth solution has been adopted, to determine the earthing mode by finding a compromise between three often contradictory requirements: s to sufficiently damp overvoltages, s to limit damage and disturbances caused by an earth fault, s to provide simple, selective protective devices. Earthing can be of different types: s direct (without impedance-dependent current limiting), s through a reactor, s through a resistor. direct earthing This type of earthing is the most efficient in limiting overvoltages; protection selectivity presents no difficulties.
  • 5. Merlin Gerin Technical Specification n° 62 / p.5 3. requirements imposed by overvoltages 4. requirements imposed by networks its path and in particular to the cable shields. The maximum current withstood by the cable shields may be specified by the constructors. As a general rule, the value used is between 500 and 3 000 A for 1 second. The above criterion is used to define the lower limit of the phase to earth fault current. To determine the upper limit, it is necessary to check that the fault current does not cause damage along fig. 1 : a zigzag or neutral point coil provides an earth fault current limiting reactor. current IC in the event of an earth fault. Hence the relation IL ≥ 2 IC. Determination of the cable capacitance values depends on their design (see appendix for this calculation). earthing through a current limiting reactor (see fig. 1) The study of overvoltages that occur when short-circuits are eliminated from networks with the neutral earthed through a reactor gives the following results: s let, I0ω be the earth fault current limiting reactance, s and Lω the network three-phase short-circuit reactance. The neutral-to-earth overvoltage occurring when short-circuits are eliminated is: ∆V V = 1 2 I0 L for a radial field cable network, ∆V V = 1 2 I0 L for all other cases. In practise, the earth fault current is limited to at most 10 % of the three- phase short-circuit current, as applied by the EDF to its HV power distribution network. s U 3 r is the value of the earth fault current IL in the earthing connection, s 3 C ω U 3 is the network capacitive earthing through a resistor As recommended by EDF for hydroelectric power networks. The resistance value r is détermined in order to obtain a total active power loss : U 2 3 r equal to or greater than the capacitive power 2 C ω U 2 in the event of a phase-earth fault, i.e.: U 2 3 r ≥ 2 C ω U 2 . When dividing by U 3 , this become U 3 r ≥ 2 . 3 C ω U 3 where:
  • 6. Merlin Gerin Technical Specification n° 62 / p.6 5. requirements imposed by receivers between 3 kV and 15 kV, most frequently 5.5 kV in France; the earth fault current should not exceed 20 A in order to avoid damage to the steel plating of the machines, for if reworking a winding is a regular repair, repairing a machine when the metal plating is damaged is much more time consuming and more costly. 6. calculating fault currents The currents in the different circuits are easily calculated using a simple approximative method. This consists in ignoring the short- circuit impedance of the source and the coupled impedances with respect to the neutral earth impedance and the network capacitances. In other words, we consider that earth fault currents are much lower than three-phase short- circuit currents (see fig. 2). To calculate the neutral-to-earth potential, the sum of the currents flowing to earth is considered to be zero (see diagram). IN + IrD + Σ IrS = 0 0 = g VN + [G + jω C] (VN + E) + jωC (VN + a2 E) + jωC (VN + aE) 0 = VN [g + G + 3jωC] + GE + jω CE (1 + a2 + a) Since 1 + a 2 + a = 0 This gives: VN = − GE g + G + 3j ω C where VN = − zE z + Z + 3 j ω C z Z fig. 2: Earth fault current calculation parameters. In HV networks, receivers are transformers which have no particular requirements as concerns the neutral earthing in a power supply network. However, industrial HV networks can supply rotating machines with voltages z = 1 g Z= 1 G Neutral earth impedance Phase to earth fault impedance CD Phase to earth capacitanc e of the faulty outgoing feeder CS Phase to earth capacitance of a sound outgoing feeder C = Σ CS Total phase to earth capacitance of the network E Network phase voltage VN Neutral point to earth potential IN Neutral to earth current ID Fault current IrD Residual current of the faulty outgoing feeder IrS Residual current of a sound outgoing feeder EVN 3 2 1 g = 1 z IN G = 1 Z CD I r D I r S CS ID aE a E 2
  • 7. Merlin Gerin Technical Specification n° 62 / p.7 In the event of a short-circuit Z = 0, the above formulae become: s s s s s s Since we know VN, the different currents (IN neutral to earth current, ID fault current, IrD and IrS residual currents in outgoing feeders) are calculated as shown below: s s I N = −E z 7. earth protection mode The neutral earthing impedance affects the required method of protection against phase to earth faults. As a general rule, the higher the fault currents, the easier they are to detect; the lower they are, the harder they are to detect . Moreover, it is advisable, even essential, to ensure protection not at one single point, but in all branches of the network, since the relays operate selectively. Phase to earth protection is provided by overcurrent relays supplied by the earth current. This current can be measured as follows: s either by a core balance transformer around the three phase conductors and which directly detects the sum of their currents (zero if no earth fault) ; s or by three current transformers the secondary windings of which are connected to form a neutral conductor through which the sum of the three currents flows. The core balance transformer solution is the most accurate, however it can only be installed on cables, not on busbars or overhead lines. The 3 current transformers solution is often used, in particular when these 3 transformers are already required for another application. But the measurement obtained is degraded by the inaccuracies of all three transformers, in particular in the event of transient overcurrents when the transformers become saturated. earth protection setting This must be adjusted according to the measurement accuracy. It must ensure maximum protection and authorize selectivity. If the measurement is carried out using the sum of the secondary currents of the three transformers, it will be degraded by the dispersion of the transformers. In particular, a residual current is measured if there is no earth fault when the transformers become saturated. Saturation is caused by excessive amplitude of the phase current, but more specifically by the DC component induced in a short-circuit or unbalanced inrush current. Note that, in transient conditions, the DC component can induce saturation of the transformers even though the peak value of the transient current is around 10 times less than the saturation value for a steady-state balanced current. An earth protection device supplied by 3 transformers must therefore include a time delay in order to avoid spurious triggering resulting from transients. The current setting must not be lower than 6 % of the transformer rating at best, or 15 or 20 % of the transformer ratings in the most unfavourable cases. Moreover, if an earth fault occurs in a star winding near a neutral point, the maximum fault current is only a small part of the maximum fault current which is limited by the neutral earth impedance. For this reason, the current setting is usually 20% of the maximum current limited by the neutral earth in order to protect 80% of the windings. But, as the calculation shows, in the event of a fault, a residual capacitive current flows through the sound parts of the network. So, to prevent the protective device of a sound line from tripping spuriously, the threshold must be set to 30% higher than the capacitive current flowing through this sound line when a phase to earth short- circuit affects the network. Moreover, we must take into account the possible presence of voltage harmonics likely to produce currents IrD = ID + 3jωC D VN = g + 3 jω C − CD( ) g+G+3jωC GE = 1+ 3jω C − CD( )z Z + z + 3jωCzZ E IrD = 1 z + 3jω C − CD( )    E ID = 1 z +3jωC    E IrS = − 3jω CS E IN = gVN −gGE g + G + 3jωC = −E Z +z + 3jωCzZ ID = G VN +E( )= g + 3jωC g + G + 3jωC GE 1+ 3jωCz Z + z + 3jωCzZ IrS = 3jωC S VN = − 3jωC S g + G + 3jωC GE = 1− 3jωC S z Z +z + 3jωCzZ E VN = − E
  • 8. Merlin Gerin Technical Specification n° 62 / p.8 which increase as the order of the harmonics increases. Note that 3rd harmonics and multiples of 3 exist even in steady-state conditions. Finally, the neutral earth impedance characteristics must be coordinated with the protective devices so that this impedance itself is not degraded by the fault current before it is eliminated. Note: that this concerns circuit protection and not personnel protection. Conclusion: when the earthed neutral solution is selected for a medium voltage network, it is advisable to use earthing through a resistor rather than other systems. Calculating r and IL This resistance r and the maximum current IL = U 3 r are determined taking the following requirements into account: s the current IL must be greater (or equal) to twice the network capacitive current in the event of an earth fault IL ≥ 2 LC in order to limit overvoltages, s the current IL must be less than the maximum overcurrent that can be withstood by the cable shields, normally between 500 and 3 000 A, depending on the cable cross section, s in a network containing HV motors, it is preferable to respect the relation: 5 A ≤ IL ≤ 20 A but, if this is incompatible with the first condition, IL can be up to 50 A, s in order to ensure correct protection of receivers, the Ir threshold settings should not exceed 0,2 IL, i.e. Ir ≤ 0,2 IL, s in order to ensure selectivity with regard to sound connections, the relation Ir ≥ 1,3 IC, must be respected, where IC is the capacitive current of the line when a phase to earth fault occurs, s if the earth current is measured by 3 transformers of rating In , then Ir must be ≥ 0,06 In, s the thermal withstand of resistor r must allow for current IL to flow during the maximum fault clearing time required (1 to 1.5 s) or, conversely, the earth fault must be cleared sufficiently rapidly to avoid damaging the resistor. earthing with accessible neutral The resistor is connected to the neutral output terminal and to the earthing system, either directly, or through a single-phase transformer the secondary winding of which is loaded by an equivalent resistance, as is used in networks supplied through a transformer which has a star-connected secondary winding with accesible neutral and for AC generators with accessible neutral (see fig. 3). If the network is supplied through several transformers or AC generators, it is advisable to have one single neutral earth connection to prevent the maximum earth fault current from varying with the number of sources in service. a) b) R r fig. 3: neutral earthing at the secondary winding of a star-coupled transformer, through a resistor either connected directly (a) or connected through a single-phase transformer (b). earthing with an artificial neutral If the neutral of the source is inaccessible (as for delta-connected windings), or if there are several parallel-connected sources, earthing can be ensured by an artificial neutral (see figs. 4 and 5) (or earthing transformer) fig. 4: earthing a network neutral by means of a star-delta transformer associated to: a) a resistor connected to the HV side; in this case the transformer secondary winding can supply the auxiliaries; b) a resistor series-connected to the secondary winding. r b) I ∆ R a) I ∆
  • 9. Merlin Gerin Technical Specification n° 62 / p.9 Several solutions are possible: s a star/delta transformer with a resistor; s a zigzag coil (see figs. 1 and 6): this is used in cases where the maximum earth fault current is limited to values over 100 A; s or, a special transformer, since to set up an artificial neutral it may be more economical to use the transformer which supplies the substation LV auxiliaries (see figs. 7 and 8). The resulting impedance : ro + jIoω appears as a resistance if ro ≥ 2Ioω, with ro and Io referenced to the same voltage. r I ∆ fig. 7: neutral earthing by means of a double-star transformer with compensating delta windings around a resistor. fig. 8: neutral earthing by means of a zigzag transformer. fig. 5: special transformer for neutral earting R I ∆ fig. 6: neutral earthing by means of a zigzag coil. R I ∆
  • 10. Merlin Gerin Technical Specification n° 62 / p.10 appendix 1:how to determine the capacitance values of a network The capacitance of the cables depends on their design: s single-pole cable The conductor is surrounded by a shield and the capacitance C is that measured between the conductor and the earthed shield. s three-pole radial field cable Each conductor is surrounded by a shield and the capacitance C is that measured between each conductor and its earthed shield. s three-pole belted type cable A single shield surrounds the three conductors. There is a capacitance K between conductors and a capacitance C between each conductor and the earthed shield. be known is therefore: Ic = 3 Cω V which only takes into account the capacitance C regardless of the cable type. In practise, cable manufacturers use the term star connection capacitance, for which they indicate the following: s the value of C for radial field cables, s the value of 3 K + C for belted type cables. They do not normally give this C capacitance value for belted type cables. On request, they give three measurement results for these cables: s the capacitance C1 measured between a conducting core and the other cores connected to the metal sheathing; this gives the relation C1 = 2 K + C, s the capacitance C2 measured between the three conducting cores bound together and the metal sheathing; this gives the relation: C2 = 3 C, s the capacitance C3 measured between two conducting cores, with the third connected to the metal sheathing; this gives the relation: C3 = 3 K + C 2 Thus, capacitance C2 must be known in order to directly obtain the value of: C = C2 3 C C C K K K For the single-pole cable and the three-pole radial field cable, there is no ambiguity since there is only one capacitance, C which is a phase-to- earth capacitance. If there is no fault and in three-phase steady-state operating conditions, a capacitive current ic flows through each phase and is absorbed by the cable capacitance C under the phase voltage V, flowing from phase to earth, at the network frequency: ic = CωV = Cω U 3 Since this capacitive load is three- phased and balanced, it does not disturb the network and does not affect the protection operation. On the other hand, if an earth fault occurs in the network, in other words when a phase is earthed, the cable capacitance is equivalent to an unbalanced load composed of the capacitance C between the two sound phases and the earth under phase to phase voltage U. The two currents CωU which are out of phase by 60° flow through the two sound phases; the sum of these two currents is known as the capacitive current IC of the network in the event of an earth fault. i.e. IC = 3 CωV. For the three-pole belted type cable, if there is no fault, current ic flowing in balanced conditions is: ic = 3 Kω U + CωV = 3 Kω V + CωV i.e. ic = (3 K + C) ω V per phase, and the sum of the currents of the three phases is zero Cable manufacturers generally give this 3 K + C capacitance value for belted-type cables. On the other hand, if there is an earth fault in the network, in other words if a phase is earthed, the capacitive load includes: s the three K capacitance values under the phase to phase voltage which form a balanced load; s the three C capacitance values, two of which are under phase to phase voltages and are out of phase by 60°; the third under a zero voltage. The sum of these currents (ic per phase), known as the capacitive current Ic of the network in the event of an earth fault is: ic = 2 CωV cos π 6 = 3 CωU i.e. Ic = 3 Cω V. Conclusion: when determining the resistance of an earth connection or the adjustment of an earth protection device, the capacitive current that must Ic = 2Cω V cos π 6 3 CωU
  • 11. Merlin Gerin Technical Specification n° 62 / p.11 [1] Le Verre: «Overvoltages occurring when elimining short-circuits in networks with the neutral earthed through a resistor». Société Française des Electriciens (French Electricians' Guild) Bulletin, 8th series, Volume 1, No. 4 (April, 1960). [2] E.D.F.: Memo on protection of hydraulic power generators. NP 69 03. appendix 2:bibliography
  • 12. Merlin Gerin Technical Specification n° 62 / p.12 Réal. DTE - Photo IPV DTE -05-96 - 1500 - Printing:Clerc