1) The document discusses converting existing three-phase double circuit 400kV transmission lines to six-phase transmission lines as a solution for bulk power transmission over long distances. 2) Simulation results show that six-phase transmission allows for 1.7-1.74 times more power transfer capability compared to the three-phase line. It also allows for lower transmission voltages and reduced tower sizes for the same power transferred. 3) Fault current magnitudes are lower for six-phase transmission compared to three-phase transmission for the same fault type and location, with four-phase to ground faults being the most severe for six-phase lines. Load voltages also exhibit less distortion for faults on six-phase lines.