Addressing Control
   Applications Using
  WirelessHART Devices
Marty Zielinski - Director of HART and
         Fieldbus Technology
  Mark Nixon – Director, Research
Terry Blevins – Principal Technologist
Presenters


    Marty Zielinski



    Terry Blevins



    Mark Nixon
Introduction

 The PIDPlus capability in DeltaV may be used to
 implement closed loop control using WirelessHART
 devices. In this workshop we address
    Wireless Impact on Control
    PIDPlus for Control Using Wireless Measurements
    Performance Comparison to Wired Transmitter
    Addressing Lost Communications
    Test results – Field Installations

 The PIDPlus may be used with slow and variable
 communication updates
Challenge – Control Using WirelessHART

     Transmitter power consumption may be minimized by reducing the
      number of times the measurement value is communicated.

     Conventional PID execution synchronizes the measurement value
      with control action, by over-sampling the measurement by a factor of
      2-10X.

     The rule of thumb to minimize control variation is to have feedback
      control executed 4X to 10X times faster than the process response
      time (process time constant plus process delay).

     The conventional PID design (i.e., difference equation and z-
      transform) assumes that a new measurement value is available at
      each execution and that control is executed on a fixed periodic
      basis.
Conventional Approach – Over
Sampling of Measurement
                                                           Process Output




                                           63% of Change                        O


                    Time Constant (   )
                    Deadtime (TD )


              Process Input


          I



                                                                  Control Execution

                                            New Measurement Available
Conventional PID - Impact of Wireless

     The underlying assumption in traditional control design is that the
      PID is executed on a periodic basis 4X-10X times over the process
      response time .
     When the measurement update is variable or updated less
      frequently, the calculated reset action may not be appropriate.
     If control action is only executed when a new measurement is
      communicated, this could result in a delayed control response to
      setpoint changes and feedforward action on measured disturbances.




                   Conventional PID Design
Emerson’s WirelessHART Solution

   Power consumption of the wireless device is reduced by
    transmitting the measurement value only as often as required
    to allow control action to correct for unmeasured disturbances.
   The PID may be configured to execute much faster than the
    measurement value is communicated. The PIDPlus is
    designed to automatically compensate for the slower
    measurement update and any variation in measurement
    update rates.
   Tuning of the PIDPlus is based strictly on the process
    dynamics independent of the measurement update rate and is
    not impacted by variations in measurement update.
Conventional PID - Impact of Wireless

     The underlying assumption in traditional control design is that the
      PID is executed on a periodic basis 4X-10X times over the process
      response time .
     When the measurement update is variable or updated less
      frequently, the calculated reset action may not be appropriate.
     If control action is only executed when a new measurement is
      communicated, this could result in a delayed control response to
      setpoint changes and feedforward action on measured disturbances.




                   Conventional PID Design
PIDPlus for WirelessHART Communications
     To provide the best control for slow or variable measurement update
      rates, the PID must be modified to reflect the reset contribution for
      the expected process response since the last measurement update.
     Control execution is set faster than measurement update. This
      permits immediate action on setpoint change and update in the
      faceplate.
     PIDPlus is a standard feature of DeltaV v11.3 (released 2010)




                   PIDPlus Design in DeltaV v11.3
PIDPlus Reset (Integral) Calculation
The filter output used in the positive feedback network is calculated in the
following manner when a new measurement is received.




PIDPlus tuning is based on the process dynamic (e.g. RESET= process
time constant plus deadtime); PIDPlus reset automatically compensates
for slow updates and variations in the measurement update rate. No
change in GAIN is required for varying update rate.
PIDPlus Modification for Setpoint Change

 Automatic compensation for setpoint change; measurement update
 rate. No need to modify tuning as sample rate changes




               No         Yes




     PIDPlus –DeltaV v12.3 release in 2012
PIDPlus Using Wireless Transmitter vs.
Conventional PID and Wired Transmitter

   Lambda Tuning ʎ = 1.0
   Variable communication Update Rate

                                                   Control
      Setpoint                          PIDPlus    Measurement


                                             PID

                                        PIDPlus
                                                   Control Output

                                          PID


                                                   Unmeasured
                                                   Disturbance
CONTROL PERFORMANCE DIFFERENCE
    Communications transmissions are reduced by over 96 %
     using slower communication update rates.
    The impact of slower updates and variations in
     measurement updates on control performance as
     measured by Integral of Absolute Error (IAE) is minimized
     through the use of PIDPlus for wireless communication.

       Communications/Control            Number of      IAE
                                       Communications
     Periodic/standard PI Controller        692         123

         Update Using Wireless               25         159
       communication/ PI Control
PIDPlus - Modified Derivative Action




       No   Yes
PID Performance for Lost Communications

     The Conventional PID provides poor dynamic
      response when wireless communications are lost.

     The PIDPlus improves the dynamic response
      under these conditions
Wireless Communication Loss –
During Setpoint Change


            Setpoint        PIDPlus
                                              Control
                                              Measurement

                             PID

                       PIDPlus


                                              Control Output
                             PID


                         Communication Loss
Wireless Communication Loss –
During Process Disturbance


                              PIDPlus
         Setpoint                        Control
                                         Measurement


                                 PID


                       PIDPlus
                                         Control Output


                        PID

                    Communication Loss
Testing PIDPlus –Communication’s Setup
   For testing purposes, the WirelessHART communications and the
    process can be dynamically simulated in a DeltaV module for PID and
    PIDPlus control.
   Communication setup is defined by the “Transmission” composite block.
Installation at Broadley James
                                    Portable
                                     Hyclone 100
                                     liter disposable
                                     bioreactor
                                    Rosemount
                                     WirelessHART
                                     gateway and
                                     transmitters for
                                     measurement
                                     and control of
                                     pH and
                                     temperature.
                                     Pressure
                                     monitored
                                    BioNet is based
                                     on the DeltaV
                                     Control system.
Installation at Broadley James (Cont)
                                       Detail view of
                                        Rosemount pH
                                        WirelessHART
                                        Transmitter.
                                       Battery powered –
                                        3 to 5 year battery
                                        life expected for
                                        this application.
Broadley James Bioreactor Setup
                                                                                                     VSD



                                    VSD                                                          Media

                                                   37 oC                                             VSD
                                  Inoculums         TC            TT
                                                   41-7          41-7
                                                                          VSD                  Glutamine
                                   VSD                                                               VSD



                              Bicarbonate                                                       Glucose

                                                   Heater
                                   7.0 pH

                 AY                 AC               AT                                            AT
     Splitter                                                                                                 AC
                41-1               41-1             41-1                                         41-4s1     41-4s1
                                  0.002 g/L         pH                                           Glucose    2.0 g/L
                                    AC               AT                                            AT                   AC
                                   41-2             41-2                                         41-4s2               41-4s2
                                                    DO                                          Glutamine
                                                                                                                      2.0 g/L
                                            AT     AT                                                 AT
                                          41-5x1 41-5x2
                                                                        Bioreactor
                                                                                                     41-6
                                          Viable   Dead                                          Product
                                           Cells   Cells
   CO2          MFC                                                                           LT
                                                                                             41-14

                                    AY                                                       Level
                       Splitter                                                      VSD
                                   41-2

                                              O2           MFC
                                                                                     Drain
                   Air             MFC
Example - Automatically Identified Temperature
Dynamics Using DeltaV Insight




   DeltaV Insight – Standard Since DeltaV v9.3
Wireless Temperature Loop Test Results
Wireless pH Loop Test Results
Elimination of Ground Noise Spikes




              Requirement:
              Tight pH control via 0.001 pH wireless resolution setting


        Temperature compensated wireless pH controlling at 6.9 pH set point




                Wired pH ground noise spike
Separations Research Program,
University of Texas at Austin
                           The Separations Research
                            Program was established at
                            the J.J. Pickle Research
                            Campus in 1984
                           This cooperative
                            industry/university program
                            performs fundamental
                            research of interest to
                            chemical, biotechnological,
                            petroleum refining, gas
                            processing, pharmaceutical,
                            and food companies.
                           CO2 removal from stack gas
                            is a focus project for which
                            WirelessHART transmitters
                            were installed for pressure
                            and steam flow control
WirelessHART Transmitter

                     Standard WirelessHART
                      pressure and flow transmitters
                      were installed to demonstrate
                      and test control using
                      WirelessHART.
                     Standard WirelessHART pH
                      transmitters are used to support
                      studies associated with CO2
                      removal from stack gases.
                     Standard WirelessHART multi-
                      element temperature
                      transmitters are used to monitor
                      absorber and stripper
                      temperatures.
Steam Flow To Stripper Heater
Column Pressure Control
PC215 On-line Column Pressure Control
                                          The same
                                           dynamic control
                Wired Measurement          response was
                Used in Control            observed for
                                           SP changes
                                          Original plant
                                           PID tuning
                                           was used for
                                           both wired
                                           and wireless
                                           control
                                            GAIN=2.5
                                            RESET=4
                                            RATE=1
                Wireless Measurement
                Used in Control
Control Performance – Wired vs Wireless
                                                                  Comparable control
                                                                   as measured by IAE
  LOOP              FIC202       PC215   FIC202     PC215
                                                                   was achieved using
  Selected Input    Wired        Wired   Wireless   Wireless       WirelessHART
                                                                   Measurements and
  IAE               9134         145     10645      198            PIDPlus vs. control
                                                                   with wired
  Number of         13655        6649    1184       912            measurements and
  Communication                                                    PID.
  Test Time (sec)   6830         6829    5926       5925          The number of
                            Test 1               Test 2
                                                                   measurement
                                                                   samples with
                                                                   WirelessHART vs
                                                                   Wired transmitter was
                                                                   reduced by a factor of
                                                                   10X for flow control
                                                                   and 6X for pressure
                                                                   control – accounting
                                                                   for differences in test
                                                                   duration.
Separations Research Program,
University of Texas at Austin
                           The Separations Research
                            Program was established at
                            the J.J. Pickle Research
                            Campus in 1984
                           This cooperative
                            industry/university program
                            performs fundamental
                            research of interest to
                            chemical, biotechnological,
                            petroleum refining, gas
                            processing, pharmaceutical,
                            and food companies.
                           CO2 removal from stack gas
                            is a focus project for which
                            WirelessHART transmitters
                            were installed for pressure
                            and steam flow control
Current Product: Discrete Control



                      Video
Future Product:
4300 Series Wireless On/Off Control

                 Release planned for the end of 2012




               Currently in 7 End User Field Trials Sites
                7 different applications
                6 industrial market segments
Business Results Achieved
    The PIDPlus allows WirelessHART devices to be
     used for closed loop control of quality parameters
     that currently may not be available in the control
     system.
    The reduction in process variability achieved through
     closed loop control may lead to improved process
     operation e.g. reduction in product quality variation,
     improved efficiency.
    Field installations have documented robust control
     performance using the PIDPlus with WirelessHART
     transmitters. The results were shown for control of
     liquid flow, gas pressure, pH and temperature.
Summary
   WirelessHART measurements may be used in closed loop
    control applications.
     – Slower reporting minimizes power consumption
   PIDPlus is a standard feature of DeltaV and works with
    standard WirelessHART devices.
     – Standard DeltaV Tools support Simulation and Tuning
   The performance of PIDPlus in a wireless control network is
    comparable to PID with wired inputs
     – PIDPlus handles lost communications better than
       conventional PID.
   PIDPlus tuning depends only upon process dynamics, not on
    wireless update rate
Where To Get More Information
    PID Advances in Industrial Control, IFAC Conference on Advances in PID Control PID'12,
     Brescia, Italy, 28-30 March 2012 http://pid12.ing.unibs.it/sp_blevins.html
    DeltaV v11 PID Enhancements for Wireless, DeltaV Whitepaper, August, 2010
     http://www2.emersonprocess.com/siteadmincenter/PM%20DeltaV%20Documents/Whitepap
     ers/WP_DeltaV%20PID%20Enhancements%20for%20Wireless.pdf
    WirelessHART Successfully Handles Control, Chemical Processing, January, 2011
     http://www2.emersonprocess.com/siteadmincenter/PM%20Articles/WirelessHART%20Succ
     essfully%20Handles%20Control.pdf
    Wireless – Overcoming Challenges of PID Control& Analyzer Applications, InTech,
     July/August, 2010
     http://www.isa.org/InTechTemplate.cfm?template=/ContentManagement/ContentDisplay.cfm
     &ContentID=83041
    PIDPlus An Enhanced PID Control Algorithm for Wireless Automation, AS-74.3199 Wireless
     Automation, Aalto University, Finland http://autsys.tkk.fi/intranet/as-0.3200/attach/S09-
     19/loppuraportti.pdf
    Incorporating Wireless Devices into Single-Use Disposable Bioreactor Design, 2009
     Dhirubhai Ambani Life Sciences Symposium http://www.modelingandcontrol.com/Wireless-
     Devices-in-Single-Use-Bioreactors.pdf
    Improving PID Control with Unreliable Communications, ISA EXPO Technical Conference,
     2006. http://www.automation.com/pdf_articles/10_improving_pid.pdf
    Similarity-based Traffic Reduction to Increase Battery Life in a Wireless Process Control
     Network, ISA EXPO2005, Houston, TX www.cs.utexas.edu/~sjp/publications/isa06.doc

Addressing control applications using wireless hart devices

  • 1.
    Addressing Control Applications Using WirelessHART Devices Marty Zielinski - Director of HART and Fieldbus Technology Mark Nixon – Director, Research Terry Blevins – Principal Technologist
  • 2.
    Presenters  Marty Zielinski  Terry Blevins  Mark Nixon
  • 3.
    Introduction The PIDPluscapability in DeltaV may be used to implement closed loop control using WirelessHART devices. In this workshop we address  Wireless Impact on Control  PIDPlus for Control Using Wireless Measurements  Performance Comparison to Wired Transmitter  Addressing Lost Communications  Test results – Field Installations The PIDPlus may be used with slow and variable communication updates
  • 4.
    Challenge – ControlUsing WirelessHART  Transmitter power consumption may be minimized by reducing the number of times the measurement value is communicated.  Conventional PID execution synchronizes the measurement value with control action, by over-sampling the measurement by a factor of 2-10X.  The rule of thumb to minimize control variation is to have feedback control executed 4X to 10X times faster than the process response time (process time constant plus process delay).  The conventional PID design (i.e., difference equation and z- transform) assumes that a new measurement value is available at each execution and that control is executed on a fixed periodic basis.
  • 5.
    Conventional Approach –Over Sampling of Measurement Process Output 63% of Change O Time Constant ( ) Deadtime (TD ) Process Input I Control Execution New Measurement Available
  • 6.
    Conventional PID -Impact of Wireless  The underlying assumption in traditional control design is that the PID is executed on a periodic basis 4X-10X times over the process response time .  When the measurement update is variable or updated less frequently, the calculated reset action may not be appropriate.  If control action is only executed when a new measurement is communicated, this could result in a delayed control response to setpoint changes and feedforward action on measured disturbances. Conventional PID Design
  • 7.
    Emerson’s WirelessHART Solution  Power consumption of the wireless device is reduced by transmitting the measurement value only as often as required to allow control action to correct for unmeasured disturbances.  The PID may be configured to execute much faster than the measurement value is communicated. The PIDPlus is designed to automatically compensate for the slower measurement update and any variation in measurement update rates.  Tuning of the PIDPlus is based strictly on the process dynamics independent of the measurement update rate and is not impacted by variations in measurement update.
  • 8.
    Conventional PID -Impact of Wireless  The underlying assumption in traditional control design is that the PID is executed on a periodic basis 4X-10X times over the process response time .  When the measurement update is variable or updated less frequently, the calculated reset action may not be appropriate.  If control action is only executed when a new measurement is communicated, this could result in a delayed control response to setpoint changes and feedforward action on measured disturbances. Conventional PID Design
  • 9.
    PIDPlus for WirelessHARTCommunications  To provide the best control for slow or variable measurement update rates, the PID must be modified to reflect the reset contribution for the expected process response since the last measurement update.  Control execution is set faster than measurement update. This permits immediate action on setpoint change and update in the faceplate.  PIDPlus is a standard feature of DeltaV v11.3 (released 2010) PIDPlus Design in DeltaV v11.3
  • 10.
    PIDPlus Reset (Integral)Calculation The filter output used in the positive feedback network is calculated in the following manner when a new measurement is received. PIDPlus tuning is based on the process dynamic (e.g. RESET= process time constant plus deadtime); PIDPlus reset automatically compensates for slow updates and variations in the measurement update rate. No change in GAIN is required for varying update rate.
  • 11.
    PIDPlus Modification forSetpoint Change Automatic compensation for setpoint change; measurement update rate. No need to modify tuning as sample rate changes No Yes PIDPlus –DeltaV v12.3 release in 2012
  • 12.
    PIDPlus Using WirelessTransmitter vs. Conventional PID and Wired Transmitter Lambda Tuning ʎ = 1.0 Variable communication Update Rate Control Setpoint PIDPlus Measurement PID PIDPlus Control Output PID Unmeasured Disturbance
  • 13.
    CONTROL PERFORMANCE DIFFERENCE  Communications transmissions are reduced by over 96 % using slower communication update rates.  The impact of slower updates and variations in measurement updates on control performance as measured by Integral of Absolute Error (IAE) is minimized through the use of PIDPlus for wireless communication. Communications/Control Number of IAE Communications Periodic/standard PI Controller 692 123 Update Using Wireless 25 159 communication/ PI Control
  • 14.
    PIDPlus - ModifiedDerivative Action No Yes
  • 15.
    PID Performance forLost Communications  The Conventional PID provides poor dynamic response when wireless communications are lost.  The PIDPlus improves the dynamic response under these conditions
  • 16.
    Wireless Communication Loss– During Setpoint Change Setpoint PIDPlus Control Measurement PID PIDPlus Control Output PID Communication Loss
  • 17.
    Wireless Communication Loss– During Process Disturbance PIDPlus Setpoint Control Measurement PID PIDPlus Control Output PID Communication Loss
  • 18.
    Testing PIDPlus –Communication’sSetup  For testing purposes, the WirelessHART communications and the process can be dynamically simulated in a DeltaV module for PID and PIDPlus control.  Communication setup is defined by the “Transmission” composite block.
  • 19.
    Installation at BroadleyJames  Portable Hyclone 100 liter disposable bioreactor  Rosemount WirelessHART gateway and transmitters for measurement and control of pH and temperature. Pressure monitored  BioNet is based on the DeltaV Control system.
  • 20.
    Installation at BroadleyJames (Cont)  Detail view of Rosemount pH WirelessHART Transmitter.  Battery powered – 3 to 5 year battery life expected for this application.
  • 21.
    Broadley James BioreactorSetup VSD VSD Media 37 oC VSD Inoculums TC TT 41-7 41-7 VSD Glutamine VSD VSD Bicarbonate Glucose Heater 7.0 pH AY AC AT AT Splitter AC 41-1 41-1 41-1 41-4s1 41-4s1 0.002 g/L pH Glucose 2.0 g/L AC AT AT AC 41-2 41-2 41-4s2 41-4s2 DO Glutamine 2.0 g/L AT AT AT 41-5x1 41-5x2 Bioreactor 41-6 Viable Dead Product Cells Cells CO2 MFC LT 41-14 AY Level Splitter VSD 41-2 O2 MFC Drain Air MFC
  • 22.
    Example - AutomaticallyIdentified Temperature Dynamics Using DeltaV Insight DeltaV Insight – Standard Since DeltaV v9.3
  • 23.
  • 24.
    Wireless pH LoopTest Results
  • 25.
    Elimination of GroundNoise Spikes Requirement: Tight pH control via 0.001 pH wireless resolution setting Temperature compensated wireless pH controlling at 6.9 pH set point Wired pH ground noise spike
  • 26.
    Separations Research Program, Universityof Texas at Austin  The Separations Research Program was established at the J.J. Pickle Research Campus in 1984  This cooperative industry/university program performs fundamental research of interest to chemical, biotechnological, petroleum refining, gas processing, pharmaceutical, and food companies.  CO2 removal from stack gas is a focus project for which WirelessHART transmitters were installed for pressure and steam flow control
  • 27.
    WirelessHART Transmitter  Standard WirelessHART pressure and flow transmitters were installed to demonstrate and test control using WirelessHART.  Standard WirelessHART pH transmitters are used to support studies associated with CO2 removal from stack gases.  Standard WirelessHART multi- element temperature transmitters are used to monitor absorber and stripper temperatures.
  • 28.
    Steam Flow ToStripper Heater
  • 29.
  • 30.
    PC215 On-line ColumnPressure Control  The same dynamic control Wired Measurement response was Used in Control observed for SP changes  Original plant PID tuning was used for both wired and wireless control GAIN=2.5 RESET=4 RATE=1 Wireless Measurement Used in Control
  • 31.
    Control Performance –Wired vs Wireless  Comparable control as measured by IAE LOOP FIC202 PC215 FIC202 PC215 was achieved using Selected Input Wired Wired Wireless Wireless WirelessHART Measurements and IAE 9134 145 10645 198 PIDPlus vs. control with wired Number of 13655 6649 1184 912 measurements and Communication PID. Test Time (sec) 6830 6829 5926 5925  The number of Test 1 Test 2 measurement samples with WirelessHART vs Wired transmitter was reduced by a factor of 10X for flow control and 6X for pressure control – accounting for differences in test duration.
  • 32.
    Separations Research Program, Universityof Texas at Austin  The Separations Research Program was established at the J.J. Pickle Research Campus in 1984  This cooperative industry/university program performs fundamental research of interest to chemical, biotechnological, petroleum refining, gas processing, pharmaceutical, and food companies.  CO2 removal from stack gas is a focus project for which WirelessHART transmitters were installed for pressure and steam flow control
  • 33.
  • 34.
    Future Product: 4300 SeriesWireless On/Off Control Release planned for the end of 2012 Currently in 7 End User Field Trials Sites  7 different applications  6 industrial market segments
  • 35.
    Business Results Achieved  The PIDPlus allows WirelessHART devices to be used for closed loop control of quality parameters that currently may not be available in the control system.  The reduction in process variability achieved through closed loop control may lead to improved process operation e.g. reduction in product quality variation, improved efficiency.  Field installations have documented robust control performance using the PIDPlus with WirelessHART transmitters. The results were shown for control of liquid flow, gas pressure, pH and temperature.
  • 36.
    Summary  WirelessHART measurements may be used in closed loop control applications. – Slower reporting minimizes power consumption  PIDPlus is a standard feature of DeltaV and works with standard WirelessHART devices. – Standard DeltaV Tools support Simulation and Tuning  The performance of PIDPlus in a wireless control network is comparable to PID with wired inputs – PIDPlus handles lost communications better than conventional PID.  PIDPlus tuning depends only upon process dynamics, not on wireless update rate
  • 37.
    Where To GetMore Information  PID Advances in Industrial Control, IFAC Conference on Advances in PID Control PID'12, Brescia, Italy, 28-30 March 2012 http://pid12.ing.unibs.it/sp_blevins.html  DeltaV v11 PID Enhancements for Wireless, DeltaV Whitepaper, August, 2010 http://www2.emersonprocess.com/siteadmincenter/PM%20DeltaV%20Documents/Whitepap ers/WP_DeltaV%20PID%20Enhancements%20for%20Wireless.pdf  WirelessHART Successfully Handles Control, Chemical Processing, January, 2011 http://www2.emersonprocess.com/siteadmincenter/PM%20Articles/WirelessHART%20Succ essfully%20Handles%20Control.pdf  Wireless – Overcoming Challenges of PID Control& Analyzer Applications, InTech, July/August, 2010 http://www.isa.org/InTechTemplate.cfm?template=/ContentManagement/ContentDisplay.cfm &ContentID=83041  PIDPlus An Enhanced PID Control Algorithm for Wireless Automation, AS-74.3199 Wireless Automation, Aalto University, Finland http://autsys.tkk.fi/intranet/as-0.3200/attach/S09- 19/loppuraportti.pdf  Incorporating Wireless Devices into Single-Use Disposable Bioreactor Design, 2009 Dhirubhai Ambani Life Sciences Symposium http://www.modelingandcontrol.com/Wireless- Devices-in-Single-Use-Bioreactors.pdf  Improving PID Control with Unreliable Communications, ISA EXPO Technical Conference, 2006. http://www.automation.com/pdf_articles/10_improving_pid.pdf  Similarity-based Traffic Reduction to Increase Battery Life in a Wireless Process Control Network, ISA EXPO2005, Houston, TX www.cs.utexas.edu/~sjp/publications/isa06.doc