ACTION: Apply the theory of power circuits and transformers.
CONDITIONS: Given a LabVolt EMS system, LabVolt courseware,
Fluke electrical metering devices, and applicable references.
STANDARD: Effectively use transformers and power circuits theory to
solve complex engineering problems in an austere environment.
UNCLASSIFIED
UNCLASSIFIED
• Safety Requirements: None
• Risk Assessment Level: Low
• Environmental Considerations: None
• Evaluation: Students will be evaluated on this
block of instruction during the Electrical Systems
Design Examination 1. Students must receive a
score of 80 percent or above to receive a GO.
UNCLASSIFIED
UNCLASSIFIED
FESTO Electrical Power Technology Using Data Acquisition:
Power Circuits and Transformers
UNCLASSIFIED
UNCLASSIFIED
ACTION: Understand Three-Phase Transformers
CONDITIONS: Given a LabVolt EMS system, LabVolt courseware,
Fluke electrical metering devices, and applicable references.
STANDARD: Understand the operating characteristics of three- phase
transformers. You will be able to connect transformer windings in wye
and delta configurations, and verify that windings are connected with
the proper phase relationships. Voltage and current measurements will
be used to study transformer operation and working characteristics.
UNCLASSIFIED
UNCLASSIFIED
• When you have completed this unit, you will be familiar with
operating characteristics of three-phase transformers.
• You will be able to connect transformer windings in wye
and delta configurations, and verify that windings are
connected with the proper phase relationships.
• Voltage and current measurements will be used to study
transformer operation and working characteristics.
S3D03-6
Lesson Objectives
UNCLASSIFIED
UNCLASSIFIED
• Many of the concepts used in this unit were seen in Unit 6,
and it may be useful to review its contents to ensure better
understanding of the material presented here.
• The main features of three-phase circuits that are important
to recall are that there are two types of connections, wye
and delta.
• Furthermore, in wye-connected three-phase circuits, the
line voltages are greater than the phase voltages by the
factor √3 and the line and phase currents are equal.
• On the other hand, in delta-connected three-phase circuits,
the line currents are greater than the phase currents by the
factor √3 and the line and phase voltages are equal.
UNCLASSIFIED
UNCLASSIFIED
• Many of the concepts used in this unit were seen in Unit 6,
and it may be useful to review its contents to ensure better
understanding of the material presented here.
• The main features of three-phase circuits that are important
to recall are that there are two types of connections, wye
and delta.
• Furthermore, in wye-connected three-phase circuits, the
line voltages are greater than the phase voltages by the
factor √3 and the line and phase currents are equal.
• On the other hand, in delta-connected three-phase circuits,
the line currents are greater than the phase currents by the
factor √3 and the line and phase voltages are equal.
UNCLASSIFIED
UNCLASSIFIED
• A three-phase transformer can be a single unit or three
single-phase units, and the primary and secondary
windings can be connected in either wye or delta to give
four types of connections, delta-delta, wye-wye, delta-
wye, and wye-delta.
• Usually, three-phase power systems have a line voltage of
208 V (380 V or 415 V in some countries), and standard
120-V voltage (220 V or 240 V in some countries) can be
obtained between a line wire and the neutral wire as shown
in Figure 9-1.
UNCLASSIFIED
UNCLASSIFIED
• The wye-connected secondary provides three-phase
120/208-V power using 4 wires as shown, and the primary
side of the transformer may be connected in delta like in
the figure, or in wye.
• One big advantage of using a delta configuration for the
primary is that only three wires are needed to distribute the
three phases.
UNCLASSIFIED
UNCLASSIFIED
• An advantage of a delta-delta connection is that two single-
phase transformers (instead of three) can be operated in
what is known as the open-delta or "V" configuration if one
of the three transformers becomes damaged or is removed
from service.
• The open-delta transformer bank still delivers phase
voltages and currents in the correct relationship, but the
capacity of the bank is reduced to 57.7% (1⁄√3) of the total
nominal capacity available with three transformers in
service.
UNCLASSIFIED
UNCLASSIFIED
• In the delta-delta and wye-wye configurations, the line
voltage at the secondary is equal to the line voltage at the
primary times the inverse of the turns ratio.
• In the delta-wye configuration, the line voltage at the
secondary is equal to the line voltage at the primary times
the inverse of the turn ratio times √3.
• In the wye-delta configuration, the line voltage at the
secondary is equal to the line voltage at the primary times
the inverse of the turn ratio times 1⁄√3.
UNCLASSIFIED
UNCLASSIFIED
• Regardless of how the windings in a three-phase
transformer are connected, precautions must be taken to
ensure that the secondaries are connected with the proper
phase relationships.
• For a wye configuration, this means that the voltage
measured across any two secondary windings (line
voltage) must be √3 times greater than the voltage across
either winding (phase voltage).
• If not, the connections must be reversed before continuing.
UNCLASSIFIED
UNCLASSIFIED
• With a delta configuration, the voltage measured between
the ends of two series-connected secondary windings must
equal the voltage across either winding.
• If not, the connections must be reversed.
• When one end of the third winding is connected, the
voltage measured across all three series-connected
windings must equal zero before connecting them together
to close the delta.
• It is extremely important to verify that the voltage within the
delta equals zero before the delta is closed.
• If not, the resulting current will be very high and damage
the windings.
UNCLASSIFIED
UNCLASSIFIED
• When you have completed this exercise, you will be able to connect
three-phase transformers in delta-delta and wye-wye configurations.
• You will measure winding voltages to verify that the secondary
windings are connected with the proper phase relationships, and you
will verify that the voltage within a delta equals zero before the delta
is closed.
LSA 1: Three-Phase Transformer Connections
Time: 4 hrs
PE: 50 mins
Check on Learning: Blackboard Quiz 9-1
UNCLASSIFIED
UNCLASSIFIED
• As mentioned earlier, four common ways of connecting
transformer windings to form a three-phase transformer are:
• delta-delta
• wye-wye
• delta-wye
• Wye-delta
• As seen in Unit 6, in order to set up a wye connection, first
connect the three components (windings) together at a common
point for interconnection with the neutral wire, then connect the
other end of each component in turn to the three line wires.
• To set up a delta connection, connect the first component in
series with the second, the second in series with the third, and
the third in series with the first to close the delta loop.
• The three line wires are then separately connected to each of the
junction nodes in the delta loop.
UNCLASSIFIED
UNCLASSIFIED
• As mentioned earlier, four common ways of connecting
transformer windings to form a three-phase transformer are:
• delta-delta
• wye-wye
• delta-wye
• Wye-delta
• As seen in Unit 6, in order to set up a wye connection, first
connect the three components (windings) together at a common
point for interconnection with the neutral wire, then connect the
other end of each component in turn to the three line wires.
• To set up a delta connection, connect the first component in
series with the second, the second in series with the third, and
the third in series with the first to close the delta loop.
• The three line wires are then separately connected to each of the
junction nodes in the delta loop.
UNCLASSIFIED
UNCLASSIFIED
• As mentioned earlier, four common ways of connecting
transformer windings to form a three-phase transformer are:
• delta-delta
• wye-wye
• delta-wye
• Wye-delta
• As seen in Unit 6, in order to set up a wye connection, first
connect the three components (windings) together at a common
point for interconnection with the neutral wire, then connect the
other end of each component in turn to the three line wires.
• To set up a delta connection, connect the first component in
series with the second, the second in series with the third, and
the third in series with the first to close the delta loop.
• The three line wires are then separately connected to each of the
junction nodes in the delta loop.
UNCLASSIFIED
UNCLASSIFIED
• Before a three-phase transformer
is put into service, the phase
relationships must be verified.
• For a wye configuration, the line
voltages at the secondary
windings must all be √3 times
greater than the corresponding
phase voltages.
• If not, winding connections must
be reversed.
UNCLASSIFIED
UNCLASSIFIED
• To verify that phase relationships are correct for a wye
configuration, the voltage between two windings (EAB) is measured
as shown in Figure 9-4a to confirm that it is √3 times greater than
the line-to-neutral voltage across either winding (for example EAN).
• The voltages between the third winding and the others (EBCand
ECA) are then measured to confirm that they are also √3 times
greater than the phase voltage (EAN), as shown in Figure 9-4b.
UNCLASSIFIED
UNCLASSIFIED
• For a delta configuration, the line voltages at the secondary
windings must all be equal.
• If not, winding connections must be reversed.
• To verify that phase relationships are correct for a delta
configuration, the voltage across two series-connected
windings (ECA) is measured as shown in Figure 9-5a to
confirm that it is equal to the voltage across either winding
(EAB and EBC).
UNCLASSIFIED
UNCLASSIFIED
• The third winding is then connected in series, and the voltage
across the series combination of the three windings is measured to
confirm that it is zero before the delta is closed, as shown in Figure
9-5b.
• This is extremely important for a delta configuration, because a
very high short-circuit current will flow if the voltage within the delta
is not equal to zero when it is closed.
UNCLASSIFIED
UNCLASSIFIED
• Conduct Lab 9-1
• Complete Quiz 9-1
UNCLASSIFIED
UNCLASSIFIED
• In this exercise, you connected transformer windings in
three-phase delta-delta and wye-wye configurations, and
measured winding voltages to ensure that secondary
windings were connected with the proper phase
relationships.
• You confirmed that the voltage within a delta was zero
before closing the delta, and that the delta-delta and wye-
wye configurations produced no phase shift between the
incoming primary voltages and the outgoing secondary
voltages.
UNCLASSIFIED
UNCLASSIFIED
Voltage and Current Relationships
Time: 1 hr 25 min
Practical Exercise: 25 min
Check on Learning: Blackboard Quiz 9-2
UNCLASSIFIED
UNCLASSIFIED
• The 30° phase shift between the primary and secondary does not create any
problems for isolated groups of loads connected to the outgoing lines from the
secondary.
• However, if the outgoing lines from the secondary of a three-phase transformer
have to be connected in parallel with another source, the phase shift might
make such a parallel connection impossible, even if the line voltages are the
same.
• Recall that in order for three-phase circuits and sources to be connected in
parallel, line voltages must be equal, have the same phase sequence, and be
in phase when the parallel connection is made.
UNCLASSIFIED
UNCLASSIFIED
• Figure 9-8 shows a three-phase transformer, with a turns ratio equal to 1:1,
connected in the delta-wye configuration and feeding a three-phase load.
• The voltage across each primary winding EPRI equals the incoming line voltage,
but the outgoing line voltage ESEC is √3 times that voltage because the voltage
across any two secondary windings is √3 times greater than the voltage across
a single secondary winding.
• Note that if the three-phase transformer had a turns ratio of 1:10, the line
voltage at the secondary would be 10 x √3 times greater the line voltage at the
primary, because the inverse of the turns ratio is multiplied by the √3 factor.
• The line current in the secondary is the same as the phase current, but the line
current in the primary is √3 times greater than the corresponding phase current.
UNCLASSIFIED
UNCLASSIFIED
• Conduct Lab 9-2
• Complete Quiz 9-2
UNCLASSIFIED
UNCLASSIFIED
• In this exercise, you connected a 1:1 three-phase
transformer in wye-delta and delta-wye configurations, and
saw that the line voltage between primary and secondary
either increased or decreased by a √3 factor.
• You also confirmed that the outgoing line voltages at the
secondary were shifted 30° with respect to the incoming
line voltages at the primary.
UNCLASSIFIED
UNCLASSIFIED
Open-Delta Connection
Time: 1 hr 25 min
Practical Exercise: 25 min
Check on Learning: Blackboard Quiz 9-3
UNCLASSIFIED
UNCLASSIFIED
• When you have completed this exercise, you will be able to connect two
transformers in an open-delta configuration to supply a balanced three-phase
load.
• You will also be able to demonstrate that the maximum power in the open-delta
configuration is 57.7% (1⁄√3) the capacity of a normal delta-delta configuration.
UNCLASSIFIED
UNCLASSIFIED
• The open-delta connection allows three-phase balanced loads to be supplied
using only two transformers.
• This configuration is useful if the amount of load power is not excessive, or
when one of the three transformers must be taken out of service because of
damage or some other reason.
• The most important thing to note is that the power capacity in the open-delta
configuration is 57.7% of the total capacity of the normal delta-delta
configuration, or 86.6% of the capacity of the two remaining transformers.
UNCLASSIFIED
UNCLASSIFIED
• The reason for this is quite simple, and Figure 9-11 will be used to illustrate the
explanation.
UNCLASSIFIED
UNCLASSIFIED
• In a standard delta configuration, the line current is √3 times greater
than the current flowing in the phase winding.
• When one of the transformers is absent, full line current flows through
the phase windings, since line and phase currents are the same in an
open-delta configuration.
• The large increase in current will cause the phase windings to overheat
and will damage the transformer unless load power is reduced.
• The line current must therefore be reduced by √3, meaning that the
power capacity in the open-delta configuration is limited to 57.7% of the
power capacity normal delta-delta configuration.
UNCLASSIFIED
UNCLASSIFIED
• The following example illustrates the calculation of maximum power.
• When three 50-kVA transformers are connected in delta-delta configuration, the
total capacity of the bank is their sum, or 150 kVA.
• For two transformers in an open-delta configuration, the capacity is 150
kVA⁄√3, or 86.6 kVA, which is the same as 86.6% of the total capacity of two
transformers (0.866 x 100 kVA = 86.6 kVA).
UNCLASSIFIED
UNCLASSIFIED
• Conduct Lab 9-3
• Complete Quiz 9-3
UNCLASSIFIED
UNCLASSIFIED
• In this exercise, you set up a three-phase transformer in the
open-delta configuration and observed that it supplies a
three-phase load with voltages and currents in the proper
phase relationships.
• You also demonstrated that load power must be reduced by
57.7% (1⁄√3) to avoid exceeding the current rating of the
phase windings.
UNCLASSIFIED
UNCLASSIFIED
Check on Learning:
Complete Unit 9 Quiz on Blackboard
UNCLASSIFIED
UNCLASSIFIED
• The Autotransformer
• Transformers in Parallel
• Distribution Transformers

More Related Content

What's hot

Polyphase circuit vbr
Polyphase circuit   vbrPolyphase circuit   vbr
Polyphase circuit vbr
Vijay Raskar
 
Delta star relationship (1)
Delta star relationship (1)Delta star relationship (1)
Delta star relationship (1)
140120109032
 
Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3
Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3
Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3
Raghvendra Tiwari
 

What's hot (20)

Three phase-circuits
Three phase-circuitsThree phase-circuits
Three phase-circuits
 
Transformer single phase and three phase
Transformer single phase and three phaseTransformer single phase and three phase
Transformer single phase and three phase
 
Polyphase circuit vbr
Polyphase circuit   vbrPolyphase circuit   vbr
Polyphase circuit vbr
 
Transmission lines
Transmission linesTransmission lines
Transmission lines
 
Representation of short & medium transmission lines
Representation of short & medium transmission linesRepresentation of short & medium transmission lines
Representation of short & medium transmission lines
 
3phase circuits
3phase circuits3phase circuits
3phase circuits
 
Capacitance on transmission line
Capacitance on transmission lineCapacitance on transmission line
Capacitance on transmission line
 
153010010 mohammad babor
153010010  mohammad  babor153010010  mohammad  babor
153010010 mohammad babor
 
Star & Delta Connection
Star & Delta ConnectionStar & Delta Connection
Star & Delta Connection
 
Delta star relationship (1)
Delta star relationship (1)Delta star relationship (1)
Delta star relationship (1)
 
Ch11 polyphase
Ch11 polyphaseCh11 polyphase
Ch11 polyphase
 
transmission line
transmission line transmission line
transmission line
 
3 phase ac
3 phase ac3 phase ac
3 phase ac
 
1.6 three phase power measurement
1.6 three phase power measurement1.6 three phase power measurement
1.6 three phase power measurement
 
Three phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generatorsThree phase balanced load circuits and synchronous generators
Three phase balanced load circuits and synchronous generators
 
Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3
Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3
Powerpoint slides to_chapter_12_three_phase_circuits_and_systems-corrected3
 
Power system calculations
Power system calculationsPower system calculations
Power system calculations
 
short transmission line
short transmission lineshort transmission line
short transmission line
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
 
Three phase System
Three phase SystemThree phase System
Three phase System
 

Similar to 120A-WOBC H06 elo i

Power Circuits and Transforers-Unit 9 Labvolt Student Manual
Power Circuits and Transforers-Unit 9 Labvolt Student ManualPower Circuits and Transforers-Unit 9 Labvolt Student Manual
Power Circuits and Transforers-Unit 9 Labvolt Student Manual
phase3-120A
 
Polyphase circuit electrical maintenace
Polyphase circuit   electrical maintenacePolyphase circuit   electrical maintenace
Polyphase circuit electrical maintenace
Vijay Raskar
 
unit-1-Three phase circuits and power systems.pptx
unit-1-Three phase circuits and power systems.pptxunit-1-Three phase circuits and power systems.pptx
unit-1-Three phase circuits and power systems.pptx
deepaMS4
 
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student ManualPower Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
phase3-120A
 
power system 1 unit 5 contains for various faults & circuit breakers
power system 1 unit 5 contains for various faults & circuit breakerspower system 1 unit 5 contains for various faults & circuit breakers
power system 1 unit 5 contains for various faults & circuit breakers
monikavardia
 

Similar to 120A-WOBC H06 elo i (20)

Power Circuits and Transforers-Unit 9 Labvolt Student Manual
Power Circuits and Transforers-Unit 9 Labvolt Student ManualPower Circuits and Transforers-Unit 9 Labvolt Student Manual
Power Circuits and Transforers-Unit 9 Labvolt Student Manual
 
Unit 9 Labvolt Student Manual
Unit 9 Labvolt Student ManualUnit 9 Labvolt Student Manual
Unit 9 Labvolt Student Manual
 
Three Phase Transformer Connections.pptx
Three Phase Transformer Connections.pptxThree Phase Transformer Connections.pptx
Three Phase Transformer Connections.pptx
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
 
120A-WOBC H06 elo h
120A-WOBC H06 elo h120A-WOBC H06 elo h
120A-WOBC H06 elo h
 
ELECTRICAL WIRING.pptx
ELECTRICAL WIRING.pptxELECTRICAL WIRING.pptx
ELECTRICAL WIRING.pptx
 
BEEIE UNIT 3 PPT -24-5-2021.pptx
BEEIE UNIT 3 PPT -24-5-2021.pptxBEEIE UNIT 3 PPT -24-5-2021.pptx
BEEIE UNIT 3 PPT -24-5-2021.pptx
 
THREE PHASE TRANSFORMERS
THREE PHASE TRANSFORMERSTHREE PHASE TRANSFORMERS
THREE PHASE TRANSFORMERS
 
Polyphase circuit electrical maintenace
Polyphase circuit   electrical maintenacePolyphase circuit   electrical maintenace
Polyphase circuit electrical maintenace
 
unit-1-Three phase circuits and power systems.pptx
unit-1-Three phase circuits and power systems.pptxunit-1-Three phase circuits and power systems.pptx
unit-1-Three phase circuits and power systems.pptx
 
H06 elo g
H06 elo g H06 elo g
H06 elo g
 
Transformers TR.pptx
Transformers TR.pptxTransformers TR.pptx
Transformers TR.pptx
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdf
 
Lecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdfLecture Notes ELE A6.pdf
Lecture Notes ELE A6.pdf
 
Three phase transformer ( vector groups)
Three phase  transformer ( vector groups)Three phase  transformer ( vector groups)
Three phase transformer ( vector groups)
 
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student ManualPower Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
 
Wattmeter
WattmeterWattmeter
Wattmeter
 
power system 1 unit 5 contains for various faults & circuit breakers
power system 1 unit 5 contains for various faults & circuit breakerspower system 1 unit 5 contains for various faults & circuit breakers
power system 1 unit 5 contains for various faults & circuit breakers
 
LEC2 j.pdf
LEC2                               j.pdfLEC2                               j.pdf
LEC2 j.pdf
 

More from phase3-120A

Power Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student ManualPower Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student Manual
phase3-120A
 
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student ManualPower Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
phase3-120A
 
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student ManualPower Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
phase3-120A
 
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student ManualPower Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
phase3-120A
 
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student ManualPower Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
phase3-120A
 
Power Circuits and Transforers-Unit 1 Labvolt Student Manual
Power Circuits and Transforers-Unit 1 Labvolt Student ManualPower Circuits and Transforers-Unit 1 Labvolt Student Manual
Power Circuits and Transforers-Unit 1 Labvolt Student Manual
phase3-120A
 
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student ManualPower Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
phase3-120A
 

More from phase3-120A (20)

Power Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student ManualPower Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student Manual
 
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student ManualPower Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
 
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student ManualPower Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
 
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student ManualPower Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
 
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student ManualPower Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
 
Power Circuits and Transforers-Unit 1 Labvolt Student Manual
Power Circuits and Transforers-Unit 1 Labvolt Student ManualPower Circuits and Transforers-Unit 1 Labvolt Student Manual
Power Circuits and Transforers-Unit 1 Labvolt Student Manual
 
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student ManualPower Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
 
H21 operational energy
H21 operational energyH21 operational energy
H21 operational energy
 
120A beb PE occupation plans
 120A beb PE occupation plans 120A beb PE occupation plans
120A beb PE occupation plans
 
H07 Power Load Survey
H07 Power Load SurveyH07 Power Load Survey
H07 Power Load Survey
 
H33 ac dc motors and generators
H33 ac dc motors and generatorsH33 ac dc motors and generators
H33 ac dc motors and generators
 
H09 Building Level Design
H09 Building Level DesignH09 Building Level Design
H09 Building Level Design
 
H08 Principles of Power Systems Design
H08 Principles of Power Systems Design H08 Principles of Power Systems Design
H08 Principles of Power Systems Design
 
Civil 3d surface import
Civil 3d surface importCivil 3d surface import
Civil 3d surface import
 
Career maps for da pam 600 3 update
Career maps for da pam 600 3 updateCareer maps for da pam 600 3 update
Career maps for da pam 600 3 update
 
Fall 2018 engineer branch newsletter
Fall 2018 engineer branch newsletterFall 2018 engineer branch newsletter
Fall 2018 engineer branch newsletter
 
Act career maps (warrant officer) en-us-120 a
Act career maps (warrant officer) en-us-120 aAct career maps (warrant officer) en-us-120 a
Act career maps (warrant officer) en-us-120 a
 
120A- WOBC H05 Electrical safety day 3
120A- WOBC H05 Electrical safety day 3120A- WOBC H05 Electrical safety day 3
120A- WOBC H05 Electrical safety day 3
 
120A- WOBC H05 Electrical safety day 2
120A- WOBC H05 Electrical safety day 2120A- WOBC H05 Electrical safety day 2
120A- WOBC H05 Electrical safety day 2
 
120A- WOBC H05 Electrical safety day 1
120A- WOBC H05 Electrical safety day 1120A- WOBC H05 Electrical safety day 1
120A- WOBC H05 Electrical safety day 1
 

Recently uploaded

Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 

Recently uploaded (20)

School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Electromagnetic relays used for power system .pptx
Electromagnetic relays used for power system .pptxElectromagnetic relays used for power system .pptx
Electromagnetic relays used for power system .pptx
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
Path loss model, OKUMURA Model, Hata Model
Path loss model, OKUMURA Model, Hata ModelPath loss model, OKUMURA Model, Hata Model
Path loss model, OKUMURA Model, Hata Model
 
Memory Interfacing of 8086 with DMA 8257
Memory Interfacing of 8086 with DMA 8257Memory Interfacing of 8086 with DMA 8257
Memory Interfacing of 8086 with DMA 8257
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Post office management system project ..pdf
Post office management system project ..pdfPost office management system project ..pdf
Post office management system project ..pdf
 
Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)
 
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptx
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Signal Processing and Linear System Analysis
Signal Processing and Linear System AnalysisSignal Processing and Linear System Analysis
Signal Processing and Linear System Analysis
 
Introduction to Geographic Information Systems
Introduction to Geographic Information SystemsIntroduction to Geographic Information Systems
Introduction to Geographic Information Systems
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 

120A-WOBC H06 elo i

  • 2. UNCLASSIFIED UNCLASSIFIED ACTION: Apply the theory of power circuits and transformers. CONDITIONS: Given a LabVolt EMS system, LabVolt courseware, Fluke electrical metering devices, and applicable references. STANDARD: Effectively use transformers and power circuits theory to solve complex engineering problems in an austere environment.
  • 3. UNCLASSIFIED UNCLASSIFIED • Safety Requirements: None • Risk Assessment Level: Low • Environmental Considerations: None • Evaluation: Students will be evaluated on this block of instruction during the Electrical Systems Design Examination 1. Students must receive a score of 80 percent or above to receive a GO.
  • 4. UNCLASSIFIED UNCLASSIFIED FESTO Electrical Power Technology Using Data Acquisition: Power Circuits and Transformers
  • 5. UNCLASSIFIED UNCLASSIFIED ACTION: Understand Three-Phase Transformers CONDITIONS: Given a LabVolt EMS system, LabVolt courseware, Fluke electrical metering devices, and applicable references. STANDARD: Understand the operating characteristics of three- phase transformers. You will be able to connect transformer windings in wye and delta configurations, and verify that windings are connected with the proper phase relationships. Voltage and current measurements will be used to study transformer operation and working characteristics.
  • 6. UNCLASSIFIED UNCLASSIFIED • When you have completed this unit, you will be familiar with operating characteristics of three-phase transformers. • You will be able to connect transformer windings in wye and delta configurations, and verify that windings are connected with the proper phase relationships. • Voltage and current measurements will be used to study transformer operation and working characteristics. S3D03-6 Lesson Objectives
  • 7. UNCLASSIFIED UNCLASSIFIED • Many of the concepts used in this unit were seen in Unit 6, and it may be useful to review its contents to ensure better understanding of the material presented here. • The main features of three-phase circuits that are important to recall are that there are two types of connections, wye and delta. • Furthermore, in wye-connected three-phase circuits, the line voltages are greater than the phase voltages by the factor √3 and the line and phase currents are equal. • On the other hand, in delta-connected three-phase circuits, the line currents are greater than the phase currents by the factor √3 and the line and phase voltages are equal.
  • 8. UNCLASSIFIED UNCLASSIFIED • Many of the concepts used in this unit were seen in Unit 6, and it may be useful to review its contents to ensure better understanding of the material presented here. • The main features of three-phase circuits that are important to recall are that there are two types of connections, wye and delta. • Furthermore, in wye-connected three-phase circuits, the line voltages are greater than the phase voltages by the factor √3 and the line and phase currents are equal. • On the other hand, in delta-connected three-phase circuits, the line currents are greater than the phase currents by the factor √3 and the line and phase voltages are equal.
  • 9. UNCLASSIFIED UNCLASSIFIED • A three-phase transformer can be a single unit or three single-phase units, and the primary and secondary windings can be connected in either wye or delta to give four types of connections, delta-delta, wye-wye, delta- wye, and wye-delta. • Usually, three-phase power systems have a line voltage of 208 V (380 V or 415 V in some countries), and standard 120-V voltage (220 V or 240 V in some countries) can be obtained between a line wire and the neutral wire as shown in Figure 9-1.
  • 10. UNCLASSIFIED UNCLASSIFIED • The wye-connected secondary provides three-phase 120/208-V power using 4 wires as shown, and the primary side of the transformer may be connected in delta like in the figure, or in wye. • One big advantage of using a delta configuration for the primary is that only three wires are needed to distribute the three phases.
  • 11. UNCLASSIFIED UNCLASSIFIED • An advantage of a delta-delta connection is that two single- phase transformers (instead of three) can be operated in what is known as the open-delta or "V" configuration if one of the three transformers becomes damaged or is removed from service. • The open-delta transformer bank still delivers phase voltages and currents in the correct relationship, but the capacity of the bank is reduced to 57.7% (1⁄√3) of the total nominal capacity available with three transformers in service.
  • 12. UNCLASSIFIED UNCLASSIFIED • In the delta-delta and wye-wye configurations, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turns ratio. • In the delta-wye configuration, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turn ratio times √3. • In the wye-delta configuration, the line voltage at the secondary is equal to the line voltage at the primary times the inverse of the turn ratio times 1⁄√3.
  • 13. UNCLASSIFIED UNCLASSIFIED • Regardless of how the windings in a three-phase transformer are connected, precautions must be taken to ensure that the secondaries are connected with the proper phase relationships. • For a wye configuration, this means that the voltage measured across any two secondary windings (line voltage) must be √3 times greater than the voltage across either winding (phase voltage). • If not, the connections must be reversed before continuing.
  • 14. UNCLASSIFIED UNCLASSIFIED • With a delta configuration, the voltage measured between the ends of two series-connected secondary windings must equal the voltage across either winding. • If not, the connections must be reversed. • When one end of the third winding is connected, the voltage measured across all three series-connected windings must equal zero before connecting them together to close the delta. • It is extremely important to verify that the voltage within the delta equals zero before the delta is closed. • If not, the resulting current will be very high and damage the windings.
  • 15. UNCLASSIFIED UNCLASSIFIED • When you have completed this exercise, you will be able to connect three-phase transformers in delta-delta and wye-wye configurations. • You will measure winding voltages to verify that the secondary windings are connected with the proper phase relationships, and you will verify that the voltage within a delta equals zero before the delta is closed. LSA 1: Three-Phase Transformer Connections Time: 4 hrs PE: 50 mins Check on Learning: Blackboard Quiz 9-1
  • 16. UNCLASSIFIED UNCLASSIFIED • As mentioned earlier, four common ways of connecting transformer windings to form a three-phase transformer are: • delta-delta • wye-wye • delta-wye • Wye-delta • As seen in Unit 6, in order to set up a wye connection, first connect the three components (windings) together at a common point for interconnection with the neutral wire, then connect the other end of each component in turn to the three line wires. • To set up a delta connection, connect the first component in series with the second, the second in series with the third, and the third in series with the first to close the delta loop. • The three line wires are then separately connected to each of the junction nodes in the delta loop.
  • 17. UNCLASSIFIED UNCLASSIFIED • As mentioned earlier, four common ways of connecting transformer windings to form a three-phase transformer are: • delta-delta • wye-wye • delta-wye • Wye-delta • As seen in Unit 6, in order to set up a wye connection, first connect the three components (windings) together at a common point for interconnection with the neutral wire, then connect the other end of each component in turn to the three line wires. • To set up a delta connection, connect the first component in series with the second, the second in series with the third, and the third in series with the first to close the delta loop. • The three line wires are then separately connected to each of the junction nodes in the delta loop.
  • 18. UNCLASSIFIED UNCLASSIFIED • As mentioned earlier, four common ways of connecting transformer windings to form a three-phase transformer are: • delta-delta • wye-wye • delta-wye • Wye-delta • As seen in Unit 6, in order to set up a wye connection, first connect the three components (windings) together at a common point for interconnection with the neutral wire, then connect the other end of each component in turn to the three line wires. • To set up a delta connection, connect the first component in series with the second, the second in series with the third, and the third in series with the first to close the delta loop. • The three line wires are then separately connected to each of the junction nodes in the delta loop.
  • 19. UNCLASSIFIED UNCLASSIFIED • Before a three-phase transformer is put into service, the phase relationships must be verified. • For a wye configuration, the line voltages at the secondary windings must all be √3 times greater than the corresponding phase voltages. • If not, winding connections must be reversed.
  • 20. UNCLASSIFIED UNCLASSIFIED • To verify that phase relationships are correct for a wye configuration, the voltage between two windings (EAB) is measured as shown in Figure 9-4a to confirm that it is √3 times greater than the line-to-neutral voltage across either winding (for example EAN). • The voltages between the third winding and the others (EBCand ECA) are then measured to confirm that they are also √3 times greater than the phase voltage (EAN), as shown in Figure 9-4b.
  • 21. UNCLASSIFIED UNCLASSIFIED • For a delta configuration, the line voltages at the secondary windings must all be equal. • If not, winding connections must be reversed. • To verify that phase relationships are correct for a delta configuration, the voltage across two series-connected windings (ECA) is measured as shown in Figure 9-5a to confirm that it is equal to the voltage across either winding (EAB and EBC).
  • 22. UNCLASSIFIED UNCLASSIFIED • The third winding is then connected in series, and the voltage across the series combination of the three windings is measured to confirm that it is zero before the delta is closed, as shown in Figure 9-5b. • This is extremely important for a delta configuration, because a very high short-circuit current will flow if the voltage within the delta is not equal to zero when it is closed.
  • 23. UNCLASSIFIED UNCLASSIFIED • Conduct Lab 9-1 • Complete Quiz 9-1
  • 24. UNCLASSIFIED UNCLASSIFIED • In this exercise, you connected transformer windings in three-phase delta-delta and wye-wye configurations, and measured winding voltages to ensure that secondary windings were connected with the proper phase relationships. • You confirmed that the voltage within a delta was zero before closing the delta, and that the delta-delta and wye- wye configurations produced no phase shift between the incoming primary voltages and the outgoing secondary voltages.
  • 25. UNCLASSIFIED UNCLASSIFIED Voltage and Current Relationships Time: 1 hr 25 min Practical Exercise: 25 min Check on Learning: Blackboard Quiz 9-2
  • 26. UNCLASSIFIED UNCLASSIFIED • The 30° phase shift between the primary and secondary does not create any problems for isolated groups of loads connected to the outgoing lines from the secondary. • However, if the outgoing lines from the secondary of a three-phase transformer have to be connected in parallel with another source, the phase shift might make such a parallel connection impossible, even if the line voltages are the same. • Recall that in order for three-phase circuits and sources to be connected in parallel, line voltages must be equal, have the same phase sequence, and be in phase when the parallel connection is made.
  • 27. UNCLASSIFIED UNCLASSIFIED • Figure 9-8 shows a three-phase transformer, with a turns ratio equal to 1:1, connected in the delta-wye configuration and feeding a three-phase load. • The voltage across each primary winding EPRI equals the incoming line voltage, but the outgoing line voltage ESEC is √3 times that voltage because the voltage across any two secondary windings is √3 times greater than the voltage across a single secondary winding. • Note that if the three-phase transformer had a turns ratio of 1:10, the line voltage at the secondary would be 10 x √3 times greater the line voltage at the primary, because the inverse of the turns ratio is multiplied by the √3 factor. • The line current in the secondary is the same as the phase current, but the line current in the primary is √3 times greater than the corresponding phase current.
  • 28. UNCLASSIFIED UNCLASSIFIED • Conduct Lab 9-2 • Complete Quiz 9-2
  • 29. UNCLASSIFIED UNCLASSIFIED • In this exercise, you connected a 1:1 three-phase transformer in wye-delta and delta-wye configurations, and saw that the line voltage between primary and secondary either increased or decreased by a √3 factor. • You also confirmed that the outgoing line voltages at the secondary were shifted 30° with respect to the incoming line voltages at the primary.
  • 30. UNCLASSIFIED UNCLASSIFIED Open-Delta Connection Time: 1 hr 25 min Practical Exercise: 25 min Check on Learning: Blackboard Quiz 9-3
  • 31. UNCLASSIFIED UNCLASSIFIED • When you have completed this exercise, you will be able to connect two transformers in an open-delta configuration to supply a balanced three-phase load. • You will also be able to demonstrate that the maximum power in the open-delta configuration is 57.7% (1⁄√3) the capacity of a normal delta-delta configuration.
  • 32. UNCLASSIFIED UNCLASSIFIED • The open-delta connection allows three-phase balanced loads to be supplied using only two transformers. • This configuration is useful if the amount of load power is not excessive, or when one of the three transformers must be taken out of service because of damage or some other reason. • The most important thing to note is that the power capacity in the open-delta configuration is 57.7% of the total capacity of the normal delta-delta configuration, or 86.6% of the capacity of the two remaining transformers.
  • 33. UNCLASSIFIED UNCLASSIFIED • The reason for this is quite simple, and Figure 9-11 will be used to illustrate the explanation.
  • 34. UNCLASSIFIED UNCLASSIFIED • In a standard delta configuration, the line current is √3 times greater than the current flowing in the phase winding. • When one of the transformers is absent, full line current flows through the phase windings, since line and phase currents are the same in an open-delta configuration. • The large increase in current will cause the phase windings to overheat and will damage the transformer unless load power is reduced. • The line current must therefore be reduced by √3, meaning that the power capacity in the open-delta configuration is limited to 57.7% of the power capacity normal delta-delta configuration.
  • 35. UNCLASSIFIED UNCLASSIFIED • The following example illustrates the calculation of maximum power. • When three 50-kVA transformers are connected in delta-delta configuration, the total capacity of the bank is their sum, or 150 kVA. • For two transformers in an open-delta configuration, the capacity is 150 kVA⁄√3, or 86.6 kVA, which is the same as 86.6% of the total capacity of two transformers (0.866 x 100 kVA = 86.6 kVA).
  • 36. UNCLASSIFIED UNCLASSIFIED • Conduct Lab 9-3 • Complete Quiz 9-3
  • 37. UNCLASSIFIED UNCLASSIFIED • In this exercise, you set up a three-phase transformer in the open-delta configuration and observed that it supplies a three-phase load with voltages and currents in the proper phase relationships. • You also demonstrated that load power must be reduced by 57.7% (1⁄√3) to avoid exceeding the current rating of the phase windings.
  • 39. UNCLASSIFIED UNCLASSIFIED • The Autotransformer • Transformers in Parallel • Distribution Transformers