5. Electrical Wiring in Residential
Buildings
• Electricity Supply Specifications (MS IEC
60038 standards)
1. Single phase supply with nominal voltage of
230V, range +10%, -6%;
2. Three phase supply with nominal voltage of
400V, range +10%, -6%;
3. Permitted frequency is 50Hz + 1%;
4. Earthing system type (TT System)
10. Supply Voltage Options
• Low Voltage
i. Single-phase, two-wire, 240V, up to 12 kVA
maximum demand
ii. Three-phase, four-wire, 415V, up to 45 kVA
maximum demand
iii. Three-phase, four-wire, C.T. metered, 415V,
up to 1,000 kVA maximum demand
11. Supply Voltage Options
• Medium Voltage & High Voltage
i. Three-phase, three-wire and 11 kV for load
of 1,000 kVA maximum demand and above
ii. Three-phase, three-wire, 22kV or 33kV for
load of 5,000 kVA maximum demand and
above
iii. Three-phase, three-wire, 66kV, 132kV and
275kV for exceptionally large load of above
25 MVA maximum demand
16. Domestic Electrical System Design
(Building)
• Type of Electrical Load Source
• Lighting
• Ceiling Fan
• Switched Socket 13A
• Switched Socket 15A
S/S/O (Switched Socket Outlet) 13A
S/S/O (Switched Socket Outlet) 15A
17. Domestic Electrical System Design
(Building)
• Type of Electrical Load Source (Con’t…)
• Water Heater
• Air-Con
• Electric Motor
• Exhaust Fan
• Cooker Point
• The portable appliances like TV, radio, washing
machine, computer etc are the sub-loads to the
switched socket.
18. Domestic Electrical System Design
(Building)
• Type of PVC covered copper cable:
• Cable 1.5sqmm – red and yellow-blue colours, for load source
like lighting and ceiling fan wiring use.
• Cable 2.5sqmm – red and yellow-blue colours, for load source
like switch socket 13A and 15A, heater, air-con etc.
• Cable 4.0sqmm – red and yellow-blue colours, for load source
like electrical motors etc.
• Cable 6.0sqmm – for earthing purpose.
• Cable 25.0sqmm – for wiring between kWh meter and DB.
19. Domestic Electrical System Design
(Building)
• Types of DB
• PVC c/w plastic cover
• Metal clad c/w cover
• Rating of the 1ø DB – 30A SPN and 63A SPN.
• Rating of the 3ø DB – 30A TPN, 60A TPN,
100A TPN, 150A TPN.
22. Domestic Electrical System Design
(Building)
• Types of circuit Protection Components:
• Switch Fuse – 30A, 60A SPN.
• Moulded Case Circuit Breaker (MCCB)
• Earth Leakage Circuit Breaker (ELCB) or Residue Current
Circuit Breaker (RCCB) – 32A/ 60A with 100mA/ 30mA
(sensitivity).
• Over current Miniature Circuit Breaker (MCB) – 6A, 10A,
and 20A.
• 1 outgoing MCB ≈ 10 lighting point/ fan point
• 1 outgoing MCB ≈ 3 power point (S/S/O 13/15A)
• 1 outgoing MCB ≈ 1 air-con point
• 1 outgoing MCB ≈ 1 water heater point
23. Domestic Electrical System Design
(Building)
• Calculations of connected load and maximum demand
load:
• Loads estimated Watts:
No. Electrical Load Estimated Watt
1. Lighting Point 60 – 100W
2. Fan Point 60W
3. S/S/O Point 13A 250W
4. S/S/O Point 15A/20A 500W
5. Air-Conditioner Point 1.0 hp = 746W
6. Water Heater Point 1000W
7. Cooker Point 1500W
24. Domestic Electrical System Design
(Building)
• Example:
Type of Electrical Load
Estimate
Power
(Watt)
No.
(NOS)
Total Power
(Watt)
Lighting Point 100W 10 1000W
S/S/O – 13A 250W 6 1500W
Air-Con 746W 2 1492W
Water Heater Point 1000W 1 1000W
Total Connected Load, CL 4992W
25. Domestic Electrical System Design
(Building)
• In order to find the actual maximum total
electrical load, we use demand factor (DF),
Nominal Value, DF = 0.6.
• Example:
PMD = 4992W x 0.6 = 2995.2W.
PMD = PCL x DF
27. Basic Electrical Symbols-Layout
Descriptions Symbol Mounting Height
Lighting point Follow ceiling level
Ceiling fan point or Follow ceiling level
S/S/O 13 A 300 mm or 1450 mm
S/S/O 15 A 300 mm or 1450 mm
Air-Con point or 2050 mm (min.) adj.
Switch (1-way) 1500 mm
Switch (2-way) 1500 mm
Switch (Intermediate) 1500 mm
Heater point or 2050 mm
Exhaust fan point 2600 mm
Distribution board 2100 mm
TNB kWh meter 2650 mm
A
C
AC
2g 3g 4g 5g
WH
M
43. Examples of Socket Outlet
Schematic Wiring
Socket Outlet – RING CIRCUIT CONNECTION
44. Final Circuit For 13A Socket
Outlets
Circuit
Type
Over Current Protection
Rating (Fuse or MCB)
(Ampere)
Minimum Size of Copper
Conductor in PVC or Rubber
Insulation
(mm2)
Maximum Floor
Area
(m2)
Ring 30 or 32 2.5 100
Radial 30 or 32 4.0 50
Radial 20 2.5 20
45. Minimum Cross Sectional Area
Rating of Wiring Conductors
Conductor Cross Sectional Area
in mm2
Material Application
1.5 mm2 Copper Lighting/Fan Circuit
2.5 mm2 Copper 13A Socket Outlet Circuit
4.0 mm2 - 6.0 mm2 Copper General Power Circuit (example:
water heater, cooker unit,
motor/pump)
16.0 mm2 – 25.0 mm2 Copper Main Circuit
46. Some Electrical Accessories...
LAMP
• Fluorescent lamps using magnetic ballasts (watt
loss not exceeding 6 watts) shall be equipped with
dry paper type capacitor;
• Fluorescent lamps using electronic ballasts or high
frequency electronic ballasts do not need
capacitors;
• Outdoor domestic lamp installations shall use
weather proof and water proof lamps;
• Submerged light installations (example in
swimming pools, fountains, etc.) shall have water
proof lamps with a voltage not exceeding 12 Volt
47. Some Electrical Accessories...
ELECTRIC WATER HEATERS
• Divided into 2 types, namely instantaneous water
heaters and stored water heaters (storage tank
type)
• Instantaneous water heaters shall be equipped
with a 2 pole control switch and its own residual
current device. Storage water heaters (storage
tank type) shall be installed with an isolator and its
own residual current device; and
• Water heaters exceeding 3kW shall be
permanently connected to a 20A/30A rated circuit
breaker/fuse with an isolator switch and residual
48. Some Electrical Accessories...
ELECTRIC COOKERS
• Exceeding 3kW shall have its own circuit
connected permanently to a 30A rated circuit
breaker or fuse with an isolator switch and
cooker control unit incorporated with a 13A
socket outlet.
• Two or more cooker appliances may be
installed in the same room within a distance of
2 meters.
49. Some Electrical Accessories...
ELECTRIC MOTORS
• Fence gate, air conditioners, fountains, swimming
pools, fish ponds, water pumps exceeding 373W
but not exceeding 2238W, shall be connected
permanently to a 20A/30A rated circuit
breaker/fuse together with an isolator, motor
starter and 15A socket outlet.
• The motor starter shall be of Direct-On-Line type
with the appliance together with the contactor,
overload relay and on-off control.
• The circuit breaker/fuse which controls the motor
circuit shall be capable of withstanding the starting
50. Some Electrical Accessories...
ELECTRIC BELLS
• The circuit shall have a push button switch and
a AC/DC transformer.
CEILING FANS
• Shall conform to clause 21.101 of the MS
1219:2002 standard with regards to test on the
suspension system of ceiling fans.
51. Industrial Electrical System Design
Design
componen
ts
Non-Motor
Circuits
Motor
Circuits
Circuit
Serving
Several
Motors
Panelboard
s and
Switchboar
ds
Transforme
rs
52. Non-Motor Circuits
• For non-motor loads, the MCCBs or fuses are
not allowed to carry 100% rated current on a
continuous basis, it is normally limited to 80% of
the breaker rating.
• OC = 1.25 X Load Amperes
• Wire = 1.25 X Load Amperes
• Example: A 240 V circuit carries a load of 1200
VA. What is the correct MCCB size?
53. Motor Circuits
• Motor’s inrush current during startup (5-7 FLA).
• 2 protective devices: MCCB and time delay
fuse.
• For MCCB,
OC = 1.75 X FLA
Wire = 1.25 X FLA
• For time delay fuse,
OC = 1.25 X FLA
Wire = 1.25 X FLA
55. Motor Circuits
• Example: Design a circuit to serve a 10 HP,
240 V, single-phase AC motor. The
overcurrent device is a MCCB.
Solution:
From previous table, FLA = 50 A.
OC = 1.75 X 50 = 87.5 A (100 A/ 1P)
Wire = 1.25 X 50 = 62.5 A
56. Circuits Serving Several Motors
• For MCCB,
OC = 1.75 X FLA (Largest Motor) + Sum of FLA
for smaller motors
Wire = 1.25 X FLA (Largest Motor) + Sum of
FLA for smaller motors
• For time delay fuse,
OC = 1.25 X FLA (Largest Motor) + Sum of FLA
for smaller motors
Wire = 1.25 X FLA (Largest Motor) + Sum of
FLA for smaller motors
57. Circuits Serving Several Motors
• Example: An air conditioning unit has two
motors, a 5 HP compressor and a 1.0 HP
condensing fan. Both motors are rated at 240 V,
single-phase. Design a circuit for this unit using
a MCCB as the OC device.
Solution:
From table, FLA (5 HP) = 28 A and FLA (1 HP) =
8 A.
OC = 1.75 X 28 + 8 = 57 A (60 A/ 1P MCCB)
Wire = 1.25 X 28 + 8 = 43 A.
58. Transformers
• Transformer must have OC device protection on
both the primary and secondary sides.
• OC (Pri) = 1.25 X FLA (Pri)
• OC (Sec) = 1.25 X FLA (Sec)
• The FLA is determined from the transformer’s
rated kVA and voltage, not the load current.
59. Transformers
• Example: A 50 kVA step-down transformer with
a 3.3 kV three-phase primary and 415Y/240 V
secondary is selected to serve a lighting panel.
Select the correct OC device for this
transformer.
Solution:
60. Transformers
Solution (Cont…)
OC (Pri) = 1.25 X 8.75 = 10.94 A
(15 A/ 3P MCCB)
OC (Sec) = 1.25 X 69.56 = 86.95 A
(90 A/ 3P MCCB)
kVA / (1.732 x Voltage
trasformer)
61. Panelboards and Switchboards
No. Connected Load Demand Factor Remarks
1. Lighting 1.25 Continuous
2. Receptacles
1st 10 kVA@100%
Remainder@50%
1.00
0.50
3. Resistance Heat 1.00 or 0.00 Seasonal
4. Heat Motor 1.00 or 0.00 Seasonal
5. Air Conditioning Motors 1.00 or 0.00 Seasonal
6. Motors 1.00 Non Seasonal
7. Other Loads 1.00 or 1.25* *If Continuous
8. Water Heating 1.00
9. Kitchen 0.65 to 1.00
10. Spare Capacity 1.00
11. Largest Motor 0.25
62. Example
A 415Y/240 V panelboard serves the following loads.
Compute the total connected load and the demand load.
No. Load Rating
1. Lighting 15.0 kVA @ PF=0.95
2. Receptacles 22.0 kVA @ PF=0.90
3. Resistance Heat 9.0 kW
4. Air Conditioning 12.0 kVA @ PF=0.88
5. Motors 6.0 kVA @ PF=0.88
6. Water Heating 4.5 kW
7. Spare Capacity 10.0 kVA @ PF=0.90
63. Solution
No. Load Connected Load
1. Lighting 14.25 + j4.68
2. Receptacles 19.80 + j9.59
3. Resistance Heat 9.00 + j0.00
4. Air Conditioning 10.56 + j5.70
5. Motors 5.28 + j2.85
6. Water Heating 4.50 + j0.00
7. Spare 9.00 + j4.36
Total 72.39 + j27.18 or 77.32 kVA
The total connected load is:
64. Solution
The computed demand load will be:
No. Load Demand Load
1. Lighting (14.25 + j4.68) X 1.25 = 17.81 + j5.85
2. Receptacles (9.00 + j4.36) X 1.00 = 9.00 + j4.36
(10.80 + j5.23) X 0.50 = 5.40 + j2.62
3. Resistance Heat 0.00
4. Air Conditioning (10.56 + j5.70) X 1.00 = 10.56 + j5.70
5. Motors (5.28 + j2.85) X 1.00 = 5.28 + j2.85
6. Water Heating (4.50 + j0.00) X 1.00 = 4.50 + j0.00
7. Spare (9.00 + j4.36) X 1.00 = 9.00 + j4.36
8. Largest Motor 5 HP (3.28 + j1.77) X 0.25 = 0.82 + j0.44
Total 62.37 + j26.18 or 67.64 kVA
65. Solution
The total demand load of 67.64 kVA can then be
converted to current as follows:
So, the circuit serving the panelboard will be protected
by a 100 A/ 3P circuit breaker.