Sharad Institute of Technology College of
Engineering, Yadrav (Ichalkarnji)
A
Presentation On
transformer protection
Presented By,
Mr. Chetan Patil.
Assistant Professor
Department of Electrical Engineering

 Problems Arising In differential Protection Applied To Transformer.
 Harmonic Restraint And Harmonic Blocking.
 Restricted Earth Fault Protection
 Buchholz Relay
Contents

 Difference in lengths of pilot wires on either sides of relays.
 Difference in C.T. ratios due to error difference at high values of short
circuit current.
 Magnetizing inrush current.
 Tap changing.
 Saturation of magnetic core.
Problems Arising In differential
Protection Applied To Transformer
Harmonic Restraint And Harmonic Blocking
 When transformer is connected
to supply it will take large
current 16 to 10 times full load, to
avoid this difficulty harmonic
restraint relay is used.
This type of relay sensitive to
fault current only it does not
operate due to magnetizing
current.
Restricted Earth Fault Protection
 The restricted earth fault
relay does not operate for
earth fault beyond the
protected zone of
transformer.
 Such type of protection
system is not sensitive.
 Such type of system operate
for earth fault current of
about 15% of rated winding
current.
Buchholz Relay
 In this type of relay there are
two main circuits are used
 Alarm circuit
 Trip circuit
 The upper element is closes the
alarm circuit during incipient
fault.
 The lower element is used to
trip the CB for the internal
fault.

 It is simplest form of transformer protection.
 It is used protection against incipient fault.
Advantages

 It can be only used for the oil immersed transformer.
 It detect only the fault below oil level in the transformer.
 It is only used above 500KVA or 750KVA for the economic
consideration.
Disadvantages

 There are many problems in transformer such as magnetizing inrush
current, tap changing, saturation of magnetic core , difference in C.T.
ratios etc.
 The protective equipment's such as CB, relays are gives the protection
to the transformer from earth fault, harmonic blocking, incipient fault
and maintain the reliability of transformer.
Conclusion

Thank You

 Power system protection & Switchgear: B.Ram &
B.N. Vishwakarma.
 Switchgear & Protection: Sunil S.Rao, Khanna
Publications.
References

Transformer protection

  • 1.
    Sharad Institute ofTechnology College of Engineering, Yadrav (Ichalkarnji) A Presentation On transformer protection Presented By, Mr. Chetan Patil. Assistant Professor Department of Electrical Engineering
  • 2.
      Problems ArisingIn differential Protection Applied To Transformer.  Harmonic Restraint And Harmonic Blocking.  Restricted Earth Fault Protection  Buchholz Relay Contents
  • 3.
      Difference inlengths of pilot wires on either sides of relays.  Difference in C.T. ratios due to error difference at high values of short circuit current.  Magnetizing inrush current.  Tap changing.  Saturation of magnetic core. Problems Arising In differential Protection Applied To Transformer
  • 4.
    Harmonic Restraint AndHarmonic Blocking  When transformer is connected to supply it will take large current 16 to 10 times full load, to avoid this difficulty harmonic restraint relay is used. This type of relay sensitive to fault current only it does not operate due to magnetizing current.
  • 5.
    Restricted Earth FaultProtection  The restricted earth fault relay does not operate for earth fault beyond the protected zone of transformer.  Such type of protection system is not sensitive.  Such type of system operate for earth fault current of about 15% of rated winding current.
  • 6.
    Buchholz Relay  Inthis type of relay there are two main circuits are used  Alarm circuit  Trip circuit  The upper element is closes the alarm circuit during incipient fault.  The lower element is used to trip the CB for the internal fault.
  • 7.
      It issimplest form of transformer protection.  It is used protection against incipient fault. Advantages
  • 8.
      It canbe only used for the oil immersed transformer.  It detect only the fault below oil level in the transformer.  It is only used above 500KVA or 750KVA for the economic consideration. Disadvantages
  • 9.
      There aremany problems in transformer such as magnetizing inrush current, tap changing, saturation of magnetic core , difference in C.T. ratios etc.  The protective equipment's such as CB, relays are gives the protection to the transformer from earth fault, harmonic blocking, incipient fault and maintain the reliability of transformer. Conclusion
  • 10.
  • 11.
      Power systemprotection & Switchgear: B.Ram & B.N. Vishwakarma.  Switchgear & Protection: Sunil S.Rao, Khanna Publications. References