Corona Effect
Definition :
When an alternating potential difference is applied across two conductors whose spacing is large as
compared to their diameters, there is no apparent change in the condition of atmospheric air surrounding
the wires if the applied voltage is low. However, when the applied voltage exceeds a certain
value, called critical disruptive voltage, the conductors are surrounded by a faint violet glow called
corona.
The phenomenon of corona is accompanied by a hissing sound, production of ozone, power loss
and radio interference. The higher the voltage is raised, the larger and higher the luminous envelope
becomes, and greater are the sound, the power loss and the radio noise. If the applied voltage is
increased to breakdown value, a flash-over will occur between the conductors due to the breakdown
of air insulation.
The phenomenon of violet glow, hissing noise and production of ozone gas in an overhead
transmission line is known as corona.
If the conductors are polished and smooth, the corona glow will be uniform throughout the
length of the conductors, otherwise the rough points will appear brighter. With d.c. voltage, there is
difference in the appearance of the two wires. The positive wire has uniform glow about it, while the
negative conductor has spotty glow.
Theory of corona formation :
Some ionisation is always present in air due to cosmic rays, ultraviolet radiations and radioactivity.
Therefore, under normal conditions, the air around the conductors contains some ionised particles (i.e.,
free electrons and +ve ions) and neutral molecules. When p.d. is applied between the conductors,
potential gradient is set up in the air which will have maximum value at the conductor surfaces. Under the
influence of potential gradient, the existing free electrons
acquire greater velocities. The greater the applied voltage, the greater the potential gradient and
more is the velocity of free electrons.
When the potential gradient at the conductor surface reaches about 30 kV per cm (max. value),
the velocity acquired by the free electrons is sufficient to strike a neutral molecule with enough force
to dislodge one or more electrons from it. This produces another ion and one or more free electrons,
which is turn are accelerated until they collide with other neutral molecules, thus producing other
ions. Thus, the process of ionisation is cummulative. The result of this ionisation is that either corona
is formed or spark takes place between the conductors.
Factors Affecting Corona :
The phenomenon of corona is affected by the physical state of the atmosphere as well as by the
conditions of the line. The following are the factors upon which corona depends :
(i) Atmosphere. As corona is formed due to ionsiation of air surrounding the conductors, therefore,
it is affected by the physical state of atmosphere. In the stormy weather, the number of
ions is more than normal and as such corona occurs at much less voltage as compared with
fair weather.
(ii) Conductor size. The corona effect depends upon the shape and conditions of the conductors.
The rough and irregular surface will give rise to more corona because unevenness of
the surface decreases the value of breakdown voltage. Thus a stranded conductor has irregular
surface and hence gives rise to more corona that a solid conductor.
(iii) Spacing between conductors. If the spacing between the conductors is made very large as
compared to their diameters, there may not be any corona effect. It is because larger distance
between conductors reduces the electro-static stresses at the conductor surface, thus
avoiding corona formation.
(iv) Line voltage. The line voltage greatly affects corona. If it is low, there is no change in the
condition of air surrounding the conductors and hence no corona is formed. However, if the
line voltage has such a value that electrostatic stresses developed at the conductor surface
make the air around the conductor conducting, then corona is formed.
Advantages and Disadvantages of Corona :
Corona has many advantages and disadvantages. In the correct design of a high voltage overhead
line, a balance should be struck between the advantages and disadvantages.
Advantages
(i) Due to corona formation, the air surrounding the conductor becomes conducting and hence
virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic
stresses between the conductors.
(ii) Corona reduces the effects of transients produced by surges.
(iii)The sound generation effects of corona can be utilized to build high accuracy audio
speakers. The major advantage is that there is zero mass that needs to be moved to create
the sound, so that transient response is improved.
Disadvantages
(i) Corona is accompanied by a loss of energy in different forms as a glowing light, audible sound and
conductor vibration.This affects the transmission efficiency of the
line.
(ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical
action.
(iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal
voltage drop occurs in the line. This may cause inductive interference with neighbouring
communication lines.
(iv) The radio and TV interference occurs on the line because of corona effect.
Methods of Reducing Corona Effect :
It has been seen that intense corona effects are observed at a working voltage of 33 kV or above.
Therefore, careful design should be made to avoid corona on the sub-stations or bus-bars rated for 33
kV and higher voltages otherwise highly ionised air may cause flash-over in the insulators or between
the phases, causing considerable damage to the equipment. The corona effects can be reduced by the
following methods :
(i) By increasing conductor size. By increasing conductor size, the voltage at which corona
occurs is raised and hence corona effects are considerably reduced. This is one of the
reasons that ACSR conductors which have a larger cross-sectional area are used in transmission
lines.
(ii) By increasing conductor spacing. By increasing the spacing between conductors, the voltage
at which corona occurs is raised and hence corona effects can be eliminated. However,
spacing cannot be increased too much otherwise the cost of supporting structure (e.g., bigger
cross arms and supports) may increase to a considerable extent.
(iii) By using bundled conductors. Using a bundled conductor increases the effective diameter of the
conductor. This results in reduction of the corona discharge.
(iv) By using corona rings. The electric field is greater where the conductor curvature is sharp. Therefore,
corona discharge occurs first at the sharp points, edges and corners. To mitigate this, corona rings are
employed at the terminals of very high voltage equipments such as at the bushings of a very high voltage
transformer (Corona discharge also occurs in high voltage equipment). A corona ring is electrically
connected to the high voltage conductor, encircling the points where corona discharge may occur. This
significantly reduces the potential gradient at the surface of the conductor, as the ring distributes the
charge across a wider area due to its smooth round shape.
Corona discharges come in two forms: positive and negative. This is determined by the polarity of the electrode used
to produce the corona. Positive and negative coronas are similar but there are some key differentiations. Positive
corona discharges have a much lower free electron density, than negative coronas. However, the electrons in a
positive corona discharge are concentrated and contain more energy. Negative corona discharges appear larger
than positive ones. This is due to the free electrons being more spread out and more abundant.
Positive coronas
Properties
A positive corona is manifested as a uniform plasma across the length of a conductor. It can often be seen glowing
blue/white, though many of the emissions are in the ultraviolet. The uniformity of the plasma is caused by the
homogeneous source of secondary avalanche electrons described in the mechanism section, below. With the same
geometry and voltages, it appears a little smaller than the corresponding negative corona, owing to the lack of a non-
ionising plasma region between the inner and outer regions.
A positive corona has much lower density of free electrons compared to a negative corona; perhaps a thousandth of
the electron density, and a hundredth of the total number of electrons. However, the electrons in a positive corona
are concentrated close to the surface of the curved conductor, in a region of high potential gradient (and therefore the
electrons have a high energy), whereas in a negative corona many of the electrons are in the outer, lower-field areas.
Therefore, if electrons are to be used in an application which requires a high activation energy, positive coronas may
support a greater reaction constants than corresponding negative coronas; though the total number of electrons may
be lower, the number of very high energy electrons may be higher.
Coronas are efficient producers of ozone in air. A positive corona generates much less ozone than the corresponding
negative corona, as the reactions which produce ozone are relatively low-energy. Therefore, the greater number of
electrons of a negative corona leads to an increased production.
Beyond the plasma, in the unipolar region, the flow is of low-energy positive ions toward the flat electrode.
Mechanism
As with a negative corona, a positive corona is initiated by an exogenous ionisation event in a region of high
potential gradient. The electrons resulting from the ionisation are attracted toward the curved electrode, and the
positive ions repelled from it. By undergoing inelastic collisions closer and closer to the curved electrode, further
molecules are ionized in an electron avalanche.
In a positive corona, secondary electrons, for further avalanches, are generated predominantly in the fluid itself, in
the region outside the plasma or avalanche region. They are created by ionization caused by the photons emitted
from that plasma in the various de-excitation processes occurring within the plasma after electron collisions, the
thermal energy liberated in those collisions creating photons which are radiated into the gas. The electrons resulting
from the ionisation of a neutral gas molecule are then electrically attracted back toward the curved electrode,
attracted into the plasma, and so begins the process of creating further avalanches inside the plasma.
Negative coronas
Properties
A negative corona is manifested in a non-uniform corona, varying according to the surface features and irregularities
of the curved conductor. It often appears as tufts of corona at sharp edges, the number of tufts altering with the
strength of the field. The form of negative coronas is a result of its source of secondary avalanche electrons (see
below). It appears a little larger than the corresponding positive corona, as electrons are allowed to drift out of the
ionising region, and so the plasma continues some distance beyond it. The total number of electrons, and electron
density is much greater than in the corresponding positive corona. However, they are of a predominantly lower
energy, owing to being in a region of lower potential-gradient. Therefore, whilst for many reactions the increased
electron density will increase the reaction rate, the lower energy of the electrons will mean that reactions which
require a higher electron energy may take place at a lower rate.
Mechanism
Negative coronas are more complex than positive coronas in construction. As with positive coronas, the establishing
of a corona begins with an exogenous ionization event generating a primary electron, followed by an electron
avalanche.
Electrons ionized from the neutral gas are not useful in sustaining the negative corona process by generating
secondary electrons for further avalanches, as the general movement of electrons in a negative corona is outward
from the curved electrode. For negative corona, instead, the dominant process generating secondary electrons is
the photoelectric effect, from the surface of the electrode itself. The work function of the electrons (the energy
required to liberate the electrons from the surface) is considerably lower than the ionization energy of air at standard
temperatures and pressures, making it a more liberal source of secondary electrons under these conditions. Again,
the source of energy for the electron-liberation is a high-energy photon from an atom within the plasma body
relaxing after excitation from an earlier collision. The use of ionized neutral gas as a source of ionization is further
diminished in a negative corona by the high-concentration of positive ions clustering around the curved electrode.
Under other conditions, the collision of the positive species with the curved electrode can also cause electron
liberation.
The difference, then, between positive and negative coronas, in the matter of the generation of secondary electron
avalanches, is that in a positive corona they are generated by the gas surrounding the plasma region, the new
secondary electrons travelling inward, whereas in a negative corona they are generated by the curved electrode
itself, the new secondary electrons travelling outward.
A further feature of the structure of negative coronas is that as the electrons drift outwards, they encounter neutral
molecules and, with electronegative molecules (such as oxygenand water vapor), combine to produce negative ions.
These negative ions are then attracted to the positive uncurved electrode, completing the 'circuit'.
The mechanical design of overhead lines is determined by :
– Minimum distances of the conductors to earth, to other conductors and to the
tower
– Minimum clearances and minimum length of insulators, depending on the
pollution class
– Sag, taking account of conductor and ambient conditions
– Tensile stress of the conductor
– Wind forces on the conductor, insulators and towers.
Minimum distances for nominal system voltage U n ≥ 110 kV as indicated in
Table 9.4 are defined in IEC 60071 - 1 (VDE 0111 - 1). The length of the insulators
is determined by the minimum length of insulators and the specific creepage dis-
tance for different pollution classes according to IEC 60071 - 2 (VDE 0111 - 2).
The contamination classes are defined as follows below, whereas the specific
creepage distance refers to the highest voltage for equipment Um .
– Class 1 Lightly polluted areas without industry and with spread settlement
(houses with exhaust from heating devices to be considered); areas with small
industrial density or small populated areas, which are exposed to frequent wind
and rain; areas far from sea shores or on large heights above sea level. The
specifi c creepage distance can be kept at 1.6 cm kV− 1 .
– Class 2 Medium polluted area, industrial areas without any particular emissions,
areas with medium population density with exhaust from heating devices to be
considered; areas with high population density and/or industrial areas, which
are exposed to frequent wind and rain; areas which are more than 1 km distant
from the sea shore. The specific creepage distance shall be 2.0 cm kV− 1 .
– Class 3 Heavily polluted areas with high industrial density and suburbs of
larger cities with considerable exhaust gases from heating; areas near sea shores which are exposed to relatively
strong wind from the sea. The specific creepage distance shall be 2.5 cm kV− 1 .
– Class 4 Very heavily polluted areas of limited extent, including areas which are
exposed to thick, conductive deposits; areas of limited extent which are very
close to the sea shore with occurrence of strong salty wind. The specific creepage
distance shall be 3.1 cm kV− 1 .
The classification of air pollution with respect to exhaust from heating devices
should be done with care, since the increased use of gas for heating reduces the
relevant emissions, with a corresponding effect on the creepage distance. Classi-
fication standards are lacking in some countries.
The minimal conductor – earth distance is determined by the maximal conductor
sag and the maximal permissible continuous tensile stress of the conductor.
According to EN 50341 - 1 and EN 50423 - 1 (VDE 0201), the following shall
apply:
– The continuous tensile stress of the conductor must not be exceeded under any
of the following condition: − 5 ° C with triple the normal load or double the
increased additional load; − 5 ° C with normal additional load and wind load; or
− 5 ° C with increased additional load and wind load.
– The horizontal component of the line tensile strength shall not exceed the values
given in VDE 0201 Table 3 at the mean yearly average temperature (in Germany:
+10 ° C) without wind load.
– In order to calculate the maximal conductor sag, either +40 ° C without additional
load or − 5 ° C with normal or increased additional load are to be applied. The
smallest sag always arises from − 20 ° C without additional load. In countries
facing high current loading of the conductor during summer, higher temperatures
have to be taken into account.
– Normal additional load in newtons per meter of conductor length is to be taken
as 5 + 0.1 d N m− 1 , where d is the conductor diameter. For insulators, 50 newtons
per meter of insulator chain should be used.
– Increased additional load can amount to a multiple of the normal additional
load and its consideration should be based on observations spanning many years
as well as on topographical and meteorological characteristics. Such additional
load mainly has to be considered in cold climates because of ice and snow
deposits.
– Additional load due to warning bowls or radar reflectors is to be considered as
normal additional load with an additional 1 cm layer of ice on the entire surface
(ice lining contributes 0.0075 N cm− 3 ) for cold climates only.

More Related Content

What's hot

Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...
vishalgohel12195
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
Self-employed
 
Power system stability
Power system stabilityPower system stability
Power system stability
Balaram Das
 
BREAKDOWN IN GASES
BREAKDOWN IN GASESBREAKDOWN IN GASES
BREAKDOWN IN GASES
Niraj Solanki
 
Chapter 5 corona
Chapter 5  coronaChapter 5  corona
Chapter 5 corona
firaoltemesgen1
 
Ferranti effect
Ferranti effectFerranti effect
Ferranti effect
tarun1504
 
Chapter 02- Breakdown in Gases (part-2)
Chapter 02- Breakdown in Gases (part-2)Chapter 02- Breakdown in Gases (part-2)
Chapter 02- Breakdown in Gases (part-2)
MUET SZAB Campus Khairpur Mir's Sindh Pakistan
 
Skin effect on transmission line.
Skin effect on transmission line.Skin effect on transmission line.
Skin effect on transmission line.
Parth Patel
 
Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line
chandan kumar
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
HVDC benefits and types
HVDC benefits and typesHVDC benefits and types
HVDC benefits and types
homayon soltani
 
Mechanical design of overhead lines
Mechanical design of overhead linesMechanical design of overhead lines
Mechanical design of overhead lines
Md. Rimon Mia
 
Tripping and control of impulse generators
Tripping and control of impulse generatorsTripping and control of impulse generators
Tripping and control of impulse generatorsFariza Zahari
 
Lightning Arrestar
Lightning ArrestarLightning Arrestar
Lightning Arrestar
younistanzeela
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
RP6997
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.
Parth Patel
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
MuhammedArifTanoli
 
EE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptxEE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptx
sai karthick
 
Electric substation
Electric substation Electric substation
Electric substation
ANNU KUMAR
 
Chapter 2 transmission line parameters
Chapter 2  transmission line parametersChapter 2  transmission line parameters
Chapter 2 transmission line parameters
firaoltemesgen1
 

What's hot (20)

Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...Disadvantages of corona, radio interference, inductive interference between p...
Disadvantages of corona, radio interference, inductive interference between p...
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
 
Power system stability
Power system stabilityPower system stability
Power system stability
 
BREAKDOWN IN GASES
BREAKDOWN IN GASESBREAKDOWN IN GASES
BREAKDOWN IN GASES
 
Chapter 5 corona
Chapter 5  coronaChapter 5  corona
Chapter 5 corona
 
Ferranti effect
Ferranti effectFerranti effect
Ferranti effect
 
Chapter 02- Breakdown in Gases (part-2)
Chapter 02- Breakdown in Gases (part-2)Chapter 02- Breakdown in Gases (part-2)
Chapter 02- Breakdown in Gases (part-2)
 
Skin effect on transmission line.
Skin effect on transmission line.Skin effect on transmission line.
Skin effect on transmission line.
 
Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
HVDC benefits and types
HVDC benefits and typesHVDC benefits and types
HVDC benefits and types
 
Mechanical design of overhead lines
Mechanical design of overhead linesMechanical design of overhead lines
Mechanical design of overhead lines
 
Tripping and control of impulse generators
Tripping and control of impulse generatorsTripping and control of impulse generators
Tripping and control of impulse generators
 
Lightning Arrestar
Lightning ArrestarLightning Arrestar
Lightning Arrestar
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
EE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptxEE8701-High Voltage Engineering (1).pptx
EE8701-High Voltage Engineering (1).pptx
 
Electric substation
Electric substation Electric substation
Electric substation
 
Chapter 2 transmission line parameters
Chapter 2  transmission line parametersChapter 2  transmission line parameters
Chapter 2 transmission line parameters
 

Similar to Corona Effect

Corona1 150423103048-conversion-gate02
Corona1 150423103048-conversion-gate02Corona1 150423103048-conversion-gate02
Corona1 150423103048-conversion-gate02
GHSKassKoronaMardan
 
Corona1
Corona1Corona1
Corona Effect: What is Corona | Corona Effect in Transmission Line
Corona Effect: What is Corona | Corona Effect in Transmission LineCorona Effect: What is Corona | Corona Effect in Transmission Line
Corona Effect: What is Corona | Corona Effect in Transmission Line
vikasverma433
 
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
Tajmun1
 
Corona in trasmission line
Corona in trasmission lineCorona in trasmission line
Corona in trasmission line
atikul islam ashik
 
Corona effect
Corona effectCorona effect
Corona effect
Abdallah Rahmy
 
Corona topic
Corona topicCorona topic
Corona topic
GHSKassKoronaMardan
 
Skin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona dischargeSkin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona discharge
RoungpaSukhe
 
Chapter Five Corona and Overhead line Insulators.pptx
Chapter Five Corona and Overhead line Insulators.pptxChapter Five Corona and Overhead line Insulators.pptx
Chapter Five Corona and Overhead line Insulators.pptx
ssuserc8d444
 
Corona discharge
Corona dischargeCorona discharge
Corona discharge
ibrahim shah
 
Corona
CoronaCorona
CORONA EFFECT IN TRANSMISSION LINE
CORONA EFFECT IN TRANSMISSION LINE CORONA EFFECT IN TRANSMISSION LINE
CORONA EFFECT IN TRANSMISSION LINE
AllumiaX Engineering
 
Describe the foration of corona and discus thr factorz which affect corona loss
Describe the foration of corona and discus thr factorz  which affect corona lossDescribe the foration of corona and discus thr factorz  which affect corona loss
Describe the foration of corona and discus thr factorz which affect corona lossEngr Nazeer Jasser
 
Corona Effect (ELECTRICAL ENGINEERING)
Corona Effect (ELECTRICAL ENGINEERING)Corona Effect (ELECTRICAL ENGINEERING)
Corona Effect (ELECTRICAL ENGINEERING)
Lakshya Pandey
 
The x ray beam
The x ray beam The x ray beam
The x ray beam
airwave12
 
Corrona Effect.ppt
Corrona Effect.pptCorrona Effect.ppt
Corrona Effect.ppt
aneesurrehman54
 
Corona in-power-system
Corona in-power-systemCorona in-power-system
Corona in-power-system
R.n. Patel
 

Similar to Corona Effect (20)

Corona1 150423103048-conversion-gate02
Corona1 150423103048-conversion-gate02Corona1 150423103048-conversion-gate02
Corona1 150423103048-conversion-gate02
 
Corona1
Corona1Corona1
Corona1
 
Corona Effect: What is Corona | Corona Effect in Transmission Line
Corona Effect: What is Corona | Corona Effect in Transmission LineCorona Effect: What is Corona | Corona Effect in Transmission Line
Corona Effect: What is Corona | Corona Effect in Transmission Line
 
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
 
Corona in trasmission line
Corona in trasmission lineCorona in trasmission line
Corona in trasmission line
 
Corona effect
Corona effectCorona effect
Corona effect
 
Corona topic
Corona topicCorona topic
Corona topic
 
Skin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona dischargeSkin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona discharge
 
Chapter Five Corona and Overhead line Insulators.pptx
Chapter Five Corona and Overhead line Insulators.pptxChapter Five Corona and Overhead line Insulators.pptx
Chapter Five Corona and Overhead line Insulators.pptx
 
Corona discharge
Corona dischargeCorona discharge
Corona discharge
 
Corona
CoronaCorona
Corona
 
Rock star
Rock starRock star
Rock star
 
CORONA EFFECT IN TRANSMISSION LINE
CORONA EFFECT IN TRANSMISSION LINE CORONA EFFECT IN TRANSMISSION LINE
CORONA EFFECT IN TRANSMISSION LINE
 
corona.pptx
corona.pptxcorona.pptx
corona.pptx
 
Describe the foration of corona and discus thr factorz which affect corona loss
Describe the foration of corona and discus thr factorz  which affect corona lossDescribe the foration of corona and discus thr factorz  which affect corona loss
Describe the foration of corona and discus thr factorz which affect corona loss
 
Corona Effect (ELECTRICAL ENGINEERING)
Corona Effect (ELECTRICAL ENGINEERING)Corona Effect (ELECTRICAL ENGINEERING)
Corona Effect (ELECTRICAL ENGINEERING)
 
The x ray beam
The x ray beam The x ray beam
The x ray beam
 
Corrona Effect.ppt
Corrona Effect.pptCorrona Effect.ppt
Corrona Effect.ppt
 
IR.ppt
IR.pptIR.ppt
IR.ppt
 
Corona in-power-system
Corona in-power-systemCorona in-power-system
Corona in-power-system
 

More from Hussein Kassem

Flashover Tests
Flashover TestsFlashover Tests
Flashover Tests
Hussein Kassem
 
Electric Energy Storage Systems
Electric Energy Storage SystemsElectric Energy Storage Systems
Electric Energy Storage Systems
Hussein Kassem
 
Transducers , Sensors & Actuators
Transducers , Sensors & ActuatorsTransducers , Sensors & Actuators
Transducers , Sensors & Actuators
Hussein Kassem
 
Steering
SteeringSteering
Steering
Hussein Kassem
 
Induction Motor Tests
Induction Motor TestsInduction Motor Tests
Induction Motor Tests
Hussein Kassem
 
Classes of Squirrel Cage Motors
Classes of Squirrel Cage MotorsClasses of Squirrel Cage Motors
Classes of Squirrel Cage Motors
Hussein Kassem
 
Capacitance and Cable Testing
Capacitance and Cable TestingCapacitance and Cable Testing
Capacitance and Cable Testing
Hussein Kassem
 

More from Hussein Kassem (7)

Flashover Tests
Flashover TestsFlashover Tests
Flashover Tests
 
Electric Energy Storage Systems
Electric Energy Storage SystemsElectric Energy Storage Systems
Electric Energy Storage Systems
 
Transducers , Sensors & Actuators
Transducers , Sensors & ActuatorsTransducers , Sensors & Actuators
Transducers , Sensors & Actuators
 
Steering
SteeringSteering
Steering
 
Induction Motor Tests
Induction Motor TestsInduction Motor Tests
Induction Motor Tests
 
Classes of Squirrel Cage Motors
Classes of Squirrel Cage MotorsClasses of Squirrel Cage Motors
Classes of Squirrel Cage Motors
 
Capacitance and Cable Testing
Capacitance and Cable TestingCapacitance and Cable Testing
Capacitance and Cable Testing
 

Recently uploaded

The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
Robbie Edward Sayers
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
fxintegritypublishin
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
SupreethSP4
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
Kerry Sado
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
zwunae
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
ongomchris
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 

Recently uploaded (20)

The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
Hierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power SystemHierarchical Digital Twin of a Naval Power System
Hierarchical Digital Twin of a Naval Power System
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 

Corona Effect

  • 1. Corona Effect Definition : When an alternating potential difference is applied across two conductors whose spacing is large as compared to their diameters, there is no apparent change in the condition of atmospheric air surrounding the wires if the applied voltage is low. However, when the applied voltage exceeds a certain value, called critical disruptive voltage, the conductors are surrounded by a faint violet glow called corona. The phenomenon of corona is accompanied by a hissing sound, production of ozone, power loss and radio interference. The higher the voltage is raised, the larger and higher the luminous envelope becomes, and greater are the sound, the power loss and the radio noise. If the applied voltage is increased to breakdown value, a flash-over will occur between the conductors due to the breakdown of air insulation. The phenomenon of violet glow, hissing noise and production of ozone gas in an overhead transmission line is known as corona. If the conductors are polished and smooth, the corona glow will be uniform throughout the length of the conductors, otherwise the rough points will appear brighter. With d.c. voltage, there is difference in the appearance of the two wires. The positive wire has uniform glow about it, while the negative conductor has spotty glow. Theory of corona formation : Some ionisation is always present in air due to cosmic rays, ultraviolet radiations and radioactivity. Therefore, under normal conditions, the air around the conductors contains some ionised particles (i.e., free electrons and +ve ions) and neutral molecules. When p.d. is applied between the conductors, potential gradient is set up in the air which will have maximum value at the conductor surfaces. Under the influence of potential gradient, the existing free electrons acquire greater velocities. The greater the applied voltage, the greater the potential gradient and more is the velocity of free electrons. When the potential gradient at the conductor surface reaches about 30 kV per cm (max. value), the velocity acquired by the free electrons is sufficient to strike a neutral molecule with enough force to dislodge one or more electrons from it. This produces another ion and one or more free electrons, which is turn are accelerated until they collide with other neutral molecules, thus producing other ions. Thus, the process of ionisation is cummulative. The result of this ionisation is that either corona is formed or spark takes place between the conductors.
  • 2. Factors Affecting Corona : The phenomenon of corona is affected by the physical state of the atmosphere as well as by the conditions of the line. The following are the factors upon which corona depends : (i) Atmosphere. As corona is formed due to ionsiation of air surrounding the conductors, therefore, it is affected by the physical state of atmosphere. In the stormy weather, the number of ions is more than normal and as such corona occurs at much less voltage as compared with fair weather. (ii) Conductor size. The corona effect depends upon the shape and conditions of the conductors. The rough and irregular surface will give rise to more corona because unevenness of the surface decreases the value of breakdown voltage. Thus a stranded conductor has irregular surface and hence gives rise to more corona that a solid conductor. (iii) Spacing between conductors. If the spacing between the conductors is made very large as compared to their diameters, there may not be any corona effect. It is because larger distance between conductors reduces the electro-static stresses at the conductor surface, thus avoiding corona formation. (iv) Line voltage. The line voltage greatly affects corona. If it is low, there is no change in the condition of air surrounding the conductors and hence no corona is formed. However, if the line voltage has such a value that electrostatic stresses developed at the conductor surface make the air around the conductor conducting, then corona is formed. Advantages and Disadvantages of Corona : Corona has many advantages and disadvantages. In the correct design of a high voltage overhead line, a balance should be struck between the advantages and disadvantages. Advantages (i) Due to corona formation, the air surrounding the conductor becomes conducting and hence virtual diameter of the conductor is increased. The increased diameter reduces the electrostatic stresses between the conductors. (ii) Corona reduces the effects of transients produced by surges. (iii)The sound generation effects of corona can be utilized to build high accuracy audio speakers. The major advantage is that there is zero mass that needs to be moved to create the sound, so that transient response is improved. Disadvantages (i) Corona is accompanied by a loss of energy in different forms as a glowing light, audible sound and conductor vibration.This affects the transmission efficiency of the line. (ii) Ozone is produced by corona and may cause corrosion of the conductor due to chemical action. (iii) The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line. This may cause inductive interference with neighbouring communication lines. (iv) The radio and TV interference occurs on the line because of corona effect.
  • 3. Methods of Reducing Corona Effect : It has been seen that intense corona effects are observed at a working voltage of 33 kV or above. Therefore, careful design should be made to avoid corona on the sub-stations or bus-bars rated for 33 kV and higher voltages otherwise highly ionised air may cause flash-over in the insulators or between the phases, causing considerable damage to the equipment. The corona effects can be reduced by the following methods : (i) By increasing conductor size. By increasing conductor size, the voltage at which corona occurs is raised and hence corona effects are considerably reduced. This is one of the reasons that ACSR conductors which have a larger cross-sectional area are used in transmission lines. (ii) By increasing conductor spacing. By increasing the spacing between conductors, the voltage at which corona occurs is raised and hence corona effects can be eliminated. However, spacing cannot be increased too much otherwise the cost of supporting structure (e.g., bigger cross arms and supports) may increase to a considerable extent. (iii) By using bundled conductors. Using a bundled conductor increases the effective diameter of the conductor. This results in reduction of the corona discharge. (iv) By using corona rings. The electric field is greater where the conductor curvature is sharp. Therefore, corona discharge occurs first at the sharp points, edges and corners. To mitigate this, corona rings are employed at the terminals of very high voltage equipments such as at the bushings of a very high voltage transformer (Corona discharge also occurs in high voltage equipment). A corona ring is electrically connected to the high voltage conductor, encircling the points where corona discharge may occur. This significantly reduces the potential gradient at the surface of the conductor, as the ring distributes the charge across a wider area due to its smooth round shape.
  • 4. Corona discharges come in two forms: positive and negative. This is determined by the polarity of the electrode used to produce the corona. Positive and negative coronas are similar but there are some key differentiations. Positive corona discharges have a much lower free electron density, than negative coronas. However, the electrons in a positive corona discharge are concentrated and contain more energy. Negative corona discharges appear larger than positive ones. This is due to the free electrons being more spread out and more abundant. Positive coronas Properties A positive corona is manifested as a uniform plasma across the length of a conductor. It can often be seen glowing blue/white, though many of the emissions are in the ultraviolet. The uniformity of the plasma is caused by the homogeneous source of secondary avalanche electrons described in the mechanism section, below. With the same geometry and voltages, it appears a little smaller than the corresponding negative corona, owing to the lack of a non- ionising plasma region between the inner and outer regions. A positive corona has much lower density of free electrons compared to a negative corona; perhaps a thousandth of the electron density, and a hundredth of the total number of electrons. However, the electrons in a positive corona are concentrated close to the surface of the curved conductor, in a region of high potential gradient (and therefore the electrons have a high energy), whereas in a negative corona many of the electrons are in the outer, lower-field areas. Therefore, if electrons are to be used in an application which requires a high activation energy, positive coronas may support a greater reaction constants than corresponding negative coronas; though the total number of electrons may be lower, the number of very high energy electrons may be higher. Coronas are efficient producers of ozone in air. A positive corona generates much less ozone than the corresponding negative corona, as the reactions which produce ozone are relatively low-energy. Therefore, the greater number of electrons of a negative corona leads to an increased production. Beyond the plasma, in the unipolar region, the flow is of low-energy positive ions toward the flat electrode. Mechanism As with a negative corona, a positive corona is initiated by an exogenous ionisation event in a region of high potential gradient. The electrons resulting from the ionisation are attracted toward the curved electrode, and the positive ions repelled from it. By undergoing inelastic collisions closer and closer to the curved electrode, further molecules are ionized in an electron avalanche. In a positive corona, secondary electrons, for further avalanches, are generated predominantly in the fluid itself, in the region outside the plasma or avalanche region. They are created by ionization caused by the photons emitted from that plasma in the various de-excitation processes occurring within the plasma after electron collisions, the thermal energy liberated in those collisions creating photons which are radiated into the gas. The electrons resulting from the ionisation of a neutral gas molecule are then electrically attracted back toward the curved electrode, attracted into the plasma, and so begins the process of creating further avalanches inside the plasma. Negative coronas Properties A negative corona is manifested in a non-uniform corona, varying according to the surface features and irregularities of the curved conductor. It often appears as tufts of corona at sharp edges, the number of tufts altering with the strength of the field. The form of negative coronas is a result of its source of secondary avalanche electrons (see below). It appears a little larger than the corresponding positive corona, as electrons are allowed to drift out of the ionising region, and so the plasma continues some distance beyond it. The total number of electrons, and electron density is much greater than in the corresponding positive corona. However, they are of a predominantly lower energy, owing to being in a region of lower potential-gradient. Therefore, whilst for many reactions the increased electron density will increase the reaction rate, the lower energy of the electrons will mean that reactions which require a higher electron energy may take place at a lower rate.
  • 5. Mechanism Negative coronas are more complex than positive coronas in construction. As with positive coronas, the establishing of a corona begins with an exogenous ionization event generating a primary electron, followed by an electron avalanche. Electrons ionized from the neutral gas are not useful in sustaining the negative corona process by generating secondary electrons for further avalanches, as the general movement of electrons in a negative corona is outward from the curved electrode. For negative corona, instead, the dominant process generating secondary electrons is the photoelectric effect, from the surface of the electrode itself. The work function of the electrons (the energy required to liberate the electrons from the surface) is considerably lower than the ionization energy of air at standard temperatures and pressures, making it a more liberal source of secondary electrons under these conditions. Again, the source of energy for the electron-liberation is a high-energy photon from an atom within the plasma body relaxing after excitation from an earlier collision. The use of ionized neutral gas as a source of ionization is further diminished in a negative corona by the high-concentration of positive ions clustering around the curved electrode. Under other conditions, the collision of the positive species with the curved electrode can also cause electron liberation. The difference, then, between positive and negative coronas, in the matter of the generation of secondary electron avalanches, is that in a positive corona they are generated by the gas surrounding the plasma region, the new secondary electrons travelling inward, whereas in a negative corona they are generated by the curved electrode itself, the new secondary electrons travelling outward. A further feature of the structure of negative coronas is that as the electrons drift outwards, they encounter neutral molecules and, with electronegative molecules (such as oxygenand water vapor), combine to produce negative ions. These negative ions are then attracted to the positive uncurved electrode, completing the 'circuit'.
  • 6. The mechanical design of overhead lines is determined by : – Minimum distances of the conductors to earth, to other conductors and to the tower – Minimum clearances and minimum length of insulators, depending on the pollution class – Sag, taking account of conductor and ambient conditions – Tensile stress of the conductor – Wind forces on the conductor, insulators and towers. Minimum distances for nominal system voltage U n ≥ 110 kV as indicated in Table 9.4 are defined in IEC 60071 - 1 (VDE 0111 - 1). The length of the insulators is determined by the minimum length of insulators and the specific creepage dis- tance for different pollution classes according to IEC 60071 - 2 (VDE 0111 - 2). The contamination classes are defined as follows below, whereas the specific creepage distance refers to the highest voltage for equipment Um . – Class 1 Lightly polluted areas without industry and with spread settlement (houses with exhaust from heating devices to be considered); areas with small industrial density or small populated areas, which are exposed to frequent wind and rain; areas far from sea shores or on large heights above sea level. The specifi c creepage distance can be kept at 1.6 cm kV− 1 . – Class 2 Medium polluted area, industrial areas without any particular emissions, areas with medium population density with exhaust from heating devices to be considered; areas with high population density and/or industrial areas, which are exposed to frequent wind and rain; areas which are more than 1 km distant from the sea shore. The specific creepage distance shall be 2.0 cm kV− 1 . – Class 3 Heavily polluted areas with high industrial density and suburbs of larger cities with considerable exhaust gases from heating; areas near sea shores which are exposed to relatively strong wind from the sea. The specific creepage distance shall be 2.5 cm kV− 1 . – Class 4 Very heavily polluted areas of limited extent, including areas which are exposed to thick, conductive deposits; areas of limited extent which are very close to the sea shore with occurrence of strong salty wind. The specific creepage distance shall be 3.1 cm kV− 1 .
  • 7. The classification of air pollution with respect to exhaust from heating devices should be done with care, since the increased use of gas for heating reduces the relevant emissions, with a corresponding effect on the creepage distance. Classi- fication standards are lacking in some countries. The minimal conductor – earth distance is determined by the maximal conductor sag and the maximal permissible continuous tensile stress of the conductor. According to EN 50341 - 1 and EN 50423 - 1 (VDE 0201), the following shall apply: – The continuous tensile stress of the conductor must not be exceeded under any of the following condition: − 5 ° C with triple the normal load or double the increased additional load; − 5 ° C with normal additional load and wind load; or − 5 ° C with increased additional load and wind load. – The horizontal component of the line tensile strength shall not exceed the values given in VDE 0201 Table 3 at the mean yearly average temperature (in Germany: +10 ° C) without wind load. – In order to calculate the maximal conductor sag, either +40 ° C without additional load or − 5 ° C with normal or increased additional load are to be applied. The smallest sag always arises from − 20 ° C without additional load. In countries facing high current loading of the conductor during summer, higher temperatures have to be taken into account. – Normal additional load in newtons per meter of conductor length is to be taken as 5 + 0.1 d N m− 1 , where d is the conductor diameter. For insulators, 50 newtons per meter of insulator chain should be used. – Increased additional load can amount to a multiple of the normal additional load and its consideration should be based on observations spanning many years as well as on topographical and meteorological characteristics. Such additional load mainly has to be considered in cold climates because of ice and snow deposits. – Additional load due to warning bowls or radar reflectors is to be considered as normal additional load with an additional 1 cm layer of ice on the entire surface (ice lining contributes 0.0075 N cm− 3 ) for cold climates only.